You are on page 1of 25

Methods of Testing

Heavy Duty Dampers


for Rating

AIR MOVEMENT AND CONTROL


ASSOCIATION INTERNATIONAL INC.
The International Authority on Air System Components
AMCA Publications

Authority AMCA International Standard 510 was approved by the membership of the Air Movement and Control
Association International Inc. on July 26, 2008. It was approved as an American National Standard by the
American National Standards Institute (ANSI) and became effective on October 9, 2009.

As of 2015, this document no longer undergoes routine maintenance and has been withdrawn due to
a lack of use. Since the document is no longer regularly reviewed by engineers as part of AMCA's
document review cycle, it is to be used as a historic reference. It is not a current American National
Standard.

Copyright © 2009 by Air Movement and Control Association International Inc.

All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections
107 and 108 of the United States Copyright Act without the permission of the copyright owner is unlawful.
Requests for permission or further information should be addressed to the Executive Director, Air
Movement and Control Association International, Inc. at 30 West University Drive, Arlington Heights, IL
60004-1893 U.S.A.

Objections Air Movement and Control Association International, Inc. will consider and decide all written complaints
regarding its standards, certification programs, or interpretations thereof. For information on procedures for
submitting and handling complaints, write to:

Air Movement and Control Association International


30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.

AMCA International, Incorporated


c/o Federation of Environmental Trade Associations
2 Waltham Court, Milley Lane, Hare Hatch
Reading, Berkshire, United Kingdom
RG10 9TH

Disclaimer AMCA uses its best efforts to produce standards for the benefit of the industry and the public in light of
available information and accepted industry practices. However, AMCA does not guarantee, certify or
assure the safety or performance of any products, components or systems tested, designed, installed or
operated in accordance with AMCA standards or that any tests conducted under its standards will be non-
hazardous or free from risk.
Review Committee

John Hughey, Chair Clarage

Per Olesen Air Clean Damper Co.

Shane Glidewell Barron Industries

Johnny Johnson Barron Industries

Dave Forney Effox, Inc.

Jack Neiser Effox, Inc.

Pete Connor Ron-Noc Industries, Inc.

Scott Hall Wahlco Metroflex

John Powell Wahlco Metroflex

Joseph Brooks AMCA International, Inc.

Tim Orris AMCA International, Inc.


Related AMCA Documents

Related AMCA Publication 502 Damper Application Manual for Heating/ Ventilating, and Air Conditioning
Publications
AMCA Publication 503 Fire, Ceiling (Radiation), Smoke and Fire/Smoke Damper Application
Manual

Related ANSI/AMCA Standard 210 Laboratory Methods of Testing Fans for Certified Aerodynamic
Standards Performance

ANSI/AMCA Standard 500-D Labortory Methods of Testing Dampers for Rating


Contents

1. Purpose and Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

2. Normative References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3. Definitions / Units of Measure / Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3.1 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3.2 Units of measure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

4. Instruments / Methods of Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

5. Observations / Conduct of Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

5.1 Leakage test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

5.2 Cycle test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

5.3 Obstruction test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

5.4 Deflection test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

5.5 Seal gap test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

5.6 Seal air consumption test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

5.7 Stall test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

5.8 Drive redundancy test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

6. Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

Annex A Flow Measurement (Normative) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

Annex B Test Report Form (Informative) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11


Methods of Testing
Heavy Duty Dampers for Rating

1. Purpose and Scope 3.1.2.5 Leakage


Leakage is the amount of gas passing though a device
The purpose of this standard is to establish testing methods when it is in the closed position at a specific pressure differ-
to be used in measuring the performance of dampers used ential and density. It is expressed as the volumetric rate or
in the utility and heavy industry. The scope of the products percentage of specified flow.
covered in this standard shall include dampers, which are
used to control flow of a gas (be it a specific gas, a mixture 3.1.2.6 Gland leakage
of gas and air, or air alone) or to isolate one section of a duct A gland is a device, such as the outer sleeve of a stuffing
system from another section of the system. The scope box, designed to prevent a fluid from leaking past a moving
narrows to those dampers generally described as “custom machine part. In this context, gland leakage refers to leak-
design,” “heavy duty,” or “severe service,” because such age thru any moving part sealing device intended to prevent
dampers are normally used in applications where elevated or limit the amount of gas from leaking from inside the
temperature, erosion and/or corrosion conditions exist. damper to the atmosphere or vice versa.

