Project: ETAP Page: 1

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable8 Size (mm2) 300 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.60
From Bus Bus8 Insulation XLPE Sheath type None
To Bus Bus14 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 3.20
Length (m) 30.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
337.70 (A) Derated
Operating 40 90 50 249.25 343.00 337.70

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 249.3 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.728 1.00 27.728
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 300 337.70 0.02 Short-Circuit Overload
Optimal Size 1 300 338.00 0.02 0.00 299
1 Size Smaller 1 240 297.00 0.02 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 249.3
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 337.70
Base Capacity It* 343.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 2

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable10 Size (mm2) 300 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.60
From Bus Bus9 Insulation XLPE Sheath type None
To Bus Bus15 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 3.20
Length (m) 30.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
337.70 (A) Derated
Operating 40 90 50 156.07 343.00 337.70

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 156.1 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.288 1.00 27.288
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 300 337.70 0.01 Short-Circuit Overload
Optimal Size 1 300 338.00 0.01 0.00 294
1 Size Smaller 1 240 297.00 0.01 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 156.1
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 337.70
Base Capacity It* 343.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 3

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable12 Size (mm2) 300 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.60
From Bus Bus14 Insulation XLPE Sheath type None
To Bus Bus19 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 3.20
Length (m) 45.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
337.70 (A) Derated
Operating 40 90 50 163.42 343.00 337.70

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 163.4 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.648 1.00 27.648
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 300 337.70 0.02 Short-Circuit Overload
Optimal Size 1 300 338.00 0.02 0.00 298
1 Size Smaller 1 240 297.00 0.02 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 163.4
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 337.70
Base Capacity It* 343.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 4

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable13 Size (mm2) 300 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.60
From Bus Bus14 Insulation XLPE Sheath type None
To Bus Bus23 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 3.20
Length (m) 45.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
337.70 (A) Derated
Operating 40 90 50 85.86 343.00 337.70

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 85.86 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.648 1.00 27.648
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 300 337.70 0.01 Short-Circuit Overload
Optimal Size 1 300 338.00 0.01 0.00 298
1 Size Smaller 1 240 297.00 0.01 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 85.86
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 337.70
Base Capacity It* 343.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 5

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable14 Size (mm2) 300 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.60
From Bus Bus15 Insulation XLPE Sheath type None
To Bus Bus24 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 3.20
Length (m) 45.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
337.70 (A) Derated
Operating 40 90 50 21.09 343.00 337.70

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 21.09 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.288 1.00 27.288
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 300 337.70 0.00 Short-Circuit Overload
Optimal Size 1 300 338.00 0.00 0.00 294
1 Size Smaller 1 240 297.00 0.00 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 21.09
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 337.70
Base Capacity It* 343.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 6

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable15 Size (mm2) 300 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.60
From Bus Bus15 Insulation XLPE Sheath type None
To Bus Bus18 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 3.20
Length (m) 45.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
337.70 (A) Derated
Operating 40 90 50 134.98 343.00 337.70

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 135 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.432 1.00 27.432
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 300 337.70 0.01 Short-Circuit Overload
Optimal Size 1 300 338.00 0.01 0.00 296
1 Size Smaller 1 240 297.00 0.02 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 135
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 337.70
Base Capacity It* 343.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 7

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable16 Size (mm2) 300 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.60
From Bus Bus23 Insulation XLPE Sheath type None
To Bus Bus18 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 3.20
Length (m) 30.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
337.70 (A) Derated
Operating 40 90 50 7.01 343.00 337.70

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 7.01 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.520 1.00 27.520
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 300 337.70 0.00 Short-Circuit Overload
Optimal Size 1 300 338.00 0.00 0.00 297
1 Size Smaller 1 240 297.00 0.00 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 7.01
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 337.70
Base Capacity It* 343.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 8

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable17 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus19 Insulation XLPE Sheath type None
To Bus Bus27 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 1360.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 94.24 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 94.24 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.058 1.00 27.058
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.45 Short-Circuit Overload
Optimal Size 1 300 338.00 0.31 0.00 292
1 Size Smaller 1 240 297.00 0.36 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 94.24
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 9

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable19 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus29 Insulation XLPE Sheath type None
To Bus Bus27 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 120.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 47.64 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 47.64 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 19.562 1.00 19.562
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.02 Short-Circuit Overload
Optimal Size 1 240 297.00 0.02 0.00 211
1 Size Smaller 1 185 256.00 0.02 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 47.64
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 10

