You are on page 1of 10

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/225565653

Heat transfer and pressure drop of R-134a condensation in a coiled, double


tube

Article  in  Heat and Mass Transfer · June 2009


DOI: 10.1007/s00231-009-0484-y

CITATIONS READS

26 203

4 authors, including:

Mohamed Mosaad
Mansoura University
40 PUBLICATIONS   294 CITATIONS   

SEE PROFILE

All content following this page was uploaded by Mohamed Mosaad on 30 March 2017.

The user has requested enhancement of the downloaded file.


Heat Mass Transfer (2009) 45:1107–1115
DOI 10.1007/s00231-009-0484-y

ORIGINAL

Heat transfer and pressure drop of R-134a condensation


in a coiled, double tube
M. El-Sayed Mosaad Æ M. Al-Hajeri Æ
R. Al-Ajmi Æ Abo. M. Koliub

Received: 10 April 2008 / Accepted: 26 March 2009 / Published online: 9 April 2009
Ó Springer-Verlag 2009

Abstract An experimental study was carried out to dc Coil diameter (m)


investigate condensation heat transfer and pressure drop Dew Waterside Dean number Rew [(di - do)/dc]0.5
characteristics of R-134a in a coiled double tube oriented hfg Condensation latent heat (J/kg)
with its helix axis in the vertical direction. Measurements k Thermal conductivity (W/m °C)
were obtained at inlet pressure of 815 kPa for refrigerant M_ Mass flux (kg/m2s)
mass flux ranging from 95 to 710 kg/m2s and cooling water m_ cw Cooling water mass flow rate (kg/s)
Reynolds number varying from 1000 to 14000. Presented Nu Nusselt number ad/k
results illustrate the effects of refrigerant mass flux and p Pressure (kPa)
average condensation temperature difference on the con- Pr Prandtl number Cpl/k
densation heat transfer coefficient and pressure drop. Q_ L Condensation load (W) M_ r hfg
Comparison with relevant data from other sources indicates Q_ cw Heat rate absorbed by cooling water (W), defined by
a reasonable agreement. An empirical correlation was Eq. 1
obtained for predicting condensation heat transfer coeffi- Rt Thermal resistance of inner tube wall
cient. The present study may be considered of a practical 
(m2 °C/W)
and theoretical interest for the design of the helical double- Rerr Refrigerant Reynolds number, cf., Eq. 6
tube condensers using R-134a as the working fluid. Rew Water Reynolds number M_ w ðdo  di Þ=lw
T Temperature (°C)
Abbreviations Ts Refrigerant saturation temperature (°C)
CFC Chlorofluorocarbon Tcw Average cooling water temperature
HCFC Hydro chlorofluorocarbon (°C) (Tcwi ? Tcwo)/2
HTC Heat transfer coefficient xm Mean vapour quality

List of symbols Greek symbols


A Heat transfer surface area (m2) a Heat transfer coefficient (W/m2°C)
Cp Specific heat at constant pressure (J/kg °C) l Dynamic viscosity (kg/m s)
do Outer diameter of inner coil tube (m) q Density (kg/m3)
di Inside diameter of external coil tube (m) DP Refrigerant pressure drop across the test section
(kPa/m)
DTs Average vapour-to-water temperature difference
M. El-Sayed Mosaad is on leave from Mechanical Engineering (°C) (Ts - Tcw)
Department, Mansoura University, Egypt.
DTm Logarithmic mean temperature difference (°C),
M. El-Sayed Mosaad (&)  M. Al-Hajeri  R. Al-Ajmi  defined by Eq. 3
Abo. M. Koliub
Subscripts
Mechanical Power and Refrigeration Department, Faculty of
Technological Studies, P.O. Box 64268, 7045 Shuwaikh, Kuwait c Condensation
e-mail: mosaad77@hotmail.com w Water

