Professional Documents
Culture Documents
Methods of Testing Heavy Duty Dampers PDF
Methods of Testing Heavy Duty Dampers PDF
Authority AMCA International Standard 510 was approved by the membership of the Air Movement and Control
Association International Inc. on July 26, 2008. It was approved as an American National Standard by the
American National Standards Institute (ANSI) and became effective on October 9, 2009.
As of 2015, this document no longer undergoes routine maintenance and has been withdrawn due to
a lack of use. Since the document is no longer regularly reviewed by engineers as part of AMCA's
document review cycle, it is to be used as a historic reference. It is not a current American National
Standard.
All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections
107 and 108 of the United States Copyright Act without the permission of the copyright owner is unlawful.
Requests for permission or further information should be addressed to the Executive Director, Air
Movement and Control Association International, Inc. at 30 West University Drive, Arlington Heights, IL
60004-1893 U.S.A.
Objections Air Movement and Control Association International, Inc. will consider and decide all written complaints
regarding its standards, certification programs, or interpretations thereof. For information on procedures for
submitting and handling complaints, write to:
Disclaimer AMCA uses its best efforts to produce standards for the benefit of the industry and the public in light of
available information and accepted industry practices. However, AMCA does not guarantee, certify or
assure the safety or performance of any products, components or systems tested, designed, installed or
operated in accordance with AMCA standards or that any tests conducted under its standards will be non-
hazardous or free from risk.
Review Committee
Related AMCA Publication 502 Damper Application Manual for Heating/ Ventilating, and Air Conditioning
Publications
AMCA Publication 503 Fire, Ceiling (Radiation), Smoke and Fire/Smoke Damper Application
Manual
Related ANSI/AMCA Standard 210 Laboratory Methods of Testing Fans for Certified Aerodynamic
Standards Performance
2. Normative References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
3.1 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
6. Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
ANSI/AMCA 510-09 | 1
3.2.4 Pressure 5.1.2.1 Test equipment
The unit of pressure is the pascal (Pa) or the millimeter of • Calibrated orifice plate or pitot tube
mercury (mm Hg); the I-P unit is either the inch water gauge
(in. wg), or the inch mercury (in. Hg). Values in mm Hg or in • A manometer of the liquid column type using inclined or
in. Hg shall be used only for barometric pressure measure- vertical legs or other instruments which provide a maxi-
ments. mum uncertainty of 1% of the maximum observed test
reading during the test or 1 Pa (0.005 in. wg) whichever
3.2.5 Torque is larger
The unit of torque is the newton-meter (N-m); the I-P unit is
the foot-pound (ft-lbf). • A thermometer capable of temperature accuracies within
5°C (9°F) and with a temperature range that covers the
3.2.6 Gas properties specified operating temperature during the test
The unit of density is the kilogram per cubic meter (kg/m3);
the I-P unit is the pound mass per cubic foot (lbm/ft3). The • Method of determining the applied force or torque
unit of viscosity is the Pascal-second, (Pa-s); the I-P unit is required during the test to compare to predicted actuator
the pound mass per foot-second (lbm/ft-s). The SI unit of requirements. This may consist of a pressure gauge,
gas constant is the joule per kilogram-Kelvin (J/kg-K); the I- catalog actuator output data, a spring scale and torque
P unit is the foot-pound force per pound mass-degree arm, or other device
Rankine, (ft-lbf/lbm-°R).
5.1.2.2 Measurements to be taken during the test
3.2.7 Dimensionless groups • Temperature of air used to pressurize damper
Various dimensionless quantities appear in the text. Any
consistent system of units may be employed to evaluate • Pressure applied to damper
these quantities unless a numerical factor is included, in
which case units must be as specified. • Flow measurements as required for instrument
4. Instruments / Methods of Measurements • Applied torque or force required to maintain the meas-
ured leakage
The requirements of ANSI/AMCA 210, Section 5, shall apply
where required. 5.1.3 Test methods
2 | ANSI/AMCA 510-09
Duct Pressure Measurement
PLANE 1
Flow Measurement (Pitot or Orifice)
Flow Control
Pressurizing
Heating Fan
T1 Element
Leakage to Atmosphere
Figure 5.1
Leakage Test Setup
ANSI/AMCA 510-09 | 3
the damper fails this test. The damper shall be cycled from full open to full close three
times.
Observations shall be recorded on the Test Report Form
(see Annex B). The following observations shall be recorded on the Test
Report Form (see Annex B):
5.1.5 Gland leakage
The leakage tests measure the total leakage of the damper. • Time required for damper to move from actuator ener-
When measurement of the gland leakage is required by the gization to end of stroke in each direction
customer, a blanking plate shall be placed over the down-
stream side of the damper and the test procedure repeated. • Maximum amperage or fluid pressure during stroke in
each direction
5.2 Cycle test
• Temperature, and pressure
5.2.1 Purpose
The purpose of this test is to demonstrate the successful 5.2.4 Test evaluation
operation of a damper through its entire range of move- No calculations are required for this test.
ment.
