Professional Documents
Culture Documents
To cite this article: Yat Huang Yau & Mohammad Ahmadzadehtalatapeh (2014) Performance Analysis of a Heat Pipe Heat
Exchanger Under Different Fluid Charges, Heat Transfer Engineering, 35:18, 1539-1548, DOI: 10.1080/01457632.2014.897581
Taylor & Francis makes every effort to ensure the accuracy of all the information (the “Content”) contained
in the publications on our platform. However, Taylor & Francis, our agents, and our licensors make no
representations or warranties whatsoever as to the accuracy, completeness, or suitability for any purpose of the
Content. Any opinions and views expressed in this publication are the opinions and views of the authors, and
are not the views of or endorsed by Taylor & Francis. The accuracy of the Content should not be relied upon and
should be independently verified with primary sources of information. Taylor and Francis shall not be liable for
any losses, actions, claims, proceedings, demands, costs, expenses, damages, and other liabilities whatsoever
or howsoever caused arising directly or indirectly in connection with, in relation to or arising out of the use of
the Content.
This article may be used for research, teaching, and private study purposes. Any substantial or systematic
reproduction, redistribution, reselling, loan, sub-licensing, systematic supply, or distribution in any
form to anyone is expressly forbidden. Terms & Conditions of access and use can be found at http://
www.tandfonline.com/page/terms-and-conditions
Heat Transfer Engineering, 35:1539–1548, 2014
Copyright
C Taylor and Francis Group, LLC
ISSN: 0145-7632 print / 1521-0537 online
DOI: 10.1080/01457632.2014.897581
An experimental study was conducted on the effects of the amount of working fluid on the performance of a two-row copper-
R134a heat pipe heat exchanger at the air side. The heat pipe heat exchanger operates in the horizontal configuration, and five
different fluid charges were studied to cover the underload and overload cases. Moreover, the calculated outlet temperature
of the evaporator side, obtained from the heat exchanger simulation, was compared with the experimental results. Based on
the present study, it was found that the optimum performance of the copper-R134a heat pipe heat exchanger can be achieved
at a fluid charge slightly exceeding the amount required to saturate the wick.
INTRODUCTION The influence of the number of layers and the working fluid
loads (fluid charges) on the performance of a screen mesh
Heat pipe heat exchangers (HPHXs) are heat transfer devices copper–water heat pipe was investigated by Kempers et al. [3].
that transfer heat through a phase change. Because of the effi- Heat pipes with a total length of 177.8 mm, an outer diameter of
cient heat transfer rate and conductivity of the HPHXs, these 9.53 mm, and three layers of screen mesh were used for the test.
have been used for cooling and heating purposes. Five different fluid loads, namely, 50%, 80%, 100%, 120%, and
An HPHX consists of heat pipe tubes that are filled with a 150% of the amount of water needed to saturate the wick struc-
proper working fluid. The working fluid absorbs the heat and ture, were chosen for this purpose. It was observed that with
evaporates in the evaporator section and condenses in the con- increasing fluid load, the thermal resistance of the heat pipe also
denser section. The condensed liquid is returned to the evapora- increased. In addition, the heat pipe containing the fluid load
tor with the aid of the capillary action in the horizontal configura- close to the amount needed to fully saturate the wick showed
tion of heat pipes and gravity in thermosyphon heat exchangers. small differences in the effective thermal resistance. Based on
The performance of a HPHX mainly depends on factors such as the results, it was established that the maximum heat transfer
the container, the wick structure, and the working fluid. in the underload heat pipes was lower than that in the overload
For a certain type of working fluid, the fluid charge or the heat pipes.
amount of working fluid plays a key role in the performance of a Payakaruk et al. [4] investigated the effects of dimensionless
HPHX. For instance, Martinez et al. [1] used 3.04 g of ammonia parameters such as Bond, Froude, and Weber numbers on the
as the working fluid in their research (i.e., slightly exceeding heat transfer rate of an inclined thermosyphon. A copper tube
the amount required to saturate the wick). In a study by Kaya filled with different working fluids under the filling ratios of
and Goldak [2], a heat pipe with completely saturated wick was 50%, 80%, and 100% was tested at the different inclinational
used for the numerical study of heat and mass transfer in the angles. Based on the experiments, it was found that the filling
heat pipes. ratio has no effect on the ratio of heat transfer characteristics at
any angle to that of the vertical position.
