Professional Documents
Culture Documents
Analysis of Reinforced Concrete Silos PDF
Analysis of Reinforced Concrete Silos PDF
Analysis of Reinforced
Concrete Silos
Empirical approximation are preferred by many engineers. Tow such approximation are:
a ) H > 1.5 A
b ) H > 1.5D for circular silos
H > 1.5a for rectangular silos
The present ACI 313 Silos standard, however, uses the same method for
both silos and bunkers
γR − µ kY / R
= −
'
q 1 e
µ 'k
Where
R = ratio of area to perimeter of horizontal cross section of storage space
γ = weight per unit volume for stored material
µ` = coefficient of friction between stored material and wall or hopper surface
k = 1 − sin φ
Horizontal Pressure
p = kq
Vertical friction per unit length of wall perimeter
=
V (γY −q )R
Note:
µ`, k vary, the following combinations shall be used with maximum:
(1) Minimum µ` and minimum k for maximum vertical pressure q.
(2) Minimum µ` and maximum k for maximum lateral pressure p.
(3) Maximum µ` and maximum k for maximum vertical friction force V
Dr. Mohammed Arafa 8
Pressures and loads for hoppers
q=
y q0 + γ hy
q y tan θ
Pn = and V n Pn tan φ '
tan θ + tan φ '
or
q y ( sin 2 θ + k cos 2 θ )
Pn = and q y (1 − k ) sin θ ⋅ cos θ
Vn =
sin θ
T = pdes ( a 2 )
1 − cos θ
Dr. Mohammed Arafa 11
Sections with combined tension and bending
Mu h
Small eccentricity e= < − d ''
Fu 2
Fu e ' Fu e ''
As = A 's
φ f y (d − d ') φ f y (d − d '')
E c h αc 2
=Mt ∆T
12 (1 −ν )
∆T = (T i −T 0 − 80o F ) K t = (T i −T 0 − 27o C ) K
0.08h
Kt =
4.09 + 0.08h
The thickness of silo or stacking tube walls shall be not less than 6
in. (150 mm) for cast-in-place concrete, nor less than 2 in. (50 mm)
for precast concrete.
The following formula can also be used in service loading
ε sh E s + f s − nfct
t= T
100f s fct
w = 0.0001f s 3 d c A
Load factors for silo or stacking tube design shall conform to those
specified in ACI 318.
The weight of and pressures due to stored material shall be
considered as live load.
For concrete cast in stationary forms, strength reduction factors, φ,
shall be as given in ACI 318.
For slip forming, unless continuous inspection is provided, strength
reduction factors given in ACI 318 shall be multiplied by 0.95.
The compressive axial load strength per unit area for walls in which
buckling (including local buckling) does not control shall be
computed by
Flat Bottom
The simplest flat bottom is a slab of uniform thickness. The flat bottom
may also be a ribbed slab or beam-slab system.
For a slab without hopper-forming fill, the design loads are dead load
and pressure, qdes computed at the top of the slab..
=
W u 1.4DL + 1.7q des
With earthquake vertical friction at the wall is assumed to be zero, so
that the ultimate vertical pressure on the bottom is:
Wu 0.75 (1.4DL + 1.7γ H )
Slab
Dr. Shear stresses
Mohammed Arafa should be checked. 25
Additional Load at Openings
Conical hopper
qy D WL Wg
Fmu = 1.7 + + 1.4
4sin α π D sin α π D sin α
qα D
Ftu = 1.7
2sin α
q=
α p=n P sin 2
α + q cos 2
α
b a
Ftau =
1.7 αb ,des
q sin α a and Ftbu 1.7 qα a ,des sin αb
2 2
Dr. Mohammed Arafa 27
Additional Load at Openings
Pyramidal hopper
b 2a2
=
A r a1b1 −
2
y =
Ar
An equivalent rectangle of height a a = 2y
and b is substituted for the pentagon b = Ar a
Dr. Mohammed Arafa 31
Circular Concrete Ring-Beam and Column System
Supporting a Steel Hopper
Design the wall and hopper of a wheat silo with an internal diameter of
10 meter and with the height of cylindrical portion of 40 m. The central
hopper is supported by eight columns monolithic with the lower walls.
