SPECIAL REPORT

HOW TO TROUBLESHOOT
AND CALIBRATE

4-20 mA
www.controldesign.com

How to troubleshoot and


calibrate 4-20 mA
Best practices for troubleshooting analog circuits to the PLC
By Mike Bacidore, editor in chief

A
Control Design reader writes: We have several temperature, pressure and flow
sensors on a new medical-device cleaning skid that we are developing. These in-
struments are connected to a PLC as 4-20 mA inputs, and there is also a 4-20 mA
output used to control a pump motor speed. A recent failure of a flow sensor brought the
process skid instrumentation to my company’s quality manager’s attention. He asked how
we know that the temperatures, pressure and flow are accurate, and how do we know that
we are cleaning properly. I’ve been tasked to write a procedure for troubleshooting, cali-
brating and testing the 4-20 mA instruments on the skid. I can probably stumble through
this, but what are some best practices for troubleshooting the analog circuits to the PLC;
how do I calibrate the instruments; and how should I periodically test the devices? Should I
add programming to the PLC and HMI to simplify these functions?

How to troubleshoot and calibrate 4-20 mA 2


www.controldesign.com

ANSWERS
How do I calibrate the instruments; and
BEST PRACTICES, CALIBRATION how should I periodically test the devices?
AND PROGRAMMING Instrument calibration should be performed
What are some best practices for trouble- by a qualified instrument technician. If you
shooting the analog circuits to the PLC? choose to self-perform, it may be best to
Once the skid has completed startup and shadow a third-party technician until you
commissioning, there is a limited amount have purchased the necessary calibration
of troubleshooting to maintain the system. equipment and learned the skills needed to
If a short in the wiring occurs in the analog do the calibrations. Calibration serves as the
wires, you will likely get a blown fuse indica- testing of the devices, and the test or cali-
tion. If an open occurs in the analog wires, bration interval is determined by the level of
you likely have a loose termination and accuracy required for your application. Ob-
this will be found with continuity checks. viously the higher the required accuracy is,
For failures in the transmitter, the indica- the more often calibration will be required.
tion will either be an overdriven signal (>20 Typically annual calibrations are sufficient;
mAdc, for example, 22 mAdc) or a signal however, this will need to be determined
significantly below zero, such as 3.5 mAdc. from experience with this specific equip-
The direction the transmitter drives to in ment and application.
a failure mode will depend on whether the
transmitter is set up to provide an upscale Should I add programming to the PLC and
or downscale burnout (upscale 22 mAdc HMI to simplify these functions? No pro-
vs. downscale 3.5 mAdc). The determina- gramming is necessary or helpful in simpli-
tion of which failure mode to use—upscale fying the calibration work; however, good
or downscale burnout—depends on the use alarming is always helpful in troubleshoot-
of the transmitter. This selection is made ing and maintaining a control system. While
based on making the loop failsafe. For ex- adequate alarming is important, also con-
ample, if it is a temperature transmitter and sider moderation when applying alarms. If
it is used for a high-temperature interlock, you flood the HMI with too many alarms in
we would select upscale burnout. In con- an attempt to build in troubleshooting intel-
trast, assume a flow transmitter for control- ligence, you will overwhelm the equipment
ling the cooling for motor bearings. If we operator. Also, excessive alarms can quickly
have a flow transmitter failure, we may want become a nuisance, so they begin to be ig-
to apply full cooling. If so, we would prefer nored. A flood of redundant alarms can also
a downscale burnout so that we respond by distract from a pertinent or critical alarm
applying full flow. that may be missed as a result of overuse.

How to troubleshoot and calibrate 4-20 mA 3


www.controldesign.com

In addition to a proper calibration inter- rity, like making sure there isn’t a VFD nearby
val, quality checks of the signals can aid in that would throw out electromagnetic inter-
detecting a deteriorating transmitter. For ference that would distort signal.
example, as a transmitter begins to lose
its accuracy, the calibrated span typically Calibration of the instruments are fairly
shifts above or below zero (4 mAdc). For straightforward when using standard cali-
example, in a flow transmitter, the 16 mAdc bration tools, but will vary between instru-
span (4–20 mAdc) may still be accurate ment manufacturers.
but, with zero flow through the sensing
element, the transmitter may be sending a Given that 4-20 mA instruments aren’t
signal of 4.3 mAdc. This means that a 20.3 smart—able to diagnose themselves or alert
mAdc output may represent full flow in- operations to issues—I would think there is
stead of 20 mAdc. To detect this condition definitely periodic testing that should occur.
you may consider doing off-state verifica- In today’s day and age, I would be recom-
tion. In short, by monitoring the flow signal mending to this individual that he consider
when the pump is not running, you will a digital solution that provides a lot more
catch an elevated zero as an indication of robust information about the health of the
a need for calibration. The same technique skid. HART is a simple upgrade to an exist-
could be used to indicate an improperly ing 4-20 mA skid and provides familiarity.
calibrated pressure transmitter. A compari- If the individual wants to make a drastic
son of pump speed to flow and pressure is step change and go fully digital with some
another means of qualifying the accuracy increased horsepower, he should consider
of these transmitters. It will only detect a Foundation Fieldbus (FF). FF actually makes
gross error, but this may be useful data for fantastic solutions in skid mounts be-
depending on the application. cause everything can be completed at the
factory level and then, when delivered on
— Tim Green, director of field services, site, it’s as simple as landing a trunk line to
Maverick Technologies, www.mavtechglobal.com
the host system and you can rock and roll.
Columbia, Illinois
— Talon Petty, marketing and business development
manager, FieldComm Group,
LET’S GET DIGITAL www.fieldcommgroup.org
This gentleman indicates he’s using purely
4-20 mA instrumentation on his system. CALIBRATE INPUT/OUTPUT
There are no “smarts” in analog. If he’s using First, the calibration and verification of cali-
HART on his 4-20 mA instruments, then there bration depends on the type of sensor used.
is hope. Without it, then he’s only going to be I will include general calibration procedure
able to verify calibration and segment integ- at the end. There are several things that can