In a different research study by Wong and Kao [5], the effect
Address correspondence to Associate Professor Yat H. Yau, Department of fluid charge and wick size on the performance of a single
of Mechanical Engineering, University of Malaya, 50603 Kuala Lumpur,
tube horizontal heat pipe was investigated. A transparent heat
Malaysia. E-mail: yhyau@um.edu.my
Color versions of one or more of the figures in the article can be found online pipe with two layers of copper mesh as the wick structure was
at www.tandfonline.com/uhte. employed in the study. Three different fluid charges, including
1539
1540 Y. H. YAU AND M. AHMADZADEHTALATAPEH
HPHX
(Condenser)
Adiabatic
Section
4 3 Fan
Air
Outlet
Velocity Straightener
Traverse HPHX
Location (Evaporator) Heater
Sensor Line for
Heater Control Control Box
Box
PC
*:1,2,3 and 4 are
Downloaded by [Northwestern University] at 19:32 24 March 2015
Measuring points
Data
logger
80%, 100%, and 120% of the amount of water needed to saturate Experimental Setup
the wick structure, were selected for the tests. The heat load to
the evaporator section was increased stepwise from 20 to 45 W. It To study the thermal performance of the HPHX, a test rig
was found that the combination of a fine bottom mesh layer and a consisting of an air duct of 0.42 × 0.35 m2, an HPHX, an electric
fluid charge approximately saturating the wick could lead to the heater, and a variable-speed fan was set up, as illustrated in
optimum thermal characteristics. It was also seen that with the Figure 1.
underload fluid charge and wick with the fine mesh bottom layer,
partial dry-out occurred in the evaporator section. The effect of
the filling ratio on the steady-state heat transfer performance of Table 1 Design specifications of the two-row HPHX
a vertical two-phase closed thermosyphon was studied by Jiao
et al. [6]. For this purpose, a theoretical model based on the flow Evaporator and condenser 420 mm width × 350 mm height
patterns was developed. The filling ratio, which was defined as dimensions
Adiabatic length (mm) 180
the volume ratio of filled liquid to the whole two-phase closed Number of rows Two
thermosyphon, is set at 4.5%, 6.37%, 10.1%, 11.8%, 13.5%, Tube material Copper
15.2%, 18.5%, and 20.2% in this study. The study showed that Outer tube diameter (mm) 13.4
the proper range of filling ratio, which can maintain a two-phase Inner tube diameter (mm) 12.7
closed thermosyphon steady and effective, is between the upper Longitudinal tube spacing (mm) 27.5
Transverse tube spacing (mm) 31.75
boundary of 10% and the lower boundary of 9%. Vacuum level The vacuuming process was achieved at
These mentioned research studies mostly used a single-tube a vacuum level as low as 10−3 mbar
heat pipe and water as the working fluid, and they have studied Working fluid R-134a: Liquid density (1.013 bar and
the effect of fluid charge on the heat pipe itself rather than at 25◦ C): 1206 kg m−3,
the air side. To this end, this research has been performed and Boiling point (1.013 bar): –26.6◦ C,
Latent heat of vaporization (1.013 bar
the major objective was the experimental study of the effect of at boiling point): 215.9 kJ kg−1
different fluid charges on the performance of a typical two-row Wick structure:
HPHX at the air side. The HPHX was operating in the horizontal
Number of mesh 100 mesh per inch
configuration, and an ozone-friendly refrigerant, R-134a (HFC Number of layers 3
family), was used as the working fluid. Wire material Stainless steel 304 wire mesh
Wire diameter (mm) 0.11
Thickness (mm) 0.612
Wick porosity 0.67
EXPERIMENTAL DESCRIPTION
Fins:
The following subsections describe the experimental setup Material Aluminum corrugated
Type Wavy plate
as well as the experimental parameters examined in the present Thickness (mm) 0.15
research. The experimental setup will be described first and the Density 12 fin per inch
experimental parameters examined will be given next.
heat transfer engineering vol. 35 no. 18 2014
Y. H. YAU AND M. AHMADZADEHTALATAPEH 1541
Downloaded by [Northwestern University] at 19:32 24 March 2015
(a)
27.5 mm
35 cm
31.75
mm
42 cm 18 cm
(b)
Figure 2 (a) Fabricated HPHX, (b) Schematic of the HPHX and the arrangements of tubes.
