TABLE OF CONTENTS
VAMC Heinz i
1.0 EXECUTIVE SUMMARY
1.1 General
This summary report contains the results of analyses performed on the electrical
distribution system for the H.J. Heinz Medical Center, Aspinwall, Pennsylvania. The
purpose of this study is to evaluate the existing electrical system. data and
necessary modeling assumptions are provided under Section 6.
Revision two included the analysis of Building #71.
Revision three includes the analysis of new equipment that includes ATS-4, ATS-4A,
ATS-5A, ATS-5B, ATS-6A, ATS-6B, ATS-7A, DP-CR, and an enclosed breaker that
feeds ATS-4.
1.2 Objectives
1. Short-Circuit Analysis
Perform a short-circuit study on the electrical distribution system shown in order to
determine the available fault current at pertinent locations throughout the distribution
system. The scope of the study includes:
• Analysis begins at the incoming 4.16 kV utility service, continues through the low
voltage substations, and ends at the low voltage panelboards and motor control
centers, as shown on the one-line diagrams in Section 10.0.
The available fault currents determined by the short-circuit study will be used in the
electrical distribution analyses.
2. Equipment Evaluation
Evaluate the short-circuit ratings of existing protective devices and other distribution
equipment supplied by Eaton under this contract.
3. Coordination Study
Review the existing system overcurrent protection and coordination. Where
applicable, provide suggestions for improvement.
5. Recommendations
Provide specific recommendations for improving the electrical distribution system
performance and correcting any deficiencies found by the studies.
1. Short-Circuit Study
Cases for normal and emergency operation are evaluated. See Section 2, Section 7,
and Section 8 for more information.
2. Equipment Evaluation
The Equipment Evaluation is based on the power system worst-case short-circuit
current configuration. The short-circuit ratings of protective devices and other
distribution equipment are evaluated in Section 2, Table 2.1.
In summary of Table 2.1, Table 2.2, and Table 2.3 all equipment included in the
Building #71 addition has passed the equipment evaluation.
In summary of Table 2.1, the following equipment failed the equipment evaluation. It
is recommended that the overdutied panelboards be reviewed for breaker and/or
panelboard replacement to comply with the short-circuit current ratings required.
• Building 32 Panelboards B32-PNLA and B32-PP32B1
• Building 50 Panelboards B50U1-1ALA, B50U1-EC1E, B50U1-GALA, and
B50U1-GAPC
• Building 51 Panelboards B51A2-1ALE and B51A2 GALC.
• Building 50 Panelboard B50U1-ECGE
In summary of Table 2.1, Panelboard B50U1-ECGE in Building 50 has failed the
equipment evaluation and are considered overdutied. This panelboard must be
series rated in order to pass the equipment evaluation. "Series-rated" distribution
equipment must be labeled in accordance with NEC Articles 110.22 and 240.86.
The short-circuit withstand ratings of low voltage disconnect switches are not
evaluated in this study. Care should be taken in order to ensure that these devices
are applied within their UL listed short-circuit withstand ratings. The typical withstand
ratings for Cutler-Hammer disconnect switches (safety switches) range from 10,000A
to 200,000A for certain fused types.
See Section 2 for detailed analysis and evaluation results.
3. Coordination Study
The time-current coordination plots of the protective overcurrent devices are shown
in Section 3. In developing the device settings, consideration was given to the
isolation of faults, protection of cables, and protection of transformers.
Efforts were made to provide the best coordination possible with the existing
protective devices. It should be understood that coordination between two
instantaneous trip units cannot be achieved for fault levels above the instantaneous
pickup of the upstream device. There is some overlapping of curves that cannot be
avoided.
All of the adjustable low voltage electronic trip and thermal magnetic circuit breakers
and medium voltage equipment should be tested and adjusted according to the
recommended settings given in Section 4.
2.1 General
The short-circuit study determines the fault currents that flow in the system during
various fault conditions. A system model was created using SKM Systems Analysis
software. The calculated fault currents are used in the device evaluation and
coordination studies. See Section 7 and Section 8 for the computer generated input
data and output data. NEC-2014, Article 110.24(A) requires that service entrance
equipment is labeled with the following pieces of information:
• Maximum available fault current
• Date on which the fault current was calculated
Article 110.24(B) adds that if there is a modification that may change this fault
current value, it must be recalculated. The field marking must be updated to reflect
the new value of maximum fault current.
Separate “Z” (complex), “X” (reactive), and "R" (resistive) networks are used for the
short-circuit analysis. Complex network reduction and the relationship E/Z are used
to calculate the fault current magnitude and angle at each faulted bus. The complex
equivalent circuit impedance, Z, is calculated by the reduction of the “Z” (complex)
network. The X/R ratios calculated for each fault condition are based on the separate
reduction of the X and R networks. These X/R ratios are used for the calculation of
fault duty multipliers, to evaluate the short-circuit ratings of system components.
The software is capable of generating three types of short-circuit reports for both
balanced (three-phase bolted) and unbalanced (line-to-ground) faults. The reports
that are generated depend on the system that is being evaluated.
The three types of short-circuit reports are:
• Fault Report (for low voltage)
• Momentary Duty Report (for medium voltage)
• Interrupting Duty Report (for medium voltage)
1. Fault Report
The fault currents reported in the “Fault Report” are applicable to low voltage devices
and components. The fault currents calculated in this report are based on the
contribution data derived from IEEE Std C37.13™. The fault currents are calculated
as follows:
• Motor and generator subtransient reactance values (Xd”) are adjusted per the
first cycle duty multipliers described in IEEE Std 141™.
• The complex equivalent circuit impedance, Z, is calculated by network reduction
of the “Z” (complex) network.
• The momentary symmetrical current = E/Z.
• The X/R ratio is equal to the equivalent circuit reactance, X, divided by the
equivalent circuit resistance, R. As discussed above, X is calculated by the
reduction of the “X” (reactive) network and R is calculated by the reduction of the
“R” (resistive) network.
Impedance Impedance
(First Cycle (Interrupting
Machine Type Duty) Duty)
Turbine generators,
Condensers,
1.0 Xd" 1.0 Xd"
Hydrogenerators with
amortisseur windings
2.2 Objectives
The objective of the short-circuit analysis is to calculate the maximum short-circuit
currents produced by balanced three-phase and unbalanced faults at each bus
shown on the one-line diagrams.
1. Short-Circuit System Model
The system was modeled for worst-case fault currents. Short-circuit currents were
calculated for a three-phase bolted fault and single-line-to-ground fault at each bus
shown on the study one-line diagrams.
a) Evaluated Short-Circuit Cases:
The following short-circuit study cases were evaluated:
(*N1) System X/R higher than Test X/R, Calc INT kA modified based on low voltage factor.
Note: Panelboards B32-A1 and B32-B1 are applied at approximately 98% of their interrupting current rating.
(*N1) System X/R higher than Test X/R, Calc INT kA modified based on low voltage factor.
3.1 General
The protective device coordination study determines overcurrent protective relay and
circuit breaker settings in order to provide an optimal compromise between protection
and selectivity.
3.2 Objectives
Using the appropriate maximum fault currents, the time-current coordination curves were
plotted as operating time versus current magnitudes to show protective device tripping
and/or clearing characteristics and coordination among these devices.
Consideration was given to provide both selective isolation of faults and maximum
protection of equipment such as cables, transformers, motors, etc.
To achieve the optimum protection and selectivity, the following guidelines were followed
throughout the study:
1. Ideally, the settings of any overcurrent device should be high enough to permit
the continuous full-load operating capacity of the cables and the equipment they
supply, and to ride through system temporary disturbances such as in-rush current.
On the other hand, the settings should be low enough to provide overload and short-
circuit protection under minimum fault conditions.
2. Considering any two protective devices in series:
• The maximum available fault current at the downstream device
determines the upper limit of the coordination range between these two devices.
• The minimum available fault current at the downstream device or the
pick-up setting of the upstream device determines the lower limit of the
coordination range.
• Series instantaneous devices do not coordinate unless there is sufficient
impedance between the two devices.
• When plotting coordination curves, certain time intervals must be
maintained between the curves in order to ensure correct selectivity. These time
intervals vary, depending on the device types. In general, however, the following
must be taken into consideration when determining the appropriate time
separation interval: Breaker clearing time, relay tolerances, induction disk over-
travel, and a reasonable safety margin for error.
3. Motors
The motors should have appropriate protective devices to meet the basic protection
requirements for overloads and fault current withstand values. In addition, the motor
short-circuit and ground fault protective devices should be set to ride through motor
starting current.
• R-B55-SGA-MAIN
• R-B55-SGB-MAIN
• R-B55-SGA-11
• R-B55-SGB-15
• 71-DPBH-MAIN
• 71-DSBL-MAIN
• B71-DSWG-T-1
• 71-DSBL-71-1LA
• 71-DSBL-71-1LB
• 71-DSBL-71-1LC
• 71-DSBL-71-1LD
• 71-DSBL-71-1LF
• 71-DSBL-71-1LG
• 71-DSBL-71-1LH
• 71-DSBL-71-1LI
• B71-DSWG-71-BHA
• B71-DSWG-71-1HC
• B71-DSWG-71-1HA
• B71-DSWG-ATS-ELEV (Note: The LTPU was increased to 1.0)
100
10K
1K
1 10
1000 1000
R-B55-SGA-MAIN R-B55-SGA-10
CUTLER-HAMMER
50P/51P, 5A Rated
TYPE: FP-5000 CBL-0225
CT Ratio 600 / 5 A Size: 1 - 500 AWG/kcmil
Settings Phase
51P PH 1.7 (1020A) F-B50U1
100 100
I2t 10 125 AS,
50P-1 PH 7 (4200A)
Delay, 50P-1 30 T-B50U1
750.0 kVA
B50U1-MSB-MAIN
3200 AS,
R-B55-SGA-10
CUTLER-HAMMER
Phase Settings
TYPE: Digitrip 3000
10 CT Ratio 400 / 5 A 10
Settings Phase
LDPU 1.3 (520A)
I4T 6
SDPU 8 (3200A)
TIME IN SECONDS
SDT 0.2
INST 10 (4000A)
T-B50U1
750 kVA
4160 / 208 V
1 1
B50U1-MSB-MAIN
WESTNHOUSE
DIGTRP RMS
TYPE: DS
Sensor/Trip: 3200A, Settings Phase
LTPU 0.8 (2560A)
LTD 4.0
STPU 3.0 (9600A)
STD-I2T 0.4 (I^2t Out)
INST 12.0 (38400A) CBL-0225
Size: 500 AWG/kcmil
Qty/Ph: 1
TX Inrush
0.10 0.10
F-B50U1
GOULD SHAWMUT
TYPE: CS-3, 5.5kV E-Rated
Sensor/Trip: 125A, Settings Phase
125 Amps
0.01 0.01
100
1K
10K
0.5 1 10
100
10K
1K
0.5 1 10
1000
T-B32-T2
1000 kVA
4160 / 480 V
R-B55-SGA-MAIN
R-B55-SGA-MAIN B55-SGA
CUTLER-HAMMER 4160.0 V
50P/51P, 5A Rated
TYPE: FP-5000 R-B55-SGA-11
Phase
51P PH 2 (1200A) CBL-0650
I2t 10 Size: 1 - 500 AWG/kcmil
100
50P-1 PH 7 (4200A)
Delay, 50P-1 48 F-B32-T2
200 AS,
P
T-B32-T2
S 1000.0 kVA
B32-MDS-MAIN
1600 AS, 1600 AT
10
TIME IN SECONDS
B32-MDS-MAIN
CUTLER-HAMMER
LSI, 1600AF, 1600A Plugs
TYPE: Magnum DS, RMS 520
Sensor/Trip: 1600A, Plug: 1600 AT
Phase
LTPU (0.4-1.0 x P) 1 (1600A) 1
LTD (2-24 Sec.) 15
STPU (2-12 x LTPU) 6 (9600A)
STD (0.1-0.5 Sec.) 0.5 (I^2t Off)
CBL-0650
F-B32-T2 Size: 500 AWG/kcmil
COOPER Qty/Ph: 1
18C-200C
TYPE: NX (C-Rated), 4.3kV
R-B55-SGA-11 Sensor/Trip: 200A, Phase TX Inrush
CUTLER-HAMMER 200.0 Amps 0.10
Phase Settings
TYPE: Digitrip 3000
Phase
LDPU 1.5 (600A)
I2T 17.5
SDPU 8.5 (3400A)
SDT 0.25
INST 15 (6000A)
0.01
100
10K
1K
0.5 1 10
1000
R-B55-SGA-MAIN
CUTLER-HAMMER R-B55-SGA-MAIN
50P/51P, 5A Rated
TYPE: FP-5000 B55-SGA
Phase 4160.0 V
51P PH 2 (1200A)
I2t 10 R-B55-SGA-8
50P-1 PH 7 (4200A)
Delay, 50P-1 48 CBL-0227
100
Size: 1 - 500 AWG/kcmil
F-B52
125 AS,
P
S T-B52
750.0 kVA
B52-MSG-MN
1200 AS,
R-B55-SGA-8
CUTLER-HAMMER
Phase Settings
TYPE: Digitrip 3000 10
Phase
LDPU 0.9 (360A)
I4T 6
SDPU 7 (2800A)
SDT 0.1
TIME IN SECONDS
INST 8 (3200A)
T-B52
750 kVA
4160 / 480 V
B52-MSG-MN
GE PWRBK 2 1
100-2000A
TYPE: MVT+PM STD
Sensor/Trip: 1200A, Phase
LTPU 0.9; 1 (1080A)
LTD 2
STPU 4.0 (4320A)
STD-I2T MAX (I^2t Off)
CBL-0227
Size: 500 AWG/kcmil
Qty/Ph: 1
TX Inrush
0.10
F-B52
GE
25-900A
TYPE: 9F62 EJ0-1, 5.5kV
Sensor/Trip: 125A, Phase
125 Amps
0.01
100
10K
1K
0.5 1 10
1000
R-B55-SGA-MAIN
CUTLER-HAMMER
50P/51P, 5A Rated R-B55-SGA-MAIN
TYPE: FP-5000
Phase B55-SGA
51P PH 2 (1200A) 4160.0 V
I2t 10
50P-1 PH 7 (4200A) R-B55-SGA-9
Delay, 50P-1 48
CBL-0226
Size: 1 - 500 AWG/kcmil
B52-SW-CHILL-B52
4160.0 V 100
F-B52-CHILLERS
300 AS,
B52-CHILL-1
4160.0 V
582.8 Hp F-B52-CHILL-1
100 AS,
M-B52-CHILL-1
500.0 hp
10
TIME IN SECONDS
R-B55-SGA-9
CUTLER-HAMMER
Phase Settings
TYPE: Digitrip 3000
Phase
LDPU 1 (300A)
I2T 20
SDPU 10 (3000A)
1
SDT 0.2
INST 15 (4500A)
CBL-0226
F-B52-CHILLERS Size: 500 AWG/kcmil
GOULD SHAWMUT Qty/Ph: 1
TYPE: CS-3, 5.5kV E-Rated
Sensor/Trip: 300A, Phase
300 Amps
0.10
F-B52-CHILL-1
WESTNHOUSE
4.3-5.5
TYPE: CLS 1/2 R
Sensor/Trip: 100A, Phase
Opening Clearing Curve
0.01
100
10K
1K
1 10
1000 1000
R-B55-SGB-MAIN
B55-SGB
4160.0 V
100 100
R-B55-SGA-TIE-SGB
B55-SGA
4160.0 V
R-B55-SGA-10
10 10
TIME IN SECONDS
CUTLER-HAMMER
FP-5000
FP5100-00
Settings Ground
51R PH 0.15 (90A)
ANSI Moderately Inv 0.3
50R-1 PH 1 (600A)
1 1
Delay, 50R-1 24
CUTLER-HAMMER
Digitrip 3000
DT-3100
Settings Ground
LDPU 0.1 (60A)
ANSI MOD 0.2
SDPU 0.5 (300A)
SDT 0.1
0.10 0.10
CUTLER-HAMMER
Digitrip 3000
DT-3100
Settings Ground
LDPU 0.5 (25A)
ANSI MOD 0.1
INST 2.5 (125A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
0.5 1 10
1000
R-B55-SGA-MAIN
B55-SGA
4160.0 V 100
R-B55-SGA-11
R-B55-SGA-TIE-SGB
R-B55-SGA-TIE-SGB
CUTLER-HAMMER
Phase Settings
TYPE: Digitrip 3000
phase new device
LDPU 1.2 (720A)
I2T 9
10
SDPU 6 (3600A)
SDT 0.5
TIME IN SECONDS
R-B55-SGA-11 R-B55-SGA-MAIN
CUTLER-HAMMER CUTLER-HAMMER
Phase Settings 50P/51P, 5A Rated
TYPE: Digitrip 3000 TYPE: FP-5000
Phase Phase
LDPU 1.5 (600A) 51P PH 2 (1200A) 1
I2T 17.5 I2t 10
SDPU 8.5 (3400A) 50P-1 PH 7 (4200A)
SDT 0.25 Delay, 50P-1 48
INST 15 (6000A)
CBL-0223 0.10
Size: 500 AWG/kcmil
Qty/Ph: 1
0.01
100
10K
1K
1 10
1000 B32-ESWBD-A-MAIN 1000
1200 AS, 1200 AT
B32-ESWBD-A
480.0 V
B32-ESWBDA-ATSA1
400 AS, 400 AT
CBL-2011
Size: 2 - 4/0 AWG/kcmil
E N
B32-ATSA1-B32
100 100
400.0 A
B32-A1-T3 B32-ATS-A1
CUTLER-HAMMER 480.0 V
15-150A
TYPE: FDB CBL-2027
Sensor/Trip: 125A, Settings Phase Size: 2 - 4/0 AWG/kcmil
Fixed
B32-A1-MAIN
400 AS,
B32-A1
480.0 V
10 B32-A1-T3 10
125 AS,
TIME IN SECONDS
B32-A1-MAIN
CUTLER-HAMMER CBL-2027
100-400A Size: 4/0 AWG/kcmil
TYPE: KD Qty/Ph: 2
1 Sensor/Trip: 400A, Settings Phase 1
Thermal Curve (Fixed)
INST (5-10 x Trip) 5.63 (2252A)
B32-ESWBDA-ATSA1
CUTLER-HAMMER
LS, 70-400A Fixed Plug
TYPE: CHKD, RMS 310
Sensor/Trip: 400A, Plug: 400 AT
Settings Phase
LTPU (1.0 x P) Fixed (400A)
LTD (Fixed) Fixed
STPU (2-8 x P) 8 (3200A)
STD (Fixed) Fixed (I^2t Out)
INST (4000A) Fixed (4000A)
0.10 0.10
B32-ESWBD-A-MAIN
CUTLER-HAMMER
LSI, 400-1200A Fixed Plug
TYPE: CHND, RMS 310
Sensor/Trip: 1200A, Plug: 1200 AT
Settings Phase
LTPU (1.0 x P) Fixed (1200A)
LTD (Fixed) Fixed
STPU (2-8 x P) 6 (7200A)
STD (Inst-300 ms) 200 ms (I^2t Out)
INST (14000A) Fixed (14000A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B32-ESWBD-A-MAIN
1200 AS, 1200 AT
B32-ESWBD-A
480.0 V
TIME IN SECONDS
B32-ESWBD-A-MAIN
CUTLER-HAMMER
LSI, 400-1200A Fixed Plug
TYPE: CHND, RMS 310
Sensor/Trip: 1200A, Plug: 1200 AT
Settings Phase
1
LTPU (1.0 x P) Fixed (1200A) 1
LTD (Fixed) Fixed
STPU (2-8 x P) 6 (7200A)
STD (Inst-300 ms) 200 ms (I^2t Out)
INST (14000A) Fixed (14000A)
B32-UPS-A-BKR
*ABB-SACE
ABB S5N
TYPE: PR212, LSI
0.10
Sensor/Trip: 600A, Settings Phase 0.10
LTPU 1 (600A)
LTD D
STPU 8 (4800A)
STD B (I^2t Out)
INST 10 (6000A)
CBL-2007
Size: 500 AWG/kcmil
Qty/Ph: 2
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10 GEN-B32-DATA CTR
1000 1000.0 kW 1000
B32-EMPD-MAIN 1504 A
CUTLER-HAMMER B32-GEN-DATA CTR
480.0 V
LSI, 1000-2000A Fixed Plug
TYPE: CRD, RMS 310 CBL-2015
Sensor/Trip: 2000A, Plug: 1600 AT Size: 5 - 500 AWG/kcmil
Settings Phase
B32-EMPD-MAIN
LTPU (1.0 x P) Fixed (1600A) 2000 AS, 1600 AT
LTD (Fixed) Fixed
STPU (2-8 x P) 6 (9600A) B32-EMPD
STD (Inst-300 ms) 300 ms (I^2t Out) 480.0 V
INST (17500A) Fixed (17500A)
B32-EMPD-ATSA
1200 AS, 1200 AT
100 100
CBL-2013
Size: 4 - 500 AWG/kcmil
E N
B32-EMPD-ATSA B32-ATSA-B32
1200.0 A
CUTLER-HAMMER
LSI, 400-1200A Fixed Plug Gen SC
B32-ATS-A
TYPE: CHND, RMS 310 480.0 V
Sensor/Trip: 1200A, Plug: 1200 AT
CBL-2005
Settings Phase
Size: 4 - 500 AWG/kcmil
LTPU (1.0 x P) Fixed (1200A)
LTD (Fixed) Fixed B32-ESW BD-A-MAIN
STPU (2-8 x P) 8 (9600A) 1200 AS, 1200 AT
10 STD (Inst-300 ms) 300 ms (I^2t Out) 10
B32-ESW BD-A
INST (14000A) Fixed (14000A) 480.0 V
TIME IN SECONDS
1000 kW
480 V
1 1
CBL-2005
Size: 500 AWG/kcmil
Qty/Ph: 4
B32-ESWBD-A-MAIN
CUTLER-HAMMER
LSI, 400-1200A Fixed Plug
CBL-2015
TYPE: CHND, RMS 310
Size: 500 AWG/kcmil
0.10 Sensor/Trip: 1200A, Plug: 1200 AT 0.10
Qty/Ph: 5
Settings Phase