How to troubleshoot and calibrate 4-20 mA 4


www.controldesign.com

be done in the design stage to increase the 3. Verify that the signals are changing with
reliability of a system using analog sensors. respect to changes in the process that af-
fects that signal.
The use of 0-20 mA analog cards instead 4. If the normal response time for a certain
of 4-20 mA analog cards will allow the output to be registered as an anticipated
program to detect a signal less than 4 mA, input can be determined, then this can be
which could mean a sensor is bad or the checked on a frequent basis to determine
signal cable has a break in it. Without this if the system response is within expecta-
check, the PLC would just assume the ana- tions. If it is not, then the system may have
log signal is at its lowest state. to be checked and possibly re-calibrated.
5. As part of the maintenance procedure,
Another design method can be to use the gauges mentioned above could be
redundant sensors—one could be assigned checked on a regular basis.
as the primary signal, and the logic could
be programmed such that if one of these Calibration of the loops is required both at
signals varies by x%, then an error message commissioning and also when an issue has
is sent and the program could either shut been detected by the methods indicated
down or choose which sensor to use and above. The loops should be verified both at
call for maintenance to resolve. the low (zero or 4 mA) end, and then the
span is calibrated to obtain the correct set-
In general, there should always be a me- ting for the high (100% or 20 mA) end.
chanical gauge on the equipment that
would allow an operator or maintenance For input devices: The analog system is best
person to make sure that the measured tested from the source to the PLC. Devices
signal on the HMI matches the mechanical can be used to inject generated signals into
gauge within reason. the PLC, but this does not test the sensor.
1. The input sensors have a procedure to set
Within the program, several checks can be the sensor to provide a zero (4 mA) signal.
made to ensure that the sensors are work- 2. By connecting a calibrated meter with
ing as required. the current loop, the actual current flow-
1. Verify that the signal is at its resting state, ing can be read.
(4 mA or 20 mA, depending on its func- 3. The PLC should have the ability in setup
tion) when the system is turned off. mode to consider this reading to be the
2. Verify that the signal changes when the zero point, even if it is not quite accurate.
part of the system related to this device 4. The sensor should be set to provide the
is started up. high (20 mA) signal or the span.

How to troubleshoot and calibrate 4-20 mA 5


www.controldesign.com

5. Again, the meter should verify this is pro- the output will increase linearly from this
ducing close to 20 mA. zero position as the signal increases. If
6. The PLC should then be set to read this the zero point is determined to be 4.2
value to the high setting. mA, then the setup routine should re-
7. Note that the new low setting and the cord this value as the zero point, or the
new high setting will be the minimum output device should be adjusted.
and maximum set points of the scaling 4. In this case, the PLC setup should allow
of the loop. the output loop to generate a high (20
8. Further verification can be made by ap- mA) signal or the span.
plying a known value to the sensor and 5. A calibrated meter should be connected
verifying that the PLC reads the same into the current loop so the actual current
value. For instance, if the device is mea- flowing can be read.
suring pressure and its range is 0-100 6. Once the high signal is generated, the
psi, then the sensor could be attached output of the controlled device needs
to a pressure source with a calibrated to be determined. Furthermore, the out-
source. If 0 psi and 100 psi are applied, put device needs to be manipulated by
then the PLC should read the same val- changing the output loop to make sure
ues. This additional calibration should the output will decrease linearly from
also be conducted after the meter used this max position as the signal decreas-
for calibration has been taken out of the es. If the span point is determined to be
circuit to make sure the circuit has been 19.5 mA, then the setup routine should
reconnected correctly. record this value as the span point or
the output device should be adjusted.
For output devices: Again, the whole loop 7. N
 ote that the new low setting and the
should be tested at the same time. new high setting will be the minimum
1. In this case the PLC setup should allow and maximum set points of the scaling
the output loop to generate a low of the loop.
(4 mA) signal. — Kevin J Pitts, automation application engineer,
Eaton, www.eaton.com
2. A
 calibrated meter should be connected
into the current loop so the actual current
flowing can be read. 4 QUESTIONS
3. Once the low signal is generated, the How do we know that we are cleaning
output of the controlled device needs to properly?
be determined. Furthermore, the out- 1. There are specific cleaning requirements
put device needs to be manipulated by that you can research through the U.S.
changing the output loop to make sure Food & Drug Administration. Piping,