2. Normative References 3.1.3 Miscellaneous

ANSI/AMCA 210-07 Laboratory Methods of Testing 3.1.3.1 Shall and should


Fans for Aerodynamic Performance Rating, Air The word shall is to be understood as mandatory, the word
should as advisory.
Movement and Control Association International, Inc., 30 W.
University Drive, Arlington Heights, IL 60004-1893 U.S.A.,
2007.
3.2 Units of Measure

3.2.1 System of units


3. Definitions / Units of Measure / Symbols
SI units (The International System of Units, Le Systéme
International d'Unités) [1] are the primary units employed in
3.1 Definitions
this standard, with I-P units (Inch-Pound) given as the
secondary reference. SI units are based on the fundamen-
3.1.1 Heavy duty damper
tal values of the International Bureau of Weights and
A device used to control, isolate or divert a gas in a process,
Measures [1], and I-P values are based on the values of the
industrial or power generation application in accordance
National Institute of Standards and Technology, which are in
with customer requirements.
turn based on the values of the International Bureau.

3.1.2 Performance variables


3.2.2 Basic units
The unit of length is the meter(m), or the millimeter (mm); I-
3.1.2.1 Shop conditions P units are the foot (ft) or the inch (in). The unit of mass is
Ambient temperature and atmospheric pressure in the the kilogram (kg); the I-P unit is the pound mass (lbm). The
manufacturing test facility at the time of the damper test. unit of time is either the minute (min), or the second (s). The
unit of temperature is either the degree Celsius (°C), or the
3.1.2.2 System conditions degree Kelvin (°K). I-P units are either the degree
The design temperature and pressure conditions under
which the damper will operate, as specified by the Fahrenheit (°F), or the degree Rankine (°R). The unit of
purchaser. force is the newton (N); the I-P unit is the pound force(lbf).

3.1.2.3 Pressure drop 3.2.3 Flow rate and velocity


Pressure drop is a measure of the resistance to airflow
across a device. It is expressed as the difference in static 3.2.3.1 Flow rate
pressure across an air control device for a specific rate of The unit of volumetric flow rate is the cubic meter per
airflow. second (m3/s); the I-P unit is the cubic foot per minute (cfm).

3.1.2.4 Closure pressure 3.2.3.2 Velocity


Pressure drop across a closed damper. The unit of velocity is the meter per second (m/s); the I-P
unit is the foot per minute (fpm).

ANSI/AMCA 510-09 | 1
3.2.4 Pressure 5.1.2.1 Test equipment
The unit of pressure is the pascal (Pa) or the millimeter of • Calibrated orifice plate or pitot tube
mercury (mm Hg); the I-P unit is either the inch water gauge
(in. wg), or the inch mercury (in. Hg). Values in mm Hg or in • A manometer of the liquid column type using inclined or
in. Hg shall be used only for barometric pressure measure- vertical legs or other instruments which provide a maxi-
ments. mum uncertainty of 1% of the maximum observed test
reading during the test or 1 Pa (0.005 in. wg) whichever
3.2.5 Torque is larger
The unit of torque is the newton-meter (N-m); the I-P unit is
the foot-pound (ft-lbf). • A thermometer capable of temperature accuracies within
5°C (9°F) and with a temperature range that covers the
3.2.6 Gas properties specified operating temperature during the test
The unit of density is the kilogram per cubic meter (kg/m3);
the I-P unit is the pound mass per cubic foot (lbm/ft3). The • Method of determining the applied force or torque
unit of viscosity is the Pascal-second, (Pa-s); the I-P unit is required during the test to compare to predicted actuator
the pound mass per foot-second (lbm/ft-s). The SI unit of requirements. This may consist of a pressure gauge,
gas constant is the joule per kilogram-Kelvin (J/kg-K); the I- catalog actuator output data, a spring scale and torque
P unit is the foot-pound force per pound mass-degree arm, or other device
Rankine, (ft-lbf/lbm-°R).
5.1.2.2 Measurements to be taken during the test
3.2.7 Dimensionless groups • Temperature of air used to pressurize damper
Various dimensionless quantities appear in the text. Any
consistent system of units may be employed to evaluate • Pressure applied to damper
these quantities unless a numerical factor is included, in
which case units must be as specified. • Flow measurements as required for instrument