LTPU (1.0 x P) Fixed (1200A)
LTD (Fixed) Fixed
STPU (2-8 x P) 6 (7200A)
STD (Inst-300 ms) 200 ms (I^2t Out)
INST (14000A) Fixed (14000A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B32-MDS-MAIN
1600 AS, 1600 AT
B32-MDS-ATSA
1600 AS, 1600 AT
10 10
B32-MDS-ATSA
TIME IN SECONDS
CUTLER-HAMMER
GF, 200-6300A
TYPE: Magnum DS, RMS 520
Sensor/Trip: 1200A, Plug: 1200 AT
Settings Ground
GFPU (0.25-1.00 x P 200-1200A) 0.25 (300A)
GFD (0.1-0.5 Sec.) 0.3 (I^2t Out)
1 B32-MDS-MAIN 1
CUTLER-HAMMER
GF, 200-6300A
TYPE: Magnum DS, RMS 520
Sensor/Trip: 1600A, Plug: 1600 AT
Settings Ground
GFPU (0.25-1.00 x P 200-1200A) 0.25 (400A)
GFD (0.1-0.5 Sec.) 0.4 (I^2t Out)
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B32-MDS-MAIN
1600 AS, 1600 AT
B32-MDS
480.0 V
B32-MDS-ATSA
1600 AS, 1600 AT
B32-MDS-ATSA
CBL-2003
CUTLER-HAMMER Size: 4 - 500 AWG/kcmil
LSI, 1600AF, 1600A Plugs E N
100
TYPE: Magnum DS, RMS 520 B32-ATSA-B32 100
Sensor/Trip: 1600A, Plug: 1600 AT 1200.0 A
Settings Phase
LTPU (0.4-1.0 x P) 0.8 (1280A) B32-ATS-A
LTD (2-24 Sec.) 15 480.0 V
STPU (2-12 x LTPU) 6 (7680A)
STD (0.1-0.5 Sec.) 0.4 (I^2t Out) CBL-2005
INST (2-12 x P) 10 (16000A) Size: 4 - 500 AWG/kcmil
B32-ESWBD-A-MAIN
1200 AS, 1200 AT
B32-ESWBD-A
480.0 V
10 10
TIME IN SECONDS
B32-MDS-MAIN
CUTLER-HAMMER
LSI, 1600AF, 1600A Plugs
TYPE: Magnum DS, RMS 520
Sensor/Trip: 1600A, Plug: 1600 AT
Settings Phase
LTPU (0.4-1.0 x P) 1 (1600A)
1
LTD (2-24 Sec.) 15 1
STPU (2-12 x LTPU) 6 (9600A)
STD (0.1-0.5 Sec.) 0.5 (I^2t Out)
B32-ESWBD-A-MAIN
CUTLER-HAMMER
LSI, 400-1200A Fixed Plug
TYPE: CHND, RMS 310
Sensor/Trip: 1200A, Plug: 1200 AT
Settings Phase
LTPU (1.0 x P) Fixed (1200A)
LTD (Fixed) Fixed
STPU (2-8 x P) 6 (7200A)
STD (Inst-300 ms) 200 ms (I^2t Out)
INST (14000A) Fixed (14000A) CBL-2005
0.10 0.10
Size: 500 AWG/kcmil
Qty/Ph: 4
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B32-UPS-A-BKR
600 AS,
B32-UPS-A
480.0 V
B32-UPSA-MIS
600 AS,
B32-BYP-PNL-A
B32-UPSA-MIS 480.0 V
100 100
*CUTLER-HAMMER
MCS 600A CBL-2039
TYPE: LD-K Size: 2 - 500 AWG/kcmil
Sensor/Trip: 600A, Settings Phase
INST OR Fixed (6000A) B32-DPA-MAIN
600 AS,
B32-DP-A
480.0 V
B32-DPA-PDUA
225 AS,
10 10
TIME IN SECONDS
CBL-2039
Size: 500 AWG/kcmil
Qty/Ph: 2
1 1
B32-DPA-MAIN
CUTLER-HAMMER
300-600A
TYPE: LD B32-UPS-A-BKR
Sensor/Trip: 600A, Settings Phase *ABB-SACE
Thermal Curve (Fixed) ABB S5N
INST (5-10 x Trip) 7.5 (4500A) TYPE: PR212, LSI
0.10 Sensor/Trip: 600A, Settings Phase 0.10
LTPU 1 (600A)
LTD D
STPU 8 (4800A)
STD B (I^2t Out)
INST 10 (6000A)
B32-DPA-PDUA
CUTLER-HAMMER
15-225A
TYPE: FD
Sensor/Trip: 225A, Settings Phase
Fixed
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
CBL-0417
1000
Size: 2 - 350 AWG/kcmil1000
B32-DP-MAIN
500 AS,
B32-PNLEA-EB
WESTNHOUSE B32-DP
100 AF 208.0 V
TYPE: HFD
B32-DP-ATS
Sensor/Trip: 100A, Settings Phase 200 AS,
Opening Clearing Curve
CBL-0424
Size: 1 - 4/0 AWG/kcmil
N E
100 B32-ATS-1-B32 100
260.0 A
B32-ATS-1
208.0 V
CBL-0431
Size: 1 - 4/0 AWG/kcmil
B32-PNLEA-MN
225 AS,
B32-PNLEA-MN
B32-PNLEA
B32-DP-ATS WESTNHOUSE 208.0 V
Cutler-Hammer 70-225 A
10 70-250A TYPE: HJD B32-PNLEA-EB 10
TIME IN SECONDS
CBL-0424
Size: 4/0 AWG/kcmil
1 1
Qty/Ph: 1
B32-DP-MAIN CBL-0417
WESTNHOUSE Size: 350 AWG/kcmil
SELTRONIC Qty/Ph: 2
TYPE: LCA,HLCA
Sensor/Trip: 500A, Settings Phase
LTPU 1.0 (500A)
LTD 14.5
STPU 9.0 (4500A)
0.10 STD-I2T 0.066 (I^2t In) 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
GEN-B32
60.0 kW
B32-GEN-MN
B32-PNLEA-EB 225 AS,
WESTNHOUSE
100 AF B32-GEN
TYPE: HFD 208.0 V
Sensor/Trip: 100A, Settings Phase
Opening Clearing Curve N E
B32-ATS-1-B32
260.0 A
100 100
B32-ATS-1
208.0 V
CBL-0431
Size: 1 - 4/0 AWG/kcmil
60 kW
208 V
Gen SC
B32-PNLEA-MN
225 AS,
B32-PNLEA-MN
WESTNHOUSE B32-PNLEA
70-225 A 208.0 V
TYPE: HJD
B32-PNLEA-EB
10 Sensor/Trip: 225A, Settings Phase 100 AS, 10
LTD
INST 8.75 (1968.75A)
TIME IN SECONDS
B32-GEN-MN
1 1
SQUARE D
100-225 A
TYPE: Q2-Q2L
Sensor/Trip: 225A, Settings Phase
Opening Clearing Curve
CBL-0431
Size: 4/0 AWG/kcmil
Qty/Ph: 1
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B49-EBMDP-MAIN
CUTLER-HAMMER
300-800A B49-EBMDP-MAIN
TYPE: HMDL 800 AS,
Sensor/Trip: 800A, Settings Phase
Thermal Curve (Fixed) B49-EBMDP
INST (4-8 x Trip) 4 (3200A)
480.0 V
B49-EBMDP-EBHB
100
250 AS, 100
CBL-0660
Size: 2 - 3/0 AWG/kcmil
B49-EBHB
B49-EBMDP-EBHB 480.0 V
CUTLER-HAMMER
70-250A
B49-EBHB-BRANCH
TYPE: HJD
Sensor/Trip: 250A, Settings Phase 150 AS,
Thermal Curve (Fixed)
INST (5-10 x Trip) 5 (1250A)
10 10
TIME IN SECONDS
1 B49-EBHB-BRANCH 1
CUTLER-HAMMER
15-150A
TYPE: FDB
Sensor/Trip: 150A, Settings Phase
Fixed
CBL-0660
0.10
Size: 3/0 AWG/kcmil 0.10
Qty/Ph: 2
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
T-B49-T3
B49-EBRA-EBRC
CUTLER-HAMMER
100-225A B49-EBMDP-T3
TYPE: EDB, EDS, 240V, 2 & 3 Pole 175 AS,
Sensor/Trip: 200A, Settings Phase
Opening Clearing Curve
P
T-B49-T3
S
112.5 kVA
100
B49-EBRA-MAIN
100
400 AS,
B49-EBRA
208.0 V
B49-EBRA-EBRC
200 AS,
10 10
TIME IN SECONDS
T-B49-T3
113 kVA
480 / 208 V
1 1
B49-EBRA-MAIN
CUTLER-HAMMER
250-400A
TYPE: DK
Sensor/Trip: 400A, Settings Phase
Thermal Curve (Fixed)
INST (5-10 x Trip) 10 (4000A)
B49-EBMDP-T3
TX Inrush CUTLER-HAMMER
15-225A
0.10 0.10
TYPE: HFD
Sensor/Trip: 175A, Settings Phase
Fixed
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
T-B49-T4
B49-EBMDP-T4
125 AS,
P
T-B49-T4
S 75.0 kVA
B49-EBRB
208.0 V
B49-EBRB-BRANCH
B49-EBMDP-T4 100 AS,
CUTLER-HAMMER
15-225A
TYPE: HFD
Sensor/Trip: 125A, Settings Phase
Fixed
10 10
TIME IN SECONDS
T-B49-T4
75 kVA
480 / 208 V
1 1
B49-EBRB-MAIN
CUTLER-HAMMER
250-400A
TYPE: DK
Sensor/Trip: 250A, Settings Phase
Thermal Curve (Fixed)
INST (5-10 x Trip) 6.88 (1720A)
TX Inrush
0.10 0.10
B49-EBRB-BRANCH
CUTLER-HAMMER
15-100A
TYPE: BAB, 3-Pole
Sensor/Trip: 100A, Settings Phase
Fixed
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
T-B49-T2
B49-EBMDP-T2
175 AS,
P
T-B49-T2
S
112.5 kVA
100
B49-MDP-MAIN
100
225 AS,
B49-MDP
208.0 V
B49-MDP-PNLB
225 AS,
10 10
T-B49-T2
113 kVA
480 / 208 V
TIME IN SECONDS
B49-MDP-PNLB
GE
100-225A
TYPE: THQD
Sensor/Trip: 225A, Settings Phase
Fixed
1 1
B49-MDP-MAIN
GE J600 B49-EBMDP-T2
125-400 A CUTLER-HAMMER
TYPE: THJK4 15-225A
Sensor/Trip: 225A, Settings Phase TYPE: HFD
LTD Sensor/Trip: 175A, Settings Phase
INST 10.0 (2250A) Fixed
TX Inrush
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
GEN-B50
1000 kW
480 V
GEN-B50
1000.0 kW
B50-GENBKR-2
B50-GEN
SQUARE D
480.0 V
LSI, 250-1200A, UL
TYPE: Powerpact P-Frame, 6.0A/P/H
Sensor/Trip: 1200A, Settings Phase B50-GENBKR-2
1200 AS,
LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 4
STPU (1.5-10 x LTPU) 2 (2400A)
100 STD (0-0.4) 0.3 (I^2t Out) CBL-0445 100
B50-EPD1-MAIN
600 AS, 600 AT
Gen SC B50-EPD1
480.0 V
B50-EPD1-MAIN
B50-EPD1-LB
CUTLER-HAMMER
LSI, 300-600A Fixed Plug 400 AS, 400 AT
TYPE: HLD, RMS 310
Sensor/Trip: 600A, Plug: 600 AT
10 Settings Phase 10
TIME IN SECONDS
INST (5500A) Fixed (5500A)
CBL-0445
Size: 500 AWG/kcmil
B50-EPD1-LB Qty/Ph: 3
1 CUTLER-HAMMER 1
LSI, 70-400A Fixed Plug
TYPE: HKD, RMS 310
Sensor/Trip: 400A, Plug: 400 AT
Settings Phase
LTPU (1.0 x P) Fixed (400A)
LTD (Fixed) Fixed
STPU (2-8 x P) 3 (1200A)
STD (Inst-300 ms) 100 ms (I^2t Out)
INST (4000A) Fixed (4000A)
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10 B50U1-MSB
1000 208.0 V 1000
B50U1-21
500 AS,
CBL-0406
Size: 2 - 250 AWG/kcmil
N E
B50U1-ATS-1-B50U1
600.0 A
B50U1-ATS-1
208.0 V
CBL-0410
100 Size: 2 - 250 AWG/kcmil 100
B50U1-ECGS-MN
600 AS,
B50U1-ECGS
B50U1-ECGS-F2 208.0 V
CUTLER-HAMMER
100-400A B50U1-ECGS-F2
TYPE: KD 150 AS,
Sensor/Trip: 150A, Settings Phase CBL-0412
Thermal Curve (Fixed) Size: 1 - 2 AWG/kcmil
INST (5-10 x Trip) 8.75 (1312.5A)
B50U1-EC1E-MAIN
150 AS,
10 10
B50U1-EC1E
208.0 V
TIME IN SECONDS
CBL-0410
Size: 250 AWG/kcmil
Qty/Ph: 2
B50U1-EC1E-MAIN
WESTNHOUSE
1 1
225 AF
TYPE: CAH 2,3P
Sensor/Trip: 150A, Settings Phase
Opening Clearing Curve
CBL-0412
Size: 2 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
B50-EMD
1K
1 10
1000 480.0 V 1000
B50-EMD-TX2
250 AS,
CBL-0447
Size: 1 - 250 AWG/kcmil
T-TX2-B50
P
150.0 kVA
S
B50U1-ELCG-MN
600 AS, 3.189 kA
B50U1-ELCG
100 100
208.0 V
B50U1ELCG-ATS1
600 AS,
N E
B50U1-ATS-1-B50U1
600.0 A
B50U1-ATS-1
208.0 V
CBL-0410
Size: 2 - 250 AWG/kcmil
B50U1-ECGS-MN
10 WESTNHOUSE B50U1-ECGS-MN 10
SELTRONIC 600 AS, 3.006 kA
TYPE: LCA,HLCA
Sensor/Trip: 600A, Settings recommended
LTPU 1.0 (600A)
LTD 14.5 T-TX2-B50
TIME IN SECONDS
STPU 5.0 (3000A) 150 kVA
STD-I2T 0.066 (I^2t In) 480 / 208 V
Override 1.0 (7200A)
B50U1ELCG-ATS1
WESTINGHOUSE
300-600A
1 1
TYPE: LC SELTRNC
Sensor/Trip: 600A, Settings Phase
LTPU 1.0 (600A)
LTD LTD
B50-EMD-TX2 STPU 6.0 (3600A)
*WESTINGHOUSE STD-I2T STD (I^2t In)
SELTRONIC LSI
TYPE: HKD/CHKD
Sensor/Trip: 250A, Settings Phase
LTPU 1.0 (250A)
LTD LTD
STPU 8.0 (2000A)
STD 300 CBL-0447
TX Inrush
0.10 Override 1.0 (4000A) Size: 250 AWG/kcmil 0.10
Qty/Ph: 1
B50U1-ELCG-MN
WESTINGHOUSE
300-600A
TYPE: LC SELTRNC CBL-0410
Sensor/Trip: 600A, Settings Phase Size: 250 AWG/kcmil
LTPU 1.0 (600A) Qty/Ph: 2
LTD LTD
STPU 6.0 (3600A)
STD-I2T STD (I^2t In)
Override 1.0 (6800A)
0.01 0.01
100
10K
1K
0.5 1 10
100
10K
1K
1 10
1000 1000
B50-EMD
480.0 V
B50-EMD-TX2
250 AS,
CBL-0447
Size: 1 - 250 AWG/kcmil
T-TX2-B50
150.0 kVA
B50U1-ELCG
208.0 V
B50U1ELCG-ATS2
N E
225 AS,
B50U1-ATS-2-B50U1
260.0 A
B50U1-ELGS-MN
225 AS, 2.421 kA
10 10
B50U1-ELCG-MN
WESTINGHOUSE
300-600A
TYPE: LC SELTRNC
Sensor/Trip: 600A, Settings Phase
TIME IN SECONDS
LTPU 1.0 (600A) T-TX2-B50
LTD LTD 150 kVA
STPU 6.0 (3600A) 480 / 208 V
STD-I2T STD (I^2t In)
Override 1.0 (6800A)
1 1
CBL-0447
Size: 250 AWG/kcmil
Qty/Ph: 1
B50U1-ELGS-MN
WESTNHOUSE
225 AF
TYPE: CAH 2,3P
Sensor/Trip: 225A, Settings Phase
Opening Clearing Curve
TX Inrush
0.10 0.10
B50-EMD-TX2
*WESTINGHOUSE
SELTRONIC LSI
TYPE: HKD/CHKD
Sensor/Trip: 250A, Settings Phase
LTPU 1.0 (250A)
LTD LTD
STPU 8.0 (2000A)
STD 300
Override 1.0 (4000A)
0.01 0.01
100
1K
10K
0.5 1 10
100
10K
1K
1 10 B50U1-MSB-MAIN
1000 3200 AS, 1000
B50U1-MSB
208.0 V
B50U1-18
250 AS,
CBL-0387
Size: 1 - 250 AWG/kcmil
N E
B50U1-ATS-2-B50U1
260.0 A
B50U1-ATS-2
100 208.0 V 100
CBL-0393
Size: 1 - 250 AWG/kcmil
B50U1-ELGS-MN
225 AS,
B50U1-ELGS
208.0 V
B50U1-ELGS-EL
175 AS,
B50U1-EL1A-MAIN
150 AS,
10 10
B50U1-EL1A
208.0 V
B50U1-ELGS-MN
TIME IN SECONDS
WESTNHOUSE
225 AF
TYPE: CAH 2,3P
Sensor/Trip: 225A, Settings Phase
Opening Clearing Curve
CBL-0387
Size: 250 AWG/kcmil
Qty/Ph: 1 B50U1-EL1A-MAIN
1 WESTNHOUSE 1
225 AF
TYPE: CAH 2,3P
Sensor/Trip: 150A, Settings Phase
Opening Clearing Curve
B50U1-18
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 250A, Settings existing
LTPU 1.0 (250A)
LTD LTD
0.10 STPU 8.0 (2000A) 0.10
STD 300
Override 1.0 (4000A)
B50U1-ELGS-EL
WESTNHOUSE
70-250 A
TYPE: JDB,JD
Sensor/Trip: 175A, Settings Phase
LTD
INST 10.0 (1750A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 GEN-B50 1000
1000.0 kW
B50-GEN
1000 kW 480.0 V
480 V
B50-GENBKR-1
1200 AS,
CBL-0444
Size: 3 - 500 AWG/kcmil
B50-EMD
480.0 V
B50-EMD-TX1
250 AS,
100 100
CBL-0446
Size: 1 - 250 AWG/kcmil
B50-GENBKR-1
SQUARE D T-TX1-B50
LSI, 250-1200A, UL P
150.0 kVA
TYPE: Powerpact P-Frame, 6.0A/P/H Gen SC S
B50-TX1-ATS-3
Sensor/Trip: 1200A, Settings Phase
600 AS,
LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 8
STPU (1.5-10 x LTPU) 2 (2400A) CBL-0452
STD (0-0.4) 0.4 (I^2t Out) N E
Size: 2 - 250 AWG/kcmil
INST (2-15 x S) 6 (7200A)
B50U1-ATS-3-B50U1
600.0 A
10 10
F-ELEVRM-PS2
250 AS,
TIME IN SECONDS
T-TX1-B50
150 kVA
480 / 208 V
B50-EMD-TX1
*WESTINGHOUSE
SELTRONIC LSI CBL-0444
TYPE: HKD/CHKD Size: 500 AWG/kcmil
Sensor/Trip: 250A, Settings Phase Qty/Ph: 3
1 1
LTPU 1.0 (250A)
LTD LTD
STPU 8.0 (2000A)
STD 200
Override 1.0 (4000A)
CBL-0446
Size: 250 AWG/kcmil
TX Inrush
F-ELEVRM-PS2 Qty/Ph: 1
0.10 0.10
BUSSMANN
FRS-R RK5
TYPE: 15-600A
Sensor/Trip: 250A,
CBL-0452
B50-TX1-ATS-3 Size: 250 AWG/kcmil
CUTLER-HAMMER Qty/Ph: 2
300-600A
TYPE: LD
Sensor/Trip: 600A, Settings Phase
Thermal Curve (Fixed)
INST (5-10 x Trip) 5 (3000A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B50U1-MSB
208.0 V
B50U1-20
500 AS,
CBL-0401
Size: 2 - 250 AWG/kcmil
N E
B50U1-ATS-3-B50U1
600.0 A
B50U1-ATS-3
100 208.0 V 100
CBL-0402
Size: 2 - 250 AWG/kcmil
B50U1-ELEVRM-WW
208.0 V
CBL-0405
Size: 1 - 3/0 AWG/kcmil
F-ELEVRM-PS1
58.3 Hp 250 AS,
M-ELEVRM-PS1
10 50.0 hp 10
F-ELEVRM-PS1
TIME IN SECONDS
BUSSMANN
FRS-R RK5
TYPE: 15-600A
Sensor/Trip: 250A, CBL-0401
Size: 250 AWG/kcmil
Qty/Ph: 2
1 1
CBL-0405
Size: 3/0 AWG/kcmil
Qty/Ph: 1
B50U1-20
WESTNHOUSE
0.10 SELTRONIC 0.10
TYPE: LCA,HLCA
Sensor/Trip: 600A, Settings Phase
LTPU 1.0 (600A)
LTD 14.5
STPU 7.0 (4200A)
STD-I2T 0.105 (I^2t In)
Override 1.0 (7200A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B50U1-MSB-MAIN
3200 AS,
B50U1-MSB
208.0 V
B50U1-14
250 AS,
100 100
F-B50U1-COMPAC CBL-0398
BUSSMANN Size: 2 - 3/0 AWG/kcmil
FRN-R RK5
TYPE: 15-600A B50U1-COMPAC
Sensor/Trip: 45A, 208.0 V
F-B50U1-COMPAC
45 AS,
10 10
B50U1-MSB-MAIN
WESTNHOUSE
DIGTRP RMS
TYPE: DS
TIME IN SECONDS
Sensor/Trip: 3200A, Settings Phase
LTPU 0.8 (2560A)
LTD 4.0
STPU 3.0 (9600A)
STD-I2T 0.4 (I^2t Out)
INST 12.0 (38400A)
1 1
B50U1-14
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD CBL-0398
Sensor/Trip: 250A, Settings Phase Size: 3/0 AWG/kcmil
LTPU 1.0 (250A) Qty/Ph: 2
0.10 LTD LTD 0.10
STPU 5.0 (1250A)
STD 100
Override 1.0 (4000A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B50U1-GALA-FDR
CUTLER-HAMMER
15-100A
TYPE: BAB, 3-Pole
Sensor/Trip: 100A, Settings Phase
Fixed
B50U1-MSB-MAIN
3200 AS,
B50U1-MSB
208.0 V
CBL-0381
Size: 1 - 500 AWG/kcmil
B50U1-GALA-MN
150 AS,
10 10
TIME IN SECONDS
B50U1-MSB-MAIN
1 WESTNHOUSE 1
DIGTRP RMS
TYPE: DS
Sensor/Trip: 3200A, Settings Phase CBL-0381
LTPU 0.8 (2560A) Size: 500 AWG/kcmil
LTD 4.0 Qty/Ph: 1
STPU 3.0 (9600A)
STD-I2T 0.4 (I^2t Out)
INST 12.0 (38400A)
0.10 0.10
B50U1-6
Cutler-Hammer
RMS-310
TYPE: KD,HKD LSI
Sensor/Trip: 200A, Settings Phase
LTPU 1.0 (200A)
LTD 12.0
STPU 8.0 (1600A)
STD-I2T 0.1 (I^2t Out)
Override 1.0 (4000A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B50U1-MSB-MAIN
3200 AS,
B50U1-MSB
208.0 V
B50U1-GAPB-MN
TIME IN SECONDS
WESTNHOUSE
225 AF
TYPE: CAH 2,3P
Sensor/Trip: 150A, Settings Phase
Opening Clearing Curve
1 1
CBL-0382
Size: 250 AWG/kcmil
Qty/Ph: 1
B50U1-8
WESTINGHOUSE
RMS310 LSI
0.10 TYPE: HKD/CHKD 0.10
Sensor/Trip: 300A, Settings Phase
LTPU 1.0 (300A)
LTD LTD
STPU 8.0 (2400A)
STD 100
Override 1.0 (4000A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B50U1-MSB-MAIN
3200 AS,
B50U1-MSB
208.0 V
B50U1-15
150 AS,
100 100
CBL-0386
Size: 1 - 1/0 AWG/kcmil
B50U1-GAPB-MN
150 AS,
B50U1-GAPB
208.0 V
10 10
B50U1-MSB-MAIN
WESTNHOUSE
DIGTRP RMS
TIME IN SECONDS
TYPE: DS
Sensor/Trip: 3200A, Settings Phase
LTPU 0.8 (2560A)
LTD 4.0
STPU 3.0 (9600A)
STD-I2T 0.4 (I^2t Out)
INST 12.0 (38400A)
1 1
B50U1-GAPB-MN
WESTNHOUSE
225 AF
TYPE: CAH 2,3P
Sensor/Trip: 150A, Settings Phase
Opening Clearing Curve
B50U1-15
CBL-0386 WESTINGHOUSE
Size: 1/0 AWG/kcmil RMS310 LSI
Qty/Ph: 1 TYPE: HKD/CHKD
0.10 Sensor/Trip: 150A, Settings Phase 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B50U1-MSB-MAIN
3200 AS,
B50U1-MSB
208.0 V
B50U1-13
225 AS,
100 100
CBL-0399
Size: 2 - 3/0 AWG/kcmil
B50U1-GAPC-MN
200 AS,
B50U1-GAPC
208.0 V
10 10
CBL-0399
TIME IN SECONDS
B50U1-MSB-MAIN
WESTNHOUSE Size: 3/0 AWG/kcmil
DIGTRP RMS Qty/Ph: 2
TYPE: DS
Sensor/Trip: 3200A, Settings Phase
LTPU 0.8 (2560A)
LTD 4.0
STPU 3.0 (9600A)
1 STD-I2T 0.4 (I^2t Out) 1
B50U1-GAPC-MN
INST 12.0 (38400A)
WESTNHOUSE
225 AF
TYPE: CAH 2,3P
Sensor/Trip: 200A, Settings Phase
Opening Clearing Curve
B50U1-13
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
0.10 0.10
Sensor/Trip: 225A, Settings Phase
LTPU 1.0 (225A)
LTD LTD
STPU 8.0 (1800A)
STD 100
Override 1.0 (4000A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B50U1-MSB-MAIN
3200 AS,
B50U1-MSB
208.0 V
B50U1-1
300 AS,
10 10
B50U1-GEPA-MN
WESTNHOUSE
225 AF
TYPE: CAH 2,3P
TIME IN SECONDS
Sensor/Trip: 200A, Settings Phase
Opening Clearing Curve
CBL-0360
Size: 250 AWG/kcmil
Qty/Ph: 2
1 1
CBL-0363
Size: 4/0 AWG/kcmil
Qty/Ph: 1
B50U1-1
WESTINGHOUSE
RMS310 LSI
0.10 TYPE: HKD/CHKD 0.10
Sensor/Trip: 300A, Settings Existing
LTPU 1.0 (300A)
LTD LTD
STPU 8.0 (2400A)
STD 100
Override 1.0 (4000A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
312 A B50U1-MCCP1-MN
WESTNHOUSE
TYPE: MC 800A
Sensor/Trip: 800A, Settings Existing B50U1-MCCP1-MN
LTD 700 AS,
INST 7 (5600A)
B50U1-MCCP1
208.0 V
B50U1-MCCP1-T
300 AS,
T-B50U1-MCCP1
112.5 kVA
B50U1-AC-1-M
100 AS,
B50U1-AC-1
480.0 V
10 10
B50U1-MCCP1-T
WESTNHOUSE
TIME IN SECONDS
100-400A
TYPE: HKD T-B50U1-MCCP1
Sensor/Trip: 300A, Settings Phase 113 kVA
LTD 208 / 480 V
INST 10.0 (3000A)
1 1
CBL-0388
Size: 300 AWG/kcmil
Qty/Ph: 1
TX Inrush
0.10 0.10
B50U1-AC-1-M
WESTNHOUSE
90-150A
TYPE: FD
Sensor/Trip: 100A, Settings Phase
Opening Clearing Curve
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B50U1-MSB-MAIN
3200 AS,
B50U1-MSB
208.0 V
B50U1-11
400 AS,
100 100
CBL-0530
Size: 2 - 500 AWG/kcmil
B50U1-K
208.0 V
B50U1-K-FDR
20 AS,
10 10
B50U1-MSB-MAIN
WESTNHOUSE
DIGTRP RMS
TIME IN SECONDS
TYPE: DS
Sensor/Trip: 3200A, Settings Phase
LTPU 0.8 (2560A)
LTD 4.0
STPU 3.0 (9600A)
STD-I2T 0.4 (I^2t Out)
INST 12.0 (38400A)
1 CBL-0530 1
0.10 0.10
B50U1-K-FDR
*CUTLER-HAMMER
15-45A
TYPE: ED,FD,HFD
Sensor/Trip: 20A, Settings Phase
Opening Clearing Curve
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B50U1-MSB-MAIN
3200 AS,
208.0 V
B50U1-10
700 AS,
10 10
B50U1-MSB-MAIN
TIME IN SECONDS
*CUTLER-HAMMER
100-1200A
TYPE: DS(G) RMS
Sensor/Trip: 300A, Settings Ground
GPU 1.0 (300A)
GTD 0.4 (I^2t Out)
1 1
B50U1-10
CUTLER-HAMMER
400-800A
TYPE: MCG
Sensor/Trip: 800A, Plug: 700 AT
Settings Ground
GFPU (80-800A) 80A (80A)
GFD (3.5-30 Cycles) Min
