You are on page 1of 2

1 No of Story 11

Length(ft) 20.42 O11


Width(ft) 12
Thickness(in) 5 Slab load(kip) 62.5 X 11 X
Beam Area 1(in2) 240 Beam Load(Kp) 240 / 144 X
Beam 1Length(ft) 32.42 Wall load(kp) 0.4 X 32.4 X
Beam Area 2(in2) 216 F finish(kp) 25 X 11 X
Beam 2Length(ft) 0 Random load(kp) 40 X 10 X
Wall 1(kip/ft) 0.4 Column Load(kp) 432 / 144 X
Wall 1 Length 32.42
Wall2(kip/ft) 0 Total DeadLoad(kp)
Wall 2 Length 10 Total Live Load (KP) 40 x 10.3 x
Floor height 10
Floor Finish(psf) 25
R.Wall (psf) 40 TotalUnfactored Load
Col.area(in2) 432
L. load (psf) 40 Total FactoredLoad

LL Factor 1.7 Magnifying factor


Dl Factor 1.4

Column information
B 18 in Pu= 0.52 ( 0.85 x
H 24 in P=
As% 1.5
As 6.48 in2
f'c 2.5 ksi
fy 40 ksi
O11
Kip
20.42 X 12 / 1000 168.465
150 X 32 X 12 97.26
10 129.68
20.42 X 12 / 1000 67.386
20.42 X 12 / 1000 98.016
116 X 150 / 1000 52.20

613.0
20.42 x 12 / 1000 100.466

713.5

1029

2.5 ( 432 - 6.48 ) + 40 x 6.48 ) = 604.984


1029

UNSATISFACTORY