4. Instruments / Methods of Measurements • Applied torque or force required to maintain the meas-
ured leakage
The requirements of ANSI/AMCA 210, Section 5, shall apply
where required. 5.1.3 Test methods

5. Observations / Conduct of Tests 5.1.3.1 Leakage testing – shop condition


With the duct pressurized to the specified condition, and
5.1 Leakage test maintained for a period of ten minutes, record temperature,
pressure at the damper, applied torque (or force), and flow
5.1.1 Purpose measurement.
The purpose of this test is to determine the amount of leak-
age past the closed damper at a specified operating pres- 5.1.3.2 Leakage testing – system condition
sure. Partially open damper blade(s) allowing enough flow for
heating. Heat damper until temperature reaches the test
5.1.2 Test setup temperature and maintain for ten minutes.
A test apparatus is to be used that allows pressure to be
applied against the closed damper. The amount of gas that Close the damper blade(s) fully, and adjust upstream pres-
flows past the damper can be determined using a calibrated sure to test pressure, record temperature, pressure at the
orifice plate or pitot tube (see Annex A). damper, applied torque (or force), and flow measurement
data.
The customer is to specify if testing is to be done at system
conditions otherwise the testing will be done at shop condi- 5.1.4 Test evaluation
tions and adjusting for actual conditions by the ratio of spec- The calculations require having the test data adjusted for
ified and tested gas density. temperature, altitude or other operating conditions different
from any test conditions.
Dampers shall be oriented in the installed position for test-
ing when specified. Pass/fail criteria: If the damper exceeds the manufacturers
quoted leakage rate or if the applied torque required to
achieve acceptable leakage rates exceeds specifications,

2 | ANSI/AMCA 510-09
Duct Pressure Measurement

PLANE 1
Flow Measurement (Pitot or Orifice)

Flow Control

Pressurizing
Heating Fan
T1 Element

Leakage to Atmosphere

Test Damper Fully Closed


in Position of Installation

Figure 5.1
Leakage Test Setup

ANSI/AMCA 510-09 | 3
the damper fails this test. The damper shall be cycled from full open to full close three
times.
Observations shall be recorded on the Test Report Form
(see Annex B). The following observations shall be recorded on the Test
Report Form (see Annex B):
5.1.5 Gland leakage
The leakage tests measure the total leakage of the damper. • Time required for damper to move from actuator ener-
When measurement of the gland leakage is required by the gization to end of stroke in each direction
customer, a blanking plate shall be placed over the down-
stream side of the damper and the test procedure repeated. • Maximum amperage or fluid pressure during stroke in
each direction
5.2 Cycle test
• Temperature, and pressure
5.2.1 Purpose
The purpose of this test is to demonstrate the successful 5.2.4 Test evaluation
operation of a damper through its entire range of move- No calculations are required for this test.
ment.
Pass/fail criteria: If the damper manifests any of the follow-
5.2.2 Test setup ing symptoms during the cycle test, it will be considered to
The damper is to be placed in the positioning which it is to have failed the test:
be installed, unless otherwise agreed to by the customers.
• Failure to operate
If the damper is to be tested at conditions other than ambi-
ent conditions, the purchaser must specify the temperature • Requiring any assistance to facilitate movement
and/or pressure that is to be applied to the damper during
the cycle test. • Any evidence of permanent distortion or damage after
the test is complete
5.2.2.1 Test equipment:
• A timer • Overload of motor