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51A1-MSG-MAIN
B51A1-MSG-MAIN
WESTNHOUSE
1200 AS,
DIGTRP RMS
TYPE: DS
Sensor/Trip: 1200A, Settings Phase B51A1-MSG
LTPU 1.0 (1200A) 480.0 V
LTD 4.0
STPU 3.0 (3600A) B51A1-12
STD-I2T 0.4 (I^2t Out) 150 AS,
100 100
CBL-0354
Size: 1 - 1/0 AWG/kcmil
B51A1-1AHA
480.0 V
B51A1-1AHA-BRANCH
90 AS,
10 10
B51A1-12
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 150A, Settings Phase
TIME IN SECONDS
LTPU 1.0 (150A)
LTD LTD
STPU 8.0 (1200A)
STD 100
Override 1.0 (4000A)
CBL-0354
1
Size: 1/0 AWG/kcmil 1
Qty/Ph: 1
0.10 0.10
B51A1-1AHA-BRANCH
CUTLER-HAMMER
15-150A
TYPE: FD
Sensor/Trip: 90A, Settings Phase
Fixed
0.01 0.01
0.5 1 10
100
10K
1K
100
10K
1K
1 10
1000 1000
B51A1-MSG-MAIN
WESTNHOUSE B51A1-MSG-MAIN
DIGTRP RMS 1200 AS,
TYPE: DS
Sensor/Trip: 1200A, Settings Phase B51A1-MSG
LTPU 1.0 (1200A) 480.0 V
LTD 4.0
STPU 3.0 (3600A) B51A1-11
STD-I2T 0.4 (I^2t Out) 225 AS,
100 100
CBL-0353
Size: 1 - 4/0 AWG/kcmil
B51A1-1AHB-MAIN
90 AS,
B51A1-1AHB
480.0 V
10 10
B51A1-11
WESTINGHOUSE
RMS310 LSI
TIME IN SECONDS
TYPE: HKD/CHKD
Sensor/Trip: 225A, Settings Phase
LTPU 1.0 (225A)
LTD LTD
STPU 8.0 (1800A)
STD 100
Override 1.0 (4000A)
1 1
B51A1-1AHB-MAIN
CUTLER-HAMMER
15-150A CBL-0353
TYPE: FD Size: 4/0 AWG/kcmil
Sensor/Trip: 90A, Settings Phase Qty/Ph: 1
Fixed
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51A1-MSG-MAIN
1200 AS,
B51A1-MSG
480.0 V
B51A1-10
100 AS,
100 100
B51A1-MSG-MAIN CBL-0351
WESTNHOUSE Size: 1 - 2 AWG/kcmil
DIGTRP RMS
TYPE: DS B51A1-2AHA-MAIN
Sensor/Trip: 1200A, Settings Phase 70 AS,
LTPU 1.0 (1200A)
LTD 4.0
STPU 3.0 (3600A) B51A1-2AHA
STD-I2T 0.4 (I^2t Out) 480.0 V
10 10
B51A1-10
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 100A, Settings Phase
TIME IN SECONDS
LTPU 1.0 (100A)
LTD LTD
STPU 8.0 (800A)
STD 100
Override 1.0 (4000A)
1 1
B51A1-2AHA-MAIN
CUTLER-HAMMER
15-150A
TYPE: FD
Sensor/Trip: 70A, Settings Phase
Fixed
CBL-0351
Size: 2 AWG/kcmil
0.10 Qty/Ph: 1 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
B51A1-MSG-MAIN
1000 1000
1200 AS,
B51A1-MSG
480.0 V
B51A1-8
100 AS,
B51A1-MSG-MAIN
WESTNHOUSE CBL-0350
DIGTRP RMS Size: 1 - 1 AWG/kcmil
TYPE: DS N E
Sensor/Trip: 1200A, Settings Phase B51A1-ATS-2A-B51A1
150.0 A
LTPU 1.0 (1200A)
LTD 4.0 B51A1-ATS-2A
100 100
STPU 3.0 (3600A) 480.0 V
STD-I2T 0.4 (I^2t Out)
CBL-0357
Size: 1 - 1 AWG/kcmil
B51A1-JB
480.0 V
CBL-0537
Size: 1 - 2 AWG/kcmil
B51A1-EL1A
480.0 V
10 B51A1-EL1A-FDR 10
60 AS,
B51A1-8
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
TIME IN SECONDS
Sensor/Trip: 100A, Settings Phase
LTPU 1.0 (100A)
LTD LTD
STPU 8.0 (800A)
STD 200
Override 1.0 (4000A)
1 1
B51A1-EL1A-FDR
Cutler-Hammer
100 AF
TYPE: GHB 2,3P
Sensor/Trip: 60A, Settings Phase
Opening Clearing Curve
0.10 0.10
CBL-0350
Size: 1 AWG/kcmil
Qty/Ph: 1
CBL-0537
Size: 2 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
GEN-B50
1000 kW
1000.0 kW
480 V
B50-GEN
480.0 V
B50-GENBKR-1
1200 AS,
CBL-0444
Size: 3 - 500 AWG/kcmil
B50-EMD
480.0 V
100 100
B50-EMD-ATS-3A
250 AS,
CBL-0451
Size: 1 - 350 AWG/kcmil
Gen SC N E
B51A1-ATS-3A-B51A1
260.0 A
58.3 Hp F-B51A1-ELEVP1
110 AS,
M-B51A1-ELEVP1
10 10
50.0 hp
TIME IN SECONDS
B50-EMD-ATS-3A
*WESTINGHOUSE
SELTRONIC LSI
TYPE: HKD/CHKD
Sensor/Trip: 250A, Settings Phase CBL-0451
LTPU 1.0 (250A) Size: 350 AWG/kcmil
LTD LTD Qty/Ph: 1
1 1
STPU 7.0 (1750A)
STD 100
Override 1.0 (4000A)
B50-GENBKR-1
SQUARE D
LSI, 250-1200A, UL
F-B51A1-ELEVP1
TYPE: Powerpact P-Frame, 6.0A/P/H
BUSSMANN
Sensor/Trip: 1200A, Settings Phase
FRS-R RK5
LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 8
TYPE: 15-600A
STPU (1.5-10 x LTPU) 2 (2400A)
Sensor/Trip: 110A,
STD (0-0.4) 0.4 (I^2t Out)
INST (2-15 x S) 6 (7200A)
0.10 0.10
CBL-0444
Size: 500 AWG/kcmil
Qty/Ph: 3
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51A1-MSG-MAIN
B51A1-4 1200 AS,
WESTINGHOUSE
RMS310 LSI B51A1-MSG
TYPE: HKD/CHKD 480.0 V
Sensor/Trip: 250A, Settings Phase
LTPU 1.0 (250A) B51A1-4
LTD LTD 250 AS,
STPU 8.0 (2000A)
STD 200
Override 1.0 (4000A) CBL-0352
Size: 1 - 500 AWG/kcmil
100 N E 100
B51A1-ATS-3A-B51A1
260.0 A
B51A1-ATS-3A
480.0 V
CBL-0541
Size: 1 - 500 AWG/kcmil
B51A1-ELEV
480.0 V
F-B51A1-ELEVP1
10 10
110 AS,
TIME IN SECONDS
CBL-0352
Size: 500 AWG/kcmil
Qty/Ph: 1
F-B51A1-ELEVP1
BUSSMANN
FRS-R RK5
TYPE: 15-600A B51A1-MSG-MAIN
Sensor/Trip: 110A, WESTNHOUSE
1 1
DIGTRP RMS
TYPE: DS
Sensor/Trip: 1200A, Settings Phase
LTPU 1.0 (1200A)
LTD 4.0
STPU 3.0 (3600A)
STD-I2T 0.4 (I^2t Out)
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
B51A1-MSG-MAIN
100
10K
1K
0.5 1 10
1200 AS, 1000
430 A
B51A1-MSG-MAIN B51A1-MSG
WESTNHOUSE 480.0 V
DIGTRP RMS B51A1-13
TYPE: DS 400 AS,
Sensor/Trip: 1200A, Phase
LTPU 1.0 (1200A) CBL-0355
LTD 4.0 Size: 1 - 500 AWG/kcmil
STPU 4.0 (4800A) E N
STD-I2T 0.4 (I^2t Off) ATS 5A
ATS-5A
480.0 V
CBL-0492 100
B51A1-MCC1A1
480.0 V
CBL-0551
Size: 1 - 4 AWG/kcmil
10
M-B51A1-SF-5
40.0 hp
TIME IN SECONDS
MCC1A1-MAIN
WESTNHOUSE
300-600A
B51A1-13 TYPE: LC LCG
WESTINGHOUSE Sensor/Trip: 400A, Phase
RMS310 LSI LTD
TYPE: HKD/CHKD INST 5 (2000A)
Sensor/Trip: 400A, Phase 1
CBL-0355
Size: 500 AWG/kcmil
Qty/Ph: 1
0.10
CBL-0521
46.6 Hp Size: 250 AWG/kcmil
Qty/Ph: 1
CBL-0551
Size: 4 AWG/kcmil
Qty/Ph: 1
0.01
100
10K
1K
0.5 1 10 GEN-B50
1000
CBL-0445
CBL-0478 B50-GEN
CBL-0492
CBL-0521 B50-GENBKR-2
CBL-0445
B50-EPD1
B50-ATS-5A
CBL-0478
100
E N
ATS 5A
ATS-5A
CBL-0492
B51A1-TAP-13
CBL-0521
MCC1A1-MAIN
10
B51A1-MCC1A1
TIME IN SECONDS
Device: B50-GENBKR-2
Powerpact P-Frame, 6.0A/P/H
1200A
Device: B50-ATS-5A Settings Phase
HKD, RMS 310 LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 4
400A/400A STPU (1.5-10 x LTPU) 2 (2400A)
Settings Phase STD (0-0.4) 0.3 (I^2t Off) 1
Name CBL-0445
Size 500 AWG/kcmil
Qty/Ph 3
Name CBL-0478
Device: MCC1A1-MAIN Size 500 AWG/kcmil 0.10
LC LCG
Qty/Ph 1
400A
Settings Phase
LTD Name CBL-0492
INST 5 (2000A) Size 500 AWG/kcmil
Qty/Ph 1
Name CBL-0521
Size 250 AWG/kcmil
Qty/Ph 1
0.01
B51A1-MSG-MAIN
100
10K
1K
0.5 1 10
1200 AS, 1000
430 A
B51A1-MSG
430 A 480.0 V
B51A1-2
400 AS,
CBL-0346
Size: 1 - 500 AWG/kcmil
E N
ATS 4A
ATS-4A
480.0 V
CBL-0488 100
Size: 1 - 500 AWG/kcmil
B51A1-TAP-2
480.0 V
CBL-0531
Size: 1 - 500 AWG/kcmil
B51A1-MCC3A1-MAIN
400 AS,
B51A1-MCC3A1
480.0 V
CBL-0553
Size: 1 - 4 AWG/kcmil
10
M-51A1-SF-1
40.0 hp
TIME IN SECONDS
46.6 Hp B51A1-MSG-MAIN
WESTNHOUSE
DIGTRP RMS
TYPE: DS
Sensor/Trip: 1200A, Phase
LTPU 1.0 (1200A)
LTD 4.0
B51A1-MCC3A1-MAIN STPU 3.0 (3600A) 1
CUTLER-HAMMER STD-I2T 0.4 (I^2t Off)
100-400A
TYPE: HKD
Sensor/Trip: 400A, Phase
Thermal Curve (Fixed)
INST (5-10 x Trip) 5 (2000A) CBL-0346
Size: 500 AWG/kcmil
Qty/Ph: 1
CBL-0553 CBL-0488
B51A1-2 Size: 4 AWG/kcmil Size: 500 AWG/kcmil
WESTINGHOUSE Qty/Ph: 1 Qty/Ph: 1
0.10
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 400A, Phase
LTPU 1.0 (400A)
LTD LTD
STPU 7.0 (2800A)
STD 200
Override 1.0 (4000A)
CBL-0531
Size: 500 AWG/kcmil
Qty/Ph: 1
0.01
GEN-B50
100
10K
1K
0.5 1 10
1000
CBL-0445 B50-GEN
CBL-0531
B50-GENBKR-2
CBL-0445
B50-EPD1
B50-ATS-4A
CBL-0480
E N
100
ATS 4A
ATS-4A
CBL-0488
B51A1-TAP-2
CBL-0531
B51A1-MCC3A1-MAIN
10
B51A1-MCC3A1
TIME IN SECONDS
Device: B50-GENBKR-2
Powerpact P-Frame, 6.0A/P/H
1200A
Settings Phase
LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 4
Device: B50-ATS-4A STPU (1.5-10 x LTPU) 2 (2400A)
HKD, RMS 310 STD (0-0.4) 0.3 (I^2t Off)
400A/400A INST (2-15 x S) 6 (7200A)
Settings Phase 1
Name CBL-0445
Size 500 AWG/kcmil
Device: B51A1-MCC3A1-MAIN 0.10
Qty/Ph 3
HKD
400A
Settings Phase
Thermal Curve (Fixed)
INST (5-10 x Trip) 5 (2000A)
Name CBL-0531
Size 500 AWG/kcmil
Qty/Ph 1
0.01
100
10K
B51A1-MSG-MAIN
1K
0.5 1 10
1200 A S, 1000
430 A MCCGB3-MAIN
WESTNHOUSE B51A1-MSG
480.0 V
SELTRONIC
TYPE: MC,HMC
B51A1-3
Sensor/Trip: 600A, Phase 400 AS ,
LTPU 1.0 (600A)
LTD 17.0 CBL-0345
STPU 4.0 (2400A) Size: 1 - 500 AWG/kcmil
STD-I2T 0.075 (I^2t Off) E N
Override 1.0 (9500A)
ATS 6A
ATS-6A 100
480.0 V
CBL-0489
Size: 1 - 500 AWG/kcmil
MCCGB3-MAIN
600 AS ,
B51A1-MCCGB3
480.0 V
46.6 Hp
MCC-GB3-1-C
300 AS ,
10
M-MCCGB3-FP
40.0 hp
TIME IN SECONDS
B51A1-MSG-MAIN
WESTNHOUSE
DIGTRP RMS
TYPE: DS
Sensor/Trip: 1200A, Phase
LTPU 1.0 (1200A)
LTD 4.0
1
STPU 3.0 (3600A)
STD-I2T 0.4 (I^2t Off)
CBL-0345
Size: 500 AWG/kcmil
Qty/Ph: 1
CBL-0489
MCC-GB3-1-C Size: 500 AWG/kcmil
CUTLER-HAMMER Qty/Ph: 1
0.10
100-400 A B51A1-3
TYPE: HKD WESTINGHOUSE
Sensor/Trip: 300A, Phase RMS310 LSI
LTD TYPE: HKD/CHKD
INST 5.0 (1500A) Sensor/Trip: 400A, Phase
LTPU 1.0 (400A)
LTD LTD
STPU 7.0 (2800A)
STD 200
Override 1.0 (4000A)
0.01
100
10K
1K
0.5 1 10
GEN-B50 1000
CBL-0445
CBL-0481 B50-GEN
CBL-0489
B50-GENBKR-2
CBL-0445
B50-EPD1
B50-ATS-6A
CBL-0481
100
E N
ATS 6A
ATS-6A
CBL-0489
MCCGB3-MAIN
B51A1-MCCGB3
MCC-GB3-1-C 10
Device: B50-ATS-6A
HKD, RMS 310
400A/400A
Settings Phase
TIME IN SECONDS
LTPU (1.0 x P) Fixed (400A)
LTD (Fixed) Fixed Device: B50-GENBKR-2
STPU (2-8 x P) 5 (2000A) Powerpact P-Frame, 6.0A/P/H
STD (Inst-300 ms) Inst (I^2t Off) 1200A
INST (4000A) Fixed (4000A) Settings Phase
LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 4
STPU (1.5-10 x LTPU) 2 (2400A)
STD (0-0.4) 0.3 (I^2t Off) 1
INST (2-15 x S) 6 (7200A)
Device: MCCGB3-MAIN
MC,HMC
600A
Settings Phase
LTPU 1.0 (600A) Name CBL-0445
LTD 17.0 Size 500 AWG/kcmil
STPU 3.0 (1800A) Qty/Ph 3
STD-I2T 0.075 (I^2t Off)
Override 1.0 (9500A)
0.10
Name CBL-0481
Size 500 AWG/kcmil
Qty/Ph 1
Device: MCC-GB3-1-C
HKD
300A
Settings Phase Name CBL-0489
LTD Size 500 AWG/kcmil
INST 5.0 (1500A) Qty/Ph 1
0.01
100
10K
1K
0.5 1 10
1000
CBL-0490
CBL-0487
B51A1-MSG-MAIN
B51A1-MSG
B51A1-5
CBL-0490
E N
ATS 7A 100
ATS-7A
CBL-0487
DP-CR MAIN
DP-CR
DP-CR-UPS
10
Device: B51A1-5
HKD/CHKD
400A
TIME IN SECONDS
Settings Phase Device: B51A1-MSG-MAIN
LTPU 1.0 (400A) DS
LTD LTD 1200A
STPU 8.0 (3200A) Settings Phase
STD I LTPU 1.0 (1200A)
LTD 4.0
STPU 3.0 (3600A)
STD-I2T 0.4 (I^2t Off) 1
0.10
Device: DP-CR-UPS
HFD
200A
Settings Phase
Fixed Name CBL-0490
Size 500 AWG/kcmil
Qty/Ph 1
0.01
100
10K
1K
0.5 1 10
1000
CBL-0444 GEN-B50
CBL-0486 B50-GEN
CBL-0487
B50-GENBKR-1
CBL-0444
B50-EMD
B50-EMD-ATS-7A
CBL-0486
100
E N
ATS 7A
ATS-7A
CBL-0487
DP-CR MAIN
DP-CR
DP-CR-UPS
10
TIME IN SECONDS
Device: B50-EMD-ATS-7A Device: B50-GENBKR-1
HKD/CHKD Powerpact P-Frame, 6.0A/P/H
350A 1200A
Settings Phase Settings Phase
LTPU 1.0 (350A) LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 8
LTD LTD STPU (1.5-10 x LTPU) 2 (2400A)
STPU 8.0 (2800A) STD (0-0.4) 0.4 (I^2t Off) 1
STD I INST (2-15 x S) 6 (7200A)
0.10
Name CBL-0444
Device: DP-CR-UPS Size 500 AWG/kcmil
HFD Qty/Ph 3
200A
Settings Phase
Fixed
Name CBL-0487
Size 500 AWG/kcmil
Qty/Ph 1
0.01
100
10K
1K
1 10
1000 1000
B51A1-MSG-MAIN
WESTNHOUSE
Type DS
1200AS
480V
B51A1-3
WESTINGHOUSE
Type HKD/CHKD
400AS
B51A1-MSG-MAIN
10 *CUTLER-HAMMER 10
100-1200A
TYPE: DS(G) RMS
Sensor/Trip: 300A, Settings Ground
GPU 1.0 (300A)
GTD 0.4 (I^2t Out)
TIME IN SECONDS
1 1
B51A1-3
CUTLER-HAMMER
GF, 70-400A
TYPE: CHKD, RMS 310
Sensor/Trip: 400A, Plug: 400 AT
Settings Ground
GFPU (1 x Ig) 1 x Ig (80A)
GFD (Inst-500ms) 150 ms (I^2t Out)
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51A2-1ALA-MN
B51A2-MSG-MAIN
WESTNHOUSE
100 AF 2000 AS,
TYPE: EHD, FDB
Sensor/Trip: 100A, Settings Phase B51A2-MSG
Opening Clearing Curve 208.0 V
B51A2-10
225 AS,
CBL-0322
Size: 1 - 4/0 AWG/kcmil
100 100
B51A2-TAP-10
208.0 V
CBL-0517
Size: 1 - 2 AWG/kcmil
B51A2-1ALA-MN
100 AS,
B51A2-1ALA
208.0 V
10 10
TIME IN SECONDS
B51A2-MSG-MAIN
WESTNHOUSE
DIGTRP RMS
TYPE: DS
Sensor/Trip: 2000A, Settings Recommended
LTPU 1.0 (2000A)
LTD 4.0
1
STPU 3.0 (6000A) 1
STD-I2T 0.3 (I^2t Out) B51A2-10
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 225A, Settings Phase
LTPU 1.0 (225A)
LTD LTD
STPU 8.0 (1800A)
STD 100
Override 1.0 (4000A)
0.10 0.10
CBL-0322
Size: 4/0 AWG/kcmil
Qty/Ph: 1
CBL-0517
Size: 2 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51A2-MSG-MAIN
2000 AS,
B51A2-MSG
208.0 V
B51A2-11
300 AS,
B51A2-TAP-11
208.0 V
CBL-0519
Size: 1 - 4/0 AWG/kcmil
B51A2-1ALB-MN
225 AS,
10 10
B51A2-MSG-MAIN
WESTNHOUSE
TIME IN SECONDS
DIGTRP RMS
TYPE: DS
Sensor/Trip: 2000A, Settings Recommended
LTPU 1.0 (2000A)
LTD 4.0
STPU 3.0 (6000A)
STD-I2T 0.3 (I^2t Out) CBL-0321
Size: 300 AWG/kcmil
1 1
Qty/Ph: 1
CBL-0519
Size: 4/0 AWG/kcmil
Qty/Ph: 1
B51A2-11
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
0.10 0.10
Sensor/Trip: 300A, Settings Phase
LTPU 1.0 (300A)
LTD LTD
B51A2-1ALB-MN STPU 8.0 (2400A)
WESTNHOUSE STD 100
225 AF Override 1.0 (4000A)
TYPE: CAH 2,3P
Sensor/Trip: 225A, Settings Phase
Opening Clearing Curve
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51A2-1ALC-MN
WESTNHOUSE
225 AF
B51A2-MSG-MAIN
TYPE: CAH 2,3P
Sensor/Trip: 125A, Settings Phase 2000 AS,
Opening Clearing Curve
B51A2-MSG
208.0 V
CBL-0320
Size: 1 - 1 AWG/kcmil
B51A2-1ALC-MN
125 AS,
10 10
CBL-0320
TIME IN SECONDS
Size: 1 AWG/kcmil B51A2-MSG-MAIN
Qty/Ph: 1 WESTNHOUSE
DIGTRP RMS
TYPE: DS
Sensor/Trip: 2000A, Settings Recommended
LTPU 1.0 (2000A)
LTD 4.0
STPU 3.0 (6000A)
1 STD-I2T 0.3 (I^2t Out) 1
B51A2-5
0.10 0.10
Cutler-Hammer
RMS-310
TYPE: KD,HKD LSI
Sensor/Trip: 125A, Settings Recommended
LTPU 1.0 (125A)
LTD 12.0
STPU 8.0 (1000A)
STD-I2T 0.1 (I^2t Out)
Override 1.0 (4000A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51A2-9
B51A2-MSG-MAIN
WESTINGHOUSE
RMS310 LSI 2000 AS,
TYPE: HKD/CHKD
B51A2-MSG
Sensor/Trip: 400A, Settings Phase
208.0 V
LTPU 1.0 (400A)
LTD LTD
STPU 8.0 (3200A) B51A2-9
STD 100 400 AS,
Override 1.0 (4000A)
CBL-0325
Size: 1 - 500 AWG/kcmil
100 100
B51A2-TAP-9
208.0 V
CBL-0515
Size: 1 - 2/0 AWG/kcmil
B51A2-2ALB-MN
175 AS,
B51A2-2ALB
208.0 V
10 10
B51A2-2ALB-MN
TIME IN SECONDS
WESTNHOUSE
225 AF
TYPE: CAH 2,3P
Sensor/Trip: 175A, Settings Phase
Opening Clearing Curve
B51A2-MSG-MAIN
1 WESTNHOUSE 1
DIGTRP RMS
TYPE: DS
Sensor/Trip: 2000A, Settings Recommended
LTPU 1.0 (2000A)
LTD 4.0
STPU 3.0 (6000A)
STD-I2T 0.3 (I^2t Out)
CBL-0325
0.10 Size: 500 AWG/kcmil 0.10
Qty/Ph: 1
CBL-0515
Size: 2/0 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51A2-MSG-MAIN
2000 AS,
B51A2-MSG
208.0 V
B51A2-12
400 AS,
B51A2-MSG-MAIN
WESTNHOUSE CBL-0319
DIGTRP RMS Size: 1 - 500 AWG/kcmil
TYPE: DS N E
100
Sensor/Trip: 2000A, Settings Recommended
LTPU 1.0 (2000A) B51A2-ATS-1A-B51A2100
400.0 A
LTD 4.0
STPU 3.0 (6000A)
B51A2-ATS-1A
STD-I2T 0.3 (I^2t Out) 208.0 V
CBL-0335
Size: 1 - 500 AWG/kcmil
B51A2-ECGA-MAIN
175 AS,
B51A2-ECGA
208.0 V
10 B51A2-12 10
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 400A, Settings Phase
LTPU 1.0 (400A)
TIME IN SECONDS
LTD LTD
STPU 8.0 (3200A)
STD 100
Override 1.0 (4000A)
1 CBL-0319 1
B51A2-ECGA-MAIN
WESTNHOUSE
225 AF
TYPE: CAH 2,3P
Sensor/Trip: 175A, Settings Phase
Opening Clearing Curve
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51A2-GALC-MN
WESTNHOUSE B51A2-MSG-MAIN
250-400A 2000 AS,
TYPE: DK
Sensor/Trip: 300A, Settings Phase B51A2-MSG
LTD 208.0 V
INST 10.0 (3000A)
B51A2-6
300 AS,
B51A2-GALC-MN
300 AS,
B51A2-GALC
208.0 V
B51A2-GALCGALD
WESTNHOUSE B51A2-GALCGALD
225 AF 175 AS,
TYPE: CAH 2,3P
Sensor/Trip: 175A, Settings Phase
10 Opening Clearing Curve 10
B51A2-6
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
TIME IN SECONDS
Sensor/Trip: 300A, Settings Phase
LTPU 1.0 (300A)
LTD LTD
STPU 8.0 (2400A)
STD 100
Override 1.0 (4000A) B51A2-MSG-MAIN
WESTNHOUSE
DIGTRP RMS
1 TYPE: DS 1
Sensor/Trip: 2000A, Settings Recommended
LTPU 1.0 (2000A)
LTD 4.0
STPU 3.0 (6000A)
STD-I2T 0.3 (I^2t Out)
CBL-0326
Size: 350 AWG/kcmil
Qty/Ph: 1
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51A2-MSG-MAIN
2000 AS,
B51A2-9
400 AS,
10 10
TIME IN SECONDS
B51A2-MSG-MAIN
*CUTLER-HAMMER
1 100-1200A 1
0.10 0.10
B51A2-9
*CUTLER-HAMMER
400AF(=80)
TYPE: K(G)DIG310
Sensor/Trip: 80A, Settings Ground
GPU 1.0 (80A)
GTD .150
Override Override (4000A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51A3-MDP-MAIN
600 AS, 3.340 kA
B51A3-MDP
480.0 V
B51A3-3
350 AS,
B51A3-XRB-MAIN
300 AS, 3.744 kA
B51A3-XRB
480.0 V
B51A3-XRB-FDR
100 AS,
B51A3-MDP-MAIN
10 WESTNHOUSE 10
DIGTRP RMS
TYPE: DS
Sensor/Trip: 600A, Settings Recommended
LTPU 0.7 (420A)
LTD 12.0
TIME IN SECONDS
STPU 8.0 (4800A)
STD-I2T 0.3 (I^2t Out)
INST 12.0 (7200A)
B51A3-3
1 WESTINGHOUSE 1
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 350A, Settings Recommended
LTPU 1.0 (350A)
LTD LTD
STPU 8.0 (2800A)
STD 100
Override 1.0 (4000A)
B51A3-XRB-MAIN
*CUTLER-HAMMER CBL-0340
0.10
TH-MAG LI Size: 350 AWG/kcmil 0.10
TYPE: KD Qty/Ph: 1
Sensor/Trip: 300A, Settings Phase
LTD
INST 6.25 (1875A)
B51A3-XRB-FDR
CUTLER-HAMMER
15-150A
TYPE: FD
Sensor/Trip: 100A, Settings Phase
Fixed
0.01 0.01
100
1K
10K
0.5 1 10
100
10K
1K
1 10
1000 1000
B51A3-MDP-MAIN
600 AS,
B51A3-3
350 AS,
B51A3-MDP-MAIN
10 10
*CUTLER-HAMMER
100-1200A
TYPE: DS(G) RMS
Sensor/Trip: 200A, Settings Ground
GPU 1.0 (200A)
TIME IN SECONDS
GTD 0.3 (I^2t Out)
B51A3-3
*CUTLER-HAMMER
1 1
400AF(=80)
TYPE: K(G)DIG310
Sensor/Trip: 80A, Settings Ground
GPU 1.0 (80A)
GTD .150
Override Override (4000A)
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B1-MAIN
WESTNHOUSE B51B1-MAIN
DIGTRP RMS 1200 AS,
TYPE: DS
Sensor/Trip: 1200A, Settings recommended B51B1-MSG
LTPU 1.0 (1200A) 480.0 V
LTD 7.0
STPU 5.0 (6000A) B51B1-10
STD-I2T 0.3 (I^2t Out) 150 AS,
B51B1-1BHB-MN
225 AS,
B51B1-1BHB
480.0 V
B51B1-1BHB-MN B51B1-1BHB-FDR
WESTNHOUSE 20 AS,
70-250 A
TYPE: JDB,JD
10 Sensor/Trip: 225A, Settings Phase 10
LTD
INST 6.25 (1406.25A)
TIME IN SECONDS
B51B1-10
Cutler-Hammer
RMS-310
TYPE: KD,HKD LSI
1
Sensor/Trip: 150A, Settings Recommended 1
LTPU 1.0 (150A)
LTD 12.0
STPU 8.0 (1200A)
STD-I2T 0.1 (I^2t Out)
Override 1.0 (4000A)
B51B1-1BHB-FDR
CUTLER-HAMMER
0.10 15-150A 0.10
TYPE: FD CBL-0305
Sensor/Trip: 20A, Settings Phase Size: 4/0 AWG/kcmil
Fixed Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 GEN-B50 1000
1000.0 kW
B50-GEN