How to troubleshoot and calibrate 4-20 mA 6


www.controldesign.com

installation of instruments and cleaning 1. Each Instrument has an accuracy state-


methods all need to be researched. ment and depending on how you calibrate
2. S
 ome of these methods, such as clean- and test will determine how accurate your
in-place (CIP) or remove and clean, will instruments really are.
depend on his application. 2. This is where you need a good instrument
3. There are also specific chemicals to use, service company to take a role in your
as well as a time limit for cleaning. maintenance and calibration process.
4. L
 astly, the way the instruments are in- 3. Look to partner with a service company
stalled, the actual materials used in the that is ISO and ISA quality-compliant and
process and whether they will affect the certified.
instruments all come into play as to how 4. Your relationship with that service orga-
you would clean the system. nization will increase your confidence in
the accuracy of your instruments.
How do we troubleshoot, calibrate and test — Antonio J. Biondo, northeast regional service account
manager, measurement & analytics, ABB,
the instruments?
www.abb.com
1. The instrument manufacturer should have
a documented procedure for testing and LOOK FOR LINEARITY
calibrating each instrument. First and foremost, the questions you are
2. T
 here are specific pieces of test equip- asking about are handled differently be-
ment used for each device in-place. tween companies and even between lines
3. The International Society of Automation with different requirements. So, the short
(ISA) has a number of good manuals that answer is there is no real “standard” to go
cover calibration, testing, startup and by. In our experience, calibration of analog
troubleshooting. equipment should occur every year, but it
may be more frequent depending on how
How do I test the PLC? accurate the signal is required to be. As for
1. PLCs normally do not need calibration the procedure to troubleshoot the equip-
after the initial programming and testing. ment, it may closely resemble the calibra-
My experience is that they are pass/fail. tion procedure, or at a minimum include
By that, I mean the input is either good or components of the calibration process. If
it is bad. The PLC should have the capa- possible, consider side-by-side testing for
bility to differentiate between the two equipment calibration or better yet, NIST
conditions. The same goes for outputs. traceable paths. Using NIST traceable tests
may help to confirm the display readings
How do we know that the instruments are and that the equipment is accurately cali-
accurate? brated. Realistically, there should be a linear

How to troubleshoot and calibrate 4-20 mA 7


www.controldesign.com

relationship between the required signal If the emissivity and temperature of the
accuracy and how often the equipment is measurement target are unknown, use the
maintained, or calibrated. optional black body tape to take simplified
— Jeff Thornton, product manager—automation, measurements.
Red Lion Controls, www.redlion.net
1. Stick the black body tape to the measure-
ment target, heat it to a suitable tem-
BETTER TO PREDICT AND PREVENT perature (+20 °C (+68 °F) or more above
I cannot offer much on best practices, room temperature), and maintain that
troubleshooting and calibration procedures temperature as best as possible.
since these are all post-mortem steps after 2. Set the emissivity to 0.95 (emissivity of
an incident occurs. I am suggesting hav- black body tape).
ing the foresight to see these events occur 3. Measure the temperature of the portion
before a downtime or quality event causes of the target covered in black body tape
action to be taken. Predictive analytics and and take note of the measured value.
applying machine-learning agents detect 4. Remove the black body tape and measure
early onset anomalies that can prevent the temperature of the target on an area
such events. The need for developing good that is close to the area measured in 3.
troubleshooting and calibration procedures 5. Choose “set by temperature” and enter
will always be standard practice, but the the temperature measured in 3 to set the
value to the client to predict and apply pro- emissivity.
active procedures to see a problem develop 6. The emissivity of the measurement target
surpasses any traditional methods. is set.
— Aldo Ferrante, president and CEO, In terms of frequency of monitoring, the
ITG Technologies, www.itgtec.com, CSIA
more often the better, but monthly is typi-
(www.controlsys.org) member, Jacksonville, Florida
cally adequate, depending on how dirty the
BLACK BODY TAPE process is. These checks can be done in a
This is directly from our instruction manual manual or an automated fashion, but I’ve
for our temperature sensor lineup. The seen HMI buttons for calibration that would
black body tape will have a fixed emissivity, require setting master parts in the fixtures.
so, as long as you can adjust the emissivity Doing it manually will take time, but hav-
of your sensor, this will work fine. If it isn’t ing a constant-temperature-rated item with
adjustable, likely the sensor will be set at a the black body tape applied can be a quick
.95 emissivity. At this point, take a target check any operator can perform during
with a known temperature and apply the changeover. Based on the complexity of the
black body tape to it and follow the se- PLC programming, making sure it is aware
quence below. of a calibration will be important if the cali-

How to troubleshoot and calibrate 4-20 mA 8


www.controldesign.com

brated black body item is not going to be in instrument may be in error, or your device
the exact temperature range. (PT, TT, FT, or valve) may not be receiving
— Michael Gorsky, sales specialist, voltage (check analog output point, check
Keyence, www.keyence.com
fuses, check wiring).