The Roof load ( DL = 150 kg/m2 and LL= 100 kg/m2)
Use the following parameter
f c' = 350 kg / cm 2
f y = 4200 kg / cm 2
γ = 800 kg / m 3
φ = 25o
µ ' = 0.444
1.5m
D= 10m
D=40m
60m
D=20m
D=10m
=
R
(π 4D 2 )
= D= 4 10=
/ 4 2.5m
(π D )
H= =
/ D 40 /10 4
µ 'k
= = 4.42 t/m 2
P kq
Ring Tension
C p Pu D 1.75 (1.7 × 4.42 ) ×10
=T = = 65.74 ton
2 2
T 65.74
=A st = = 17.4 cm 2 /m ie. 8.7 cm 2 /m for each side
(φ f y ) 0.9 × 4200
use φ12@12.5 cm
ε E + f − nfct
t = sh s s
(=
0.0003 × 200 ⋅10 + 1680 − 8 ( 35 ) ) 4.42 ×10
4
T 7.5cm
100f s fct 100 ×1680 × 35 2
The thickness of silo walls shall be not less than 150 mm for cast-in-place concrete.
Use Wall thickness t=20cm
A = 0.002 × 20 ×100
Dr. Mohammed Arafa
st = 4 cm 2 /m 43
Design Example
Design for the hopper
q=
y q0 + γ hy 5.0m
at h y = 1.0 m
q=
y 7.65 + 0.8 ×=
1 8.45 t/m 2
W L = weight of the material in hopper
0.8π 4.1
( 4.1) + ( 0.75 ) ( 5.8 ) =
2 2
WL= 84.4 ton
3
2.5π 5.8m
Wg = [ 2 × 4.1× 0.2 + 2 × 0.75 × 0.2] ( 5.8) =29.5 ton
3
Merdional forces and required reinforcing
0.75
qy D WL Wg
Fmu = 1.7 + + 1.4
4sin α π D sin α π D sin α
1.5 × 8.45 × 2 ( 4.1) 84.4 29.5
F= 1.7 + + 1.4 = 59.2 ton/m
mu
4sin 60 π ( 2 × 4.1) sin 60 π ( 2 × 4.1) sin 60
59.2
A st = 16.5cm 2 /m
0.9 × 4200
Dr. Mohammed Arafa 44
Design Example
Hoop Reinforcement
1.5 × qα D
Ftu = 1.7
2sin α
=qα P sin 2 α + q cos 2 α
where P =kq =0.577 × 8.45 =4.87 t/m 2
qα = 4.87 sin 2 60 + 8.45cos 2 60 = 5.765t/m 2
assume φ ' = 25
q y tan θ 8.45 tan 30
or q=
α p= = = 4.67t/m 2
tan θ + tan φ ' tan 30 + tan 25
n
use q=
α =
p n 4.67t/m 2
a1 = 100 33
b1 = 90 28.5
100cm r=467cm
a2 = 100 32.9
b 2 = 57 90
A r = 6150
=x 32.9= cm , y 42.3cm
a = 87.2cm 33cm
b = 74.5cm
M t = 0.285 × 684 = 19.5 t .m 28.5
90cm R=4.67m
32.9
Dr. Mohammed Arafa 46
90cm
Design Example
Design of the Circular Beam
R=
5 − 32.9 /100 =
4.67 m 33cm
π
=
W g 2.5 ( 2 × 4.1× 0.2 + 2 × 0.75 × 0.2 ) =
× 5.8 29.5 ton 90cm
3
qy D WL Wg
Fmu = 1.7 + + 1.4
4sin α π D sin α π D sin α
1.5 × 8.1× 10 116.5 29.5
Fmu 1.7 + + 1.4 =68.4 ton
4sin 60 π (10 ) sin 60 π (10 ) sin 60
= mu cos α
Fx F= =
68.4 cos 60 34.2ton
Fy= 0.615 × 2.5 ×1.4 + 68.4sin 60= 61.5ton
Dr. Mohammed Arafa 47
Design Example
Design of the Circular Beam
Dead Load
Weight of hopper forming fill
2π 3 ( 5 ) ( 5 )( 2.5 )
2
Wg = 8.33 t/m 2
π ( 5)
2
28.4π ( 5 − 0.35 )
2
Vu = 66 ton
2π ( 5 − 0.35 )
φV c = 0.53 ( 0.85 ) 300 ( 35 ) ( 2π ( 5 − 0.35 ) ) = 798 ton >V u
Total Reaction
Total reaction at the bottom wall must includes
From Roof, Material above the hopper, Material in the hopper,
hopper filling form, Bottom Slab, Upper Wall, and Lower Wall
f y = 4200 kg / cm 2 30m
3m
7m
Openning0.5x0.5m
Ground Floor Plan
Dr. Mohammed Arafa 53