The whole test rig was insulated by using a 13-mm insulation output signal from the sensors to degrees Celsius. The recorded
sheet to minimize heat exchange with the ambient environment. data were analyzed by DASYLab software. All the RTD sensors
The fresh air is preheated in the condenser section and then were calibrated in the temperature range of 10 to 50◦ C against
passes through an electric heater to be heated to the desired a laboratory Dry-Well calibrator with an accuracy of ± 0.1◦ C.
temperature. The warmed air then enters the evaporator section. An extra duct with a straightener was added to the evaporator
The two air streams flow through the HPHX in a counterflow outlet to determine the air velocity based on ANSI/ASHRAE
configuration. [7] requirements.
The design specifications of the HPHX are listed in Table 1. In order to establish the desired coil face velocities, the log-
An HPHX consists of 22 copper tubes in two rows of 11 tubes, Tchebycheff rule for rectangular ducts [7] was employed for the
designed and fabricated, as illustrated in Figure 2. The tubes velocity traverse study. For this purpose, the duct cross section
are in staggered configuration and three layers of stainless-steel was divided into 25 grid points and the mean duct air velocity
wire mesh were pressed against the internal tube wall as a wick was evaluated by measuring air velocity at the grid points. A
structure. The total length of each tube is 1020 mm, with 420 mm digital flowmeter with an accuracy of ±0.015 m s−1 was used
in the evaporator and condenser sections, and 180 mm for the to measure the air velocity.
adiabatic section. The desired air temperature of the evaporator
inlet was maintained by using a 5.5-kW electric heater with a
control box operating with an on/off position. Experimental Parameters
The dry-bulb temperature (DBT) of the various air states was
measured using resistance temperature detector (RTD) sensors, Parameters considered in this research were fluid charge, coil
and a data logging system was used to record and convert the face velocity, and evaporator inlet air temperature.
heat transfer engineering vol. 35 no. 18 2014
1542 Y. H. YAU AND M. AHMADZADEHTALATAPEH
According to Figure 1, process 3–4, the heat transfer occurs fectiveness is the most relevant parameter to characterize the
from air to the refrigerant, which leads to a temperature reduc- HPHX performance [10]. The effectiveness in Eq. (1) is defined
tion in the passing air stream. Therefore, this section can be as the ratio of the actual heat transfer to the maximum possible
used as a precooling process in heating, ventilation, and air con- heat transfer in the heat exchanger,
ditioning (HVAC) systems. For this purpose, the HPHX could Q act
be installed in air-conditioning systems as a way to precool ε= (1)
Q max
the supply of air before it reaches the cooling coils. As a re-
sult, the energy demand of the air-conditioning system will be and
reduced. Normally, in these situations, the HPHX evaporator
Q act = ṁ e (h 3 − h 4 ) (2)
section will be in direct contact with the ambient air; therefore,
to study the effect of different fluid charges on the HPHX per- and
formance, a range of temperatures close to the temperatures in
Q max = ṁ min (h 3 − h 1 ) (3)
Kuala Lumpur, Malaysia, were selected as the evaporator inlet
temperatures. The average daily temperature of Kuala Lumpur From Eqs. (1)–(3), the total effectiveness can be determined by
is at 23.1–33.5◦ C [8]. Coil face velocities representing those
ṁ e h3 − h4
that could typically occur in practice were established in the εtot = (4)
ṁ min h 3 − h 1
Downloaded by [Northwestern University] at 19:32 24 March 2015
The uncertainty in calculating the energy balance ratio For the condenser side:
(EBR) and sensible effectiveness was estimated as about 0.7% n
1− CCvc εc1
and 0.6%, respectively. The method used for the uncertainty 1−εe1
−1
evaluation is based on the calculation of the relative error εcn = n (15)
squares, referred to in the readings for T1 , T2 , T3 , and T4 , 1− CCve εc1
1−εc1
− Cc
Cv
adding them and extracting the square root (root sum square
method).
For Ce /Cv = 0 and Cc /Cv = 0 the preceding equations will
SIMULATION OF THE HPHX be in the form of
εen = 1 − (1 − εe1 )n (16)
The method using the effectiveness number of transfer units
(NTU) was employed to predict the heat transfer performance and
of the HPHX in the present research [11]. For constant specific
heat and heat transfer properties throughout the heat exchanger, εcn = 1 − (1 − εc1 )n (17)
the effectiveness can be written as [12] Then the overall effectiveness (total effectiveness) of the
Downloaded by [Northwestern University] at 19:32 24 March 2015
30
30
Sen sib le effectiven ess (%)
25
Sensible Effectiveness(%)
25
20
20
15
15
DBT= 27 (°C) 10 F.C = 80%
F.C = 90%
10 DBT= 29 (°C)
F.C = 100%
DBT= 31 (°C) 5 F.C = 110%
5 DBT= 33 (°C) F.C = 120%
DBT= 35 (°C) 0
0 25 27 29 31 33 35 37
80 90 100 110 120
Fluid Charge (%) Evaporator Inlet DBT (°C)
Figure 3 The influence of fluid charge on sensible effectiveness at face velocity Figure 5 The influence of evaporator inlet DBT on sensible effectiveness at
of 1.7 m s−1. face velocity of 1.7 m s−1.