1000 kW 480.0 V
480 V
B50-GENBKR-1
1200 AS,
CBL-0444
Size: 3 - 500 AWG/kcmil
B51B1-EL3B-MAIN
CUTLER-HAMMER
15-150A B50-EMD
480.0 V
100
TYPE: FD 100
Sensor/Trip: 70A, Settings Phase
Fixed B50-EMD-B51
300 AS,
CBL-0448
Size: 1 - 350 AWG/kcmil
Gen SC
B51B1-ATS-2B
480.0 V
CBL-0542
Size: 1 - 2 AWG/kcmil
10 B51B1-EL3B-MAIN 10
70 AS,
TIME IN SECONDS
CBL-0448
B50-EMD-B51 Size: 350 AWG/kcmil
*WESTINGHOUSE Qty/Ph: 1
SELTRONIC LSI
TYPE: HKD/CHKD
1 Sensor/Trip: 300A, Settings Phase CBL-0444 1
LTPU 1.0 (300A) Size: 500 AWG/kcmil
LTD LTD Qty/Ph: 3
STPU 6.0 (1800A)
STD 100
Override 1.0 (4000A) CBL-0542
Size: 2 AWG/kcmil
Qty/Ph: 1
B50-GENBKR-1
SQUARE D
LSI, 250-1200A, UL
TYPE: Powerpact P-Frame, 6.0A/P/H
0.10 Sensor/Trip: 1200A, Settings Phase 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B1-MAIN
1200 AS,
B51B1-MSG
480.0 V
B51B1-5
100 AS,
CBL-0301
Size: 1 - 2 AWG/kcmil
N E
100 100
B51B1-ATS-2B-B51B1
400.0 A
B51B1-ATS-2B
480.0 V
CBL-0549
Size: 1 - 2 AWG/kcmil
B51B1-EL3B-MAIN
70 AS,
B51B1-EL3B
10 B51B1-5 480.0 V 10
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 100A, Settings Phase
TIME IN SECONDS
LTPU 1.0 (100A)
LTD LTD
STPU 8.0 (800A)
STD 100
Override 1.0 (4000A)
1 1
B51B1-MAIN
WESTNHOUSE
DIGTRP RMS
TYPE: DS
Sensor/Trip: 1200A, Settings recommended
LTPU 1.0 (1200A)
LTD 7.0
STPU 5.0 (6000A)
STD-I2T 0.3 (I^2t Out)
CBL-0301
Size: 2 AWG/kcmil
Qty/Ph: 1
0.10 0.10
B51B1-EL3B-MAIN
CUTLER-HAMMER
15-150A
TYPE: FD
Sensor/Trip: 70A, Settings Phase
Fixed
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B1-MAIN
WESTNHOUSE B51B1-MAIN
DIGTRP RMS 1200 AS,
TYPE: DS
Sensor/Trip: 1200A, Settings recommended B51B1-MSG
LTPU 1.0 (1200A) 480.0 V
LTD 7.0
B51B1-6
STPU 5.0 (6000A) 250 AS,
STD-I2T 0.3 (I^2t Out)
CBL-0312
Size: 1 - 350 AWG/kcmil
N E
100 100
B51B1-ATS-3B-B51B1
400.0 A
B51B1-ATS-3B
480.0 V
CBL-0311
B51B1-6 Size: 1 - 2 AWG/kcmil
WESTINGHOUSE
RMS310 LSI B51B1-ELEV
TYPE: HKD/CHKD 480.0 V
Sensor/Trip: 250A, Settings Phase M-B51-ELEV-S4
LTPU 1.0 (250A) 60.0 hp
LTD LTD
10 STPU 4.0 (1000A) 10
STD 100
Override 1.0 (4000A)
TIME IN SECONDS
1 1
69.9 Hp
CBL-0312
0.10 Size: 350 AWG/kcmil 0.10
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
GEN-B50
1000.0 kW
B50-GEN
480.0 V
1000 kW
480 V B50-GENBKR-1
1200 AS,
B50-EMD
480.0 V
B50-EMD-ATS-4B
600 AS,
100 100
CBL-0450
Size: 2 - 300 AWG/kcmil
B51B1-ATS4B-1B
N E
600 AS,
Gen SC
B51B1-ATS4B-B51B1
600.0 A
B51B1-ATS4B
480.0 V
MCCGB2-MAIN
10 10
600 AS,
CBL-0450
Size: 300 AWG/kcmil
Qty/Ph: 2
TIME IN SECONDS
B50-EMD-ATS-4B
WESTINGHOUSE
B51B1-ATS4B-1B 300-600A
WESTINGHOUSE TYPE: LC SELTRNC
400-800A Sensor/Trip: 600A, Settings Phase
TYPE: HMC SELTNC LTPU 1.0 (600A)
Sensor/Trip: 600A, Settings Phase LTD LTD
LTPU 0.9 (540A) STPU 5.0 (3000A)
1 1
LTD LTD STD-I2T STD (I^2t Out)
STPU 3.0 (1800A)
STD-I2T STD (I^2t Out)
Override 1.0 (9000A) B50-GENBKR-1
SQUARE D
LSI, 250-1200A, UL
TYPE: Powerpact P-Frame, 6.0A/P/H
Sensor/Trip: 1200A, Settings Phase
LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 8
STPU (1.5-10 x LTPU) 2 (2400A)
STD (0-0.4) 0.4 (I^2t Out)
INST (2-15 x S) 6 (7200A)
0.10 0.10
MCCGB2-MAIN
WESTNHOUSE
SELTRONIC
TYPE: MC,HMC
Sensor/Trip: 600A, Settings Phase
LTPU 1.0 (600A)
LTD 17.0
STPU 4.0 (2400A)
STD-I2T 0.075 (I^2t Out)
Override 1.0 (9500A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10 B51B1-MAIN
1000 1200 AS, 1000
B51B1-ATS4B-1A B51B1-MSG
WESTNHOUSE 480.0 V
TYPE: MC 800A
B51B1-13
Sensor/Trip: 600A, Settings Phase 600 AS,
LTD
INST 5.63 (3378A) CBL-0307
Size: 2 - 300 AWG/kcmil
B51-ATS4B-1A
480.0 V
B51B1-ATS4B-1A
600 AS,
CBL-0313
100 Size: 2 - 4/0 AWG/kcmil 100
N E
B51B1-ATS4B-B51B1
600.0 A
B51B1-ATS4B
480.0 V
CBL-0308
Size: 2 - 300 AWG/kcmil
B51B1-MAIN
WESTNHOUSE MCCGB2-MAIN
DIGTRP RMS 600 AS,
TYPE: DS B51B1-MCCGB2
Sensor/Trip: 1200A, Settings recommended 480.0 V
10 LTPU 1.0 (1200A) 10
MCCGB2-FDR
LTD 7.0 300 AS,
STPU 5.0 (6000A)
STD-I2T 0.3 (I^2t Out)
TIME IN SECONDS
CBL-0313
Size: 4/0 AWG/kcmil
Qty/Ph: 2
B51B1-13
WESTINGHOUSE
1 RMS310 LSI 1
TYPE: HLD/CHLD CBL-0308
Sensor/Trip: 600A, Settings Phase Size: 300 AWG/kcmil
LTPU 1.0 (600A) Qty/Ph: 2
LTD LTD
STPU 8.0 (4800A)
STD 100
Override 1.0 MCCGB2-MAIN
WESTNHOUSE
SELTRONIC
TYPE: MC,HMC
Sensor/Trip: 600A, Settings Phase
LTPU 1.0 (600A)
0.10
LTD 17.0 0.10
STPU 4.0 (2400A)
STD-I2T 0.075 (I^2t Out)
Override 1.0 (9500A)
MCCGB2-FDR
WESTNHOUSE
100-400A
TYPE: HKD
Sensor/Trip: 300A, Settings Phase
LTD
INST 5.0 (1500A)
0.01 0.01
0.5 1 10
100
10K
1K
100
10K
1K
1 10
1000 1000
B51B1-MAIN
1200 AS,
B51B1-MSG
480.0 V
B51B1-4
100 AS,
B51B1-MAIN
WESTNHOUSE
100 DIGTRP RMS CBL-0297 100
M-ELEVS6
40.0 hp
10 10
CBL-0309
Size: 1/0 AWG/kcmil
TIME IN SECONDS
Qty/Ph: 1
B51B1-4
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 100A, Settings Phase
1 LTPU 1.0 (100A) 1
LTD LTD
STPU 8.0 (800A)
STD 100
Override 1.0 (4000A)
F-ELEVS6
BUSSMANN
FRS-R RK5
TYPE: 15-600A
Sensor/Trip: 90A,
0.10 0.10
46.6 Hp
CBL-0297
Size: 2 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B1-MAIN
WESTNHOUSE B51B1-MAIN
DIGTRP RMS 1200 AS,
TYPE: DS
Sensor/Trip: 1200A, Settings recommended B51B1-MSG
LTPU 1.0 (1200A) 480.0 V
LTD 7.0
STPU 5.0 (6000A) B51B1-2
STD-I2T 0.3 (I^2t Out)
225 AS,
CBL-0295
Size: 1 - 4/0 AWG/kcmil
100 100
B51B1-TAP-2
480.0 V
CBL-0511
B51B1-GBHA-FDR Size: 1 - 1/0 AWG/kcmil
Cutler-Hammer
90-150A B51B1-GBHA
TYPE: FD (NEW) 480.0 V
Sensor/Trip: 100A, Settings Phase
Opening Clearing Curve B51B1-GBHA-FDR
100 AS,
10 10
TIME IN SECONDS
B51B1-2
WESTINGHOUSE
RMS310 LSI
1
TYPE: HKD/CHKD 1
Sensor/Trip: 225A, Settings recommended
LTPU 1.0 (225A)
LTD LTD
STPU 8.0 (1800A)
STD 100
Override 1.0 (4000A)
CBL-0295
0.10 0.10
Size: 4/0 AWG/kcmil
Qty/Ph: 1
CBL-0511
Size: 1/0 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B1-MAIN
WESTNHOUSE
DIGTRP RMS
B51B1-MAIN
TYPE: DS
Sensor/Trip: 1200A, Settings recommended 1200 AS,
LTPU 1.0 (1200A)
LTD 7.0 B51B1-MSG
STPU 5.0 (6000A) 480.0 V
STD-I2T 0.3 (I^2t Out)
B51B1-3
175 AS,
B51B1-K1-FDR
100 AS,
10 10
TIME IN SECONDS
B51B1-3
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 175A, Settings Phase
LTPU 1.0 (175A)
LTD LTD
STPU 8.0 (1400A)
1 1
STD 100
Override 1.0 (4000A)
CBL-0296
Size: 4/0 AWG/kcmil
Qty/Ph: 1
0.10 0.10
B51B1-K1-FDR
Cutler-Hammer
90-150A
TYPE: FD (NEW)
Sensor/Trip: 100A, Settings Phase
Opening Clearing Curve
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
0.5 1 10
1200 AS, 1000
B51B1-MAIN B51B1-MSG
WESTNHOUSE 480.0 V
DIGTRP RMS
TYPE: DS B51B1-11
CBL-0705
CBL-0493 Sensor/Trip: 1200A, recommended 400 AS,
LTPU 1.0 (1200A) CBL-0304
LTD 7.0 Size: 1 - 500 AWG/kcmil
STPU 5.0 (6000A)
STD-I2T 0.3 (I^2t Off)
E N
ATS 6B
ATS-6B 100
480.0 V
CBL-0493
Size: 1 - 500 AWG/kcmil
B51B1-11-TAP
480.0 V
CBL-0705
Size: 1 - 400 AWG/kcmil
MCC2B1-MAIN
MCC2B1-MAIN 400 AS,
WESTNHOUSE B51B1-MCC2B1
SELTRONIC 480.0 V
TYPE: LC,HLC
10
Sensor/Trip: 400A, Phase B51B1-MCC2-FDR
LTPU 1.0 (400A) 150 AS,
LTD 14.5
STPU 5.0 (2000A)
STD-I2T 0.066 (I^2t On)
Override 1.0 (7400A)
TIME IN SECONDS
B51B1-11
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD 1
CBL-0493
Size: 500 AWG/kcmil
Qty/Ph: 1
0.10
CBL-0705
B51B1-MCC2-FDR Size: 400 AWG/kcmil
Cutler-Hammer Qty/Ph: 1
90-150A
TYPE: FD (NEW)
Sensor/Trip: 150A, Phase
Opening Clearing Curve
0.01
GEN-B50
100
10K
1K
0.5 1 10
1000
CBL-0445
CBL-0479 B50-GEN
CBL-0493 B50-GENBKR-2
CBL-0705
CBL-0445
B50-EPD1
B50-ATS-6B
CBL-0479
E N
100
ATS 6B
ATS-6B
CBL-0493
B51B1-11-TAP
CBL-0705
MCC2B1-MAIN
B51B1-MCC2B1
10
B51B1-MCC2-FDR
TIME IN SECONDS
Device: B50-GENBKR-2
Device: B50-ATS-6B Powerpact P-Frame, 6.0A/P/H
HKD, RMS 310 1200A
400A/400A Settings Phase
Settings Phase LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 4
LTPU (1.0 x P) Fixed (400A) STPU (1.5-10 x LTPU) 2 (2400A)
LTD (Fixed) Fixed STD (0-0.4) 0.3 (I^2t Off)
STPU (2-8 x P) 5 (2000A) INST (2-15 x S) 6 (7200A) 1
Name CBL-0479
Device: MCC2B1-MAIN
Size 500 AWG/kcmil
LC,HLC
Qty/Ph 1
400A
Settings Phase
LTPU 1.0 (400A)
LTD 14.5
Name CBL-0493
STPU 5.0 (2000A) 0.10
Size 500 AWG/kcmil
STD-I2T 0.066 (I^2t On)
Qty/Ph 1
Override 1.0 (7400A)
Name CBL-0445
Size 500 AWG/kcmil
Qty/Ph 3
Device: B51B1-MCC2-FDR
FD (NEW)
150A Name CBL-0705
Settings Phase Size 400 AWG/kcmil
Opening Clearing Curve Qty/Ph 1
0.01
100K
100
10K
1K
0.5 1 10
1000
CBL-0302
CBL-0344
B51B1-MAIN
B51B1-MSG
B51B1-8
CBL-0344
E N
ATS 5B 100
ATS-5B
CBL-0302
MCCGB1-MAIN
B51B1-MCCGB1
Device: B51B1-MAIN
DS
1200A B51B1-MCC1B1-GBLC
Settings recommended
LTPU 1.0 (1200A)
LTD 7.0
10
STPU 5.0 (6000A)
STD-I2T 0.3 (I^2t Off)
TIME IN SECONDS
Device: B51B1-8
HKD/CHKD
400A
Settings existing
LTPU 1.0 (400A)
LTD LTD
STPU 7.0 (2800A) 1
STD 100 Name CBL-0302
Override 1.0 (4000A) Size 500 AWG/kcmil
Qty/Ph 1
Name CBL-0344
Device: MCCGB1-MAIN Size 500 AWG/kcmil
LC,HLC Qty/Ph 1
400A
Settings Phase
LTPU 1.0 (400A)
LTD 14.5
STPU 5.0 (2000A)
0.10
STD-I2T 0.066 (I^2t On)
Override 1.0 (7400A)
Device: B51B1-MCC1B1-GBLC
HFD
25A
Settings Phase
Fixed
0.01
100K
100
10K
1K
0.5 1 10
1000
CBL-0445 GEN-B50
CBL-0476 B50-GEN
CBL-0302
B50-GENBKR-2
CBL-0445
B50-EPD1
B50-ATS-5B
CBL-0476
100
E N
ATS 5B
ATS-5B
CBL-0302
MCCGB1-MAIN
B51B1-MCCGB1
B51B1-MCC1B1-GBLC
10
TIME IN SECONDS
Device: B50-ATS-5B
HKD, RMS 310 Device: B50-GENBKR-2
400A/400A Powerpact P-Frame, 6.0A/P/H
Settings Phase 1200A
LTPU (1.0 x P) Fixed (400A) Settings Phase
LTD (Fixed) Fixed LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 4
STPU (2-8 x P) 5 (2000A) STPU (1.5-10 x LTPU) 2 (2400A)
STD (Inst-300 ms) Inst (I^2t Off) STD (0-0.4) 0.3 (I^2t Off)
1
INST (4000A) Fixed (4000A) INST (2-15 x S) 6 (7200A)
Name CBL-0476
Device: MCCGB1-MAIN Size 500 AWG/kcmil
LC,HLC Qty/Ph 1
400A
Settings Phase
LTPU 1.0 (400A)
LTD 14.5
STPU 5.0 (2000A)
STD-I2T 0.066 (I^2t On) 0.10
Device: B51B1-MCC1B1-GBLC
HFD
25A Name CBL-0302
Settings Phase Size 500 AWG/kcmil
Fixed Qty/Ph 1
0.01
100
10K
1K
1 10
1000 1000
B51B1-MAIN
1200 AS,
B51B1-MSG
480.0 V
B51B1-11
WESTINGHOUSE B51B1-11
RMS310 LSI 400 AS,
TYPE: HKD/CHKD
100 Sensor/Trip: 400A, Settings recommended CBL-0304 100
10 10
TIME IN SECONDS
B51B1-MAIN
WESTNHOUSE
DIGTRP RMS
TYPE: DS
Sensor/Trip: 1200A, Settings recommended
LTPU 1.0 (1200A)
LTD 7.0
STPU 5.0 (6000A)
1 1
STD-I2T 0.3 (I^2t Out) CBL-0304
Size: 500 AWG/kcmil
Qty/Ph: 1
B51B1-MCC3B1-MAIN
CUTLER-HAMMER
100-400
TYPE: HKD
Sensor/Trip: 400A, Settings Phase
LTD
0.10 INST 5.0 (2000A) 0.10
B51B1-MCC3B1-3BLC
CUTLER-HAMMER
15-150A
TYPE: HFD
Sensor/Trip: 25A, Settings Phase
Fixed
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B1-MAIN
1200 AS,
B51B1-13
600 AS,
10 10
TIME IN SECONDS
B51B1-MAIN
*CUTLER-HAMMER
100-1200A
1 TYPE: DS(G) RMS 1
0.10 0.10
B51B1-13
*CUTLER-HAMMER
600AF(=120
TYPE: L(G)DIG310
Sensor/Trip: 120A, Settings Ground
GPU 1.0 (120A)
GTD .150
Override Override (5500A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B2-MAIN
WESTNHOUSE
DIGTRP RMS
TYPE: DS B51B2-MAIN
Sensor/Trip: 2000A, Settings Recommended Settings 2000 AS,
LTPU 1.0 (2000A)
LTD 4.0 B51B2-MSG
STPU 2.5 (5000A) 208.0 V
STD-I2T 0.3 (I^2t Out)
B51B2-2
350 AS,
10 10
B51B2-1BLC-MN
Cutler-Hammer
250-400A
TIME IN SECONDS
TYPE: DK
Sensor/Trip: 350A, Settings Phase
LTD
INST 7.5 (2625A)
1 CBL-0277 1
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B2-MAIN
2000 AS,
B51B2-MSG
208.0 V
B51B2-12
175 AS,
100 100
CBL-0283
Size: 1 - 2/0 AWG/kcmil
B51B2-1BLE
208.0 V
B51B2-MAIN
WESTNHOUSE B51B2-1BLE-BRANCH
DIGTRP RMS 60 AS,
TYPE: DS
Sensor/Trip: 2000A, Settings Recommended Settings
LTPU 1.0 (2000A)
10
LTD 4.0 10
STPU 2.5 (5000A)
STD-I2T 0.3 (I^2t Out)
TIME IN SECONDS
B51B2-12
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 175A, Settings Recommended Settings
LTPU 1.0 (175A) CBL-0283
1 LTD LTD Size: 2/0 AWG/kcmil1
STPU 8.0 (1400A) Qty/Ph: 1
STD 100
Override 1.0 (4000A)
B51B2-1BLE-BRANCH
WESTNHOUSE
3P 100 AF
0.10 TYPE: BA,HQNP C 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B2-MAIN
2000 AS,
B51B2-MSG
208.0 V
B51B2-3
300 AS,
100 100
CBL-0286
Size: 1 - 350 AWG/kcmil
B51B2-3BLA
208.0 V
B51B2-MAIN B51B2-3BLA-FDR
WESTNHOUSE 70 AS,
DIGTRP RMS
TYPE: DS
Sensor/Trip: 2000A, Settings Recommended Settings
LTPU 1.0 (2000A)
10 10
LTD 4.0
STPU 2.5 (5000A)
STD-I2T 0.3 (I^2t Out)
TIME IN SECONDS
B51B2-3
WESTINGHOUSE CBL-0286
RMS310 LSI Size: 350 AWG/kcmil
1 TYPE: HKD/CHKD Qty/Ph: 1 1
Sensor/Trip: 300A, Settings existing settings
LTPU 1.0 (300A)
LTD LTD
STPU 6.0 (1800A)
STD 100
Override 1.0 (4000A)
B51B2-3BLA-FDR
0.10 *CUTLER-HAMMER 0.10
QBH 70AMP
TYPE: BAB,HBA,QC
Sensor/Trip: 70A, Settings Phase
Opening Clearing Curve
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
GEN-B50
GEN-B50
1000.0 kW
B50-GEN
480.0 V
B50-GENBKR-1
1200 AS,
CBL-0444
Size: 3 - 500 AWG/kcmil
100 100
B50-EMD
B50-GENBKR-1 480.0 V
SQUARE D
LSI, 250-1200A, UL B50-EMD-ATS-1A
TYPE: Powerpact P-Frame, 6.0A/P/H 250 AS,
Gen SC
Sensor/Trip: 1200A, Settings Phase
LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 8 CBL-0449
STPU (1.5-10 x LTPU) 2 (2400A) Size: 1 - 500 AWG/kcmil
STD (0-0.4) 0.4 (I^2t Out)
INST (2-15 x S) 6 (7200A) F-B51B2-ATS1B
200 AS,
10 10
F-B51B2-ATS1B
BUSSMANN
TIME IN SECONDS
FRS-R RK5
TYPE: 15-600A
Sensor/Trip: 200A, CBL-0444
Size: 500 AWG/kcmil
Qty/Ph: 3
1 1
1000 kW
480 V
CBL-0449
Size: 500 AWG/kcmil
Qty/Ph: 1
0.10 0.10
B50-EMD-ATS-1A
*WESTINGHOUSE
SELTRONIC LSI
TYPE: HKD/CHKD
Sensor/Trip: 250A, Settings Phase
LTPU 1.0 (250A)
LTD LTD
STPU 7.0 (1750A)
STD 100
Override 1.0 (4000A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 B51B2-MAIN 1000
2000 AS,
B51B2-MSG
208.0 V
B51B2-5
400 AS,
CBL-0279
Size: 1 - 500 AWG/kcmil
E N
B51B2-ATS-1B-B51B2
400.0 A
100 100
B51B2-ECGB-MN
WESTNHOUSE B51B2-ATS-1B
225 AF 208.0 V
TYPE: CAH 2,3P
Sensor/Trip: 150A, Settings Phase CBL-0315
Opening Clearing Curve Size: 1 - 500 AWG/kcmil
B51B2-TAP-5
208.0 V
CBL-0505
Size: 1 - 1/0 AWG/kcmil
10 B51B2-ECGB-MN 10
150 AS,
B51B2-5
WESTINGHOUSE
TIME IN SECONDS
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 400A, Settings Phase
LTPU 1.0 (400A) B51B2-MAIN
LTD LTD WESTNHOUSE
STPU 8.0 (3200A) DIGTRP RMS
STD 100 TYPE: DS
Override 1.0 (4000A) Sensor/Trip: 2000A, Settings Recommended Settings
1 1
LTPU 1.0 (2000A)
LTD 4.0
STPU 2.5 (5000A)
STD-I2T 0.3 (I^2t Out)
CBL-0315
Size: 500 AWG/kcmil
Qty/Ph: 1
0.10 0.10
CBL-0505
Size: 1/0 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
GEN-B50
1000 1000
1000.0 kW
1000 kW
B50-GEN
480 V 480.0 V
B50-GENBKR-1
1200 AS,
CBL-0444
Size: 3 - 500 AWG/kcmil
B50-EMD
T-B51B2-ATSEK6&EK7 480.0 V
300 kVA
B50-EMD-ATS-EK6&EK7
480 / 208 V 400 AS,
100 100
CBL-0469
Size: 1 - 500 AWG/kcmil
P
T-B51B2-ATSEK6&EK7
S 300.0 kVA
F-B51B2-EK6
Gen SC 400 AS,
N E
B51B2-ATS-EK6-B51B2
B51B2-ATS-EK6
208.0 V
CBL-0403
Size: 1 - 500 AWG/kcmil
10 10
B51B2-EK6-MAIN
400 AS,
CBL-0444
Size: 500 AWG/kcmil
TIME IN SECONDS
Qty/Ph: 3
CBL-0469 B50-EMD-ATS-EK6&EK7
Size: 500 AWG/kcmil *WESTINGHOUSE
Qty/Ph: 1 SELTRONIC LSI
TYPE: HKD/CHKD
1 1
Sensor/Trip: 400A, Settings Phase
LTPU 1.0 (400A)
LTD LTD
STPU 8.0 (3200A)
STD 300
Override 1.0 (4000A)
B50-GENBKR-1
SQUARE D
LSI, 250-1200A, UL
F-B51B2-EK6 TYPE: Powerpact P-Frame, 6.0A/P/H
TX Inrush Sensor/Trip: 1200A, Settings Phase
BUSSMANN
0.10
FRN-R RK5 LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 8 0.10
B51B2-EK6-MAIN
GE
250-400A
TYPE: TJD CBL-0403
Sensor/Trip: 400A, Settings Phase Size: 500 AWG/kcmil
Fixed Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B2-MAIN
B51B2-EK6-MAIN 2000 AS,
GE
250-400A B51B2-MSG
TYPE: TJD 208.0 V
Sensor/Trip: 400A, Settings Phase
Fixed B51B2-13
400 AS,
CBL-0303
Size: 1 - 500 AWG/kcmil
N E
100 100
B51B2-ATS-EK6-B51B2
B51B2-ATS-EK6
208.0 V
CBL-0403
Size: 1 - 500 AWG/kcmil
B51B2-EK6-MAIN
400 AS,
B51B2-EK6
208.0 V
10 10
TIME IN SECONDS
B51B2-MAIN
WESTNHOUSE
DIGTRP RMS
TYPE: DS
Sensor/Trip: 2000A, Settings Recommended Settings
LTPU 1.0 (2000A)
1 LTD 4.0 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B2-MAIN
2000 AS,
B51B2-MSG
208.0 V
CBL-0280
Size: 1 - 500 AWG/kcmil
B51B2-1BLA-MN
350 AS,
10 10
TIME IN SECONDS
B51B2-MAIN
WESTNHOUSE
DIGTRP RMS
TYPE: DS
Sensor/Trip: 2000A, Settings Recommended Settings
LTPU 1.0 (2000A)
1
LTD 4.0 1
STPU 2.5 (5000A)
STD-I2T 0.3 (I^2t Out)
CBL-0287
B51B2-1BLA-MN Size: 500 AWG/kcmil
WESTNHOUSE Qty/Ph: 1
100-400A
TYPE: KDB
Sensor/Trip: 350A, Settings Phase
0.10 0.10
LTD B51B2-6
INST 5.0 (1750A) Cutler-Hammer
RMS-310
TYPE: KD,HKD LSI
Sensor/Trip: 400A, Settings Recommended Settings
LTPU 1.0 (400A)
LTD 12.0
STPU 7.0 (2800A)
STD-I2T 0.1 (I^2t In)
Override 1.0 (4000A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B2-MAIN
2000 AS,
B51B2-MSG
B51B2-MAIN 208.0 V
WESTNHOUSE
DIGTRP RMS B51B2-7
TYPE: DS 350 AS,
Sensor/Trip: 2000A, Settings Recommended Settings
LTPU 1.0 (2000A) CBL-0281
LTD 4.0 Size: 1 - 350 AWG/kcmil
STPU 2.5 (5000A)
STD-I2T 0.3 (I^2t Out)
100 B51B2-GBLB 100
208.0 V
CBL-0509
Size: 1 - 500 AWG/kcmil
B51B2-JBOX-7
208.0 V
CBL-0293
B51B2-7 Size: 1 - 300 AWG/kcmil
WESTINGHOUSE
RMS310 LSI B51B2-1BLB-MN
10
TYPE: HKD/CHKD 225 AS, 10
Sensor/Trip: 350A, Settings Phase
LTPU 1.0 (350A)
LTD LTD
STPU 8.0 (2800A)
STD 100
TIME IN SECONDS
Override 1.0 (4000A)
CBL-0509
Size: 500 AWG/kcmil
Qty/Ph: 1
1 1
CBL-0281
Size: 350 AWG/kcmil
Qty/Ph: 1
CBL-0293
Size: 300 AWG/kcmil
Qty/Ph: 1
0.10 0.10
B51B2-1BLB-MN
WESTNHOUSE
225 AF
TYPE: CAH 2,3P
Sensor/Trip: 225A, Settings Phase
Opening Clearing Curve
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B2-MAIN
B51B2-K4-BRANCH 2000 AS,
WESTNHOUSE
3P 100 AF
B51B2-MSG
TYPE: BA,HQNP C
208.0 V
Sensor/Trip: 90A, Settings Phase
Opening Clearing Curve
B51B2-8
400 AS,
CBL-0284
Size: 1 - 500 AWG/kcmil
B51B2-K3
208.0 V
CBL-0290
Size: 1 - 250 AWG/kcmil
B51B2-K4
208.0 V
B51B2-K4-BRANCH
10 90 AS, 10
B51B2-K3-MN
WESTNHOUSE
CBL-0290
100-400A
TIME IN SECONDS
Size: 250 AWG/kcmil
TYPE: KDB
Qty/Ph: 1
Sensor/Trip: 250A, Settings Phase
LTD
INST 10.0 (2500A) B51B2-MAIN
WESTNHOUSE