123
1108 Heat Mass Transfer (2009) 45:1107–1115

cwi Inlet cooling water temperature of R-134a has a considerable effect on the
cwo Outlet cooling water condensation HTC and pressure drop. Yu et al. [14] carried
i Inlet or inner out experimental tests on condensation of saturated R-134a
l Liquid vapour in a helical pipe with 9.4-mm inner diameter for the
o Outlet/overall same limited mass flux range investigated by Kang et al.
s Saturation and Han et al. They proved that the helical pipe orientation
r Refrigerant significantly affects the condensation HTC. In a more
v Vapour recent work, Wongwises and Polsongkram [15] experi-
mentally investigated the two-phase flow condensation of
R-134a inside a helically coiled tube-in-tube heat exchan-
ger at different fixed saturation temperatures from 40 to
1 Introduction 50°C for high mass fluxes from 400 to 800 kg/m2s. They
compared their data with straight tube data from another
The depletion of atmospheric ozone layer by CFC and source indicating that at the same mass flux and test satu-
HCFC refrigerants has generated a worldwide concern ration temperature, the condensation HTC and pressure
reflected in a number of new international rules to safe the drop of the helical tube are higher by 33–55 and 29–46%,
earth atmosphere [1]. Therefore, some ozone-safe refrig- respectively, than those of the straight tube.
erants have recently been developed and introduced in Based on our knowledge, the few studies mentioned
many refrigeration and air conditioning systems. Among above on condensation of R-134a in helical pipes are the
those new alternative refrigerants is R-134a; the substitute only ones reported in the open literature. Therefore,
to CFC-12. The present paper deals with condensation heat available heat transfer and pressure drop data are still
transfer characteristics of R-134a in a helical annular pipe. scarce and cover narrow ranges of main controlling
Numerous experimental works were done to investigate parameters. Therefore, further experimental investigations
flow and heat transfer characteristics of R-134a condensation are still needed to build up a broad and more reliable
inside straight plain tubes (e.g., Yan and Lin [2], Coleman database required for the optimal design of helical double-
and Garimella [3], and Jung et al. [4]). Other studies exam- tube condensers using R-134a as the working fluid.
ined the effects of enhanced tube surfaces (e.g., Samuel and Therefore, the present experimental work has investigated
Maltais [5], Liu [6], Nualboornueng [7, 8]). condensation heat transfer and pressure drop characteristics
Contrary to the large number studies conducted on of saturated R-134a vapour in a double-pipe helical coil for
condensation of R-134a inside straight tubes with smooth a wide mass flux range from 95 to 710 kg/m2s.
and enhanced surfaces, only few works were done on the
helical tubes, which are considered of a higher heat transfer
performance compared with the straight tubes. The sec- 2 Experimental apparatus
ondary flow created in the helical tube by the centrifugal
force due to its curvature mixes the two phases of con- A test facility has been built to investigate the condensation
densing fluid, and enhances the heat transfer. Therefore, heat transfer and pressure drop characteristics of some new
helically coiled tube-in-tube heat exchangers are used in refrigerants. The refrigerant-134a was the one tested in this
many engineering applications due to their high heat work. A schematic diagram of this test facility is shown in
transfer performance and volume compactness. Fig. 1. The system consists mainly of three closed fluid cir-
Unfortunately, most studies on the helical tubes were culating loops, a test section, and a data acquisition system.
conducted on the single-phase liquid-to-liquid heat transfer The three closed fluid loops are the refrigerant loop, the hot
(e.g., Kumar et al. [9], Rennie and Raghavan [10]). Only water loop and the cooling water loop. A detailed description
few studies have recently been reported on the two-phase of these main system components is given below.
heat transfer of R-134a condensation inside helical tubes.
Uddin et al. [11] experimentally proved that the conden- 2.1 Refrigerant loop
sation HTC of R-134a in a helical tube enhances with the
decrease of coil and tube diameters. Kang et al. [12] It contains a refrigerant storage tank, a refrigerant pump, a
experimentally investigated R-134a condensation in a filter, a coiled double-tube evaporator, an auxiliary elec-
helical tube of 12.7-mm inner diameter for mass flux trical heater, a test section, an air-cooled post-condenser, a
ranging from 95 to 400 kg/m2s. They found that the con- flow meter, and a number of control and relief valves. Sight
densation HTC and pressure drop of R-134a are higher glasses are installed before and after the evaporator and test
in the helical tube than in an equivalent straight tube. section to identify the phase state of flowing refrigerant
Han et al. [13] found that the condensation saturation at these locations. A variable speed pump drives the