• An amp meter 5.3 Obstruction test

• A thermometer 5.3.1 Purpose


The purpose of this test is to demonstrate operation of the
• A manometer or pressure gauge damper in simulated field conditions with the damper
partially obstructed.
• A pressure gauge for measuring the fluid pressure
applied to the damper actuator 5.3.2 Test setup
The damper shall be placed in the position in which it is to
5.2.2.2 Measurements to be taken during the test: be installed. The purchaser shall specify the type, amount,
• Time of operation from energizing of actuator to comple- and condition of material that is to be placed in the path of
tion of stroke in seconds damper operation (Example: twelve inches of dry cement
dust).
• Maximum power required during stroke, in amps or fluid
pressure applied to damper actuator 5.3.3 Test equipment
No test equipment is required for this test.
• Temperature of gas used to pressurize damper
5.3.4 Measurements to be taken during the test
5.2.3 Test method No measurements are required for this test.
If the damper is to be tested at other than ambient condi-
tions, the specified temperature and pressure shall be 5.3.5 Test method
applied to the damper and time allowed for equilibrium to be The damper shall be cycled through the obstruction as
reached. Minimum settling time at specified temperature specified.
shall be no less than 10 minutes.

4 | ANSI/AMCA 510-09
The damper can be placed
horizontally,vertically, or in
Damper
the position in which it is to
Drive
be installed.
AMP
When specified, damper will Meter
be tested at operational
temperature and pressure

Duct Pressure

Flow
Control
Duct Pressure
Control

Pressurizing
Heating Element Fan
T1

Figure 5.2
Damper Cycle Test Setup

ANSI/AMCA 510-09 | 5
Figure 5.3
Obstruction Test Setup

6 | ANSI/AMCA 510-09
5.3.6 Test evaluation gap present between sealing surfaces of a damper. This
No calculations are required for this test. test is intended to compare the conformance of the manu-
factured part to specifications. It is not normally performed
Pass/fail criteria: Any permanent distortion or damage, stop- under conditions of pressure and temperature unless other-
ping without completing the stroke, or requiring any assis- wise specified.
tance to continue operating will indicate that the damper has
failed the test. 5.5.2 Test setup
The damper should be placed in the position in which it is to
Observations shall be recorded on Test Report Form (see be installed with the specified closing force applied..
Annex B).
5.5.3 Test equipment
5.4 Deflection test Standard sets of “feeler” gauges are required.

5.4.1 Purpose 5.5.4 Measurements to be taken during the test


The purpose of this test is to determine blade deflection. Gap dimensions shall be measured.

5.4.2 Test setup 5.5.5 Test method


The damper shall be tested in the installed position and The damper shall be placed in the fully closed position.
temperature, and pressurized on the side of the blade(s) Measurements shall be taken at the gap between the
corresponding with the customer’s system once the damper blade(s) and the mating seal at 12" intervals, but no fewer
is fully closed. than three measurements per side. The gap will be meas-
ured by the largest feeler gauge that can be inserted
A bar or other support will be placed across the downstream between the two mating surfaces without forcing them
damper flanges at the point of maximum blade deflection. If apart. The gap measurements shall be recorded for each
this point is not readily apparent, a series of measurements location.
across the blade will be made to determine this. If the
damper consists of multiple blades having varying cross 5.5.6 Test evaluation
sections, measurements of each blade type will be made. Calculations to be made:

5.4.3 Test equipment • Average gap = sum of all gap measurements/number of


A dial indicator is required. measurement points

5.4.4 Measurements to be taken during the test • Total gap area = average gap × sealed perimeter
The blade deflection shall be measured.
Pass/fail criteria: If the average gap or the total gap area is
5.4.5 Test method more than specified, the damper has failed the test.
With the damper pressurized to the specified conditions, the
dial indicator will read directly. If a seal air system is Observations shall be recorded on the Test Report Form
required, the seal air blower should be operating. The (see Annex B).
damper shall be maintained at a near constant temperature
throughout the test. 5.6 Seal air consumption test

5.4.6 Test evaluation 5.6.1 Purpose


No calculations are required for this test. The purpose of this test is to determine the seal air fan
consumption.
Pass/fail criteria: Deflection at the blade(s) point of maxi-
mum deflection will be measured and recorded on the Test 5.6.2 Test setup
Report Form (see Annex B). Data will be compared to the The damper should be tested in the installed orientation and
specification to demonstrate conformance. The test temper- pressurized on the side of the blade(s) corresponding with
ature and pressure shall also be recorded. the customer’s system.