DIGTRP RMS
TYPE: DS
1
Sensor/Trip: 2000A, Settings Recommended Settings 1
LTPU 1.0 (2000A)
LTD 4.0
STPU 2.5 (5000A)
STD-I2T 0.3 (I^2t Out)
B51B2-8
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
0.10 0.10
Sensor/Trip: 400A, Settings Phase
LTPU 1.0 (400A)
LTD LTD
STPU 8.0 (3200A)
STD 100
Override 1.0 (4000A)
CBL-0284
Size: 500 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B51B2-MAIN
2000 AS,
B51B2-MSG
208.0 V
B51B2-9
400 AS,
B51B2-K5-MN B51B2-TAP-9
WESTNHOUSE 208.0 V
225 AF
TYPE: CAH 2,3P CBL-0291
Sensor/Trip: 125A, Settings Phase
Size: 1 - 4/0 AWG/kcmil
Opening Clearing Curve
B51B2-K5-MN
125 AS,
10 B51B2-MAIN 10
WESTNHOUSE
DIGTRP RMS
TYPE: DS
Sensor/Trip: 2000A, Settings Phase
TIME IN SECONDS
LTPU 1.0 (2000A)
LTD 4.0
STPU 2.5 (5000A)
STD-I2T 0.3 (I^2t Out) B51B2-9
WESTINGHOUSE
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 400A, Settings Phase
1 LTPU 1.0 (400A) 1
LTD LTD
STPU 6.0 (2400A)
STD 100
Override 1.0 (4000A)
CBL-0285
Size: 500 AWG/kcmil
Qty/Ph: 1
CBL-0291
0.10 0.10
Size: 4/0 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 B52-MSG-MN 1000
1200 AS,
B52-MSG
480.0 V
B52-SWBD-ATS
600 AS,
CBL-0437
Size: 2 - 300 AWG/kcmil
N E
B52-ATS-B52
100 600.0 A 100
B52-ATS
480.0 V
CBL-0438
Size: 2 - 300 AWG/kcmil
B52-ECBA-MN
600 AS,
B52-ECBA
480.0 V
10 B52-ECBA-T 10
150 AS,
TIME IN SECONDS
B52-MSG-MN
GE PWRBK 2
100-2000A
TYPE: MVT+PM STD
Sensor/Trip: 1200A, Settings Phase
LTPU 0.9; 1 (1080A)
LTD 2
STPU 4.0 (4320A)
1 1
STD-I2T MAX (I^2t Out)
CBL-0437
Size: 300 AWG/kcmil
Qty/Ph: 2
B52-ECBA-MN
GE J600
125-600 A
TYPE: TJJ, TJKR B52-SWBD-ATS
Sensor/Trip: 600A, Settings Phase GE PWRBK 2
LTD 100-2000A
INST 4 (2400A) TYPE: MVT+PM STD
0.10 Sensor/Trip: 600A, Settings recommended 0.10
LTPU 1; 1 (600A)
LTD 2
STPU 5.0 (3000A)
B52-ECBA-T STD-I2T MIN (I^2t Out)
GE INST 15.0 (9000A)
125-400A
TYPE: TJJ
Sensor/Trip: 150A, Settings Phase
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (1500A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B52-MSG-MN
1200 AS,
B52-MSG
480.0 V
B52-SWBD-B53
250 AS,
100 100
CBL-0434
Size: 1 - 4/0 AWG/kcmil
B52-B53-SWBD
480.0 V
B53-GA-MAIN
250 AS,
10 10
TIME IN SECONDS
B52-MSG-MN
GE PWRBK 2
100-2000A
TYPE: MVT+PM STD
Sensor/Trip: 1200A, Settings Phase
LTPU 0.9; 1 (1080A)
LTD 2
1 STPU 4.0 (4320A) 1
CBL-0434
Size: 4/0 AWG/kcmil
Qty/Ph: 1
B52-SWBD-B53
B53-GA-MAIN GE PWRBK 2
GE 100-2000A
0.10 0.10
250-400A TYPE: MVT+PM STD
TYPE: TLB4 Sensor/Trip: 250A, Settings Recommended
Sensor/Trip: 250A, Settings Phase LTPU 1; 1 (250A)
Thermal Curve (Fixed) LTD 4
INST (4.5-10 x Trip) HI (2500A) STPU 9.0 (2250A)
STD-I2T MIN (I^2t Out)
INST 15.0 (3750A)
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B52-MSG
480.0 V
T-B52-C B52-SWBD-CA
200 AS,
CBL-0436
Size: 1 - 2/0 AWG/kcmil
B52-CA-MAIN
175 AS,
100 100
B52-CA
480.0 V
P
T-B52-C
S 45.0 kVA
B52-C-MAIN
150 AS,
B52-C
208.0 V
10 10
T-B52-C
45 kVA
480 / 208 V
TIME IN SECONDS
CBL-0436
Size: 2/0 AWG/kcmil
1 1
Qty/Ph: 1
B52-CA-MAIN
GE F225
70-225 AMP
B52-SWBD-CA
TYPE: TFJ
GE PWRBK 2
Sensor/Trip: 175A, Settings Phase
100-2000A
LTD
TYPE: MVT+PM STD
INST 7 (1225A)
TX Inrush Sensor/Trip: 200A, Settings Recommended
0.10 LTPU 0.9; 1 (180A) 0.10
LTD 4
STPU 9.0 (1620A)
B52-C-MAIN STD-I2T MIN (I^2t Out)
GE INST 15.0 (3000A)
100-225A
TYPE: THQD
Sensor/Trip: 150A, Settings Phase
Fixed
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
T-B52-ELB
B52-ECBA-T
150 AS,
CBL-0439
Size: 1 - 1 AWG/kcmil
B52-ELBH-MN
150 AS,
P
T-B52-ELB
S
75.0 kVA
B52-ELB-MAIN
200 AS,
B52-ELB
208.0 V
10 10
TIME IN SECONDS
T-B52-ELB
75 kVA
480 / 208 V
CBL-0439
Size: 1 AWG/kcmil
1 Qty/Ph: 1 1
B52-ECBA-T
GE
125-400A
TYPE: TJJ
B52-ELBH-MN Sensor/Trip: 150A, Settings Phase
GE Thermal Curve (Fixed)
125-400A
INST (3-10 x Trip) HI (1500A)
TYPE: TJJ
Sensor/Trip: 150A, Settings Phase
Thermal Curve (Fixed) TX Inrush
0.10 INST (3-10 x Trip) 9 (1350A) 0.10
B52-ELB-MAIN
GE
100-225A
TYPE: THQD
Sensor/Trip: 200A, Settings Phase
Fixed
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B52-MSG-MN
1200 AS,
B52-MSG
480.0 V
B52-SWBD-MCC1
100 100
600 AS,
CBL-0440
Size: 2 - 300 AWG/kcmil
B52-MCC1
480.0 V
10 10
B52-MSG-MN
TIME IN SECONDS
GE PWRBK 2
100-2000A
TYPE: MVT+PM STD
Sensor/Trip: 1200A, Settings Phase
LTPU 0.9; 1 (1080A)
LTD 2
STPU 4.0 (4320A)
STD-I2T MAX (I^2t Out)
1 1
B52-SWBD-MCC1
GE PWRBK 2
100-2000A
TYPE: MVT+PM STD
Sensor/Trip: 600A, Settings Recommended
LTPU 1; 1 (600A)
LTD 2
STPU 4.0 (2400A)
STD-I2T MIN (I^2t Out)
INST 10.0 (6000A)
0.10 0.10
CBL-0440
Size: 300 AWG/kcmil
Qty/Ph: 2
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
GEN-B52
350.0 kW
B52-GEN-MN
600 AS,
B52-GEN
480.0 V
CBL-0441
Size: 2 - 300 AWG/kcmil
100 N E 100
B52-ATS-B52
600.0 A
B52-ATS
480.0 V
Gen SC
CBL-0438
Size: 2 - 300 AWG/kcmil
B52-ECBA-MN
B52-GEN-MN 600 AS,
*MERLIN GERIN GENERIC
LSI, 800A
10 TYPE: ST GENERIC 10
TIME IN SECONDS
GE J600 STD (0-0.3) 0.3
125-600 A
TYPE: TJJ, TJKR
Sensor/Trip: 600A, Settings Phase
LTD
INST 4 (2400A)
1 1
CBL-0441
Size: 300 AWG/kcmil
Qty/Ph: 2
0.10 0.10
350 kW
480 V
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
T-B53-G B53-GA-MAIN
75 kVA 250 AS,
480 / 208 V
B53-GA-LEFT
480.0 V
B53-GA-T-G
100 AS,
CBL-0526
Size: 1 - 2 AWG/kcmil
100 100
P
T-B53-G
S
75.0 kVA
B53-G-LEFT-MN
225 AS,
B53-GA-MAIN B53-G-LEFT
GE 208.0 V
250-400A
TYPE: TLB4 B53-G-BRANCH
Sensor/Trip: 250A, Settings Phase 70 AS,
10 Thermal Curve (Fixed) 10
TIME IN SECONDS
B53-GA-T-G
GE CBL-0526
90-150A Size: 2 AWG/kcmil
TYPE: THED Qty/Ph: 1
Sensor/Trip: 100A, Settings Phase
1
Opening Clearing Curve 1
B53-G-LEFT-MN
GE
70-225A
TYPE: TFJ
Sensor/Trip: 225A, Settings Phase
Thermal Curve (Fixed)
INST (4.5-10 x Trip) 7 (1575A)
TX Inrush
0.10 0.10
B53-G-BRANCH
GE
15-100A
TYPE: THQB
Sensor/Trip: 70A, Settings Phase
Fixed
0.01 0.01
0.5 1 10
1K
100
10K
100K
100
10K
1K
1 10
1000 1000
B69-MSB-MAIN
1200 AS,
25.0 Hp
B69-MSB
208.0 V
100 100
B69-MSB-AHU1S
160 AS,
CBL-1059
Size: 1 - 1/0 AWG/kcmil
M-B69-AHU-1-S
25.0 hp
10 10
B69-MSB-MAIN
TIME IN SECONDS
LITTELFUSE
150-2000A
TYPE: LDC, 600V Class L
B69-MSB-AHU1S Sensor/Trip: 1200A,
CUTLER-HAMMER
LSI, 80-225AS FLAT
TYPE: FDE/FDCE/HFDE, 310+
1 Sensor/Trip: 160A, Settings Phase 1
Ir, 160A Sensor F (125) (125A)
LTD 2
STPU 7 (875A)
STD M,N,O
INST OR Fixed (1920A)
0.10 0.10
CBL-1059
Size: 1/0 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100K
100K
100
10K
1K
1 10
1000 1000
B69-MSB-MAIN
1200 AS,
15.0 Hp B69-MSB
208.0 V
100 100
B69-MSB-AHU2S
160 AS,
B69-MSB-MAIN
LITTELFUSE CBL-1061
150-2000A Size: 1 - 2 AWG/kcmil
TYPE: LDC, 600V Class L
Sensor/Trip: 1200A, M-B69-AHU-2-S
15.0 hp
10 10
TIME IN SECONDS
B69-MSB-AHU2S CBL-1061
1 CUTLER-HAMMER Size: 2 AWG/kcmil 1
LSI, 80-225AS FLAT Qty/Ph: 1
TYPE: FDE/FDCE/HFDE, 310+
Sensor/Trip: 160A, Settings Phase
Ir, 160A Sensor E (100) (100A)
LTD 4
STPU 5 (500A)
STD M,N,O
INST OR Fixed (1920A)
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100K
100K
100
10K
10M
1K
1M
1 10
1000 1000
B69-MSB-MAIN
1200 AS,
B69-MSB
208.0 V
B69-MSB-MAIN
LITTELFUSE
150-2000A B69-MSB-1LC
100 100
TYPE: LDC, 600V Class L 400 AS, 400 AT
Sensor/Trip: 1200A,
CBL-1054
Size: 1 - 500 AWG/kcmil
B69-1LC-1
208.0 V
B69-1LC-BRANCH
50 AS,
10 10
B69-1LC-BRANCH
CUTLER-HAMMER
TIME IN SECONDS
15-125A
TYPE: QBHW, 2-Pole
Sensor/Trip: 50A, Settings Phase
Fixed
CBL-1054
1 1
Size: 500 AWG/kcmil
Qty/Ph: 1
B69-MSB-1LC
CUTLER-HAMMER
LSI, 200-400A Adj Plug
0.10 TYPE: KD, RMS 310 0.10
Sensor/Trip: 400A, Plug: 400 AT
Settings Phase
Plug Adj (200-400A) 400A (400A)
LTD (Fixed) Fixed
STPU (2-8 x LTPU) 3 (1200A)
STD (Inst-300 ms) 100 ms (I^2t Out)
INST (4000A) Fixed (4000A)
0.01 0.01
0.5 1 10
1K
1M
100
10K
10M
100K
100
10K
1K
1 10
1000 1000
B69-MSB-AHU1R
CUTLER-HAMMER
LSI, 80-225AS FLAT
TYPE: FDE/FDCE/HFDE, 310+ B69-MSB-MAIN
Sensor/Trip: 160A, Settings Phase 1200 AS,
Ir, 160A Sensor A (60) (60A)
LTD 2 B69-MSB
STPU 4 (240A)
208.0 V
STD P,Q,R
INST OR Fixed (1920A)
100 B69-MSB-AHU1R 100
160 AS,
CBL-1060
Size: 1 - 6 AWG/kcmil
B69-MSB-MAIN
7.5 Hp M-B69-AHU-1-R
LITTELFUSE
150-2000A 7.5 hp
TYPE: LDC, 600V Class L
Sensor/Trip: 1200A,
10 10
TIME IN SECONDS
1 1
CBL-1060
Size: 6 AWG/kcmil
Qty/Ph: 1
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B69-MSB-AHU2R
CUTLER-HAMMER
LSI, 80-225AS FLAT
TYPE: FDE/FDCE/HFDE, 310+ B69-MSB-MAIN
Sensor/Trip: 80A, Settings Phase 1200 AS,
Ir, 80A Sensor D (40) (40A)
LTD 2 B69-MSB
STPU 4 (160A) 208.0 V
STD P,Q,R
INST OR Fixed (960A)
100 B69-MSB-AHU2R 100
80 AS,
CBL-1062
Size: 1 - 8 AWG/kcmil
M-B69-AHU-2-R
5.0 hp
5.0 Hp
10 10
TIME IN SECONDS
B69-MSB-MAIN
LITTELFUSE
150-2000A
TYPE: LDC, 600V Class L
Sensor/Trip: 1200A,
1 1
CBL-1062
Size: 8 AWG/kcmil
Qty/Ph: 1
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100K
100
10K
1K
1 10
1000 1000
CBL-1055
B69-MSB-MAIN
1200 AS,
40.0 Hp B69-MSB
208.0 V
B69-MSB-ELEV1
100 225 AS, 100
F-B69-ELEV1
GOULD SHAWMUT CBL-1055
15-600A Size: 1 - 2/0 AWG/kcmil
TYPE: TR, 250V Class RK5
Sensor/Trip: 175A, F-B69-ELEV1
175 AS,
M-B69-ELEV1
40.0 hp
10 10
TIME IN SECONDS
B69-MSB-ELEV1 B69-MSB-MAIN
CUTLER-HAMMER LITTELFUSE
LSI, 80-225AS FLAT 150-2000A
TYPE: FDE/FDCE/HFDE, 310+ TYPE: LDC, 600V Class L
Sensor/Trip: 225A, Settings Phase Sensor/Trip: 1200A,
Ir, 225A Sensor F (175) (175A)
1 1
LTD 4
STPU 6 (1050A)
STD M,N,O
INST OR Fixed (2700A)
0.10 0.10
CBL-1055
Size: 2/0 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100K
100
1K
1 10
1000 1000
B69-MSB-MAIN
1200 AS,
B69-MSB
208.0 V
B69-MSB-ATSEQNE
160 AS,
CBL-1076
Size: 1 - 1/0 AWG/kcmil
E N
100 100
B69-ATS-EQNE
208.0 V
CBL-1077
Size: 1 - 1/0 AWG/kcmil
B69-EQNE-MAIN
150 AS,
B69-MSB-ATSEQNE B69-EQNE
CUTLER-HAMMER 208.0 V
10 LSI, 80-225AS FLAT 10
TIME IN SECONDS
STPU 12 (1800A)
STD M,N,O
INST OR Fixed (1920A)
B69-MSB-MAIN
LITTELFUSE
1
150-2000A 1
TYPE: LDC, 600V Class L
Sensor/Trip: 1200A,
B69-EQNE-MAIN
CUTLER-HAMMER
100-225A
TYPE: ED, EDB, EDS
Sensor/Trip: 150A, Settings Phase
Fixed
0.10 0.10
CBL-1076
Size: 1/0 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
100K
100
10K
1K
1 10 GEN-B69&70
1000 250.0 kW 1000
B70-MSQ-ATSQA B69&70-GEN
CUTLER-HAMMER 480.0 V
TIME IN SECONDS
B70-QHBA1-MAIN
40.0 Hp CUTLER-HAMMER
100-400A
1 TYPE: KD 1
Sensor/Trip: 400A, Settings Phase
Thermal Curve (Fixed)
INST (5-10 x Trip) 5 (2000A)
CBL-1084
Size: 250 AWG/kcmil
Qty/Ph: 2
CBL-1086
Size: 500 AWG/kcmil
Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100K
100
10K
1K
1 10 GEN-B69&70
1000 250.0 kW 1000
GEN-B69&70
B69&70-GEN-MAIN B69&70-GEN
MERLIN GERIN 480.0 V
60-400A
B69&70-GEN-MAIN
TYPE: NSJ400 w/STR23SP
400 AS,
Sensor/Trip: 400A, Settings Phase
Io, Ir 1; 1 (400A) CBL-1084
LTD Fixed Size: 2 - 250 AWG/kcmil
STPU, Im 3 (1200A)
STD Fixed B70-MSQ
Inst Fixed (3600A) 480.0 V
B70-MSQ-ATSLA
160 AS,
100 100
CBL-1083
Size: 1 - 1 AWG/kcmil
E N
Gen SC B70-ATS-LA
480.0 V
CBL-1080
Size: 1 - 1 AWG/kcmil
250 kW
480 V B70-LHBA1-MAIN
100 AS,
10 10
B70-LHBA1
480.0 V
TIME IN SECONDS
CBL-1083
Size: 1 AWG/kcmil
Qty/Ph: 1
1 1
CBL-1084
Size: 250 AWG/kcmil
Qty/Ph: 2
B70-MSQ-ATSLA
CUTLER-HAMMER
LSI, 80-225AS FLAT
TYPE: FDE/FDCE/HFDE, 310+
0.10 Sensor/Trip: 160A, Settings Phase 0.10
Ir, 160A Sensor E (100) (100A)
B70-LHBA1-MAIN LTD 24
CUTLER-HAMMER STPU 12 (1200A)
15-225A STD M,N,O
TYPE: FD INST OR Fixed (1920A)
Sensor/Trip: 100A, Settings Phase
Fixed
0.01 0.01
0.5 1 10
1K
100
10K
100
10K
1K
1 10
1000 1000
B70-MSA MAIN
1600 AS, 1600 AT
B70-MSA-NHBA2
225 AS,
B70-MSA MAIN
CUTLER-HAMMER
GF, 800-2500A
TYPE: RD, RMS 310
Sensor/Trip: 1600A, Plug: 1600 AT
Settings GROUND
10 GFPU (B-K) B (400A) 10
GFD (Inst-500 ms) 500 ms (I^2t Out)
TIME IN SECONDS
B70-MSA-NHBA2
CUTLER-HAMMER
GF, 80-225AS
TYPE: FDE/FDCE/HFDE, 310+
Sensor/Trip: 225A, Plug: 225 AT
Settings GROUND
GFPU, (0.2 - 1 x S) 0.2 (45A)
1
GFD, (Inst - 300ms) K,N,Q 1
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100K
100
10K
1K
1 10
1000 1000
B70-MSA MAIN
1600 AS, 1600 AT
10 10
TIME IN SECONDS
B70-MSA MAIN
CUTLER-HAMMER
GF, 800-2500A
TYPE: RD, RMS 310
Sensor/Trip: 1600A, Plug: 1600 AT
Settings GROUND
GFPU (B-K) B (400A)
GFD (Inst-500 ms) 500 ms (I^2t Out)
1 1
0.10 0.10
0.01 0.01
0.5 1 10
1K
100
10K
100K
100K
100
10K
1K
1 10 B70-MSA MAIN
1000 1000
1600 AS, 1600 AT
B70-MSA
B70-QHBA1-MAIN
480.0 V
CUTLER-HAMMER
100-400A B70-MSA-ATSQA
TYPE: KD 400 AS, 300 AT
Sensor/Trip: 400A, Settings Phase
CBL-1085
Thermal Curve (Fixed) Size: 1 - 500 AWG/kcmil
INST (5-10 x Trip) 5 (2000A)
E N
B70-ATS-QA
480.0 V
100 100
B70-MSA-ATSQA CBL-1086
CUTLER-HAMMER Size: 1 - 500 AWG/kcmil
LSI, 70-400A Fixed Plug
TYPE: HKD, RMS 310 B70-QHBA1-MAIN
Sensor/Trip: 400A, Plug: 300 AT 400 AS,
Settings Phase B70-QHBA1
LTPU (1.0 x P) Fixed (300A) 480.0 V
LTD (Fixed) Fixed
STPU (2-8 x P) 8 (2400A) B70-QHBA1-ELEV1
STD (Inst-300 ms) 100 ms (I^2t In) 150 AS,
INST (4000A) Fixed (4000A) CBL-1091
Size: 1 - 1/0 AWG/kcmil
10 10
M-B70-ELEV-1
40.0 hp
TIME IN SECONDS
40.0 Hp
1 1
B70-MSA MAIN
CUTLER-HAMMER
LSI, 800-1600A Adj Plug
TYPE: RD, RMS 310 CBL-1091
Sensor/Trip: 1600A, Plug: 1600 AT Size: 1/0 AWG/kcmil
Settings Phase Qty/Ph: 1
Plug Adj (800-1600A) 1600A (1600A)
LTD (Fixed) Fixed
STPU (2-8 x LTPU) 3 (4800A) CBL-1085
STD (Inst-300 ms) 200 ms (I^2t In) Size: 500 AWG/kcmil
INST (17500A) Fixed (17500A) Qty/Ph: 1
0.10 0.10
B70-QHBA1-ELEV1
CUTLER-HAMMER
15-225A
TYPE: FD
Sensor/Trip: 150A, Settings Phase
Fixed
0.01 0.01
0.5 1 10
1K
100
10K
100K
100K
100
10K
1K
1 10
1000 1000
B70-MSA MAIN
1600 AS, 1600 AT
B70-MSA
480.0 V
B70-MSA-ATSLA
160 AS,
CBL-1079
Size: 1 - 1 AWG/kcmil
E N
100 100
B70-ATS-LA
480.0 V
CBL-1080
Size: 1 - 1 AWG/kcmil
B70-LHBA1-MAIN
100 AS,
B70-LHBA1
10 B70-MSA-ATSLA 480.0 V 10
CUTLER-HAMMER
LSI, 80-225AS FLAT
TYPE: FDE/FDCE/HFDE, 310+
Sensor/Trip: 160A, Settings Phase
B70-MSA MAIN
TIME IN SECONDS
Ir, 160A Sensor E (100) (100A)
LTD 24 CUTLER-HAMMER
STPU 12 (1200A) LSI, 800-1600A Adj Plug
STD M,N,O TYPE: RD, RMS 310
INST OR Fixed (1920A) Sensor/Trip: 1600A, Plug: 1600 AT
Settings Phase
Plug Adj (800-1600A) 1600A (1600A)
LTD (Fixed) Fixed
STPU (2-8 x LTPU) 3 (4800A)
1 1
STD (Inst-300 ms) 200 ms (I^2t In)
INST (17500A) Fixed (17500A)
0.10 0.10
B70-LHBA1-MAIN
CUTLER-HAMMER
15-225A
TYPE: FD CBL-1079
Sensor/Trip: 100A, Settings Phase Size: 1 AWG/kcmil
Fixed Qty/Ph: 1
0.01 0.01
0.5 1 10
1K
100
10K
100K
100K
100
10K
B70-MSA
1K
1 10
1000 480.0 V 1000
T-B70-BA019 B70-MSA-NHBA2
75 kVA 225 AS,
480 / 208 V
CBL-1103
Size: 1 - 4/0 AWG/kcmil
B70-NHBA2
480.0 V
B70-NHBA2-NLBA2
225 AS,
CBL-1104
Size: 1 - 2/0 AWG/kcmil
P
100 T-B70-BA019 100
S 75.0 kVA
CBL-1105
Size: 1 - 1 AWG/kcmil
B70-NLBA2-MAIN
225 AS,
B70-MSA-NHBA2
CUTLER-HAMMER B70-NLBA2
LSI, 80-225AS FLAT 208.0 V
TYPE: FDE/FDCE/HFDE, 310+
B70-NLAB2-NLBB1
Sensor/Trip: 225A, Settings Phase 100 AS,
Ir, 225A Sensor H (225) (225A)
LTD 24 CBL-1106
Size: 1 - 1 AWG/kcmil
STPU 8 (1800A)
10 10
STD M,N,O B70-NLBB1
INST OR Fixed (2700A) 208.0 V
TIME IN SECONDS
B70-NHBA2-NLBA2
CUTLER-HAMMER
15-225A
TYPE: FD
Sensor/Trip: 225A, Settings Phase
1
Fixed 1
CBL-1103
Size: 4/0 AWG/kcmil
Qty/Ph: 1
B70-NLBA2-MAIN
CUTLER-HAMMER CBL-1104
100-225A Size: 2/0 AWG/kcmil
TYPE: ED, EDB, EDS Qty/Ph: 1
Sensor/Trip: 225A, Settings Phase TX Inrush
Fixed
0.10 0.10
CBL-1105
Size: 1 AWG/kcmil
Qty/Ph: 1
B70-NLAB2-NLBB1
CUTLER-HAMMER
15-100A
TYPE: QBHW, 3-Pole
Sensor/Trip: 100A, Settings Phase
Fixed
0.01 0.01
0.5 1 10
1K
100
10K
100K
100
10K
1K
0.5 1 10
1000
CBL-0385
CBL-0485
B50U1-MSB-MAIN
B50U1-MSB
B50U1-10
CBL-0385
E N 100
ATS 4
TIME IN SECONDS
Device: B50U1-10
MCA,HMCA
700A
Settings recommended
LTPU 1.0 (700A)
LTD 17.0
STPU 8.0 (5600A)
STD-I2T 0.075 (I^2t Off) Name CBL-0385 1
Override 1.0 (9500A) Size 300 AWG/kcmil
Qty/Ph 3
Name CBL-0485
Size 500 AWG/kcmil
Qty/Ph 2
Device: B50U1-MCCP1-MN
MCA,HMCA
700A
Settings recommended
LTPU 1.0 (700A) 0.10
LTD 17.0
STPU 5.0 (3500A)
STD-I2T 0.075 (I^2t On)
Override 1.0 (9500A)
0.01
100K
B50-GEN
100
10K
1K
0.5 1 10
1000
CBL-0482 B50-GENBKR-2
CBL-0484 CBL-0445
CBL-0485
B50-EPD1
T-ATS-4
B50-ATS-4
CBL-0482
P
Device: B50-GENBKR-2 T-ATS-4
Powerpact P-Frame, 6.0A/P/H S
CBL-0483
1200A
Settings Phase ATS-4 EMER ENCL BKR
LTPU/LTD (A 0.4-1.0 x S) 1 (1200A); 4 100
E N
CBL-0485
Device: B50-ATS-4
B50U1-MCCP1-MN
HLD, RMS 310 10
600A/600A B50U1-MCCP1
Settings Phase
LTPU (1.0 x P) Fixed (600A)
LTD (Fixed) Fixed
STPU (2-8 x P) 3 (1800A)
TIME IN SECONDS
STD (Inst-300 ms) 200 ms (I^2t On)
INST (5500A) Fixed (5500A)
Name CBL-0485
Size 500 AWG/kcmil
Qty/Ph 2
TX Inrush
Device: B50U1-MCCP1-MN
0.10
MCA,HMCA
700A Name CBL-0484
Settings recommended Size 300 AWG/kcmil
LTPU 1.0 (700A) Qty/Ph 3
LTD 17.0
STPU 5.0 (3500A)
STD-I2T 0.075 (I^2t On)
Override 1.0 (9500A)
0.01
100
10K
1K
1 10
1000 1000
B51A2-MSG-MAIN B51A2-MSG-MAIN
WESTNHOUSE
2000 AS,
DIGTRP RMS
TYPE: DS B51A2-MSG
Sensor/Trip: 2000A, Settings Recommended
208.0 V
LTPU 1.0 (2000A)
LTD 4.0
B51A2-4
STPU 3.0 (6000A)
STD-I2T 0.3 (I^2t Out) 400 AS,
100
CBL-0317 100
Size: 1 - 500 AWG/kcmil
CBL-0332
Size: 1 - 1 AWG/kcmil
B51A2-3ALC-MN
125 AS,
B51A2-3ALC
208.0 V
10 10
B51A2-4
WESTINGHOUSE
TIME IN SECONDS
RMS310 LSI
TYPE: HKD/CHKD
Sensor/Trip: 400A, Settings Recommended
LTPU 1.0 (400A)
LTD LTD
STPU 8.0 (3200A)
STD 100
Override 1.0 (4000A)
1 1
CBL-0317
Size: 500 AWG/kcmil
Qty/Ph: 1
B51A2-3ALC-MN
WESTNHOUSE
100-400A
TYPE: KDB
Sensor/Trip: 125A, Settings Phase
LTD
INST 10.0 (1250A)
0.10 0.10
CBL-0332
Size: 1 AWG/kcmil
Qty/Ph: 1
0.01 0.01
100
10K
1K
0.5 1 10
100
10K
1K
1 10
1000 1000
B52-MSG-MN
1200 AS,
B52-MSG-MN B52-MSG
100 100
GE
150-2000A
480.0 V
TYPE: PWRBK 2 MVT+PM
Sensor/Trip: 2000A, Settings Ground B52-SWBD-MCC1
GF Pick Up 0.2 (400A) 600 AS,
GF Delay MAX (I^2t Out)
10 10
TIME IN SECONDS
B52-SWBD-MCC1
GE
150-2000A
TYPE: PWRBK 2 MVT+PM
1 Sensor/Trip: 800A, Settings Ground 1
GF Pick Up 0.2 (160A)
GF Delay INT (I^2t Out)
0.10 0.10
0.01 0.01
100
10K
1K
0.5 1 10
100
10K
1K
1 10
1000 1000
B69-MSB-MAIN