TROUBLESHOOT, CALIBRATE, Calibration instructions: Calibration of these


TEST AND PROGRAM devices will determine if they are accurately
I manage the instrumentation service group reading the process variable (flow, pressure
for Interstates. I have techs based in the or temperature), as well as verify that they
Midwest that troubleshoot and calibrate are accurately outputting the mA represent-
instrumentation on a daily basis. I ran across ing the measured variable. Special equip-
your questions and wanted to offer my ad- ment is needed for each type of device: a
vice regarding your request. I will touch on hand pump and pressure gauge for the PT;
each of the following areas below regarding a temperature calibrator (hot block) for the
your medical device cleaning skid, including TT; and a flow calibration skid for the FT.
pressure, temperature and flow devices, as
well as a control valve and a PLC. Finally, a mA meter will be needed for mea-
suring the output. It is recommended that
Troubleshooting: Each of your devices all of this special equipment is certified (for
should be sending a 4-20 mA single to the example, NIST traceable) to ensure it is ac-
PLC, and the PLC should be sending a 4-20 curate enough to serve as the reference for
mA to your control valve. I recommend the the calibration.
following if issues occur:
If, after the calibration testing, it is determined
First start by checking the signal to/from that any of the devices are outside of the pre-
each device. A good, non-intrusive method determined accuracy specs, adjustment can
of checking for this signal would be to use a be done to the device to bring it into toler-
clamp-on dc Amp meter, such as the Fluke ance. This is typically carried out by operating
773. This device allows for measuring the the user interface on the device (buttons and
current, without having to lift any wires. display, if equipped), or by communicating to
the device via HART communication, such as
If your loop current is above 20 mA, you HART 475 handheld device.
likely have an error in the device or a short
in the wiring. PLC testing and troubleshooting: The
instructions in the above section serve as a
If your loop current is below 4 mA , your good method for periodically testing the de-

How to troubleshoot and calibrate 4-20 mA 9


www.controldesign.com

vice. Typically, we perform the above checks does, the technology exists for commu-
for our clients’ instruments annually at the nicating, configuring and troubleshooting
very least. If any of the devices are critical to each of these devices without being on-
the process or to the safety of their opera- site. This is done by using HART-enabled
tors, we typically test them once per quarter. analog input/output cards, as well as
connecting the skid to the client’s network
Testing of the PLC: This is most easily done via Ethernet. To access the instruments
by simulating a 4-20 mA signal into the remotely, all that would be needed is a
inputs or the PLC (directly at the card) or VPN connection to the client’s network, as
measure the output of the PLC. If the PLC/ well as some special software to commu-
HMI is properly displaying the simulated nicate with the devices. Interstates com-
valve and outputting the measured value, it monly uses this technology to offer clients
is typically fair to assume that your PLC is troubleshooting advice, or even fix instru-
properly functioning. ment issues without being on-site.
—A
 dam Dittbenner, PE, instrumentation service man-
ager, Interstates Construction Services,
Add programming to PLC? Some additional
http://www.interstates.com/
programming to the PLC that could aid in CSIA, www.controlsys.org
certified systems integrator
troubleshooting and/or calibration would
be the following:
TROUBLESHOOT THE LOOPS
• Interlock bypassing: If there are any The temperature, pressure and flow sen-
control loops on the skid, it would be sors on the skid are most likely connected
beneficial to add a bypass button to the to 4-20 mA process transmitters. These
HMI that could be used during testing. For transmitters will accept the temperature
example, if the control valve is modulated sensor, flow sensor or pressure sensor
off of the signal received by one of the as input and in turn produce a 4-20 mA
devices (pressure, temperature or flow), it output signal, which is connected to the
would swing open or closed if the output PLC analog input channel. At some point,
of any of the devices is being simulated. a linear scaling would need to have been
A bypass button would allow for stopping implemented in the PLC software for each
the valve from moving, while simulating 4-20 mA loop in order to get the process
the output of any of the devices. readings in engineering units (°F or °C for
• Remote access to skid for monitoring and temperature, gpm for flow, psi for pres-
troubleshooting: Each of the instruments sure). For example, if the pressure sensor
and valves likely has HART communica- measures 0-30 psi and the transmitter
tion if it is an analog device. Assuming it produces 4-20 mA output, then a signal

How to troubleshoot and calibrate 4-20 mA 10


www.controldesign.com

of 4 mA is equal to 0 psi, and a signal CALIBRATION


of 20 mA is equal to 30 psi with a linear Periodic calibration is a vital procedure to
relationship (y = mx + b) in between these maintain seamless operation and optimize
points. Once this type of relationship is uptime for nearly all machines. But at what
programmed into the PLC for each chan- interval should you perform these peri-
nel, then assuming that everything else in odic maintenance operations? The answer
the loops is working properly the readings depends entirely on your individual opera-
should be correct. If the process readings tion, how the environment changes and
(temperature, pressure, flow) appear to how susceptible the instrumentation is to
be incorrect, then there could be several the change in environment. Periodic calibra-
reasons why. There could be an issue tion ensures that measurements are within
with the 4-20 mA loop wiring (broken or prescribed tolerance limits.
loose wire), loss of power supply (most
4-20 mA loops require 24 Vdc power) or Typically, calibrations are performed on
a defective transmitter. To troubleshoot an annual basis, but that could change
the loops, make a visual inspection of the based on the system requirement. Measur-
wiring and confirm that 24 Vdc power is ing environmental factors, such as shock,
in fact being provided by the loop power vibration and temperature, as well as opera-
supply by testing with a digital voltmeter. tional figures within the chosen tolerance,
If the wiring and power supply are veri- will help to build an historical basis upon
fied, then the transmitter can be checked which necessary calibration intervals can be
by disconnecting the 4-20 mA output determined. A robust accounting of system
signal from the PLC analog input and sub- health and operating figures will enable
stituting a 4-20 mA input from a process maintenance personnel to address possible
loop calibrator. With this type of calibra- issues before they escalate into inefficient
tor, a current value anywhere between operation or worse, downtime.
4 mA and 20 mA can be simulated to
verify that the PLC analog input chan- EtherCAT diagnostics are a standard feature
nel is reading correctly. If the PLC analog set in the EtherCAT fieldbus. This establishes
input channel reads correctly with the built-in topology recognition down to the in-
calibrator input but not when the actual dividual I/O terminals. EtherCAT system veri-
process transmitter output is connected, fication cannot only take place during start-
then most likely the transmitter needs to up; automatic read-in of the network is also
be replaced. possible (configuration upload). Bit faults
— Anthony Corvini, product manager, during data transfer are reliably detected
Omega Engineering, www.omega.com
through evaluation of the CRC checksum in