5.5 Seal gap test 5.6.3 Test equipment


The seal airflow will be measured using either a pitot
5.5.1 Purpose traverse or a calibrated orifice.
The purpose of this test is to determine the total amount of

ANSI/AMCA 510-09 | 7
Figure 5.4
Seal Air Consumption Test Setup

8 | ANSI/AMCA 510-09
A static pressure tap shall be installed in the damper seal air subjected to a Damper Cycle Test as described in Section
chamber to record the chamber pressure. 5.2.

5.6.4 Measurements to be taken during the test: 5.7.6 Test evaluation


• Chamber pressure No calculations are required for this test.

• Seal air fan flow Pass/fail criteria: Any visible sign of damage or permanent
distortion or failure to pass the Damper Cycle Test will be an
5.6.5 Test method indication that the damper has failed the test.
With the damper pressurized to the specified conditions, the
seal air valve shall be opened and the seal air fan started. Observations shall be recorded on the Test Report Form
Measure and record damper seal airflow, duct static pres- (see Annex B).
sure, seal air chamber pressure and temperature on the
Test Report Form (see Annex B). 5.8 Drive redundancy test

5.6.6 Test evaluation 5.8.1 Purpose


No calculations are required for this test. The purpose of this test is to demonstrate the successful
operation of a guillotine damper with only one half of a dual-
Pass/fail criteria: If the measured seal air fan flow exceeds connected drive system operating. Due to the complexities
the specified flow, the damper has failed. of maintaining operating conditions of temperature and flow,
this test is normally performed under shop conditions unless
If the chamber pressure is below the specified value, the otherwise specified.
damper has failed.
5.8.2 Test setup
5.7 Stall test The damper shall be placed in the position in which it is to
be installed. One side of the drive system will be discon-
5.7.1 Purpose nected from the blade assembly. Any parts that might jam or
The purpose of this test is to demonstrate the structural interfere with damper operation are permitted to be
integrity of the damper under the maximum actuator output. removed prior to damper operation. It is allowable for the
damper manufacturer to completely remove one side of the
5.7.2 Test setup drive system prior to positioning the damper.
The damper should be placed horizontally, vertically or in
the position in which it is to be installed. A solid blockage 5.8.3 Test equipment
capable of stopping the operation of the damper shall be No test equipment is required for this test.
inserted into the path of damper movement. The blockage
shall be installed in such a way as to prevent movement on 5.8.4 Measurements to be taken during the test
either opening or closing. The purchaser may specify that No measurements are required for this test.
the location of the blockage be selected to produce the
maximum amount of loading eccentricity. For electrically 5.8.5 Test method
actuated dampers, the circuit protection should reasonably The damper shall be operated through one complete cycle
approximate the type of protection that will be used in final (from full open to closed and back to full open or from full
installation. The purchaser and manufacturer shall agree closed to open and back to full closed).
upon type and size of circuit protection that will be used
during the test. For dampers that are actuated pneumati- 5.8.6 Test evaluation
cally or hydraulically, the pressure of the motive fluid shall No calculations are required for this test.
be regulated as specified.
Pass/fail criteria: The damper will be considered to have
5.7.3 Test equipment failed the test if it stops at any point during the cycle or
No test equipment is required for this test. requires any form of assistance to continue its movement.

5.7.4 Measurements to be taken during the test Observations shall be recorded on the Test Report Form
No measurements are required to be taken during this test. (see Annex B).

5.7.5 Test method 6. Calculations


The damper will be either opened or closed until it contacts
the blockage and stalls. If the tests are conducted at other than operating conditions,
they shall be corrected to operating conditions.
The obstruction shall be removed and the damper shall be

ANSI/AMCA 510-09 | 9
Annex A
Flow Measurement (Normative)

Flow measurement and test setups shall conform to


ANSI/AMCA 210, Figures 1, 2A, 2B, 3, 4A, 7 and 12.

10 | ANSI/AMCA 510-09
Annex B
Test Report Form (Informative)

AN D
NT
ME CO
VE NT
O

RO
M
Insert your Logo

AIR
AMCA 510

L
here
Heavy Damper Method of Test

L
NA
AS

O
O I

S
CI AT
AT
IO E RN
N INT

MEMBER

5.1 Leakage Test

Purpose: The purpose of this test is to determine the amount of leakage past the closed Damper
at a specified operating pressure.