B69-MSB-MAIN 1200 AS,
LITTELFUSE
150-2000A B69-MSB
TYPE: LDC, 600V Class L 208.0 V
Sensor/Trip: 1200A,
B69-MSB-ATSLSNE
100 80 AS, 100
CBL-1068
Size: 1 - 6 AWG/kcmil
E N
B69-ATS-LSNE-B69
B69-LSNE MAIN
70 AS,
10 10
B69-LSNE MAIN
TIME IN SECONDS
CUTLER-HAMMER
15-100A
TYPE: QBHW, 3-Pole
Sensor/Trip: 70A, Settings Phase
Fixed
1 1
CBL-1068
Size: 6 AWG/kcmil
Qty/Ph: 1
B69-MSB-ATSLSNE
CUTLER-HAMMER
LSI, 80-225AS FLAT
TYPE: FDE/FDCE/HFDE, 310+
Sensor/Trip: 80A, Settings Phase
0.10
Ir, 80A Sensor G (70) (70A) 0.10
LTD 4
STPU 12 (840A)
STD J,K,L
INST OR Fixed (960A)
0.01 0.01
0.5 1 10
100
10K
1K
100K
100
10K
1K
0.5 1 10 R-B55-SGA-MAIN
1000
R-B55-SGA-MAIN - Phase
CBL-0689 B55-SGA-MAIN
R-B55-SGA-11 - Phase B55-SGA
CBL-0728
CBL-0729 B55-SGA-11
THIS PLOT ALSO REPRESENTS T-B71-MAIN
THE FEED FROM MAIN RELAY R-B55-SGA-11
R-55-SGB-MAIN AND FEEDER
RELAY R-B55-SGB-15 CBL-0689
B55-SGA-11-TAP
CBL-0728
100
SW-B71-T1
F-B71-T1
Device: R-B55-SGA-MAIN
FP-5000 P
T-B71-MAIN
CT Ratio 600 / 5 A
S
TIME IN SECONDS
Device: R-B55-SGA-11
Digitrip 3000
CT Ratio 400 / 5 A
Settings Phase
LDPU 1.5 (600A) Name CBL-0689
I2T 17.5 Size 1200 AWG/kcmil 1
SDPU 8.5 (3400A) Qty/Ph 1
SDT 0.25
INST 15 (6000A)
Name CBL-0728
Size 500 AWG/kcmil
Qty/Ph 1
Device: F-B71-T1
9F62 EJ0-1, 5.5kV Name CBL-0729
350A Size 3000 AWG/kcmil
Settings Phase Qty/Ph 1
350 Amps TX Inrush
0.10
Device: B71-DSWG-MAIN
Entelliguard G LVPCB, EGTU
3200A/3200A
Settings Phase
LTPU/LTD (0.5-1 x RP) 0.75X (2400A); C-5
STPU (1.5-12 x LTPU) 3X (7200A)
STD (ST01 - ST11) ST08-Max (I^2t Off)
INST(2-15 x RP) 6X (19200A)
0.01
100K
100
10K
1K
0.5 1 10
1000
CBL-0729
T-B71-MAIN SW-B71-T1 MAIN DISC
CBL-0739
SW-B71-T1
F-B71-T1
P
T-B71-MAIN
S
CBL-0729
B71-DSWG-MAIN
100
B71-DSWG
Device: F-B71-T1
9F62 EJ0-1, 5.5kV B71-DSWG-DPBH
350A
Settings Phase CBL-0739
350 Amps
71-DPBH-MAIN
71-DPBH
10
TIME IN SECONDS
Device: B71-DSWG-MAIN
Entelliguard G LVPCB, EGTU
3200A/3200A
Settings Phase
LTPU/LTD (0.5-1 x RP) 0.75X (2400A); C-5
STPU (1.5-12 x LTPU) 3X (7200A)
STD (ST01 - ST11) ST08-Max (I^2t Off)
INST(2-15 x RP) 6X (19200A) 1
Name CBL-0729
Size 3000 AWG/kcmil
Qty/Ph 1
Device: 71-DPBH-MAIN
SKLA, Spectra RMS Device: B71-DSWG-DPBH
1200A/1200A Entelliguard G LVPCB, EGTU
Settings Phase TX Inrush
1600A/1200A
MIN Settings Phase
0.10
Device: 71-DPBH-SERVELEV
SFLA, Spectra RMS
175A Name CBL-0739
Settings Phase Size 350 AWG/kcmil
MAX Qty/Ph 4
0.01
100
10K
1K
0.5 1 10
1000
B71-T-1
CBL-0740
CBL-0746
B71-DSWG-MAIN
B71-DSWG
B71-DSWG-T-1
CBL-0740
100
P
B71-T-1
S
CBL-0746
Name B71-T-1
Size 500.0 kVA 71-DSBL-MAIN
71-DSBL
10
TIME IN SECONDS
Device: B71-DSWG-MAIN
Entelliguard G LVPCB, EGTU
3200A/3200A
Settings Phase
LTPU/LTD (0.5-1 x RP) 0.75X (2400A); C-5
STPU (1.5-12 x LTPU) 3X (7200A)
STD (ST01 - ST11) ST08-Max (I^2t Off)
INST(2-15 x RP) 6X (19200A) 1
Device: B71-DSWG-T-1
Entelliguard G LVPCB, EGTU
Device: 71-DSBL-MAIN
800A/800A
MVT+PM STD
Settings Phase
2000A
LTPU/LTD (0.5-1 x RP) 0.95X (760A); C-5
Settings Phase
STPU (1.5-12 x LTPU) 2.5X (1900A)
LTPU 1; 1 (2000A)
STD (ST01 - ST11) ST06-Max (I^2t Off)
LTD 2
INST(2-15 x RP) 10X (8000A)
STPU 2.5 (5000A)
STD-I2T MIN (I^2t Off) TX Inrush
INST 8 (16000A) 0.10
Name CBL-0740
Size 500 AWG/kcmil
Qty/Ph 2
Name CBL-0746
Size 500 AWG/kcmil
Qty/Ph 5
0.01
100K
100
10K
1K
0.5 1 10
1000
CBL-0761
71-DSBL-MAIN
71-DSBL
71-DSBL-71-1LF
100
CBL-0761
71-1LF
71-1LF-BRANCH
10
TIME IN SECONDS
Device: 71-DSBL-MAIN
MVT+PM STD
2000A
Settings Phase
LTPU 1; 1 (2000A)
LTD 2
STPU 2.5 (5000A)
STD-I2T MIN (I^2t Off) 1
INST 8 (16000A)
THIS PLOT ALSO REPRESENTS
THE BRANCH CIRCUITS TO
PANELS 1LA, 1LB, 1LC, 1LD, 1LG,
1LH, AND 1LJ
Name CBL-0761
Device: 71-DSBL-71-1LF Size 500 AWG/kcmil
SGDA, Spectra RMS Qty/Ph 1
400A
0.10
Settings Phase
3
Device: 71-1LF-BRANCH
THHQB
30A
Settings Phase
Fixed
0.01
100K
100
10K
1K
0.5 1 10
1000
CBL-0765
71-DSBL-MAIN
71-DSBL
71-DSBL-71-1LL
100
CBL-0765
71-1LL
71-1LL-BRANCH
10
TIME IN SECONDS
Device: 71-DSBL-MAIN
MVT+PM STD
2000A
Settings Phase
LTPU 1; 1 (2000A)
LTD 2
STPU 2.5 (5000A) 1
Device: 71-DSBL-71-1LL
SFHA, Spectra RMS
225A
Settings Phase
MAX
0.10
Name CBL-0765
Device: 71-1LL-BRANCH Size 4/0 AWG/kcmil
THHQB Qty/Ph 1
50A
Settings Phase
Fixed
0.01
100
10K
1K
0.5 1 10
B71-DSWG-MAIN
1000
CBL-0745
B71-DSWG
CBL-0783
CBL-0789 B71-DSWG-ATS-EQ
T-4-71-EQBLA
CBL-0737
N E
ATS -EQ
ATS-EQ
CBL-0745
100
71-EQBHA
71-EQBHA-T-4
CBL-0783
P
T-4 -71 -E QBLA
S
CBL-0789
71-EQBLC-MAIN0
71-EQBLA
10
71-EQBLA-71-EQBLB
Name T-4-71-EQBLA
TIME IN SECONDS
Size 112.5 kVA Device: B71-DSWG-MAIN
Entelliguard G LVPCB, EGTU
3200A/3200A
Settings Phase
LTPU/LTD (0.5-1 x RP) 0.75X (2400A); C-5
STPU (1.5-12 x LTPU) 3X (7200A)
Device: 71-EQBHA-T-4 STD (ST01 - ST11) ST08-Max (I^2t Off)
SFLA, Spectra RMS INST(2-15 x RP) 6X (19200A) 1
175A
Settings Phase
MAX
Device: B71-DSWG-ATS-EQ
Entelliguard G LVPCB, EGTU
800A/600A
Settings Phase
LTPU/LTD (0.5-1 x RP) 1.00X (600A); C-7
STPU (1.5-12 x LTPU) 5X (3000A)
STD (ST01 - ST11) ST05-Max (I^2t Off)
Device: 71-EQBLC-MAIN0 INST(2-15 x RP) 10X (6000A)
SGDA, Spectra RMS
400A TX Inrush
0.10
Settings Phase
MAX Name CBL-0745
Size 350 AWG/kcmil
Qty/Ph 2
Name CBL-0789
Size 500 AWG/kcmil
Device: 71-EQBLA-71-EQBLB
Qty/Ph 1
THQD
225A
Settings Phase Name CBL-0783
Fixed Size 2/0 AWG/kcmil
Qty/Ph 1
0.01
100
10K
1K
0.5 1 10
1000
CBL-0785 B71-DSWG-ATS-EQ
CBL-0786 CBL-0737
CBL-0787
N E
T-5-71-EQBLC
ATS -EQ
ATS-EQ
CBL-0745
71-EQBHA
71-EQBHA-T-5
CBL-0785 100
71-EQBLC FU SW
CBL-0786
P
T-5-71 -EQB LC
S
CBL-0787
71-EQBLC-MAIN
71-EQBLC
10
71-EQBLC-71-EQBLD
TIME IN SECONDS
TO PANEL EQBHB
Entelliguard G LVPCB, EGTU
800A/600A
Settings Phase
LTPU/LTD (0.5-1 x RP) 1.00X (600A); C-7
STPU (1.5-12 x LTPU) 5X (3000A)
STD (ST01 - ST11) ST05-Max (I^2t Off)
Device: 71-EQBLC FU INST(2-15 x RP) 10X (6000A)
FRS-R, 600V Class RK5 1
150A
Device: 71-EQBHA-T-5
SELA, Spectra RMS
150A
Settings Phase
MAX
Device: 71-EQBLC-MAIN
SGHA, Spectra RMS
350A Name CBL-0787
Settings Phase Size 500 AWG/kcmil
MAX TX Inrush
Qty/Ph 1 0.10
Name CBL-0785
Device: 71-EQBLC-71-EQBLD Size 2/0 AWG/kcmil
SFHA, Spectra RMS Qty/Ph 1
225A
Settings Phase
MAX
Name CBL-0786
Size 2/0 AWG/kcmil
Qty/Ph 1
0.01
100K
100
10K
1K
0.5 1 10
1000
CBL-0738
B71-DSWG-MAIN
B71-DSWG
B71-DSWG-71-BHA
100
CBL-0738
71-BHA
71-BHA-BRANCH
10
Device: B71-DSWG-71-BHA
Entelliguard G LVPCB, EGTU
TIME IN SECONDS
400A/225A Device: B71-DSWG-MAIN
Settings Phase Entelliguard G LVPCB, EGTU
LTPU/LTD (0.5-1 x RP) 0.75X (168.75A); C-5 3200A/3200A
STPU (1.5-12 x LTPU) 9X (1518.75A) Settings Phase
STD (ST01 - ST11) ST05-Max (I^2t Off) LTPU/LTD (0.5-1 x RP) 0.75X (2400A); C-5
INST(2-15 x RP) 15X (3375A) STPU (1.5-12 x LTPU) 3X (7200A)
STD (ST01 - ST11) ST08-Max (I^2t Off)
INST(2-15 x RP) 6X (19200A) 1
0.10
Device: 71-BHA-BRANCH
Name CBL-0738
FB, 2 & 3-Pole 480V
Size 4/0 AWG/kcmil
20A
Qty/Ph 1
Settings Phase
Fixed
0.01
100K
100
10K
1K
0.5 1 10
1000
CBL-0733
B71-DSWG-MAIN
B71-DSWG
B71-DSWG-71-1HC
100
CBL-0733
71-1HC
71-1HC-BRANCH
10
Device: B71-DSWG-71-1HC
Entelliguard G LVPCB, EGTU
400A/225A
TIME IN SECONDS
Settings Phase Device: B71-DSWG-MAIN
LTPU/LTD (0.5-1 x RP) 0.75X (168.75A); C-7 Entelliguard G LVPCB, EGTU
STPU (1.5-12 x LTPU) 8X (1350A) 3200A/3200A
STD (ST01 - ST11) ST04-Max (I^2t Off) Settings Phase
INST(2-15 x RP) 15X (3375A) LTPU/LTD (0.5-1 x RP) 0.75X (2400A); C-5
STPU (1.5-12 x LTPU) 3X (7200A)
STD (ST01 - ST11) ST08-Max (I^2t Off)
INST(2-15 x RP) 6X (19200A) 1
0.10
Device: 71-1HC-BRANCH
THED
20A
Settings Phase
Fixed
Name CBL-0733
Size 4/0 AWG/kcmil
Qty/Ph 1
0.01
100K
100
10K
1K
0.5 1 10
1000
CBL-0742
CBL-0734
B71-DSWG-MAIN
B71-DSWG
B71-DSWG-ATS-ELEV
CBL-0734
N E
100
ATS- ELEV
ATS-ELEV
CBL-0742
71-EVBHA
71-EVBHA-BRANCH
10
TIME IN SECONDS
Device: B71-DSWG-MAIN
Entelliguard G LVPCB, EGTU
3200A/3200A
Settings Phase
LTPU/LTD (0.5-1 x RP) 0.75X (2400A); C-5
STPU (1.5-12 x LTPU) 3X (7200A)
STD (ST01 - ST11) ST08-Max (I^2t Off) 1
Device: B71-DSWG-ATS-ELEV
Entelliguard G LVPCB, EGTU
400A/225A
Settings Phase
LTPU/LTD (0.5-1 x RP) 1.00X (225A); Max C
STPU (1.5-12 x LTPU) 12X (2700A)
STD (ST01 - ST11) ST05-Max (I^2t Off) Name CBL-0734
INST(2-15 x RP) 15X (3375A) Size 4/0 AWG/kcmil
0.10
Qty/Ph 1
Device: 71-EVBHA-BRANCH
THED Name CBL-0742
150A Size 4/0 AWG/kcmil
Settings Phase Qty/Ph 1
Fixed
0.01
100K
100
10K
1K
0.5 1 10
1000
CBL-0743
CBL-0780 B71-DSWG-MAIN
B71-DSWG
B71-DSWG-ATS-LS
CBL-0735
N E
ATS- LS
ATS-LS 100
CBL-0743
71-LSBHA
71-LSBHA-71-LS1HA
CBL-0780
71-LS1HA
71-LS1HA-BRANCH
10
Device: B71-DSWG-ATS-LS
Entelliguard G LVPCB, EGTU
400A/225A
Settings Phase
TIME IN SECONDS
LTPU/LTD (0.5-1 x RP) 1.00X (225A); C-14
Device: B71-DSWG-MAIN
STPU (1.5-12 x LTPU) 12X (2700A)
Entelliguard G LVPCB, EGTU
STD (ST01 - ST11) ST05-Max (I^2t Off)
3200A/3200A
INST(2-15 x RP) 15X (3375A)
Settings Phase
LTPU/LTD (0.5-1 x RP) 0.75X (2400A); C-5
STPU (1.5-12 x LTPU) 3X (7200A)
STD (ST01 - ST11) ST08-Max (I^2t Off)
1
INST(2-15 x RP) 6X (19200A)
Device: 71-LSBHA-71-LS1HA
SFHA, Spectra RMS
225A
Settings Phase
3 Name CBL-0743
0.10
Size 4/0 AWG/kcmil
Qty/Ph 1
Device: 71-LS1HA-BRANCH
TEY Name CBL-0780
20A Size 4/0 AWG/kcmil
Settings Phase Qty/Ph 1
Fixed
0.01
100K
100
10K
1K
0.5 1 10
B71-DSWG 1000
CBL-0735
CBL-0798 B71-DSWG-ATS-LS
CBL-0781 CBL-0735
T-2-71-LSBLA
N E
ATS- LS
ATS-LS
CBL-0743
71-LSBHA 100
71-LSBHA-T-2-LSBLA
CBL-0781
P
T-2-71-LSBLA
S
CBL-0798
71-LSBLA-MAIN
71-LSBLA
71-LSBLA-71-LS1LA10
Name T-2-71-LSBLA
Size 75.0 kVA
TIME IN SECONDS
Device: B71-DSWG-ATS-LS
Entelliguard G LVPCB, EGTU
400A/225A
Settings Phase
LTPU/LTD (0.5-1 x RP) 1.00X (225A); C-14
STPU (1.5-12 x LTPU) 12X (2700A)
STD (ST01 - ST11) ST05-Max (I^2t Off)
1
INST(2-15 x RP) 15X (3375A)
Device: 71-LSBHA-T-2-LSBLA
THED
125A
Settings Phase
Fixed
Device: 71-LSBLA-MAIN
SGHA, Spectra RMS
300A TX Inrush Name CBL-0735
0.10
Settings Phase Size 4/0 AWG/kcmil
MAX Qty/Ph 1
Name CBL-0798
Device: 71-LSBLA-71-LS1LA
Size 350 AWG/kcmil
THQD
Qty/Ph 1
150A
Settings Phase
Fixed
Name CBL-0781
Size 1 AWG/kcmil
Qty/Ph 1
0.01
100K
100
10K
1K
0.5 1 10
B71-DSWG-MAIN
1000
CBL-0736
B71-DSWG
CBL-0784
CBL-0791 B71-DSWG-ATS-CC
T-3-CCBLA CBL-0736
N E
ATS- CC
ATS-CC
CBL-0744
100
71-CCBHA
71-CCBHA-T-3
CBL-0784
P
T-3 -CCB LA
S
CBL-0791
71CCBLA-MAIN
71-CCBLA
Name T-3-CCBLA 10
Size 112.5 kVA 71-CCBLA-71-CC1LA
TIME IN SECONDS
Device: B71-DSWG-MAIN
Device: B71-DSWG-ATS-CC Entelliguard G LVPCB, EGTU
Entelliguard G LVPCB, EGTU 3200A/3200A
400A/225A Settings Phase
Settings Phase LTPU/LTD (0.5-1 x RP) 0.75X (2400A); C-5
LTPU/LTD (0.5-1 x RP) 1.00X (225A); C-15 STPU (1.5-12 x LTPU) 3X (7200A)
STD (ST01 - ST11) ST08-Max (I^2t Off) 1
STPU (1.5-12 x LTPU) 12X (2700A)
STD (ST01 - ST11) ST05-Max (I^2t Off) INST(2-15 x RP) 6X (19200A)
INST(2-15 x RP) 15X (3375A)
Device: 71-CCBHA-T-3
SFHA, Spectra RMS Name CBL-0791
175A Size 500 AWG/kcmil
Settings Phase Qty/Ph 1
MAX
TX Inrush
Device: 71CCBLA-MAIN Name CBL-0736 0.10
Name CBL-0784
Device: 71-CCBLA-71-CC1LA Size 2/0 AWG/kcmil
THQD Qty/Ph 1
225A
Settings Phase
Fixed
0.01
100K
100
10K
1K
0.5 1 10
1000
Device: B71-DSWG-MAIN
WavePro, EGTU
3200A/3200A
Settings Ground B71-DSWG-MAIN
GFPU (0.2 - 0.37 x In) 0.32 (1024A)
GFD I2T (1-13 Bands) GFD06 (I^2t Off) B71-DSWG
B71-DSWG-DPBH
100
B71-DSWG-T-1
Device: B71-DSWG-DPBH
Entelliguard G CB
1600A/1200A B71-DSWG-ATS-EQ
Settings Ground
GFPU (0.2 - 0.6 x In) 0.3 (480A)
GFD I2T (1-14 Bands) GFD03 (I^2t Off) B71-DSWG-ATS-CC
Device: B71-DSWG-T-1
Entelliguard G CB 10
800A/800A
Settings Ground
GFPU (0.2 - 0.6 x In) 0.35 (280A)
GFD I2T (1-14 Bands) GFD03 (I^2t Off)
TIME IN SECONDS
Device: B71-DSWG-ATS-EQ
Entelliguard G CB
800A/600A
Settings Ground
GFPU (0.2 - 0.6 x In) 0.4 (320A) 1
Device: B71-DSWG-ATS-CC
Entelliguard G CB
400A/225A
Settings Ground
GFPU (0.2 - 0.6 x In) 0.2 (80A)
GFD I2T (1-14 Bands) GFD03 (I^2t Off)
0.10
0.01
100
10K
1K
0.5 1 10
GEN--1 1000
GEN--1
CBL-0806 GEN BKR
CBL-0750
MTS
CBL-0745
71-MTS
CBL-0806
71-EBHA-MAIN
71-EBHA
71-EBHA-ATS-EQ 100
CBL-0750
N E
ATS -EQ
Gen SC
ATS-EQ
CBL-0745
71-EQBHA
Name GEN--1
Size 750.000 kW 71-EQBHA-T-4 10
TIME IN SECONDS
Device: GEN BKR
Powerpact P-Frame, 3.0 & 3.0A
1200A
Settings Phase
LTPU (A);LTD 1 (1200A); 8
INST (PG 250-1200) 4 (4800A)
Device: 71-EBHA-MAIN
1
SKLA, Spectra RMS
1200A/1200A
Settings Phase
3
Name CBL-0806
Size 350 AWG/kcmil
Qty/Ph 4
Name CBL-0745
Size 350 AWG/kcmil
Qty/Ph 2
Device: 71-EQBHA-T-4
SFLA, Spectra RMS
175A
Settings Phase
MAX
0.01
100
10K
1K
0.5 1 10
1000
CBL-0747 GEN BKR
CBL-0742 MTS
71-MTS
CBL-0806
71-EBHA-MAIN
71-EBHA
71-EBHA-ATS-ELEV
100
CBL-0747
N E
ATS- ELEV
ATS-ELEV
CBL-0742
71-EVBHA
71-EVBHA-BRANCH
10
TIME IN SECONDS
Device: 71-EBHA-MAIN Device: GEN BKR
SKLA, Spectra RMS Powerpact P-Frame, 3.0 & 3.0A
1200A/1200A 1200A
Settings Phase Settings Phase
3 LTPU (A);LTD 1 (1200A); 8
INST (PG 250-1200) 4 (4800A)
1
Device: 71-EBHA-ATS-ELEV
SFLA, Spectra RMS
225A
Settings Phase
MAX
Device: 71-EVBHA-BRANCH
THED Name CBL-0747
150A Size 4/0 AWG/kcmil 0.10
Settings Phase Qty/Ph 1
Fixed
Name CBL-0742
Size 4/0 AWG/kcmil
Qty/Ph 1
0.01
100
10K
1K
0.5 1 10
1000
CBL-0748 GEN BKR
CBL-0743 MTS
71-MTS
CBL-0806
71-EBHA-MAIN
71-EBHA
71-EBHA-ATS-LS
100
CBL-0748
N E
ATS- LS
ATS-LS
CBL-0743
71-LSBHA
71-LSBHA-71-LS1HA
10
TIME IN SECONDS
1200A
Settings Phase
LTPU (A);LTD 1 (1200A); 8
INST (PG 250-1200) 4 (4800A)
1
Device: 71-EBHA-MAIN
SKLA, Spectra RMS
1200A/1200A
Settings Phase
3
Device: 71-EBHA-ATS-LS
SFLA, Spectra RMS
225A
Settings Phase 0.10
MAX
Name CBL-0748
Size 4/0 AWG/kcmil
Qty/Ph 1
Device: 71-LSBHA-71-LS1HA
SFHA, Spectra RMS Name CBL-0743
225A Size 4/0 AWG/kcmil
Settings Phase Qty/Ph 1
3
0.01
100
10K
1K
0.5 1 10
1000
CBL-0806 GEN BKR
CBL-0749
CBL-0744 MTS
71-MTS
CBL-0806
71-EBHA-MAIN
71-EBHA
71-EBHA-ATS-CC
100
CBL-0749
N E
ATS- CC
ATS-CC
CBL-0744
71-CCBHA
71-CCBHA-T-3
10
TIME IN SECONDS
Settings Phase
LTPU (A);LTD 1 (1200A); 8
INST (PG 250-1200) 4 (4800A)
Device: 71-EBHA-MAIN
1
SKLA, Spectra RMS
1200A/1200A
Settings Phase
3
Name CBL-0806
Size 350 AWG/kcmil
Qty/Ph 4
Device: 71-EBHA-ATS-CC
SFLA, Spectra RMS Name CBL-0749
225A Size 4/0 AWG/kcmil
Settings Phase Qty/Ph 1
MAX 0.10
Name CBL-0744
Size 4/0 AWG/kcmil
Qty/Ph 1
Device: 71-CCBHA-T-3
SFHA, Spectra RMS
175A
Settings Phase
MAX
0.01
Thermal Magnetic KD 400A INST (5-10 x Trip) 5.63 (2252A) Page 3-12
Thermal Magnetic LD 600A INST (5-10 x Trip) 7.5 (4500A) Page 3-17
Thermal Magnetic LD 600A INST (5-10 x Trip) 7.5 (4500A) Page 3-17
Static Trip CHND, RMS 310 1200A LTPU (1.0 x P) Fixed (1200A) Page 3-14
Ground
Disabled
Static Trip CHND, RMS 310 1200A LTPU (1.0 x P) Fixed (1200A) Page 3-14
Ground
Disabled
Static Trip CRD, RMS 310 1600A LTPU (1.0 x P) Fixed (1600A) Page 3-14
Ground
Disabled
MAIN CHND, RMS 310 1200A LTPU (1.0 x P) Fixed (1200A) Page 3-12
Ground
Disabled
ATSA1 CHKD, RMS 310 400A LTD (Fixed) Fixed Page 3-12
ATSB1 CHKD, RMS 310 400A LTD (Fixed) Fixed Page 3-12
UPSA CHLD, RMS 310 600A LTD (Fixed) Fixed Page 3-13
Static Trip LS, 300-600A Adj Plug STPU (2-8 x LTPU) 8 (4800A)
UPSB-AB CHLD, RMS 310 600A LTD (Fixed) Fixed Page 3-13
Static Trip LS, 300-600A Adj Plug STPU (2-8 x LTPU) 8 (4800A)
UPSB-MB CHLD, RMS 310 600A LTD (Fixed) Fixed Page 3-13
Static Trip LS, 300-600A Adj Plug STPU (2-8 x LTPU) 8 (4800A)
ATSA1 CHKD, RMS 310 400A LTD (Fixed) Fixed Page 3-12
ATSB CHKD, RMS 310 400A LTD (Fixed) Fixed Page 3-12
MAIN CHND, RMS 310 1200A LTPU (1.0 x P) Fixed (1200A) Page 3-13
Ground
Disabled
UPSA-AB CHLD, RMS 310 600A LTD (Fixed) Fixed Page 3-13
Static Trip LS, 300-600A Adj Plug STPU (2-8 x LTPU) 8 (4800A)
UPSA1-MB CHLD, RMS 310 600A LTD (Fixed) Fixed Page 3-13
Static Trip LS, 300-600A Adj Plug STPU (2-8 x LTPU) 8 (4800A)
UPSB CHLD, RMS 310 600A LTD (Fixed) Fixed Page 3-13
Static Trip LS, 300-600A Adj Plug STPU (2-8 x LTPU) 8 (4800A)
Static Trip Magnum DS, RMS 520 1600A LTPU (0.4-1.0 x P) 0.8 (1280A) Page 3-16
Static Trip Magnum DS, RMS 520 1600A LTPU (0.4-1.0 x P) 0.8 (1280A) Page 3-16
B32-MDS-BRANCH CUTLER-HAMMER 1600A LTPU (0.4-1.0 x P) 0.8 (1280A) B32 MDS MAIN_ESWBD-A MAIN
Static Trip Magnum DS, RMS 520 1600A LTD (2-24 Sec.) 15 Page 3-16
Static Trip Magnum DS, RMS 520 1600A LTPU (0.4-1.0 x P) 1 (1600A) Page 3-16
INST Off
INST 10 (6000A)
INST 10 (6000A)
Thermal Magnetic HJD 250A INST (5-10 x Trip) 5 (1250A) Page 3-20
Thermal Magnetic HMDL 800A INST (4-8 x Trip) 4 (3200A) Page 3-20
Thermal Magnetic DK 250A INST (5-10 x Trip) 6.88 (1720A) Page 3-22
STD 100
STD 100
STD 300
STD 100
STD 200
STD 300
B50-EPD1-LB CUTLER-HAMMER 400A LTPU (1.0 x P) Fixed (400A) B50 EPD1 EMG
Static Trip HKD, RMS 310 400A LTD (Fixed) Fixed Page 3-24
B50-EPD1-MAIN CUTLER-HAMMER 600A LTPU (1.0 x P) Fixed (600A) B50 EPD1 EMG
Static Trip HLD, RMS 310 600A LTD (Fixed) Fixed Page 3-24
Static Trip Powerpact P-Frame, 6.0A/P/H 1200A LTPU (A 0.4-1.0 x S) 1 (1200A) Page 3-63
Ground
Disabled
Static Trip Powerpact P-Frame, 6.0A/P/H 1200A LTPU (A 0.4-1.0 x S) 1 (1200A) Page 3-24
Ground
Disabled
STD 100
Ground B50U1_GND_COORD
Ground B50U1_GND_COORD
Ground B50U1_GND_COORD
STD 300
Ground B50U1_GND_COORD
STD 100
Ground B50U1_GND_COORD
STD 100
Ground B50U1_GND_COORD
STD 100
Ground B50U1_GND_COORD
STD 100
Ground B50U1_GND_COORD
STD 300
Ground B50U1_GND_COORD
STD 100
Ground B50U1_GND_COORD
Ground B50U1_GND_COORD
Ground B50U1_GND_COORD
STD 300
Ground B50U1_GND_COORD
STD 300
Ground B50U1_GND_COORD
Ground B50U1_GND_COORD
STD 100
Ground B50U1_GND_COORD
STD 300
Ground B50U1_GND_COORD
Thermal Magnetic KD 150A INST (5-10 x Trip) 8.75 (1312.5A) Page 3-25
Ground B50U1_GND-COORD
STD 100
Ground B51A1_GND_COORD
STD 100
Ground B51A1_GND_COORD
STD 100
Ground B51A1_GND_COORD
STD 200
Ground B51A1_GND_COORD
STD 200
Ground B51A1_GND_COORD
STD 200
Ground B51A1_GND_COORD
STD 200
Ground B51A1_GND_COORD
STD 200
Ground B51A1_GND_COORD
STD 200
Ground B51A1_GND_COORD
Thermal Magnetic
Thermal Magnetic
Thermal Magnetic