How to troubleshoot and calibrate 4-20 mA 11


www.controldesign.com

each EtherCAT device. Apart from breaking- Contact the manufacturer of whichever PLC
point detection and localization, the pro- that is being used and ask that question.
tocol, transfer physics and topology of the They will most likely say that no calibration is
EtherCAT system enable quality monitoring needed. They also publish analog input accu-
of each individual transmission segment. racy and it may even vary with temperature,
The automatic evaluation of the associated but again there are is nothing to adjust.
error counters enables precise localization of — Jim Rosner, lead industrial application engineer, con-
trols and power conversion division, Eaton,
critical network sections. Gradual or chang-
www.eaton.com/electrical
ing sources of error such as EMC influences,
defective connectors or cable damage are TWO-POINT SHIFT
detected and located. Verifying analog sensor readings are ac-
curate can improve product quality and
This diagnostic functionality provides an increase machine uptime. The use of this
excellent means to monitor system health, maintenance and troubleshooting proce-
particularly by leveraging the speed of the dure for a system containing a transmit-
EtherCAT industrial Ethernet system and ter with a 4-20 mA analog signal, receiver
the data management and analytics capa- (PLC) and possibly a loop power supply can
bilities of IoT solutions. System and pro- show you how to optimize your machine.
duction data can be accessed in real-time,
anywhere in the world, enabling analysis by Measure transmitter signal: The technician
decision-makers and/or engineers who may can measure the transmitter by removing
or may not be on-site. the wires to the PLC and checking the wires
— Andy Garrido and Sree Potluri, I/O specialists, Beck- from the transducer with a current meter
hoff Automation, www.beckhoff.com
to see if the device is producing 4-20 mA.
A signal present means the PLC input is
NO CALIBRATION NECESSARY bad and should be replaced. If the signal is
PLC analog inputs should not need calibra- not present, check the transmitter and loop
tion. As a matter of fact, how would you do power if present.
it when the analog modules have no adjust-
ments and are all solid-state components/ Transmitter loop power: Some transmit-
microprocessor chips? Calibrating the ters produce their own internal loop power,
transducers of the devices connected to the while other transmitters require an external
analog inputs should probably be done ev- loop power supply (Figure 1).
ery six months to a year, but there’s nothing
to calibrate/adjust on a PLC analog module If the system uses an external loop power
to my knowledge. supply, a digital multimeter (DMM) can be

How to troubleshoot and calibrate 4-20 mA 12


www.controldesign.com

EXTERNAL LOOP POWER


INTERNAL LOOP POWER

XMITER XMITER

+ +


– 4 to 20mA
PWR PWR
+
+ +

– –
PLC
PLC
+ +


LOOP POWER
Figure 1: Some transmitters produce their own internal loop power, while other transmitters require
an external loop power supply.

used to measure the power supply to see if Signal accuracy: In some cases, the accura-
it is producing at the correct voltage. If this cy of the process signal needs to be tested.
is faulty, the power supply needs to be re- It is recommended to use a high-quality
placed. If the power supply checks out, then process meter that is calibrated to calibrate
most likely the transducer is bad. the system. With most transducers, the
manufacture will supply the scaling for the
If the device has an internal loop power, a device in the data sheet. The information
DMM set in current mode can be used to provides the scale the device will produce
measure the signal at the transmitter. If the based on the 4-20 mA. For example, a tem-
signal is not present and the power sup- perature device may produce a -50 °C to
ply powering the device is good, then the 200 °C based on the 4-20 mA signal. Know-
transducer is bad. If the signal is present, ing this ratio allows the technician to supply
the same test can be done at the PLC input a 4-20 mA current into the system to see if
with the system’s wiring removed from the readout is correct.
the PLC input and the meter attached to
the transmitter wiring. If the signal is not Other times the system needs to be cali-
present at the PLC, the wiring needs to be brated to the application. This requires an
checked for loose or broken connections. external device to measure the amount of

How to troubleshoot and calibrate 4-20 mA 13


www.controldesign.com

Temperature indicated
by Controller
After offset
Upper limit of
set range, YH Upper-limit
(e.g., 260 C) temperature Input

Indicated temp. after Before offset


offset, X2 (e.g., 110 C)

Indicated temp. before


offset, Y2 (e.g., 105 C)

Indicated temp. before


offset, Y1 (e.g., 40 C)
Indicated temp. after
offset, X1 (e.g., 25 C)

Lower-limit
temperature Input
X1, Room temp. X2, Near set point Temperature
Lower limit of (e.g., 25 C) (e.g., 110 C) Indicated by
set range, thermometer
YL (e.g., 0 C)

TWO-POINT INPUT SHIFT


Figure 2: This example uses temperature, but this can be used for any linear application. The input
value is shifted at two points: near room temperature and near the set point. Check the temperature
of the sensing object with a calibrated device and the temperature indicated on the controller/dis-
play at both near room temperature and near the set point.

heat or flow. Then compare the reading from the external device to the actual sensor. In this
case, an offset may need to be entered into the raw signal the measuring device is produc-
ing. If this is the case, one way to do this is to take two separate readings. The further away
the two readings are, the more accurate the calibration will be. How accurate the system
needs to be determines if a single offset will be sufficient or if a two-point shift would need
to be implemented. With a single shift the slope remains the same and a positive or nega-
tive offset would be applied. Providing a two-point shift allows the ability to change the
slope of the overall readout.