Date: Test Personnel: Witnesses:

Reference No: Customer/User Information:

Description of Damper Installed Orientation:

Tested Orientation:

Operating Conditions: Test Conditions: Adjusted Conditions:


Gas Temperature: Gas Temperature: Gas Temperature:
Gas Pressure: Gas Pressure: Gas Pressure:
Gas Density: Gas Density: Gas Density:
Allowable Leakage: Measured Leakage: Adjusted Leakage:
Damper has Passed/Failed Test:

Comments: Approved By:

Date:

ANSI/AMCA 510-09 | 11
AN D
NT
ME CO
VE NT
O

RO
M
Insert your Logo

AIR
AMCA 510

L
here
Heavy Damper Method of Test

L
NA
AS

O
O TI

S
CI
AT NA
IO ER
N INT

MEMBER

5.2 Damper Cycle Test

Purpose: The purpose of this test is to demonstrate the successful operation of a damper
through its entire range of movement.

Date: Test Personnel: Witnesses:

Reference No: Customer/User Information:

Description of Damper: Installed Orientation:

Tested Orientation:

First Cycle
Operating Conditions: Test Conditions Open Cycle Test Conditions Closed Cycle
Gas Temperature: Gas Temperature: Gas Temperature:
Gas Pressure: Gas Pressure: Gas Pressure:
Allowable Time: Measured Time: Measured Time:
Allowable Amps/Pressure: Measured Amps/Pressure: Measured Amps/Pressure

Second Cycle:
Gas Temperature: Gas Temperature: Gas Temperature:
Gas Pressure: Gas Pressure: Gas Pressure:
Allowable Time: Measured Time: Measured Time:
Allowable Amps/Pressure: Measured Amps/Pressure: Measured Amps/Pressure:

Third Cycle:
Gas Temperature: Gas Temperature: Gas Temperature:
Gas Pressure: Gas Pressure: Gas Pressure:
Allowable Time: Measured Time: Measured Time:
Allowable Amps/Pressure: Measured Amps/Pressure: Measured Amps/Pressure
Damper has Passed/Failed Test:
Comments: Approved By:

Date:

12 | ANSI/AMCA 510-09
AN D
NT
ME CO
VE NT
O

RO
M
Insert your Logo

AIR
AMCA 510

L
here
Heavy Damper Method of Test

L
NA
AS

O
O TI

S
CI
AT NA
IO ER
N INT

MEMBER

5.3 Obstruction Test

Purpose: The purpose of this test is to demonstrate operation of the damper in simulated field
conditions with the damper partially obstructed.

Date: Test Personnel: Witnesses:

Reference No: Customer/User Information:

Description of Damper: Installed Orientation:

Description of Obstruction: Tested Orientation:

Pass/Fail Criteria: Any permanent distortion or damage, stopping without completing


the stroke, or requiring any assistance to continue operating will indicate the damper
has failed the test.
Observations: Approved by:

Date:

ANSI/AMCA 510-09 | 13
AN D
NT
ME CO
VE NT
O

RO
M
Insert your Logo

AIR
AMCA 510

L
here
Heavy Damper Method of Test

L
NA
AS

O
O TI

S
CI
AT NA
IO ER
N INT

MEMBER

5.4 Deflection Test

Purpose: The purpose of this test is to determine blade deflection.

Date: Test Personnel: Witnesses:

Reference No: Customer/User Information:

Description of Damper: Installed Orientation:

Tested Orientation:

Pass/Fail Criteria: If the deflection of the center of the blade exceeds the specified
amount, the damper has failed the test.
Specified Conditions Measured Conditions
Temperature: Temperature:
Pressure: Pressure:
Maximum Deflection: Maximum Deflection:
Based on comparison of specified to measured blade deflection, the damper has
Passed/Failed this test:

Comments: Approved By:

Date:

14 | ANSI/AMCA 510-09
AN D
NT
ME CO
VE NT
O

RO
M
Insert your Logo

AIR
AMCA 510

L
here
Heavy Damper Method of Test

L
NA
AS

O
O TI

S
CI
AT NA
IO ER
N INT

MEMBER

5.5 Seal Gap Test

Purpose: The purpose of this test is to determine the total amount of gap present between seal-
ing surfaces of a damper.