Pass/fail criteria: If the damper manifests any of the follow-
5.2.2 Test setup ing symptoms during the cycle test, it will be considered to
The damper is to be placed in the positioning which it is to have failed the test:
be installed, unless otherwise agreed to by the customers.
• Failure to operate
If the damper is to be tested at conditions other than ambi-
ent conditions, the purchaser must specify the temperature • Requiring any assistance to facilitate movement
and/or pressure that is to be applied to the damper during
the cycle test. • Any evidence of permanent distortion or damage after
the test is complete
5.2.2.1 Test equipment:
• A timer • Overload of motor
4 | ANSI/AMCA 510-09
The damper can be placed
horizontally,vertically, or in
Damper
the position in which it is to
Drive
be installed.
AMP
When specified, damper will Meter
be tested at operational
temperature and pressure
Duct Pressure
Flow
Control
Duct Pressure
Control
Pressurizing
Heating Element Fan
T1
Figure 5.2
Damper Cycle Test Setup
ANSI/AMCA 510-09 | 5
Figure 5.3
Obstruction Test Setup
6 | ANSI/AMCA 510-09
5.3.6 Test evaluation gap present between sealing surfaces of a damper. This
No calculations are required for this test. test is intended to compare the conformance of the manu-
factured part to specifications. It is not normally performed
Pass/fail criteria: Any permanent distortion or damage, stop- under conditions of pressure and temperature unless other-
ping without completing the stroke, or requiring any assis- wise specified.
tance to continue operating will indicate that the damper has
failed the test. 5.5.2 Test setup
The damper should be placed in the position in which it is to
Observations shall be recorded on Test Report Form (see be installed with the specified closing force applied..
Annex B).
5.5.3 Test equipment
5.4 Deflection test Standard sets of “feeler” gauges are required.
5.4.4 Measurements to be taken during the test • Total gap area = average gap × sealed perimeter
The blade deflection shall be measured.
Pass/fail criteria: If the average gap or the total gap area is
5.4.5 Test method more than specified, the damper has failed the test.
With the damper pressurized to the specified conditions, the
dial indicator will read directly. If a seal air system is Observations shall be recorded on the Test Report Form
required, the seal air blower should be operating. The (see Annex B).
damper shall be maintained at a near constant temperature
throughout the test. 5.6 Seal air consumption test
ANSI/AMCA 510-09 | 7
Figure 5.4
Seal Air Consumption Test Setup
8 | ANSI/AMCA 510-09
A static pressure tap shall be installed in the damper seal air subjected to a Damper Cycle Test as described in Section
chamber to record the chamber pressure. 5.2.
• Seal air fan flow Pass/fail criteria: Any visible sign of damage or permanent
distortion or failure to pass the Damper Cycle Test will be an
5.6.5 Test method indication that the damper has failed the test.
With the damper pressurized to the specified conditions, the
seal air valve shall be opened and the seal air fan started. Observations shall be recorded on the Test Report Form
Measure and record damper seal airflow, duct static pres- (see Annex B).
sure, seal air chamber pressure and temperature on the
Test Report Form (see Annex B). 5.8 Drive redundancy test
5.7.4 Measurements to be taken during the test Observations shall be recorded on the Test Report Form
No measurements are required to be taken during this test. (see Annex B).
ANSI/AMCA 510-09 | 9
Annex A
Flow Measurement (Normative)
10 | ANSI/AMCA 510-09
Annex B
Test Report Form (Informative)
AN D
NT
ME CO
VE NT
O
RO
M
Insert your Logo
AIR
AMCA 510
L
here
Heavy Damper Method of Test
L
NA
AS
O
O I
S
CI AT
AT
IO E RN
N INT
MEMBER
Purpose: The purpose of this test is to determine the amount of leakage past the closed Damper
at a specified operating pressure.
Tested Orientation:
Date:
ANSI/AMCA 510-09 | 11
AN D
NT
ME CO
VE NT
O
RO
M
Insert your Logo
AIR
AMCA 510
L
here
Heavy Damper Method of Test
L
NA
AS
O
O TI
S
CI
AT NA
IO ER
N INT
MEMBER
Purpose: The purpose of this test is to demonstrate the successful operation of a damper
through its entire range of movement.