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable20 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus31 Insulation XLPE Sheath type None
To Bus Bus29 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 145.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 28.26 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 28.26 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 19.470 1.00 19.470
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.01 Short-Circuit Overload
Optimal Size 1 240 297.00 0.01 0.00 210
1 Size Smaller 1 185 256.00 0.01 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 28.26
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 11

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable22 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus18 Insulation XLPE Sheath type None
To Bus Bus31 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 1550.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 85.33 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 85.33 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.432 1.00 27.432
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.46 Short-Circuit Overload
Optimal Size 1 300 338.00 0.32 0.00 296
1 Size Smaller 1 240 297.00 0.37 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 85.33
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 12

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable26 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus39 Insulation XLPE Sheath type None
To Bus Bus37 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 1000.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 2.07 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 2.07 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 16.216 1.00 16.216
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.01 Short-Circuit Overload
Optimal Size 1 185 256.00 0.01 0.00 175
1 Size Smaller 1 150 225.00 0.01 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 2.07
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 13

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable27 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus35 Insulation XLPE Sheath type None
To Bus Bus33 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 1000.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 6.23 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 6.23 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 18.176 1.00 18.176
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.02 Short-Circuit Overload
Optimal Size 1 240 297.00 0.02 0.00 196
1 Size Smaller 1 185 256.00 0.02 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 6.23
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 14

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable28 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus37 Insulation XLPE Sheath type None
To Bus Bus35 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 1000.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 3.77 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 3.77 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 14.941 1.00 14.941
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.01 Short-Circuit Overload
Optimal Size 1 185 256.00 0.01 0.00 161
1 Size Smaller 1 150 225.00 0.02 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 3.77
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 15

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable29 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus33 Insulation XLPE Sheath type None
To Bus Bus19 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 1000.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 36.23 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 36.23 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.058 1.00 27.058
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.13 Short-Circuit Overload
Optimal Size 1 300 338.00 0.09 0.00 292
1 Size Smaller 1 240 297.00 0.10 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 36.23
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 16

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable31 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus39 Insulation XLPE Sheath type None
To Bus Bus18 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 1500.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 32.44 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 32.44 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.432 1.00 27.432
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.17 Short-Circuit Overload
Optimal Size 1 300 338.00 0.12 0.00 296
1 Size Smaller 1 240 297.00 0.14 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 32.44
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 17

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable33 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus41 Insulation XLPE Sheath type None
To Bus Bus19 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 1000.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 33.06 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 33.06 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.058 1.00 27.058
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.12 Short-Circuit Overload
Optimal Size 1 300 338.00 0.08 0.00 292
1 Size Smaller 1 240 297.00 0.09 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 33.06
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 18

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable35 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus47 Insulation XLPE Sheath type None
To Bus Bus41 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 1960.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 15.81 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 15.81 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 17.955 1.00 17.955
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.11 Short-Circuit Overload
Optimal Size 1 240 297.00 0.09 0.00 194
1 Size Smaller 1 185 256.00 0.11 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 15.81
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 19

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable36 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus45 Insulation XLPE Sheath type None
To Bus Bus47 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 1825.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 3.99 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 3.99 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 11.036 1.00 11.036
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.03 Short-Circuit Overload
Optimal Size 1 120 199.00 0.04 0.00 119
1 Size Smaller 1 95 174.00 0.05 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 3.99
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 20

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable37 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus49 Insulation XLPE Sheath type None
To Bus Bus45 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 2530.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 7.03 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 7.03 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 8.804 1.00 8.804
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.06 Short-Circuit Overload
Optimal Size 1 95 174.00 0.11 0.00 95
1 Size Smaller 1 70 145.00 0.15 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 7.03
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 21

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable38 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus43 Insulation XLPE Sheath type None
To Bus Bus49 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 2525.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 7.03 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 7.03 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 10.098 1.00 10.098
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.06 Short-Circuit Overload
Optimal Size 1 120 199.00 0.09 0.00 109
1 Size Smaller 1 95 174.00 0.11 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 7.03
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 22

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable40 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus43 Insulation XLPE Sheath type None
To Bus Bus18 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 3550.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 10.78 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 10.78 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.432 1.00 27.432
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.13 Short-Circuit Overload
Optimal Size 1 300 338.00 0.09 0.00 296
1 Size Smaller 1 240 297.00 0.11 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 10.78
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 23