123
Heat Mass Transfer (2009) 45:1107–1115 1109

Fig. 1 Schematic diagram of T


test apparatus
T
P

Test Section
Cold –Water
Thermostat
Cold Water
Flow T

P
T

Electrical Heater
Post Condenser
W

Refrigerant
T P Flow

Storage
Tank p
T T
Ref. Pump
Evaporator

T
T

Thermostat
Hot –water
W Watt Meter Filter

Hot water
Sight Glass
T Thermocouple
Flow Meter
P Pressure Gauge Pump

refrigerant from the storage tank into the inner tube of test section layout is presented in Fig. 2. The inner
evaporator. A bypass system is built around the pump to (refrigerant) tube is a copper tube with 9.54-mm outer
regulate the flow rate. diameter and 7.39-mm inner diameter. The external tube is
also made from copper with 19.05-mm outer diameter and
2.2 Heating water loop 16.92-mm inner diameter. The coil consists of nine turns
with 216-mm outer diameter and 25.6-mm pitch. The heat
This loop supplies the evaporation load to the evaporator. It transfer surface area of this test section is 0.18 m2. The
consists of a 710-l hot-water thermostat provided with cooling water flows upwards through the test section
three 1,500-W electrical heaters. A 1,200-W centrifugal annulus with the refrigerant flowing downwards in the
pump provided with bypass to control the flow rate drives inner tube. A post-air-cooled condenser is installed after
the heating water into the evaporator annulus to evaporate the test section to cool down the returning refrigerant to
the refrigerant flowing inside.

2.3 Cooling water loop

It removes the condensation load from the test section. This


loop consists of a 710-l cold-water thermostat provided
with air-cooled refrigeration unit of cooling capacity of
7 kW. A 1,200-W centrifugal pump circulates the cooling
water through the test section annulus to condense the
refrigerant flowing in the inner tube. A bypass system is
built around the pump to regulate the water flow rate.

2.4 Test section

It is a standard double-tube helical coil of 3-m length


mounted with its helix axis in the vertical direction. The Fig. 2 Test section

123
1110 Heat Mass Transfer (2009) 45:1107–1115

nearly its initial temperature in the storage tank. This is to B±5%. During the test, the inlet and outlet temperatures of
avoid heat storage in the system. water and refrigerant as well as the difference between
evaporation and condensation loads are displayed to
2.5 Measurement instruments ascertain when steady state conditions are achieved. The
refrigerant states at the test section inlet and outlet,
The locations of the measurement instruments used are respectively, can be recognized through the installed slight
indicated by circular symbols in the facility layout pre- glasses, and with the help of the temperatures and pressures
sented in Fig. 1. Copper-constantan thermocouples from displayed continuously at these locations during the test by
T-type, calibrated in the temperature range 10–60°C against the data acquisition system.
a standard digital thermometer of ±0.1°C uncertainty, are After the test, the recorded data were filtered to select
fixed at the inlet and outlet of both the evaporator and test only those of slight inlet superheat and exit subcooling. In
section to measure the inlet and outlet temperature of both this filtration process, the refrigerant temperatures mea-
the refrigerant and water. Three turbine flow meters with sured at the test section inlet and outlet are compared with
±0.4% uncertainty are used for measuring the flow rates of the corresponding saturation temperature predicted as a
the refrigerant, cold water and hot water. The measuring function of the measured pressure via properties software.
range is 2–30 l/min for the water meters and 0.2–2 l/min for When calculated inlet superheat or outlet sucooling is
the refrigerant meter. Absolute pressure gauges with reso- found outside the range ±0.5°C, the data point is elimi-
lution of ±5 kPa are installed at the top of storage tank, as nated. In addition, as the inlet pressure fluctuates slowly
well as at the inlet and outlet of test section. Two additional during the test, the data of condensation inlet pressur-
pressure transducers of ±0.2% accuracy are connected e = 815 ± 5 kPa are only evaluated.
across the test section to measure the refrigerant pressure In this work, a series of test runs were conducted at inlet
drop. The test rig is thermally insulated from surroundings pressure of 815 kPa (equivalent to R-134a saturation
by a 40-mm thick glass fibre layer. temperature of 32°C). The measured data cover refrigerant
mass flux ranging from 95 to 710 kg/m2 s and cooling
water Reynolds number varying from 1000 to 14000 for
3 Experimental procedure average cooling water temperature between 12 and 20°C.