INST Off
Ground B51A1_GND_COORD
STD 100
Ground B51A2_GND_COORD
STD 100
Ground B51A2_GND_COORD
STD 100
Ground B51A2_GND_COORD
STD 100
Ground B51A2_GND_COORD
STD 100
Ground B51A2_GND_COORD
STD 100
Ground B51A2_GND_COORD
STD 100
Ground B51A2_GND_COORD
STD 100
Ground B51A2_GND_COORD
STD 100
Ground B51A2_GND_COORD
STD 100
Ground B51A2_GND_COORD
INST Off
Ground B51A2_GND_COORD
STD 100
Ground B51A3_GND_COORD
STD 100
Ground B51A3_GND_COORD
Ground B51A3_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Override (5500A)
Ground B51B1_GND_COORD
GTD .150
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
INST Off
Ground B51B1_GND_COORD
Thermal Magnetic
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
STD 100
Ground B51B1_GND_COORD
INST Off
Ground B51B1_GND_COORD
Thermal Magnetic TJJ 150A INST (3-10 x Trip) HI (1500A) Page 3-85
Thermal Magnetic TJJ 150A INST (3-10 x Trip) 9 (1350A) Page 3-85
INST Off
Ground
Disabled
LTD 2
INST Off
Ground B52_GND_COORD
LTD 2
Ground B52_GND_COORD
LTD 4
Ground B52_GND_COORD
LTD 4
Ground B52_GND_COORD
LTD 2
Ground B52_GND_COORD
LTD 1
Ground B52_GND_COORD
Thermal Magnetic TFJ 225A INST (4.5-10 x Trip) 7 (1575A) Page 3-88
Thermal Magnetic TLB4 250A INST (4.5-10 x Trip) HI (2500A) Page 3-88
STPU, Im 3 (1200A)
STD Fixed
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor G (150) (150A) Page 3-95
STPU 12 (1800A)
STD M,N,O
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor G (150) (150A) Page 3-95
STPU 12 (1800A)
STD M,N,O
GFPU 0.2
GFD K,N,Q
Static Trip KD, RMS 310 400A Plug Adj (200-400A) 400A Page 3-91
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor G (150) (150A) Page 3-95
STPU 12 (1800A)
STD M,N,O
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor G (150) (150A) Page 3-95
STPU 12 (1800A)
STD M,N,O
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor G (150) (150A) Page 3-95
STPU 12 (1800A)
STD M,N,O
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor G (150) (150A) Page 3-95
STPU 12 (1800A)
STD M,N,O
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor G (150) (150A) Page 3-95
STPU 12 (1800A)
STD M,N,O
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor A (60) (60A) Page 3-92
STPU 4 (240A)
STD P,Q,R
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor F (125) (125A) Page 3-89
STPU 7 (875A)
STD M,N,O
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 80A Ir, 80A Sensor D (40) (40A) Page 3-93
STPU 4 (160A)
STD P,Q,R
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor E (100) (100A) Page 3-90
STPU 5 (500A)
STD M,N,O
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor G (150) (150A) Page 3-95
STPU 12 (1800A)
STD M,N,O
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 80A Ir, 80A Sensor E (70) (70A) Page 3-106
STPU 12 (600A)
STD J,K,L
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 225A Ir, 225A Sensor F (175) (175A) Page 3-94
STPU 6 (1050A)
STD M,N,O
GFPU 0.2
Static Trip FDE/FDCE/HFDE, 310+ 225A Ir, 225A Sensor F (175) (175A) Page 3-94
STPU 6 (1050A)
STD M,N,O
GFPU 0.2
GFD K,N,Q
Static Trip FDE/FDCE/HFDE, 310+ 225A Ir, 225A Sensor F (175) (175A) Page 3-94
STPU 6 (1050A)
STD M,N,O
GFPU 0.2
GFD K,N,Q
Static Trip RD, RMS 310 1600A Plug Adj (800-1600A) 1600A Page 3-100
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor E (100) (100A) Page 3-101
STPU 12 (1200A)
STD M,N,O
GFD K,N,Q
Static Trip HKD, RMS 310 300A LTPU (1.0 x P) Fixed (300A) Page 3-100
Static Trip FDE/FDCE/HFDE, 310+ 225A Ir, 225A Sensor H (225) (225A) Page 3-102
STPU 8 (1800A)
STD M,N,O
Static Trip FDE/FDCE/HFDE, 310+ 225A Ir, 225A Sensor H (225) (225A) Page 3-102
STPU 8 (1800A)
STD M,N,O
Static Trip FDE/FDCE/HFDE, 310+ 225A Ir, 225A Sensor H (225) (225A) Page 3-102
STPU 8 (1800A)
STD M,N,O
Static Trip FDE/FDCE/HFDE, 310+ 225A Ir, 225A Sensor H (225) (225A) Page 3-102
STPU 8 (1800A)
STD M,N,O
Static Trip FDE/FDCE/HFDE, 310+ 225A Ir, 225A Sensor H (225) (225A) Page 3-102
STPU 8 (1800A)
STD M,N,O
Static Trip HKD, RMS 310 300A LTPU (1.0 x P) Fixed (300A) Page 3-100
Static Trip FDE/FDCE/HFDE, 310+ 225A Ir, 225A Sensor H (225) (225A) Page 3-102
STPU 8 (1800A)
STD M,N,O
Static Trip FDE/FDCE/HFDE, 310+ 160A Ir, 160A Sensor E (100) (100A) Page 3-97
STPU 12 (1200A)
STD M,N,O
Ground
Disabled
Static Trip KD, RMS 310 400A Plug Adj (200-400A) 350A Page 3-96
Ground
Disabled
70-250A
300-1200A 1200A
70-250A
125-400A
125-400A
125-400A
125-400A
125-400A
125-400A
125-400A
125-400A
70-250A
70-250A
70-250A
70-250A
70-250A
70-250A
100-2000A LTD 2
INST 8 (16000A)
Ground
70-250A
70-250A
125-600A
70-250A
300-1200A 1200A
15-150A
70-250A
15-150A
70-250A
125-600A
125-400A
70-250A
125-600A
125-400A
Static Trip Entelliguard G LVPCB, EGTU 400A LTPU/LTD (0.5-1 x RP) 0.75X (168.75A); C-7
Ground
Static Trip Entelliguard G LVPCB, EGTU 400A LTPU/LTD (0.5-1 x RP) 0.75X (168.75A); C-5
Ground
Static Trip Entelliguard G LVPCB, EGTU 400A LTPU/LTD (0.5-1 x RP) 0.75X (168.75A); C-7
Ground
Static Trip Entelliguard G LVPCB, EGTU 400A LTPU/LTD (0.5-1 x RP) 0.75X (168.75A); C-5
Ground
Static Trip Entelliguard G LVPCB, EGTU 400A LTPU/LTD (0.5-1 x RP) 1.00X (225A); C-15
LSI (CB), 800-5000AF, ANSI/UL1066 225A STPU (1.5-12 x LTPU) 12X (2700A)
Ground
Static Trip Entelliguard G LVPCB, EGTU 400A LTPU/LTD (0.5-1 x RP) 1.00X (225A); Max C
LSI (CB), 800-5000AF, ANSI/UL1066 225A STPU (1.5-12 x LTPU) 12X (2700A)
Ground
Static Trip Entelliguard G LVPCB, EGTU 800A LTPU/LTD (0.5-1 x RP) 1.00X (600A); C-7
Ground
Static Trip Entelliguard G LVPCB, EGTU 400A LTPU/LTD (0.5-1 x RP) 1.00X (225A); C-14
LSI (CB), 800-5000AF, ANSI/UL1066 225A STPU (1.5-12 x LTPU) 12X (2700A)
Ground
Static Trip Entelliguard G LVPCB, EGTU 1600A LTPU/LTD (0.5-1 x RP) 0.75X (900A); C-8
Ground
Static Trip Entelliguard G LVPCB, EGTU 3200A LTPU/LTD (0.5-1 x RP) 0.75X (2400A); C-5
Ground
Static Trip Entelliguard G LVPCB, EGTU 800A LTPU/LTD (0.5-1 x RP) 0.95X (760A); C-5
LSI (CB), 800-5000AF, ANSI/UL1066 800A STPU (1.5-12 x LTPU) 2.5X (1900A)
Ground
Static Trip Powerpact P-Frame, 3.0 & 3.0A 1200A INST (PG 250-1200) 4 (4800A)
LI, 250-1200A, UL
VAMC Heinz Recommended Low-Voltage Breaker Settings for the Revision 3 Equipment
Frame
/Sensor
Breaker Name / Type Description /Plug Settings: TCC Names
ATS-4 EMER ENCL BKR CUTLER-HAMMER 800A Phase B50U1 ATS-4_EMG
Static Trip HMDL, RMS 310 (06/07) 800A LTPU (1.0 x P) FIXED (800A) Page 3-103A
LSI, 400-800A Fixed Plug 800A LTD (Fixed) FIXED
STPU (2-8 x P) 4 (3200A)
STD (Inst-300 ms) Inst (I^2t On)
INST (6800A) FIXED (6800A)
Ground
GFPU (1 x Ig) 1 x Ig (160A)
GFD (Inst-500 ms) 150 ms (I^2t Off)
Frame
/Sensor
Breaker Name / Type Description /Plug Settings: TCC Names
B50-ATS-6A CUTLER-HAMMER 400A LTPU (1.0 x P) Fixed (400A) B51A1 MCC-GB3_EMG
Static Trip HKD, RMS 310 400A LTD (Fixed) Fixed Page 3-48A
LSI, 70-400A Fixed Plug 400A STPU (2-8 x P) 5 (2000A)
STD (Inst-300 ms) Inst (I^2t Off)
INST (4000A) Fixed (4000A)
5.1 General
NFPA 70E-2015, Article 110.1(G) requires that an employer developed electrical safety
program includes a risk assessment procedure that addresses worker exposure to electrical
hazards. This procedure is meant to be used before performing work on or near any
equipment at or above 50 volts or any time work is being performed where an electrical
hazard exists. This analysis presents only the results of an incident energy evaluation
conducted in accordance with 130.5(C)(1). Selection of personal protective equipment
(PPE) should be made based on the incident energy level at the working distance which is
presented in this report as part of an arc flash risk assessment to be made by the qualified
person. Other components of an arc flash risk assessment including determination of
whether or not an arc flash hazard exists for a given work task and the appropriate safe
work practices to be employed should be completed by the qualified person performing the
work. The risk of arc flash exposure when working on or near electrical equipment depends
on a number of factors including the nature of the task being performed and the condition of
the equipment. NFPA 70E-2015, Article 130.7(A) requires that employees use and
employers provide proper PPE for the tasks being performed. NFPA 70E, Table H.3(b)
provides guidance for the selection of PPE based on calculated incident energy exposure.
NFPA 70E and IEEE Std 1584 provide equations and methods to calculate the arc flash
boundary and incident energy at specific locations within a facility’s electrical system. Any
location where work may be performed on or near energized electrical conductors and
circuit parts is subject to the arc flash standards. PPE used to guard against arc flash
hazards should be considered the last line of defense. It is also important to note that the
use of PPE is not intended to prevent all injuries from an arc flash. The goal of determining
required PPE using the arc flash incident energy analysis is to identify the level of protection
required to limit the injury to the onset of a second degree burn in the event of an arc flash
while avoiding the use of more protection than is needed so as to minimize hazards of heat
stress, reduced visibility and limited body movement.
5.2 Objectives
The intent of NFPA 70E and IEEE Std 1584 guidelines is to establish standard calculations
to determine an approach boundary that will prevent the onset of a second-degree burn to
the face and the torso of the worker. An incident energy of 1.2 cal/cm2 represents the onset
of a second-degree burn.
NFPA 70E, Article 130.7(A), Informational Note 3, states that it may be necessary to place
greater emphasis on establishing an electrically safe work condition when working within the
limited approach boundary at locations where the incident energy exceeds 40 cal/cm2.
Locations with a calculated incident energy that exceeds 40 cal/cm2 are shown in Table 5.2.
The arc flash incident energy analysis considers each medium and low voltage system
location within the scope of the work. IEEE Std 1584 states that equipment below 240 V
need not be considered unless it involves at least one 125 kVA or larger low-impedance
transformer in its immediate power supply. Therefore, no detailed calculations will be
performed for 120/208 V locations supplied by a transformer smaller than 125 kVA, however
labels will be provided for these locations. These locations within the Building 71 system
can be seen in Table 5.3.
Before the arc flash equations can be applied, a detailed short-circuit and protective device
coordination study must be completed to include all locations where work may be performed
on or near energized components; e.g. motor control centers and power distribution panels.
Since the short-circuit current must be calculated at every pertinent location and the clearing
time of each location’s upstream protective device is required, the arc flash circuit model is
more detailed and extends deeper into the facility electrical distribution system than is
typical of a basic short-circuit and protective device coordination study. Accurate fault
currents and device clearing times are extremely important in deriving reliable results. A
“Load Side”
Note: Based on IEEE Std 1584, equipment below 240 V need not be considered in
arc flash calculations unless it involves at least one 125 kVA or larger low-impedance
transformer in its immediate power supply.
CBL-0483 T-ATS 4 SEC ATS-4 EMER ENC 3 208 5.0 FEET 300 Copper
Duct Material: Magnetic
+/- Impedance: 0.0464 + J 0.0493 Ohms/1000 ft 0.1787 + J 0.1899 PU
Z0 Impedance: 0.1462 + J 0.1214 Ohms/1000 ft 0.5632 + J 0.4677 PU
CBL-0484 ATS-4 EMER ENC ATS 4 EMER 3 208 5.0 FEET 300 Copper
Duct Material: Magnetic
+/- Impedance: 0.0464 + J 0.0493 Ohms/1000 ft 0.1787 + J 0.1899 PU
Z0 Impedance: 0.1462 + J 0.1214 Ohms/1000 ft 0.5632 + J 0.4677 PU
=============================================================================================
TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-LOAD NOMINAL
NAME NO NAME L-L NO NAME L-L KVA KVA
=============================================================================================
69-XFMR BUS-0086 D 480.00 BUS-0085 Y 208.00 45.00 45.00
Pos. Seq. Z%: 1.52 + J 4.41 (Zpu 33.83 + j 98.11 ) Shell Type
Zero Seq. Z%: 9999. + J 9999. (Pri Open, Sec Open)
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leads Sec.): 30.00 Deg.
=============================================================================================
TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-LOAD NOMINAL
NAME NO NAME L-L NO NAME L-L KVA KVA
=============================================================================================
T-5-71-EQBLC BUS-0716 D 480.00 BUS-0718 YG 208.00 112.50 112.50
Pos. Seq. Z%: 1.10 + J 3.74 (Zpu 9.80 + j 33.25 ) Shell Type
Zero Seq. Z%: 1.10 + J 3.74 (Sec 9.80 + j 33.25 Pri Open)
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leads Sec.): 30.00 Deg.
=============================================================================================
TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-LOAD NOMINAL
NAME NO NAME L-L NO NAME L-L KVA KVA
=============================================================================================
T-B32-PDU-E BUS-5019 D 480.00 B32-PDU-E YG 208.00 150.00 150.00
Pos. Seq. Z%: 2.40 + J 3.92 (Zpu 16.01 + j 26.15 ) Shell Type
Zero Seq. Z%: 2.40 + J 3.92 (Sec 16.01 + j 26.15 Pri Open)
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leads Sec.): 30.00 Deg.
=============================================================================================
TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-LOAD NOMINAL
NAME NO NAME L-L NO NAME L-L KVA KVA
=============================================================================================
T-B49-T3 BUS-0553 D 480.00 BUS-0552 YG 208.00 112.50 112.50
Pos. Seq. Z%: 2.68 + J 4.21 (Zpu 23.78 + j 37.44 ) Shell Type
Zero Seq. Z%: 2.68 + J 4.21 (Sec 23.78 + j 37.44 Pri Open)
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leads Sec.): 30.00 Deg.
=============================================================================================
TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-LOAD NOMINAL
NAME NO NAME L-L NO NAME L-L KVA KVA
=============================================================================================
T-B51A1-T2 B51A1-MCC3A1 D 480.00 B51A1-3ALD YG 208.00 15.00 15.00
Pos. Seq. Z%: 3.53 + J 3.82 (Zpu 235.3 + j 254.5 ) Shell Type
Zero Seq. Z%: 3.53 + J 3.82 (Sec 235.3 + j 254.5 Pri Open)
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leads Sec.): 30.00 Deg.
=============================================================================================
TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-LOAD NOMINAL
NAME NO NAME L-L NO NAME L-L KVA KVA
=============================================================================================
T-B51A3 B51A3-SW-B51A3 D 4160.00 B51A3-LV YG 480.00 300.00 300.00
Pos. Seq. Z%: 2.02 + J 5.66 (Zpu 6.74 + j 18.87 ) Shell Type
Zero Seq. Z%: 2.02 + J 5.66 (Sec 6.74 + j 18.87 Pri Open)
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leads Sec.): 30.00 Deg.
=============================================================================================
TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-LOAD NOMINAL
NAME NO NAME L-L NO NAME L-L KVA KVA
=============================================================================================
T-B51B1-T5 B51B1-MCCGB2 D 480.00 B51B1-EEGB YG 208.00 15.00 15.00
Pos. Seq. Z%: 3.53 + J 3.82 (Zpu 235.3 + j 254.5 ) Shell Type
Zero Seq. Z%: 3.53 + J 3.82 (Sec 235.3 + j 254.5 Pri Open)
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leads Sec.): 30.00 Deg.
=============================================================================================
TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-LOAD NOMINAL
NAME NO NAME L-L NO NAME L-L KVA KVA
=============================================================================================
T-B52-CHILL-3 B52-CHILL-3 D 4160.00 BUS-0627 YG 460.00 550.00 550.00
Pos. Seq. Z%: 3.10 + J 5.88 (Zpu 5.63 + j 10.70 ) Shell Type
Zero Seq. Z%: 3.10 + J 5.88 (Sec 5.63 + j 10.70 Pri Open)
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leads Sec.): 30.00 Deg.
=============================================================================================
TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-LOAD NOMINAL
NAME NO NAME L-L NO NAME L-L KVA KVA
=============================================================================================
T-B69-T1 BUS-0024 D 4160.00 B69-T1-LV YG 208.00 500.00 500.00
Pos. Seq. Z%: 0.833 + J 3.91 (Zpu 1.67 + j 7.82 ) Shell Type
Zero Seq. Z%: 0.833 + J 3.91 (Sec 1.67 + j 7.82 Pri Open)
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leads Sec.): 30.00 Deg.
=============================================================================================
TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-LOAD NOMINAL
NAME NO NAME L-L NO NAME L-L KVA KVA
=============================================================================================
T-B70-BA019 BUS-0124 D 480.00 BUS-0125 Y 208.00 75.00 75.00
Pos. Seq. Z%: 1.30 + J 4.11 (Zpu 17.36 + j 54.78 ) Shell Type
Zero Seq. Z%: 9999. + J 9999. (Pri Open, Sec Open)
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leads Sec.): 30.00 Deg.
------------------------------------------------------------------------------
ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL
INTERPRETATION AND APPLICATION BY A REGISTERED ENGINEER ONLY
SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING
FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.