Date: Test Personnel: Witnesses:

Reference No: Customer/User Information:

Description of Damper: Specified Total Gap Area:

Specified Average Gap:

Pass/Fail Criteria: If the average or total gap is greater than the specified gap, or if the
total gap area is more than specified, then the damper has failed the test.
Side 1 Side 2 Side 3 Side 4
Gap Measurement Gap Measurement Gap Measurement Gap Measurement

Average Gap = Sum of Gaps/No. Gaps = Total Gap Area =


Average Gap/Sealed Perimeter =

Based on comparison of specified to measured blade deflection, the damper has


Passed/Failed this test:
Comments: Approved by:

Date:

ANSI/AMCA 510-09 | 15
AN D
NT
ME CO
VE NT
O

RO
M
Insert your Logo

AIR
AMCA 510

L
here
Heavy Damper Method of Test

L
NA
AS

O
O TI

S
CI
AT NA
IO ER
N INT

MEMBER

5.6 Seal Air Consumption Test

Purpose: The purpose of this test is to determine the seal air consumption.

Date: Test Personnel: Witnesses:

Reference No: Customer/User Information:

Description of Damper: Installed Orientation:

Tested Orientation:

Pass/Fail Criteria: If the measured seal airflow exceeds the specified flow, the damper
has failed the test.
Specified Conditions Measured Conditions
Seal air pressure: Seal air pressure:
Duct static pressure: Duct static pressure:
Specified flow: Specified flow:
Based on comparison of specified to measured seal airflow the damper has
Passed/Failed this test:

Comments: Approved By:

Date:

16 | ANSI/AMCA 510-09
AN D
NT
ME CO
VE NT
O

RO
M
Insert your Logo

AIR
AMCA 510

L
here
Heavy Damper Method of Test

L
NA
AS

O
O TI

S
CI
AT NA
IO ER
N INT

MEMBER

5.7 Stall Test

Purpose: The purpose of this test is to demonstrate the structural integrity of the damper under
the maximum actuator output.

Date: Test Personnel: Witnesses:

Reference No: Customer/User Information:

Description of Damper: Installed Orientation:

Description and Location of Obstruction: Tested Orientation:

Observations:

Pass/Fail Criteria: Any visible sign of damage or permanent distortion, or failure to


pass the damper cycle test will cause the damper to fail the test.
Based on observations and passing the Approved:
Damper Cycle Test 5.2 (see attached Test
Report) the damper has Passed/Failed Date:
this Test:

ANSI/AMCA 510-09 | 17
AN D
NT
ME CO
VE NT
O

RO
M
Insert your Logo

AIR
AMCA 510

L
here
Heavy Damper Method of Test

L
NA
AS

O
O TI

S
CI
AT NA
IO ER
N INT

MEMBER

5.8 Drive Redundancy Test

Purpose: The purpose of this test is to demonstrate the successful operation of a guillotine
damper with only one half of a dual-connected drive system operating.

Date: Test Personnel: Witnesses:

Reference No: Customer/User Information:

Description of Damper: Installed Orientation:

Description of drive type and how disconnected: Tested Orientation:

Observations:

Pass/Fail Criteria: The damper will be considered to have failed the test if it stops at
any point during the cycle or requires any form of assistance to continue movement.
Based on observations and successfully Approved:
completing a complete cycle, the damper
Passed/Failed this test: Date:

18 | ANSI/AMCA 510-09
AIR MOVEMENT AND CONTROL
ASSOCIATION INTERNATIONAL INC.
30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.
Tel: (847) 394-0150 Fax: (847) 253-0088
Email : info@amca.org Web: www.amca.org

The Air Movement and Control Association International Inc. is a not-for-profit international association of
the world’s manufacturers of related air system equipment, primarily but limited to fans, louvers, dampers,
air curtains, airflow measurement stations, acoustic attenuators and other air system components for the
industrial, commercial and residential markets.

You might also like