At first, the refrigerant loop is evacuated and then charged


by a small amount of R-134a. This charging process fol- 4 Data reduction
lowed by a vacuum process is repeated two times to reject
all air and gases. After a leak inspection, a proper amount of The overall heat transfer coefficient between the water and
R-134a is charged into the loop. The coolant water is cooled refrigerant sides can be calculated from the cooling load
to a preset temperature in the range 5–10°C, while the absorbed by the coolant water in the test section as
heating water is heated to a preset temperature in the range
ao ¼ Q_ cw =ðAo :DTm Þ ð1Þ
40–60°C. The test is started by turning on the refrigerant
pump, hot-water pump and cold-water pump. Now, the The symbol Ao is the heat transfer surface area, DTm is
desired refrigerant flow rate is adjusted. In the same time, the logarithmic mean temperature difference between the
the hot water flow rate is regulated until the refrigerant water and refrigerant sides, and Q_ cw is the rate of heat
leaves the evaporator as a saturated vapour. The electrical absorbed by the cooling water in the test section, which is
heater power is controlled to superheat slightly the refrig- defined by
erant vapour by \1°C before entering the test section to
Q_ cw ¼ m_ cw Cpcw ðTcwo  Tcwi Þ ð2Þ
make it free from suspended liquid droplets. The cold-water
flow rate is gradually varied until a full condensation occurs where m_ cw , Cpcw, Tcwo, and Tcwi are the cooling water mass
and refrigerant leaves the test section with a slight subco- flow rate, water specific heat at constant pressure, and
oling \1°C. Once steady-state test conditions are attained, cooling-water temperatures at the test section outlet and
the readings of temperature, flow rate and pressure are inlet, respectively. Here it is important to point out that
recorded by data acquisition system ‘‘WebDAQ/100’’ for a Eq. 2 yields results more accurate than those calculated
period time of 3 min. The test can be repeated to conduct a from multiplying the refrigerant mass flow rate by the
new run with a different refrigerant flow rate. condensation latent heat with taking into account the slight
In all test runs, steady-sate conditions are considered superheat and subcooling at the test section inlet and exit,
attained when the difference between the evaporation load, respectively. This is because the measurement stability and
gained in the evaporator and auxiliary electrical heater, and accuracy are higher on the waterside of single liquid phase
the condensation load absorbed in the test section is found than on the refrigerant condensation side of two phases.