The formula is a good way to determine what values are needed when doing a two-point
shift (Figure 2). The example is using temperature, but this can be used for any linear
application.

How to troubleshoot and calibrate 4-20 mA 14


www.controldesign.com

1. The input value is shifted at two points: near room temperature and near the set point.
Check the temperature of the sensing object with a calibrated device and the temperature
indicated on the controller/display at both near room temperature and near the set point.
2. Use the following formulas to calculate the upper-limit temperature value (offset) and
lower-limit temperature value (offset) settings based on the values checked above.

Lower-limit temperature input offset:

Example:

Upper-limit temperature input offset:

Example:

Set both the upper-limit and lower-limit temperature input offsets and then check the tem-
perature of the sensing object and the temperature indicated on the controller/display both
near room temperature and near the set point for accuracy.

Although two points were used, near room temperature and near the set point in the
example, accuracy can be increased further by using two points as far away from each
other as possible.

Entering the equations into a PLC can simplify the procedure by applying the offset auto-
matically to display values and establish a process.

Testing/validating of the analog values should be done on a scheduled basis. Typically the
manufacture of the device provides some guidance, but it is up to the design engineer to
ultimately decide when this should be done. Documentation should be provided to note the
time interval and values to be used for the calibrations.

How to troubleshoot and calibrate 4-20 mA 15


www.controldesign.com

Cleaning the devices should also be done direction. At the same time the act of
on a scheduled time basis. Since there are tightening connections has the potential
so many different types of devices that to solve issues and give you confidence
produce an analog output, check with the in the wiring as you move forward with
manufacture of the device to determine the further tests.
best way to clean the device. 2. Check your sensor or analog output
device: The goal of this step is to ensure
With these steps completed on a regular your sensor or other analog output de-
maintenance interval, your system can run vice is sending a reference signal. For this
more efficiently and produce better out- step, you will need a multimeter that can
comes. read either 0-20 mA or 0-10 Vdc, de-
— Keith Hill, product engineer, control components & re- pending on your reference signal.
lays, Omron Automation and Safety, www.omron.com

Whenever you test an analog reference, test


TROUBLESHOOT AND CALIBRATE it at the furthest point from the source. This
Troubleshooting analog circuits: There are will ensure you don’t just test the sensor’s
a number of different theories and tech- or analog output device’s ability to gener-
niques for troubleshooting analog circuits. ate the reference signal; you also test all the
As with any troubleshooting process, your wiring up to that point.
first goal is to narrow down the location of
the problems. From there you can get into For example, you have a 4-20 mA refer-
more specifics. I have put together a few of ence signal from a pressure mMeter being
the general steps that I typically take when fed into a PLC. You would want to confirm
confronting a potential analog issue. you are able to read 4-20 mA at the analog
input terminals of the PLC. Once again, this
1. Housekeeping: Let’s face it, we live in will ensure that not only are you generating
the real world. Lighting does strike, fork- a signal, but you are able to transmit it in
lifts do knock into enclosures, people your system, as well.
will crimp the insulation and vibration
does cause wires to work their way free. Utilizing your meter in its correct setting:
A quick inspection and tightening of • Measure the 0-20 mA current signal by
connection points can work wonders placing the probes in a series connection
to fix an issue. While rarely is there just with the circuit (break the circuit).
a single issue causing the problem, a • Or measure the 0-10 Vdc signal by placing
quick inspection can provide an initial the probes in parallel with the circuit.

How to troubleshoot and calibrate 4-20 mA 16


www.controldesign.com

One of my go-to tools for troubleshooting reference signal into the device, you can use
current analog references is my mA pro- this signal for your test. If you do not have
cess meter. This was different from your that reference you will need to find some
classic Amp meter because it could read way to create one to perform this test.
down to the 0-20 mA level. The benefit is
that you can read the current value without In the past I would keep a 9 Vdc battery
breaking the circuit. This is not only a time- and potentiometer in my bag for these
saver, but it eliminates the balancing act of types of situations. By wiring the two
trying to hold a meter, two probes and the together I could create a quick adjustable
signal wires at the same time. Additionally, current or voltage source to feed my analog
some of the more advanced versions can input device. By turning the potentiometer
generate a 0-24 mA or 0-10 Vdc signal for I could also confirm that the values seen in
testing analog input devices (this will be the PLC, HMI, ac drive or SCADA system
discussed in more detail in Step 3). were able to update in real time.