------------------------------------------------------------------------------
SKM POWER*TOOLS FOR WINDOWS
A_FAULT SHORT CIRCUIT ANALYSIS REPORT
COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1996-2013
------------------------------------------------------------------------------
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 13.151 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 13.159 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 13.151 KA
CBL-0758 71-DSBL 13.151 KA ANG: -72.42
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 13.151 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 13.159 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 13.151 KA
CBL-0756 71-DSBL 13.151 KA ANG: -72.42
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 14.063 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 14.063 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 14.063 KA
CBL-0766 71-DSBL 14.063 KA ANG: -69.18
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 16.706 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 18.430 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 16.706 KA
CBL-0746 BUS-0673 16.706 KA ANG: 102.17
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 2.346 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 2.346 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 2.346 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 2.346 KA
CBL-0800 71-LSBLA 2.346 KA ANG: -49.53
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
750KW GEN BKR 3P Duty: 7.510 KA AT -87.49 DEG ( 6.24 MVA) X/R: 22.85
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0016 + J 0.0369 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 8.672 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 10.242 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 9.207 KA
CONTRIBUTIONS: GEN--1 7.510 KA ANG: -87.49
ATS-4 EMER ENC 3P Duty: 7.075 KA AT -80.62 DEG ( 2.55 MVA) X/R: 6.06
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0028 + J 0.0167 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 7.075 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 9.704 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 8.224 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 7.393 KA
CBL-0483 T-ATS 4 SEC 7.075 KA ANG: -80.62
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 14.990 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 17.227 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 15.486 KA
CBL-0302 B51B1-MCCGB1 0.512 KA ANG: -76.83
ATS 5B BUS-0778 14.479 KA ANG: 100.35
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0046 + J 0.0212 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 12.784 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 14.100 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 12.784 KA
CBL-2040 B32-DP-B 1.087 KA ANG: -71.10
CBL-0701 B32-UPS-B 11.705 KA ANG: -78.33
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 11.332 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 11.332 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 11.332 KA
CBL-0421 B32-DP 11.332 KA ANG: -55.17
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0052 + J 0.0221 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 12.199 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 13.238 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 12.199 KA
CBL-0700 B32-BYP-PNL-A 2.438 KA ANG: -243.98
B32-UPSA BUS-0617 9.837 KA ANG: -80.00
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0239 + J 0.0295 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 3.163 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 3.163 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 3.163 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 3.163 KA
CBL-0524 B49-MDP 3.163 KA ANG: -51.07
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 14.580 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 14.580 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 14.580 KA
CBL-0529 B50U1-GAPA 14.580 KA ANG: -59.14
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0076 + J 0.0087 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 10.386 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 10.386 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 10.386 KA
CBL-0392 B50U1-JB12-1 10.386 KA ANG: 131.21
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0080 + J 0.0083 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 10.410 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 10.410 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 10.410 KA
CBL-0411 B50U1-JB6 10.410 KA ANG: -46.30
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 17.784 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 17.784 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 17.784 KA
CBL-0382 B50U1-MSB 17.784 KA ANG: -64.14
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 8.584 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 8.584 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 8.584 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 8.584 KA
CBL-0370 B50U1-JB1-2 8.584 KA ANG: -231.73
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 19.410 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 19.410 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 19.410 KA
CBL-0383 B50U1-MSB 19.410 KA ANG: -64.56
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0109 + J 0.0236 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 4.613 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 4.898 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 4.613 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 4.613 KA
T-B51B2-ATS1B B51B2-SW-1B 4.613 KA ANG: -245.24
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 10.405 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 10.405 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 10.405 KA
B51A1-ATS-2A-B BUS-0288 10.405 KA ANG: -236.98
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0068 + J 0.0238 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 11.209 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 11.563 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 11.209 KA
CONTRIBUTIONS: M-MCC3A1-LS 0.037 KA ANG: -68.20
CBL-0553 BUS-0574 0.195 KA ANG: 102.74
CBL-0531 B51A1-TAP-2 10.978 KA ANG: -74.12
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
B51A151 EL3A 3P Duty: 6.134 KA AT -39.03 DEG ( 5.10 MVA) X/R: 0.81
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0351 + J 0.0285 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 6.134 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 6.134 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 6.134 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 6.134 KA
CBL-0539 B51A1-EL2A 6.134 KA ANG: -39.03
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 9.595 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 9.723 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 9.595 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 9.595 KA
CBL-0328 B51A2-TAP-11 9.595 KA ANG: -241.19
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 4.577 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 4.856 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 4.577 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 4.577 KA
T-B51A2-ATS1A BUS-5004 4.577 KA ANG: -245.19
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 5.013 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 5.740 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 5.013 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 5.013 KA
CBL-0340 B51A3-MDP 5.013 KA ANG: -70.56
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0052 + J 0.0202 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 13.302 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 14.409 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 13.302 KA
CBL-0308 B51B1-MCCGB2 2.143 KA ANG: -82.47
B51B1-ATS4B-B5 BUS-0265 11.178 KA ANG: -254.09
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 11.071 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 11.358 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 11.071 KA
CONTRIBUTIONS: M-MCC1B1-LS 0.421 KA ANG: -77.74
CBL-0543 B51B1-MCCGB1 10.651 KA ANG: -73.53
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 8.560 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 8.941 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 8.560 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 8.560 KA
CBL-0277 B51B2-MSG 8.560 KA ANG: -63.85
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0058 + J 0.0130 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 8.456 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 9.068 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 8.456 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 8.456 KA
B51B2-ATS-EK7- BUS-0592 8.456 KA ANG: -65.95
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 5.610 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 5.727 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 5.610 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 5.610 KA
CBL-0506 B51B2-ECGB 5.610 KA ANG: -61.90
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 8.456 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 9.068 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 8.456 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 8.456 KA
CBL-0282 B51B2-MSG 8.456 KA ANG: -65.95
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 2.647 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 2.647 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 2.647 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 2.647 KA
T-B52-C B52-CA 2.647 KA ANG: 124.56
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0196 + J 0.0297 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 3.371 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 3.371 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 3.371 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 3.371 KA
CBL-0473 B52-ELB 3.371 KA ANG: -56.62
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 4.535 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 4.535 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 4.535 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 4.535 KA
CBL-1041 B63&68-LV-1 4.535 KA ANG: -51.82
B63-B68 TAP 3P Duty: 4.691 KA AT -79.78 DEG ( 33.80 MVA) X/R: 6.04
VOLTAGE: 4160. EQUIV. IMPEDANCE= 0.0908 + J 0.5039 OHMS
CBL-1024 B63-SW-B68 4.691 KA ANG: -259.78
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 4.540 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 4.540 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 4.540 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 4.540 KA
CBL-1051 B64&65-LV-1 4.540 KA ANG: -51.81
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0157 + J 0.0205 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 4.652 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 4.652 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 4.652 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 4.652 KA
CBL-1033 B66&67-LV-1 4.652 KA ANG: -52.56
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 2.888 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 4.025 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 3.411 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 3.066 KA
CONTRIBUTIONS: GEN-B69&70 2.565 KA ANG: -86.49
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0311 + J 0.0153 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 3.464 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 3.464 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 3.464 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 3.464 KA
CBL-1064 B69-MSB 3.464 KA ANG: -26.11
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 1.964 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 1.964 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 1.964 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 1.964 KA
CBL-1073 BUS-0085 1.964 KA ANG: 121.03
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 5.707 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 5.707 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 5.707 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 5.707 KA
CBL-1122 B70-LH1A1 5.707 KA ANG: -36.76
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOW VOLTAGE POWER CIRCUIT BREAKER 5.036 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 5.433 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 5.036 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 5.036 KA
CBL-1115 B70-NL2A1-1 5.036 KA ANG: -66.40
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0019 + J 0.0125 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 22.149 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 23.516 KA
CBL-0739 71-DPBH 0.481 KA ANG: -251.93
CBL-0737 BUS-0670 0.433 KA ANG: -252.12
CBL-0729 B71-T1-LV 21.013 KA ANG: -81.62
DP-CR UPS 3P Duty: 9.733 KA AT -70.40 DEG ( 8.09 MVA) X/R: 2.89
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0096 + J 0.0268 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 9.733 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 9.733 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 9.733 KA
CBL-0491 DP-CR 9.733 KA ANG: -70.40
LOAD BANK 3P Duty: 5.932 KA AT -85.98 DEG ( 4.93 MVA) X/R: 14.22
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0033 + J 0.0466 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 6.594 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 9.189 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 7.788 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 7.001 KA
CBL-0475 B50-EPD1 5.932 KA ANG: -85.98
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
SW-B71-T1 MAIN 3P Duty: 5.138 KA AT -81.57 DEG ( 37.02 MVA) X/R: 7.69
VOLTAGE: 4160. EQUIV. IMPEDANCE= 0.0685 + J 0.4625 OHMS
CBL-0727 B55-SGB-15-DIS 2.292 KA ANG: -82.44
CBL-0728 B55-SGA-11-DIS 2.744 KA ANG: -81.21
T-B71-MAIN B71-T1-LV 0.103 KA ANG: -252.23
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
750KW GEN BKR 3P Duty: 7.510 23. Z1= 16.0153 11.920 9.855
SLG DUTY: 7.510 23. Z2= 16.0153 11.920
480. VOLTS LN/LN: 6.504 Z0= 16.0153
LN/LN/GND: 7.510 ( 7.510 GND RETURN KA)
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
U N B A L A N C E D F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
==============================================================================
F A U L T S T U D Y S U M M A R Y
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)
NO NAME L-L 3 PHASE X/R LINE/GRND X/R
==============================================================================
F A U L T S T U D Y S U M M A R Y
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)
NO NAME L-L 3 PHASE X/R LINE/GRND X/R
==============================================================================
F A U L T S T U D Y S U M M A R Y
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)
NO NAME L-L 3 PHASE X/R LINE/GRND X/R
==============================================================================
F A U L T S T U D Y S U M M A R Y
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)
NO NAME L-L 3 PHASE X/R LINE/GRND X/R
==============================================================================
F A U L T S T U D Y S U M M A R Y
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)
NO NAME L-L 3 PHASE X/R LINE/GRND X/R
==============================================================================
F A U L T S T U D Y S U M M A R Y
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)
NO NAME L-L 3 PHASE X/R LINE/GRND X/R
==============================================================================
F A U L T S T U D Y S U M M A R Y
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)
NO NAME L-L 3 PHASE X/R LINE/GRND X/R
==============================================================================
F A U L T S T U D Y S U M M A R Y
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)
NO NAME L-L 3 PHASE X/R LINE/GRND X/R
==============================================================================
F A U L T S T U D Y S U M M A R Y
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)
NO NAME L-L 3 PHASE X/R LINE/GRND X/R
==============================================================================
F A U L T S T U D Y S U M M A R Y
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)
NO NAME L-L 3 PHASE X/R LINE/GRND X/R
==============================================================================
F A U L T S T U D Y S U M M A R Y
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)
NO NAME L-L 3 PHASE X/R LINE/GRND X/R
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
B63-B68 TAP E/Z: 3.910 KA AT -80.91 DEG ( 28.17 MVA) X/R: 6.65
SYM*1.6: 6.256 KA MOMENTARY BASED ON X/R: 5.213 KA
SYM*2.7: 10.556 KA CREST BASED ON X/R: 8.978 KA
VOLTAGE: 4160. EQUIV. IMPEDANCE= 0.0970 + J 0.6066 OHMS
CBL-1029 BUS-0614 0.000 KA ANG: -44.41
CBL-1024 B63-SW-B68 3.910 KA ANG: -260.91
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
SW-B71-T1 MAIN E/Z: 4.231 KA AT -82.57 DEG ( 30.49 MVA) X/R: 8.45
SYM*1.6: 6.770 KA MOMENTARY BASED ON X/R: 5.910 KA
SYM*2.7: 11.424 KA CREST BASED ON X/R: 10.109 KA
VOLTAGE: 4160. EQUIV. IMPEDANCE= 0.0734 + J 0.5629 OHMS
CBL-0727 B55-SGB-15-DIS 1.920 KA ANG: -83.26
CBL-0728 B55-SGA-11-DIS 2.311 KA ANG: -82.00
U N B A L A N C E D M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT E/Z X/R EQUIVALENT MOMENTARY FAULT DUTIES
VOLTAGE TYPE KA IMPEDANCE (PU) E/Z * 1.6 @ 0.5 CYCLE
==============================================================================
U N B A L A N C E D M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT E/Z X/R EQUIVALENT MOMENTARY FAULT DUTIES
VOLTAGE TYPE KA IMPEDANCE (PU) E/Z * 1.6 @ 0.5 CYCLE
==============================================================================
U N B A L A N C E D M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT E/Z X/R EQUIVALENT MOMENTARY FAULT DUTIES
VOLTAGE TYPE KA IMPEDANCE (PU) E/Z * 1.6 @ 0.5 CYCLE
==============================================================================
U N B A L A N C E D M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
LOCATION FAULT E/Z X/R EQUIVALENT MOMENTARY FAULT DUTIES
VOLTAGE TYPE KA IMPEDANCE (PU) E/Z * 1.6 @ 0.5 CYCLE
==============================================================================
M O M E N T A R Y D U T Y S U M M A R Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
SOLUTION METHOD : E/Z
==============================================================================
BUS RECORD VOLTAGE * 3 P H A S E * * * * SLG * * *
NO NAME L-L KA X/R KA X/R
==============================================================================
T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
B51A1-SW-B51A1 E/Z: 3.327 KA AT -83.40 DEG ( 23.98 MVA) X/R: 9.07
VOLTAGE: 4160. EQUIV. IMPEDANCE= 0.0829 + J 0.7170 OHMS
CBL-0270 B51A2-B14 1.603 KA ANG: -83.88
CBL-0269 B51A2-A10 1.641 KA ANG: -83.16
T-B51A1 B51A1-LV 0.084 KA ANG: -259.01
T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
B63-B68 TAP E/Z: 3.136 KA AT -81.90 DEG ( 22.60 MVA) X/R: 7.29
VOLTAGE: 4160. EQUIV. IMPEDANCE= 0.1079 + J 0.7582 OHMS
CONTRIBUTIONS: B63-SW-B68 3.136 KA ANG: -261.90
T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
==============================================================================
T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
SW-B71-T1 MAIN E/Z: 3.351 KA AT -83.36 DEG ( 24.15 MVA) X/R: 9.07
VOLTAGE: 4160. EQUIV. IMPEDANCE= 0.0829 + J 0.7119 OHMS
CBL-0727 B55-SGB-15-DIS 1.521 KA ANG: -84.05
CBL-0728 B55-SGA-11-DIS 1.831 KA ANG: -82.78
U N B A L A N C E D I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING
TYPE KA DECREMENT FACT. DUTIES (KA)
3 PHASE SLG 3 PHASE SLG
==============================================================================
U N B A L A N C E D I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING
TYPE KA DECREMENT FACT. DUTIES (KA)
3 PHASE SLG 3 PHASE SLG
==============================================================================
U N B A L A N C E D I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING
TYPE KA DECREMENT FACT. DUTIES (KA)
3 PHASE SLG 3 PHASE SLG
==============================================================================
U N B A L A N C E D I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING
TYPE KA DECREMENT FACT. DUTIES (KA)
3 PHASE SLG 3 PHASE SLG
==============================================================================
U N B A L A N C E D I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING
TYPE KA DECREMENT FACT. DUTIES (KA)
3 PHASE SLG 3 PHASE SLG
==============================================================================
B63-B68 TAP 3P Duty: 3.14 7.3 SYM2: 1.00 1.00 3.14 2.78
VOLTS: 4160.0 SLG: 2.78 6.2 SYM3: 1.00 1.00 3.14 2.78
NACD: 0.796 LN/LN: 2.72 SYM5: 1.00 1.00 3.14 2.78
LN/LN/GND: 3.03 SYM8: 1.00 1.00 3.14 2.78
GND RETURN: 2.49 TOT2: 1.12 1.09 3.52 3.01
Z1(PU): 4.42515 TOT3: 1.01 1.00 3.18 2.78
Z2(PU): 4.42515 TOT5: 1.00 1.00 3.14 2.78
Z0(PU): 6.15535 TOT8: 1.00 1.00 3.14 2.78
U N B A L A N C E D I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING
TYPE KA DECREMENT FACT. DUTIES (KA)
3 PHASE SLG 3 PHASE SLG
==============================================================================
U N B A L A N C E D I N T E R R U P T I N G D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING
TYPE KA DECREMENT FACT. DUTIES (KA)
3 PHASE SLG 3 PHASE SLG
==============================================================================
SW-B71-T1 MAIN 3P Duty: 3.35 9.1 SYM2: 1.00 1.00 3.35 3.05
VOLTS: 4160.0 SLG: 3.05 8.9 SYM3: 1.00 1.00 3.35 3.05
NACD: 0.798 LN/LN: 2.90 SYM5: 1.00 1.00 3.35 3.05
LN/LN/GND: 3.22 SYM8: 1.00 1.00 3.36 3.05
GND RETURN: 2.79 TOT2: 1.18 1.18 3.96 3.59
Z1(PU): 4.14126 TOT3: 1.04 1.04 3.49 3.16
Z2(PU): 4.14126 TOT5: 1.00 1.00 3.36 3.05
Z0(PU): 5.38762 TOT8: 1.00 1.00 3.35 3.05
I N T E R R U P T I N G D U T Y S U M M A R Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
==============================================================================
BUS RECORD VOLTAGE NACD * 3 P H A S E * * * * S L G * * *
NO NAME L-L RATIO E/Z KA X/R E/Z KA X/R
==============================================================================
Attached one-line diagrams may include the following abbreviations and symbols.
Symbol to have identifier abbreviation followed by the following with field tag as the suffix.
E N
FU Fuse
MTR Motor
R Relay
TX Transformer
S
SW Disconnect Switch
BPS Bolted Pressure Switch
GEN Generator
B50-GEN
480V
B50-GENBKR-1 B50-GENBKR-2
Powerpact P-Frame, 6.0A/P/H Powerpact P-Frame, 6.0A/P/H
1200AS 1200AS
CBL-0444 CBL-0445
3 - #500 AWG/kcmil 3 - #500 AWG/kcmil
15 ft 15 ft
B50-EMD
B50-EPD1
480V
480V
B50-ATS-6B B50-ATS-4A B50-ATS-6A B50-ATS-4
B50-EPD1-LB B50-ATS-5B B50-ATS-5A HKD, RMS 310 HKD, RMS 310 HKD, RMS 310 HLD, RMS 310
B50-EMD-TX1 B50-EMD-TX2 B50-EMD-B51 B50-EMD-ATS-1A B50-EMD-ATS-4B B50-EMD-ATS-3A B50-EMD-ATS-EK6&EK7 B50-EMD-ATS-7A HKD, RMS 310 HKD, RMS 310 HKD, RMS 310 400AS, 400AT 400AS, 400AT 400AS, 400AT 600AS, 600AT
400AS, 400AT 400AS, 400AT 400AS, 400AT LSI LSI LSI
HKD/CHKD HKD/CHKD HKD/CHKD HKD/CHKD LC SELTRNC HKD/CHKD HKD/CHKD HKD/CHKD LSI
250AS 250AS 300AS 250AS 600AS 250AS 400AS 350AS LSI LSI LSI
LSIG CBL-0479 CBL-0480 CBL-0481 CBL-0482
CBL-0475 CBL-0476 CBL-0478 1 - #500 AWG/kcmil 1 - #500 AWG/kcmil 1 - #500 AWG/kcmil 2 - #350 AWG/kcmil
1 - #500 AWG/kcmil 1 - #500 AWG/kcmil 1 - #500 AWG/kcmil 250 ft 100 ft 100 ft 110 ft
CBL-0446 CBL-0447 CBL-0448 CBL-0449 CBL-0450 CBL-0451 CBL-0469 CBL-0486 30 ft 250 ft 100 ft
1 - #250 AWG/kcmil 1 - #250 AWG/kcmil 1 - #350 AWG/kcmil 1 - #500 AWG/kcmil 2 - #300 AWG/kcmil 1 - #350 AWG/kcmil 1 - #500 AWG/kcmil 1 - #500 AWG/kcmil
P
70 ft 70 ft 100 ft 100 ft 65 ft 100 ft 150 ft 100 ft T-ATS-4
LOAD BANK
E N E N E N E N E N S 300.0 kVA
480V
480 / 208V
B50-ATS-2A&2B-JB B50-ATS-1A&1B-JB B50-EMD-ATS4B B50-ATS-3A&3B-JB 5.47% Z
B50-ATS-EK6&EK7 ATS 5B ATS 5A ATS 6B ATS 4A ATS 6A
480V 480V 480V 480V E N
480V
CBL-0483
3 - #300 AWG/kcmil
ATS 7A ATS-5B ATS-5A ATS-6B ATS-4A ATS-6A
5 ft
TO ATS-2A BLDG. 51 TO ATS-1A BLDG. 51 TO ATS-4B BLDG. 51 TO ATS-3A BLDG. 51 480V 480V 480V 480V 480V
P P UNIT A1 DWG. PSE-3574 UNIT A2 DWG. PSE-3575 UNIT B1 DWG. PSE-3576 UNIT A1 DWG. PSE-3574
T-TX1-B50 T-TX2-B50
AND TO ATS-2B BLDG. 51 AND TO ATS-1B BLDG. 51 AND TO ATS-3B BLDG. 51 TO PNL MCCGB1 TO PNL MCC1A1 TO PNL MCC2B1 TO PNL MCC2A1 TO PNL MCCGB3 ATS-4 EMER ENCL BKR
S 150.0 kVA S 150.0 kVA
UNIT B1 DWG. PSE-3576 UNIT B2 DWG. PSE-3577 UNIT B1 DWG. PSE-3576 ATS-7A DWG. PSE-15588 AND MCCGA1 AND MCC3B1 AND MCC3A1 DWG. PSE-15586
208V
480 / 208V 480 / 208V
480V DWG. PSE-15586 DWG. PSE-15588 DWG. PSE-15586
4.51% Z 4.51% Z
TO PNL DP-CR
TO ATS-3 BLDG. 50 TO PNLBD ELCG BLDG. 50 DWG. PSE-15586 CBL-0484
3 - #300 AWG/kcmil
UNIT 1 DWG. PSE-3573 UNIT 1 DWG. PSE-3573
5 ft
E N
ATS 4
CBL-0485
2 - #500 AWG/kcmil
150 ft
TO PNL B50U1-MCCP1
DWG. PSE-15585
E N
ATS 4A
E N E N
ATS 6A
ATS-6A
480V
E N
GEN--1
SW-B71-T1 750 kW
480 V
P
T-B71-MAIN
S 2000.0 kVA MTS
4160 / 480V
5.88% Z 71-MTS
480V
CBL-0729 CBL-0806
1 - #3000 AWG/kcmil 4 - #350 AWG/kcmil
20 ft 24 ft
B71-DSWG-MAIN 71-EBHA-MAIN
Entelliguard G LVPCB, EGTU SKLA, Spectra RMS
3200AS, 3200AT 1200AS, 1200AT
B71-DSWG 480V 71-EBHA
480V
B71-DSWG-71-1HA B71-DSWG-71-1HB B71-DSWG-71-1HC B71-DSWG-ATS-ELEV B71-DSWG-ATS-LS B71-DSWG-ATS-CC B71-DSWG-ATS-EQ B71-DSWG-71-BHA B71-DSWG-DPBH B71-DSWG-T-1 71-EBHA-ATS-ELEV 71-EBHA-ATS-LS 71-EBHA-ATS-CC 71-EBHA-ATS-EQ
Entelliguard G LVPCB, EGTU Entelliguard G LVPCB, EGTU Entelliguard G LVPCB, EGTU Entelliguard G LVPCB, EGTU Entelliguard G LVPCB, EGTU Entelliguard G LVPCB, EGTU Entelliguard G LVPCB, EGTU Entelliguard G LVPCB, EGTU Entelliguard G LVPCB, EGTU Entelliguard G LVPCB, EGTU SFLA, Spectra RMS SFLA, Spectra RMS SFLA, Spectra RMS SGLA, Spectra RMS
400AS, 225AT 400AS, 225AT 400AS, 225AT 400AS, 225AT 400AS, 225AT 400AS, 225AT 800AS, 600AT 400AS, 225AT 1600AS, 1200AT 800AS, 800AT 225AS 225AS 225AS 600AS
CBL-0730 CBL-0732 CBL-0733 CBL-0734 CBL-0735 CBL-0737 CBL-0738 CBL-0739 CBL-0740 CBL-0747 CBL-0748 CBL-0749 CBL-0750
1 - #4/0 AWG/kcmil 1 - #4/0 AWG/kcmil 1 - #4/0 AWG/kcmil 1 - #4/0 AWG/kcmil 1 - #4/0 AWG/kcmil CBL-0736 2 - #350 AWG/kcmil 1 - #4/0 AWG/kcmil 4 - #350 AWG/kcmil 2 - #500 AWG/kcmil 1 - #4/0 AWG/kcmil 1 - #4/0 AWG/kcmil 1 - #4/0 AWG/kcmil 2 - #350 AWG/kcmil
256 ft 42 ft 145 ft 34 ft 28 ft 1 - #4/0 AWG/kcmil 110 ft 28 ft 20 ft 42 ft 34 ft 28 ft 35 ft 10 ft
152 ft
71-1HA 71-1HC
480V 480V
71-1HA-BRANCH 71-1HC-BRANCH
THED THED
20AS 20AS
71-BHA
CBL-0751 N E N E N E N E 480V P
1 - #4/0 AWG/kcmil CBL-0753 B71-T-1
ATS-ELEV ATS-LS ATS-CC ATS-EQ S
20 ft 1 - #4/0 AWG/kcmil 71-BHA-BRANCH 500.0 kVA
20 ft FB, 2 & 3-Pole 480V 480 / 208V
ATS-EQ LOAD 5.18% Z
20AS
ATS-ELEV LOAD ATS-LS LOAD ATS-CC LOAD 480V
71-2HA 71-2HC
480V 480V 480V
480V 480V 71-DPBH-MAIN
SKLA, Spectra RMS
CBL-0742 CBL-0743 1200AS, 1200AT
CBL-0744 CBL-0745 CBL-0746
1 - #4/0 AWG/kcmil 1 - #4/0 AWG/kcmil 2 - #350 AWG/kcmil 71-DPBH 5 - #500 AWG/kcmil
1 - #4/0 AWG/kcmil
10 ft 10 ft 10 ft 480V 20 ft
10 ft
71-1HB
480V
71-EVBHA
480V
71-1HB-BRANCH
71-DPBH-SERVELEV
FB, 2 & 3-Pole 480V
71-EVBHA-BRANCH SFLA, Spectra RMS
20AS
THED 175AS
CBL-0752
150AS
1 - #4/0 AWG/kcmil
AHU 1/4/5 SF - LS
20 ft
25.0 hp
CBL-0788
1 - #4/0 AWG/kcmil
100 ft
71-EQBLD
208V
71-EQBLD-BRANCH
THHQB
25AS
71-DSBL 208V
71-DSBL-71-1LA 71-DSBL-71-1LB 71-DSBL-71-1LJ 71-DSBL-71-1LM 71-DSBL-71-1LC 71-DSBL-71-1LD 71-DSBL-71-1LK 71-DSBL-71-1LF 71-DSBL-71-1LG 71-DSBL-71-1LH 71-DSBL-71-1LI 71-DSBL-71-1LL 71-DSBL-71-BLA 71-DSBL-71-BLB
SGDA, Spectra RMS SGDA, Spectra RMS SFHA, Spectra RMS SFHA, Spectra RMS SGDA, Spectra RMS SGDA, Spectra RMS SFHA, Spectra RMS SGDA, Spectra RMS SGDA, Spectra RMS SGDA, Spectra RMS SGDA, Spectra RMS SFHA, Spectra RMS SFHA, Spectra RMS SFHA, Spectra RMS
400AS 400AS 225AS 225AS 400AS 400AS 225AS 400AS 400AS 400AS 400AS 225AS 225AS 225AS
71-1LA 71-1LB 71-1LJ 71-1LM-1 71-1LC 71-1LD 71-1LK 71-1LF 71-1LG 71-1LH 71-1LI 71-1LL 71-BLA 71-BLB
208V 208V 208V 208V 208V 208V 208V 208V 208V 208V 208V 208V 208V 208V
71-1LA-BRANCH 71-2LB-BRANCH 71-1LJ-BRANCH 71-1LC-BRANCH 71-1LD-BRANCH 71-1LK-BRANCH 71-1LF-BRANCH 71-1LG-BRANCH 71-1LH-BRANCH 71-1LI-BRANCH 71-1LL-BRANCH 71-BLA-BRANCH 71-BLB-BRANCH
THHQB THHQB THHQB 71-1LM-BRANCH THHQB THHQB THHQB THHQB THHQB THHQB THHQB THHQB THHQB THHQB
20AS 20AS 20AS THHQB 20AS 20AS 30AS 30AS 30AS 20AS 30AS 50AS 50AS 20AS
CBL-0768 CBL-0769 20AS
1 - #500 AWG/kcmil 1 - #500 AWG/kcmil CBL-0771 CBL-0770 CBL-0772 CBL-0773 CBL-0774 CBL-0775 CBL-0776
20 ft 20 ft 1 - #4/0 AWG/kcmil 1 - #500 AWG/kcmil 1 - #500 AWG/kcmil 1 - #500 AWG/kcmil 1 - #500 AWG/kcmil 1 - #500 AWG/kcmil 1 - #500 AWG/kcmil
10 ft 20 ft 20 ft 20 ft 20 ft 20 ft 20 ft
71-2LA 71-2LB
208V 208V 71-1LM-2 71-2LC 71-2LD 71-2LF 71-2LG 71-2LH 71-2LI
208V 208V 208V 208V 208V 208V 208V