123
Heat Mass Transfer (2009) 45:1107–1115 1111

The difference between the two results was found about 5 Results and discussion
±3%.
The circulated refrigerant is considered of slight super- All test runs were conducted at inlet pressure of
heat at the test section inlet and slight subcooling at the 815 ± 5 kPa (equivalent to refrigerant mean saturation
exit, thus, the effect of a single-phase heat transfer can temperature of 32°C) for refrigerant mass flux varying
be neglected. Hence, the logarithmic mean temperature from 95 to 710 kg/m2s at fixed average vapour–water
difference can be approximated by temperature difference, DTs between 12 and 20°C. The
DTm  ½ðTro  Tcwi Þ  ðTri  Tcwo Þ=lnððTro  Tcwi Þ= results deduced from measured data are presented in
Figs. 3, 4, 5, 6, 7, 8 and 9.
ðTri  Tcwo ÞÞ ð3Þ
Rer
where Tri and Tro are, respectively, the refrigerant satura-
400 800 1200 1600 2000 2400 2800
tion temperatures at the test section inlet and exit, which 7 7
are defined according to the measured inlet and outlet
∆Ts C o

refrigerant pressures. The difference between these two ∆Ts : 12-20 oC


6 12 6
pressures represents the refrigerant pressure drop across the 14
17
test section. 5 20 5
Substituting Eqs. 2 and 3 into Eq. 1 yields the overall
heat transfer coefficient relation:

QL (kW)
4 4
m_ cw Cpcw
ao ¼ f lnððTro  Tcwi Þ=ðTri  Tcwo ÞÞ;
Ao ð4Þ 3 3
f ¼ ½1 þ ðTro  Tri Þ=ðTcwo  Tcwi Þ1
2 2
The condensation heat transfer coefficient, ac, can be
calculated from
1 1
1 1 1
¼   Rt ð5Þ
Ai ac Ao ao Ao acw 0 0
0 100 200 300 400 500 600 700 800
where acw, Ai and Rt are the waterside heat transfer coef-
Mr (kg/m2 s)
ficient, inside surface of the inner tube, and tube wall
thermal resistance, respectively. Fig. 3 Condensation load versus refrigerant mass flux
The term 1/acw in Eq. 5 is calculated by using the cor-
relations of the helically coiled tube proposed by Garimella Rer
et al. [16] for the laminar flow and those found by
400 800 1200 1600 2000 2400 2800
Gnielinski [17] for the transition and turbulent flows. The 300
laminar flow correlation is valid for water Dean number,
Dew \ 350, the transition correlation is applied for
350 \ Dew \ 800, while the turbulent flow correlation is 250
used for Dew [ 800. Kang et al. [12] and Han et al. [13]
15%
used the same correlations to predict the waterside heat 200
transfer coefficient in their experiments of similar test
h fg (kJ/kg)

sections. For more details on these correlations, one can


150
return to [12]. Validity of these correlations was also tested
in the present investigation. The validation test was con- -15%
ducted on water flowing in both the internal coil tube and 100 ∆Ts °C
12
annulus. The waterside heat transfer coefficients deduced 14
from the Wilson plot data at different mass fluxes were 50
17
20
compared with the prediction of these correlations. The
comparison indicated that these correlations predict the
0
experimentally deducted values within ±5%. 0 100 200 300 400 500 600 700 800
An error analysis executed by employing the sequence (kg/m2s)
Mr
disturbances method of Moffat [18] indicates that con-
densation and overall heat transfer coefficients have Fig. 4 Experimentally calculated condensation latent heat versus
relative uncertainties of around ±20 and 15%, respectively. refrigerant mass flux

123
1112 Heat Mass Transfer (2009) 45:1107–1115

Rer Rer
400 800 1200 1600 2000 2400 2800
400 800 1200 1600 2000 2400 2800
7000
7000
∆Ts oC o
12
∆ Ts = 12 C
6000 14 6000
17
20
5000
5000
αc (W/m2 oC)

α c (W/m2 oC)
4000
4000

3000
3000

2000
2000
Present data
Wangwises & Polsongkram : Helical tube
1000 Cavallini et al.: Straight tube
0 100 200 300 400 500 600 700 800
1000
Mr (kg/m2s) 0 100 200 300 400 500 600 700 800
Mr kg/m2 s
Fig. 5 Effect of refrigerant mass flux on condensation HTC at
different DTs
Fig. 7 Comparison of present average condensation HTCs with those
from other studies
9000
8000 Rer
7000 400 800 1200 1600 2000 2400 2800
24
6000
Present heical tube
21 Han et al. helical pipe
α c (W/m2 oC)