Tested Orientation:
First Cycle
Operating Conditions: Test Conditions Open Cycle Test Conditions Closed Cycle
Gas Temperature: Gas Temperature: Gas Temperature:
Gas Pressure: Gas Pressure: Gas Pressure:
Allowable Time: Measured Time: Measured Time:
Allowable Amps/Pressure: Measured Amps/Pressure: Measured Amps/Pressure
Second Cycle:
Gas Temperature: Gas Temperature: Gas Temperature:
Gas Pressure: Gas Pressure: Gas Pressure:
Allowable Time: Measured Time: Measured Time:
Allowable Amps/Pressure: Measured Amps/Pressure: Measured Amps/Pressure:
Third Cycle:
Gas Temperature: Gas Temperature: Gas Temperature:
Gas Pressure: Gas Pressure: Gas Pressure:
Allowable Time: Measured Time: Measured Time:
Allowable Amps/Pressure: Measured Amps/Pressure: Measured Amps/Pressure
Damper has Passed/Failed Test:
Comments: Approved By:
Date:
12 | ANSI/AMCA 510-09
AN D
NT
ME CO
VE NT
O
RO
M
Insert your Logo
AIR
AMCA 510
L
here
Heavy Damper Method of Test
L
NA
AS
O
O TI
S
CI
AT NA
IO ER
N INT
MEMBER
Purpose: The purpose of this test is to demonstrate operation of the damper in simulated field
conditions with the damper partially obstructed.
Date:
ANSI/AMCA 510-09 | 13
AN D
NT
ME CO
VE NT
O
RO
M
Insert your Logo
AIR
AMCA 510
L
here
Heavy Damper Method of Test
L
NA
AS
O
O TI
S
CI
AT NA
IO ER
N INT
MEMBER
Tested Orientation:
Pass/Fail Criteria: If the deflection of the center of the blade exceeds the specified
amount, the damper has failed the test.
Specified Conditions Measured Conditions
Temperature: Temperature:
Pressure: Pressure:
Maximum Deflection: Maximum Deflection:
Based on comparison of specified to measured blade deflection, the damper has
Passed/Failed this test:
Date:
14 | ANSI/AMCA 510-09
AN D
NT
ME CO
VE NT
O
RO
M
Insert your Logo
AIR
AMCA 510
L
here
Heavy Damper Method of Test
L
NA
AS
O
O TI
S
CI
AT NA
IO ER
N INT
MEMBER
Purpose: The purpose of this test is to determine the total amount of gap present between seal-
ing surfaces of a damper.
Pass/Fail Criteria: If the average or total gap is greater than the specified gap, or if the
total gap area is more than specified, then the damper has failed the test.
Side 1 Side 2 Side 3 Side 4
Gap Measurement Gap Measurement Gap Measurement Gap Measurement
Date:
ANSI/AMCA 510-09 | 15
AN D
NT
ME CO
VE NT
O
RO
M
Insert your Logo
AIR
AMCA 510
L
here
Heavy Damper Method of Test
L
NA
AS
O
O TI
S
CI
AT NA
IO ER
N INT
MEMBER
Purpose: The purpose of this test is to determine the seal air consumption.
Tested Orientation:
Pass/Fail Criteria: If the measured seal airflow exceeds the specified flow, the damper
has failed the test.
Specified Conditions Measured Conditions
Seal air pressure: Seal air pressure:
Duct static pressure: Duct static pressure:
Specified flow: Specified flow:
Based on comparison of specified to measured seal airflow the damper has
Passed/Failed this test:
Date:
16 | ANSI/AMCA 510-09
AN D
NT
ME CO
VE NT
O
RO
M
Insert your Logo
AIR
AMCA 510
L
here
Heavy Damper Method of Test
L
NA
AS
O
O TI
S
CI
AT NA
IO ER
N INT
MEMBER
Purpose: The purpose of this test is to demonstrate the structural integrity of the damper under
the maximum actuator output.
Observations:
ANSI/AMCA 510-09 | 17
AN D
NT
ME CO
VE NT
O
RO
M
Insert your Logo
AIR
AMCA 510
L
here
Heavy Damper Method of Test
L
NA
AS
O
O TI
S
CI
AT NA
IO ER
N INT
MEMBER
Purpose: The purpose of this test is to demonstrate the successful operation of a guillotine
damper with only one half of a dual-connected drive system operating.
Observations:
Pass/Fail Criteria: The damper will be considered to have failed the test if it stops at
any point during the cycle or requires any form of assistance to continue movement.
Based on observations and successfully Approved:
completing a complete cycle, the damper
Passed/Failed this test: Date:
18 | ANSI/AMCA 510-09
AIR MOVEMENT AND CONTROL
ASSOCIATION INTERNATIONAL INC.
30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.
Tel: (847) 394-0150 Fax: (847) 253-0088
Email : info@amca.org Web: www.amca.org
The Air Movement and Control Association International Inc. is a not-for-profit international association of
the world’s manufacturers of related air system equipment, primarily but limited to fans, louvers, dampers,
air curtains, airflow measurement stations, acoustic attenuators and other air system components for the
industrial, commercial and residential markets.