by Chang [19] as
30
kf ψA
ke f f = ψ 2
A
(1 + A)2 ψ − πB(1 − k f /ks )/2 28
2[1 + A(1 − ψ)] 26
+ + [1 + A(1 − ψ)2 ] (28) Experimental
ψ − πB(1 − k f /ks )/4 Theoretical
24
with B = Dwir e /t, A = Dwir e /w, w is the opening width of 26 28 30 32 34 36
the mesh, Dwir e is the wire diameter, and t is the thickness of a Evaporator Inlet DBT (°C)
single layer of wire mesh. For the multiple layers, t = twick /nol. Figure 7 Experimental and theoretical comparison of evaporator outlet DBT
In Eq. (28) ψ is the constant parameter dealing with the contact to evaporator inlet DBT at face velocity of 1.7 m s−1.
condition of wires in the mesh. Then the thermal resistance of
the wick for N tubular heat pipes can be estimated by Shah and were transferred to the air passing through the condenser side).
Downloaded by [Northwestern University] at 19:32 24 March 2015
Sekulic [15] as There are three possible reasons for the EBR deviation from
ln(Do /Di )wick unity: possible intervening heat transfer between evaporator and
Rwick = (29) condenser sections, possible heat transfer to the ambient air
2πL wick N ke f f
because of insufficient insulation, and not having a uniform
After calculation of the effectiveness from Eq. (18) or (19), temperature profile at the measuring stations because of the
the outlet temperature of the evaporator was obtained from the incomplete mixed air.
following equation [14]: For checking any possible intervening heat transfer between
Te,outlet = Te,inlet − εtot (Te,inlet − Tc,inlet ) (30) the evaporator and condenser sides and any possible heat transfer
to the surrounding air, the intervening heat transfer test was
The comparisons between the experimental results and the- done with zero fluid charge for all the face velocities in the
oretical values were made for the heat pipes that were under the temperature range of study. It was found that for all the tests,
100% fluid charge (i.e., the saturated wick). the maximum temperature difference between the air streams in
the evaporator and condenser sections was 0.1◦ C. Therefore, the
heat transfer through conduction of tubes and heat transfer to the
RESULTS AND DISCUSSION surrounding air were negligible. It was obvious that incomplete
mixed air (not uniform) at the measuring points caused the
The energy balance ratio (EBR) is defined as the energy deviation of the EBR from unity.
extracted from the air passing through the evaporator divided The influence of fluid charge on the sensible effectiveness
by the energy transferred to the condenser side. The EBR values is shown in Figures 3 and 4, which are the representatives of
for the tests are tabulated in Table 2. It can be seen from Table 2 results for the range of conditions tested. It was observed that
that the EBR values for most of the tests examined are not the sensible effectiveness was increased as the fluid charge in-
equal to 1 (note: EBR value should be equal to unity if all the creased from 80% to 100% and then slightly decreased from
energy extracted from the air passing through the evaporator side 110% to 120%. These results imply that at the fluid charges
lower than the amount needed to saturate the wick (i.e., 100%),
30
Sen sib le Effectiven ess (%)
34
25
Evaporator Outlet DBT (°C)
20 32
15 30
F.C = 80%
10
F.C = 90% 28
F.C = 100%
5 F.C = 110%
26
F.C = 120% Experimental
0 Theoretical
25 27 29 31 33 35 37 24
26 28 30 32 34 36
Evaporator Inlet DBT (°C) Evaporator Inlet DBT (°C)
Figure 6 The influence of evaporator inlet DBT on sensible effectiveness at Figure 8 Experimental and theoretical comparison of evaporator outlet DBT
face velocity of 1.9 m s−1. to evaporator inlet DBT at face velocity of 1.9 m s−1.