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable42 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus53 Insulation XLPE Sheath type None
To Bus Bus23 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 185.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 92.74 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 92.74 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 27.520 1.00 27.520
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.06 Short-Circuit Overload
Optimal Size 1 300 338.00 0.04 0.00 297
1 Size Smaller 1 240 297.00 0.05 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 92.74
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 24

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable44 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus59 Insulation XLPE Sheath type None
To Bus Bus53 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 160.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 72.50 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 72.5 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 25.054 1.00 25.054
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.04 Short-Circuit Overload
Optimal Size 1 300 338.00 0.03 0.00 270
1 Size Smaller 1 240 297.00 0.03 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 72.5
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 25

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable45 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus60 Insulation XLPE Sheath type None
To Bus Bus59 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 270.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 54.36 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 54.36 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 23.487 1.00 23.487
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.05 Short-Circuit Overload
Optimal Size 1 300 338.00 0.04 0.00 253
1 Size Smaller 1 240 297.00 0.04 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 54.36
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 26

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable46 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus61 Insulation XLPE Sheath type None
To Bus Bus60 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 535.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 36.18 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 36.18 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 21.079 1.00 21.079
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.07 Short-Circuit Overload
Optimal Size 1 240 297.00 0.05 0.00 228
1 Size Smaller 1 185 256.00 0.07 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 36.18
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 27

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable47 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus62 Insulation XLPE Sheath type None
To Bus Bus61 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 2650.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 20.29 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 20.29 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 17.360 1.00 17.360
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.19 Short-Circuit Overload
Optimal Size 1 240 297.00 0.15 0.00 187
1 Size Smaller 1 185 256.00 0.19 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 20.29
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 28

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable48 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus63 Insulation XLPE Sheath type None
To Bus Bus62 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 955.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 3.22 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 3.22 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 10.193 1.00 10.193
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.01 Short-Circuit Overload
Optimal Size 1 120 199.00 0.02 0.00 110
1 Size Smaller 1 95 174.00 0.02 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 3.22
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 29

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable50 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus64 Insulation XLPE Sheath type None
To Bus Bus63 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 4700.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 14.46 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 14.46 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 11.907 1.00 11.907
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.24 Short-Circuit Overload
Optimal Size 1 150 225.00 0.29 0.00 129
1 Size Smaller 1 120 199.00 0.35 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 14.46
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])


Project: ETAP Page: 30

Location: 18.0.0D Date: 17-08-2018

Contract: SN: DLR-MUMBAI

Engineer: Revision: Base

Filename: 33KV_11KV SUBSTATION

Cable Summary Report (IEC 60502-2)

General Library Physical


ID Cable52 Size (mm2) 185 Jacket type: PVC
Tag # N/A Source Caled BS6622 Jacket thickness (mm) 3.20
From Bus Bus64 Insulation XLPE Sheath type None
To Bus Bus24 kV 11.0 Sheath thickness (mm)
No./Cable 3/C % Class 100 Armor type St Armor/30dg/25w
No. Cond/Phase 1 Installation Non-Mag. Armor thickness (mm) 2.50
Length (m) 2330.000 Conductor Type AL Armor/Sheath Grounding Open
Shield Grounding Open
Shield thickness (mm) 0.127

Allowable Ampacity - Current Carrying Capacity


Ambient Temperature Conductor Temperature RHO Ampacity / Capacity Result Allowable Ampacity / Capacity
Base 20 90 150 Operating Base Derated
255.75 (A) Derated
Operating 40 90 50 21.09 262.00 255.75

Additional Derating Factors


User-Defined

Sizing Constraints Protective Device


Loading (Amps) 21.09 None In(A) I2(A)
Overload
%Vd 2 @ 11 kV
%Vst Overcurrent User-Defined Seconds kA Rating (A)
Short-Circuit (kA) 26.602 1.00 26.602
(Phase)
Overload (kA) Trip (mA) Time (ms)
3rd Harmonic % None
RCD/GFCI

Optimal Conductors Results


#/Ph Size Ampacity %Vd* %Vst Minimum. Size (mm2)
Existing Size 1 185 255.75 0.17 Short-Circuit Overload
Optimal Size 1 300 338.00 0.12 0.00 287
1 Size Smaller 1 240 297.00 0.14 0.00
* (%Vd @ 11 kV)

Cable Sizing (A)


Design Current Ib 21.09
PD Rating In
Overload Setting Ir*
Derated Capacity Iz 255.75
Base Capacity It* 262.00

* ([It >= Iz] , [Ir >= Ib])