Professional Documents
Culture Documents
Zig-Zag Transformer:
It converts ungrounded system to the grounded system
Instrument Transformer
To Reduce the unbalance
For Ex: Delta-star grounded transformer
Why 11kv/415v Transformer is dela-star grounded?? Why not delta-delta
transformer??
Ans: Delta-star Transformer reduces the unbalances.
Rectifier application:-
For Ex:
12-pulse rectifier application delta on the one side & star on
the other side. similarly you can see the old HVDC Systems,24
pulse converter station where you see the different winding
configuration of these transformer.
5.) What are the application of Transformer which is not come under the
IEC60076 Standard:-
6.) What is the rate power in the Transformers as per IEC 60076-1(GENERAL):-
The rated power is the convention value of rated power assigned to the
winding which together with the rated voltage of the winding, determine
its rated current.
Note:-
You can vectorally add these two component you will get I 2.
% OF
ETAP RESULTS RATING OF T/F LOADING
34265 31500 108.7777778
31500 31500 100
11.) What is the rated current in the transformer?
The current flowing through a line terminal of the winding which is
derived from rated power Sr and rated voltage Vr of the winding
Ultimately the current decides the Heating of the equipment.
12.) Why the voltage tolerance is more important for the transformer??
Why the voltage tolerance is important because, you need to have a rating
at each and every tap that is on the HV winding
In LV, there is only one winding
The transformer is able to maintain or manage upto 31.5MVA even when
the voltage tolerance of these much
What I mean if you have voltage tolerance of +/-5%.
The transformer rating is not the 31.5MVA. The transformer rating is
165.3A on the HV side & 1653 A on the LV side.
If the grid voltage comes down, the current rating is not come down only
the MVA rating is come down.
CURRENT IN
VGE IN KV A T/F KVA T/F MVA
110 165.33333 31499.30603 KVA 31.49931 MVA
99 165.33333 28349.37543 28.34938
How to calculate the KVA rating of Transformer with the given voltage &
full load current,
KVA of Transformer=1.732*110*165.33=31499.30KVA
So, 31.5MVA is the rated voltage & you are not specify the voltage
tolerance . By any change in the grid voltage comes down by 99kV then the
current remains same but the MVA rating of transformer will come down.
If you are not specifically ask the the transformer data sheet for
transformer procurement for what is the voltage tolerance.
Then the transformer manfacturer gives 165.33A for the rated voltage of
110kV which means when there is the reduction in the voltage the rating
also comes down.
Now if the transformer rating is 31.5MVA and its voltage tolerance is +/-10
% what does it means?
It means even if your voltage comes down to -10%, the transformer is
capable to transfer 31.5MVA which means the rated current is 165.33A
at the rated voltage.
But if the voltage comes down to 0.9P.U. in order to meet the 31.5MVA
of transformer the current is increased by 10% & transformer is capable
of withstand the current also.
So, why we ask the voltage tolerance for the transformer from the
transformer manufacturer. It is clear from the above mention.
CURRENT IN
VGE IN KV A T/F KVA T/F MVA
110 165.33333 31499.30603 KVA 31.49931 MVA
NEGATIVE TOLERANCE 99 165.33333 28349.37543 28.34938
POSITIVE TOLERANCE 121 165.33333 34649.23663 34.64924
Here the negative tolerance makes the sense Decrease in voltage from
rated kV and increase in current to maintain the MVA rating of
transformer which means in order transformer is able to withstand.
The positive tolerance is not making sensethe transformer is able to
withstand more MVA from the rated MVA.
13.) How we define the rating of the equipment (Transfomer)?
For these we need to know the ambient temperature.
Ambient temperature 40 degree Celsius
Class A insulation 105 degree celsius
So, what is the temperature allowed=105-40=65 degree Celsius.
If suppose the customer is allow upto 50 degree Celsius only, then
40+50=90 degree Celsius for Class A insulation.
No Harmonics
Harmonics
fundamental I1 100 100
I2 0 0
I3 0 0
I4 0 0
Fifth order I5 0 20 100/5=20
harmonics
I6 0 0
I7 0 14.285 100/7=14.285
I8 0 0
I9 0 0
I10 0 0
I11 0 9.090 100/11=9.090
I 100 103.3766 Sqrt(100^2+20^2+14.285^2+
9.09^2
loss 10000 10686.726 Heat loss=I*I*R
If you find out the rms value of all the values of current(harmonics) then
you get 103.376A.
Assume, R=1 ohmthen the loss would be is mention in the above
table.
17.) What is the K-factor rating in the transformer?
K-Rating of the transformer is helping to withstand the harmonics but it is
not able to eliminate the harmonics.
It is essential need to mention in the transformer especially in the data
centers & steel industry you need to know the k-factor of the transformer
where the harmonic content is rich.
Note:-
If the k-factor is not specify then k-factor is assumed as 1.
The transformer cost is high when the transformer have high value of the k-
factor.
For k-factor is 4then 100MVA transformer is withstand upto 125.8MVA.