34 35
30
32
25
30
20
28
15
26 10
Experimental
Theoretical
5 min
24
26 28 30 32 34 36 max
0
Evaporator Inlet DBT (°C) 70 80 90 100 110 120 130
Figure 9 Experimental and theoretical comparison of evaporator outlet DBT Fluid Charge (%)
to evaporator inlet DBT at face velocity of 2.1 m s−1. Figure 10 The influence of fluid charge on sensible effectiveness range
(min–max) at face velocity of 1.5 m s−1.
the heat transport between the evaporator and the condenser
through the working fluid is low. This might be due to the fact The influence of a higher DBT on the sensible effectiveness
Downloaded by [Northwestern University] at 19:32 24 March 2015
that although thermal resistance is low at fluid charges lower was not studied since the main objective of the present research
than 100%, nevertheless, the amount of working fluid (i.e., re- was to find out the optimum fluid charge in the temperature
frigerant) being insufficient to saturate the wick caused low heat range of 27–35◦ C for the purpose of future research.
transfer in the heat pipe. As the fluid charge increases, the per- Evaporator outlet temperatures were calculated from Eq. (30)
formance of the HPHX gets better because of enough liquid in and compared with the experimental data, as shown in Fig-
the heat pipes. When the fluid charge reaches to a level of over- ures 7–9 at three representative face velocities. The compari-
load (i.e., 120%), the sensible effectiveness slightly decreases. son of the experimental data and theoretical values indicates
This may be because of the fact that when the fluid charge is that there is an acceptable agreement between the experimental
significantly more than the amount needed to saturate the wick, data and theoretical values with a maximum deviation of 3%.
it causes the evaporator to flood and subsequently disturbs the Moreover, the uncertainty of recorded data for the evaporator
evaporation and condensation processes of the working fluid. outlet temperature based on the RTD sensor accuracy indicates
Figures 5 and 6 show the effect of the evaporator inlet DBT uncertainty about 1% using the root sum square method. The
on the HPHX sensible effectiveness. It is evident that for fluid uncertainty of the experimentally measured evaporator outlet
charges lower than the amount needed to saturate the wick, temperatures is shown as the error bands in Figures 7–9.
the sensible effectiveness was reduced as the evaporator inlet The sensible effectiveness range, which was the main purpose
DBT increased. In other words, the heat transfer capability of of the present experimental research, is tabulated in Table 3,
the HPHX was diminished corresponding with the increase of which shows the sensible effectiveness range (min–max) for the
the evaporator inlet DBT. This is because of the fact that by face velocities in the temperature range of the study.
increasing DBT, the heat flux to the container increases and For convenience, the reference for sensible effectiveness
since thermal resistance in these amounts of fluid charges (80% ranges (min–max) for two representative face velocities are pre-
and 90%) is lower than the other fluid charges, the possibility of sented in Figures 10 and 11. As can be seen from the figures, the
the dry-out phenomenon in the evaporator can be expected. As sensible effectiveness has the optimum amount at 110% fluid
a result, the evaporator works with a shorter effective length and charge. In other words, the optimum sensible effectiveness of
its performance declines. At higher fluid charges, the effect of
the evaporator inlet DBT on the sensible effectiveness was not 25
significant and the sensible effectiveness was almost constant in
Sensible Effectiveness (%)
Coil face 10
velocity
(m s−1) F.C: 80% F.C: 90% F.C: 100% F.C: 110% F.C: 120%
5 min
1.5 10.37–21.21 17.05–25.99 26.09–28.07 26.04–28.8 23.16–26.6 max
1.7 8.26–18.23 16.19–22.59 24.81–26.78 24.77–27.44 22.52–26.9 0
1.9 7.7–16.55 14–21.59 21.98–25.27 22.23–26.22 20.42–23.91 70 80 90 100 110 120 130
2.1 6.71–16.67 11.05–20.26 22.81–24.84 22.23–25.13 20.86–23.97 Fluid Charge (%)
2.3 6.78–14.91 10.11–19.25 19.32–24.07 20.37–23.93 18.93–21.77
Figure 11 The influence of fluid charge on sensible effectiveness range
2.5 6.38–13.84 11.31–17.18 19.34–22.28 19.33–23.15 18.02–22.86
(min–max) at face velocity of 2.5 m s−1.
HPHX takes place when the heat pipes are filled with the work- a tube distance in a row in Eq. (22), mm
ing fluid slightly exceeding the amount required to saturate the A heat transfer area, m2
wick. B dimensionless parameter defined by Dwir e /t in Eq.
(28)
b distance between the tubes in two successive rows in
CONCLUSIONS
Eq. (22), mm
cp specific heat of the ambient air, J kg−1 K−1
In the present research, the effect of fluid charge on the perfor-
C heat capacity, J s−1 K−1
mance of a typical two-row horizontal HPHX was investigated.