If you do not read an analog signal, per- Once you can confirm you are feeding your
form another test at the sensor or analog analog input device, you need to confirm
output device. If you are able to read a that it is properly reading that value. This
reference signal, you have a wiring issue. If step is dependent on the device in question.
you are not able to read a reference signal, If the device is a PLC, you will need to either
you have a sensor issue. log onto the software or create an object
on your touchscreen (HMI) to display this
If you are reading a signal, move on to the value. Otherwise the device will most likely
next step, checking the analog input device. have a sub menu, or at the very least status
lights that you can reference.
3. Check your analog input device: The goal
of this step is to ensure your analog input 4. Check for noise issues: These are some of
device is able to read the analog reference the more difficult issues to identify and fix.
that is being fed into it. To do this, you need The only real way to determine if you have
the ability to feed an active analog refer- a noise issue is to scope the analog input
ence into your device and the ability to read and see if you are experiencing a clean or
or confirm that the analog input device is “choppy” reference. Many times a system
reading said reference. that is experiencing noise-related issues
doesn’t have an issue all the time. In many
If you have performed Step 2 and confirmed cases it will only experience it when a large
via meter that you are actively feeding a load is turned on, or during certain times of

How to troubleshoot and calibrate 4-20 mA 17


www.controldesign.com

the day when other machines in your facility 1. Expose your sensor to a known process
are running at the same time. value.
2. Determine what value your analog input
If you determine you have a noise issue, the device interprets that known process
next course of action is to mitigate it. value to be.
• Ensure electrical connections are properly 3. Once you obtain those two points of data
terminated (connections are tight and above, you can subtract to determine if
wires are not crimped on the insulation). you have any error in your system.
• Ensure that signal wires are properly 4. If this error is determined to be outside
shielded and grounded. the acceptable range, you will then need
• Ensure the signal wires do not run parallel, to adjust your PLC settings/calculations
or close to, higher-voltage lines. to offset the difference.
• When possible, apply an input filter to the
analog reference to smooth out any short Before we run through an example, it’s
unwanted behavior. worth mentioning system accuracy. In this
case, accuracy is the difference between
For example, if in the course of your investi- the actual measured value and the value the
gation you determine that the analog refer- PLC interoperates it as in order to perform
ence experiences a large spike when Pump its calculations. The user needs to under-
Motor 3 starts up, first steps may include: stand this value and know at what point
•E
 nsure the signal wires are well clear of the process is affected by an error between
any of the power wires feeding Pump actual and interpreted values.
Motor 3.
• If possible, apply a ramp up to that motor Error is created and compounded by sev-
with either a soft start or ac drive. eral factors.
• If possible, apply a smoothing filter • Sensor accuracy to read the process value
across that PLC analog input, which • Sensor output resolution of the analog
will slow down the response time of the signal
system; however, it will ensure you are • Any noise or interference that is generated
getting a more reliable signal. in the transmission of that analog signal
• Your PLC input card’s resolution, filter and
Calibrating: This really depends on the ap- update time
plication and what aspect of your process
that you are trying to measure. However, Let’s give an example for your temperature
the basic process is still the same. sensor. For calibration to take place, you

How to troubleshoot and calibrate 4-20 mA 18


www.controldesign.com

will need a method to expose the tempera- ISOLATOR RECOMMENDATION


ture sensor to a known/calibrated tempera- Accuracy and consistency are crucial ele-
ture and a way to monitor what the PLC is ments in any machine or manufacturing
interpreting that value to be. process in the medical industry; we are
literally dealing with someone’s quality of
Every application is different, but when life and not just a machine production at the
possible I recommend removing the tem- end of it.
perature sensor and performing this test
independent of the machine. A popular Typically best practices and aids to trouble-
method for testing temperature probes is shoot are implemented not just from the
a calibrated bath; however methods need plant maintenance personnel, but should
to be evaluated on an application-by-ap- be a whole design philosophy from OEM
plication basis. engineering down. The tug of war between
production downtime for calibration and
Change the known/calibrated temperature verifications vs. loss of sales during that
the sensor is exposed to. Begin recording period can be lessened when a machine is
several data points relating known tem- designed to be not only accurate, but have
perature vs. PLC interoperated tempera- minimal downtime.
ture. The difference between these two
values is your error. A key design feature is to keep the cable
runs as short as possible. The longer the
If you determine the error above is not cable run, the more prone it is to errors or
acceptable in your application, you then fluctuations based on noise and surround-
will need to adjust your PLC settings and/ ing interference. If a cable has to be in
or code to compensate for this error. If place, we normally recommend an isolator
you’re lucky, the error is linear. These are for a couple of reasons.
the simplest to compensate for. Nonlinear
errors are not the end of the world; it will An isolator will prevent any voltage fluctua-
just require a bit more math to determine tion at the sensor itself since it controls/
the corrective equation to apply to your isolates the power and signal both to the
raw value. sensor and to the PLC. By decreasing any
potential voltage or current spikes, the lifes-
— Robert Ruber, product manager, Schneider Electric, pan of the instruments is extended and the
www.schneider-electric.us
calibration remains tighter.

