Professional Documents
Culture Documents
Uwe Seltsam
TRANSFORM Partner
About the Author
Uwe Seltsam
Scientific Background
Professional Background
On-load tap-changers (OLTCs) are used for changing the transmission ratio under load
U1 Transformer: 40 MVA, 110 kV 16 %
/ 21 kV
110 kV 17.6 kV
Mwg = Main winding
Cwg = Coarse winding OLTC: M III 350 Y – 123/C – 10 19 1G
Mwg Rwg = Regulating winding Step voltage: 17.6 kV : 9 steps ≙ 1.955 kV/step ≙ 1.78 %
LU = Diverter switch insert
555 wdgs
U2
Cwg - 21 kV
120 wdgs + 129 wdgs
k
Rwg 9 LU
108 wdgs 2
12 wdgs/step 1 U1 = N1
U2 N2
Nominal: U2 = 21 kV = constant
Example 1: U1 = 110 kV
N1 = 110 kV • 129 wdgs / 21 kV = 675 wdgs
U2 = 110 kV • 129 wdgs / 675 wdgs = 21.02 kV
Example 2: U1 = 116 kV
N1 = 116 kV • 129 wdgs / 21 kV = 711 wdgs
U2 = 116 kV • 129 wdgs / 711 wdgs = 21.05 kV
A,B
a,b
Main switching
e. g. M III 600 9 steps contacts
3-pole a1, b1
Transition contacts
Star connection Ra, Rb
Insulation to ground Transition resistors
Um = 123 kV Ua, Ub
Voltages of tappings
Ust
Step voltage
U, I
Voltage, current of tap-
changer terminals
A,B
a,b
Main switching
e. g. V III 200 10 steps conttacts
3-pole a1, b1
Transition contacts
Star connection R
Insulation to ground Transition resistor
Um = 76 kV Ua, Ub
Voltages of tappings
Ust
Step voltage
U, I
Voltage, current of
tap-changer terminals
VACUTAP®
Type VR® since 2004
Switching sequence
R Transition resistor
VACUTAP®
Type VV since 2000
IB
Neutral-point application
after every 5 – 7 years
after every 50,000 – 150,000 operations
Delta application
after every 2 – 4 years
after every 20,000 – 100,000 operations
Maintenance of tap selector
after every 1 to 1.2 million operations
Maintenance time
Visual presentation
Present condition 0 ... 100 %
Prediction for 100 % moment
Semaphore function green/yellow/red
Criterion:
Heat removal from the transition resistors must
not be restricted by oil carbonization.
Determining factors for degree of carbonization:
Number of operations
Arc energy
Type of oil: Little difference between naphthenic-base
or paraffin-base oil
The temperature of the oil sample must be measured at the time when the oil was taken.
The values specified for dielectric strength apply to oil temperatures of 20 ± 5 °C at the time of
evaluating the oil sample.
Recommendation:
Dielectric strength of > 50 kV / 2.5 mm for new insulating oil that must be filled in after maintenance.
Ask the OLTC manufacturer if other insulating liquids (ester liquids, etc.) are used.
Facts:
Diverter switch oil of OILTAP® is a mixture of oil,
carbon deposits and humidity
Water absorption of carbon deposits is several times
as high as water absorption of oil
Carbonized oil with inadmissibly high water content puts
insulation distances at risk which are exposed to voltage
stress
Effects:
Electrical-field distortion with local discharges
Thermal decomposition of surface of insulating material
Creepage paths
Breakdown of insulating distance with flashover
Switching shaft
Example of creepage paths
Vacuum interrupter
End position limiting device in OLTC and/or motor-drive unit Burst membrane
MPreC®
Oil
No. of ops. temp. H2 CH4 C2H6 C2H4 C2H2 CO CO2 O2 N2
[°C]
0 16 127 31 3 70 359 10 344 17500 39400
29000 50 17796 12205 3642 36170 102172 330 3032 10800 48100
50000 22 13553 13000 4200 50000 103000 317 7733 4900 25300
Example for OLTC type M
Torque measurement:
Integral part of monitoring TM100 and
TG260®, including assessment (semaphore
function). Online procedure.
Torque measurement directly on OLTC head
with mobile measuring device.
• Maintenance
maintenance intervals of the respective on-load tap-changer shall be observed at any time to
ensure trouble-free operation of the transformer. Original spare parts and trained service staff
have also be seen as mandatory.
www.reinhausen.com