D diameter, m
The HPHX was tested under different fluid charges that rep-
DBT dry bulb temperature, ◦ C
resented both underload and overload cases, and different face
EBR energy balance ratio
velocities in the range of 27–35◦ C for the evaporator inlet DBT.
F.C fluid charge,%
Inlet air temperature for the condenser was kept constant at 24◦ C
HPHX heat pipe heat exchanger
during the tests. It was found that in the temperature range of
h specific enthalpy, k J kg −1
the study, for all the face velocities, the sensible effectiveness
k thermal conductivity, W m−1 K1
was lower for the fluid charges under the amount required to
L length, m
Downloaded by [Northwestern University] at 19:32 24 March 2015
saturate the wick, and this may be due to the insufficient work-
ṁ mass flow rate, kg s−1
ing fluid to saturate the wick and possibility of a dry-out in the
NTU number of heat transfer units
evaporator section. At the higher fluid charges, a slight decrease
Nu Nusselt number
in the sensible effectiveness was observed, and this might be
N number of the tubes
due to the heat pipe flooding and consequently disturbing the
n number of rows
evaporation and condensation processes of the refrigerant. The
nol number of layers
comparison between the experimental data and simulated val-
Pr Prandtl number
ues for the saturated situation showed good agreement for the
Q heat transfer rate, W
evaporator outlet temperature. Based on the experimental re-
R thermal resistance, k W−1
sults, it was conformed that the optimum effectiveness of the
Re Reynolds number
copper-R134a HPHX can be achieved at a fluid charge slightly
RTD resistance temperature detector
exceeding the amount needed to saturate the wick.
T temperature, ◦ C
t thickness, m
ACKNOWLEDGMENTS U heat transfer coefficient, W m−2 ◦ C−1
V coil face velocity, m s−1
Special thanks are extended to Ding Lai Chet and Adrian w opening width of the mesh, mm
Liaw Wen Jye for their help during a critical period of the
project. Also, thanks are given to Prof. K. T. Joseph, scientific Greek Symbols
editor at ULPA, University of Malaya, for proofreading the
article. ε effectiveness
η fin efficiency
FUNDING δ fin thickness, m
α heat transfer coefficient, W m−2 K−1
The authors acknowledge the financial assistance of the ρ density, kg m−3
University of Malaya (UM), which awarded the PPP grant μ viscosity, N s m−2
PV074/2012A and the UMRG grant RG042/09AET to the ζ fin spacing, m
first author for research work to be conducted at University ψ constant parameter dealing with the contact condition of
of Malaya. In addition, special thanks are extended to Chabahar wires in the mesh
Maritime University (CMU) for the financial assistance pro-
vided to the co-author for research to be jointly conducted. Subscripts
Thanks are also extended to CREAM-CIDB for providing par-
tial financial support to the first author for conducting research act actual
work at University of Malaya. c condenser
cn condenser number of rows
NOMENCLATURE c1 single row condenser
e.s external surface
A dimensionless parameter defined by Dwir e /w in Eq. ef f effective
(28) e evaporator
heat transfer engineering vol. 35 no. 18 2014
1548 Y. H. YAU AND M. AHMADZADEHTALATAPEH
en evaporator number of rows [10] ANSI/ASHRAE, Method of Testing Air-to-Air Heat Ex-
e1 single row evaporator changers, ASHRAE, Atlanta, GA, Standard 84-1991,
f fluid phase 1991.
h. p heat pipe [11] Kays, W. M., and London, A. L., Compact Heat Exchang-
i inner ers Design, McGraw-Hill, New York, NY, 1984.
max maximum [12] Incropera, F. P., and DeWitt, D. P., Fundamentals of Heat
min minimum and Mass Transfer, 4th ed., John Wiley & Sons, New York,
o outer NY, 1996.
S solid phase [13] Azad, E., and Geoola, F., A Design Procedure for Gravity
sen sensible Assisted Heat Pipe Heat Exchanger, Heat Recovery Sys-
tot total tems, vol. 4, no. 2, pp. 101–111, 1984.
v vapor [14] Noie, S. H., Investigation of Thermal Performance of
an-to-air Thermosyphon Heat Exchanger Using -NTU
Method, Applied Thermal Engineering, vol. 26, pp.
REFERENCES
559–567, 2006.
[15] Shah, R. K., and Sekulic, D. P., Fundamentals of Heat
Downloaded by [Northwestern University] at 19:32 24 March 2015