How to troubleshoot and calibrate 4-20 mA 19


www.controldesign.com

An isolator with a split output will provide ging features and direct Modbus TCP con-
feedback or reassurance at the PLC and version. This conversion to a bus protocol
locally. The benefit of using a splitter is to now enables users to monitor the system
maintain the integrity of the signal from the from practically anywhere when combined
sensor without introducing excess imped- with cloud service. The set points and limits
ance into the line. Signal isolators and split- can be set via the HMI/PLC or via the user’s
ters enable the user to make measurements phone through a simple webpage.
both close to the sensor and down the line —A
 ndrew Barco, business development and
marketing manager, Weidmuller North America,
at the PLC.
www.weidmuller.com

When choosing isolators for 4-20mA sig- LOOK TO THE LOOP


nals, the important factor is to verify if it The most common problem in the simplest
can be configured to handle loop powered and most reliable method of transmitting
(sinking) or powered (sourcing) loops. One a sensor signal is the current loop. It has
unit to do it all greatly helps to reduce the two critical components: the signal and
training of the maintenance staff, and it can the power for the signal, all in just a pair
easily be replaced with one from stock no of wires. Its limitation for transmission is
matter what the input source is. Current the EMF of the transmitter, usually 24 Vdc.
measurement with Hall-effect sensors allow However, what if the sensor fails or the load
for simple wiring and the 4-20 mA signal opens or the operator doesn’t pay attention
can be fed into the PLC with limits and set or is absent?
point preconfigured on the isolators to
stop and cut off power if the currents get The same problem occurs in many critical
too high or low. To maintain the accuracy applications, including medical and nuclear.
of a temperature sensor, converting it to a Address those three important variables.
4-20 mA signal first maintains the accuracy Look for a solution that is powered by the
of the signal by eliminating any potential loop and detects and alarms if the signal
losses that might occur on long runs for fails, even post-mortem; that includes auto-
RTD or T/C wires. The 4-20 mA isolators tricolor bargraph with set points to warn
should provide the choice of cold junction the operator and PLC via serial I/O of the
compensation inside the isolator or via ex- alarm status; and that can monitor its 4-20
ternal devices. mA output to ensure load integrity via a
second loop-powered channel that moni-
As devices move toward Industry 4.0, we tors the output, as well.
increasingly see devices with onboard log- — Dr. Otto Fest, president, Otek, www.otekcorp.com

How to troubleshoot and calibrate 4-20 mA 20


www.controldesign.com

4 QUESTIONS the risk analysis and risk mitigation strat-


There are four questions to address here. egy for your control process, these device
1. Is the instrument working? calibrations may be completed on-site or
2. Is the instrument performing within ac- may require the devices to be sent back to
ceptable tolerances? a calibration provider.
3. C
 an periodic tests be performed in the
PLC to indicate an out-of-tolerance per- Using a calibration provider that is certified
formance? ISO17025 compliant means they are accred-
4. Can a control-system function automate ited by a third party, thus ensuring that all
any of these tasks? calibrations are completed by competent
personnel. A calibration provider will have
Is the instrument working? In typical control procedures where all instruments are cali-
systems where the measured instrument brated to their best capability.
provides a 4-20 mA signal to the control
system indicating the process variable, the These procedures are necessary to ensure
control system is blind to what this signal metrological traceability when following
actually represents and if it is actually work- the ISO17025 standard. The uncertainties
ing. Useful instrument diagnostic informa- of measurement devices are reduced when
tion can only be communicated via digital sending a measurement device back to a
network protocols like HART, Profibus, Eth- laboratory and—depending on the required
erNet/IP or Foundation Fieldbus. Without accuracy of the transducer—may determine
digital instrument data the only indication how it is calibrated.
a control system might get that I/O signals
are not working properly would be from The fastest way to complete calibrations
I/O card diagnostics, if available. Examples will be on-site. However, on-site calibrations
would be short circuit detection and over/ may increase the transducer inaccuracy as
under voltage and current. Today, most compared to the factory-delivered speci-
4-20 mA instruments have HART function- fication. If this increased inaccuracy is not
ality, so if your control system I/O cards acceptable for your risk-mitigation strategy,
have HART modems on them, instrument it will require replacing the device with a
diagnostic data can be obtained. newly calibrated transducer kept in stock or
simply sending it to a calibration provider
Is the instrument performing within accept- to meet factory accuracy.
able tolerances? In order to know whether
instrument measurements are in tolerance After ensuring the measurement device has
requires regular calibration. Depending on been properly ranged and put back in the

How to troubleshoot and calibrate 4-20 mA 21


www.controldesign.com

process, a loop calibration is then neces- procedures for calibration and verification
sary to make sure that all of the remaining stated in the prior question have been fol-
control items are within specifications. This lowed, then confidence can be high that the
will require using a traceable multimeter to process is not running properly, and appro-
simulate the process variable input of the priate action can be taken.
control loop.
Can a control system automate any of
Having completed an instrument/loop cali- these tasks? The only function that cannot
bration, a customer can then be confident be automated via the control system is the
that the process is now in control and the calibration process. This involves techni-
measurement device is functioning within cians performing the work. There are instru-
factory specifications from the manufacturer. ments coming into the marketplace that will
perform onboard verifications and indicate
Can periodic tests be performed in the back to the control system if a device has
PLC to indicate an out-of-tolerance perfor- failed a verification. This technology will
mance? Yes, it can, if normal/typical run- begin to address automating evaluation of
ning process conditions can be determined. device performance, but it is not a true cali-
Programmed upper and lower control limit bration and thus users still have to deter-
tests can be applied to any process vari- mine if a verification can adequately reduce
able indicating when the measurement has the out-of-tolerance risk in any particular
drifted outside a predetermined accept- process application.
able tolerance. The PLC can be set to alarm — Michael Robinson, national marketing manager,
Endress+Hauser, us.endress.com
users through the operator interface. If the

How to troubleshoot and calibrate 4-20 mA 22