5000 Cavallini et al.: straight tube


18
4000
15
∆P (kPa / m)

Mr (kg/m2s)
3000 700 12
500
300
9

2000 6
10 12 14 16 18 20 22
∆ Ts oC
3
Fig. 6 Effect of average condensation temperature difference on
condensation HTC at various mass fluxes 0
0 100 200 300 400 500 600 700 800
Figure 3 illustrates the effects of the refrigerant mass 2
M r (kg/m s)
flux on the condensation load QL calculated by Eq. 2 for
different DTs. The condensation load increases approxi- Fig. 8 Pressure drop as a function of refrigerant mass flux
mately linear with the increase of mass flux. This indicates
that the refrigerant mass flux should be increased in order The experimentally calculated latent heat is plotted
to increase the condensation load. The displayed results versus the refrigerant mass flux in Fig. 4. The experimental
also show that the condensation load is not affected sig- hfg is calculated by dividing the cooling load calculated by
nificantly with the change in DTs. Eq. 2 over the measured refrigerant mass flow rate. The

123
Heat Mass Transfer (2009) 45:1107–1115 1113

800 observed by Honda et al. [21] among others. This may be


due to the increase in the condensate layer thickness, the
700
+ 20%
main thermal resistance on the tube side facing the
refrigerant, with the increase in DTs. At a fixed condensa-
tion temperature, when the cooling water temperature
Predicted Nusselt number

600
decreases, the wall temperature also decreases. Hence, both
500 the wall subcooling (=(Ts - Tw)) and condensation tem-
- 20 % perature difference (DTs = (Ts - Tcw)) increase. Thus,
400 when DTs rises, the wall subcooling, the temperature
potential driving the condensation process, also rises
300 resulting in increasing condensate layer thickness and
decreasing condensation HTC. Jung et al. [4] reported a
200 similar explanation for the effect of wall subcooling on
condensation HTC.
100 A comparison of present data with relevant data from
other studies is shown in Fig. 7. These external data of
0 Wongwises and Polsongkram [15] were measured in a
0 200 400 600 800
Experimental Nusselt number
5.7-m long helical tube of six coils with inner tube of 8.3-
mm inner diameter at test saturation temperature of 40°C
Fig. 9 Comparison of present data and proposed correlation (6) and mass flux from 400 to 800 kg/m2s. The compared
data of Wongwises and Polsongkram are average con-
densation HTCs calculated from measured local values.
solid line plotted in the graph represents the exact latent Here, it is important to point out that in the present
heat of R-134a at the condensation pressure of 815 kPa. investigation; the variation of vapour quality was from 1
The displayed results show how much the present mea- at the test section inlet to 0 at the exit. Thus, the present
surements are well calibrated. The deviation between the data are considered of mean vapour quality = 0.5.
experimental and exact values is of an average value of Therefore, only data from this external source measured at
±12%. The relatively higher discrepancy of ±15% noted at low condensation heat flux of 5 kW/m2 and mean quality
the lowest and highest mass fluxes may be attributed to the of 0.5 are compared with present data of low DTs = 12°C
relatively higher measurement errors encountered fre- in Fig. 7. This comparison shows that the data of Won-
quently at these extreme flow conditions [19, 20]. This gwises and Polsongkram intersection the present data.
higher discrepancy at the lowest and highest mass fluxes Uddin et al. [11] experimentally explored that condensa-
may explain the slight non-linear dependence between QL, tion HTC of R-134a in a helical tube enhances with the
and M_ r shown in Fig. 3 at the two ends of the plotted data decrease in coil and tube diameters. Wongwises and
set. Polsongkram [15] experimentally found that the average
Figure 5 shows the variation in the condensation HTC, HTC decreases with the increase in test saturation tem-
ac, with the refrigerant mass flux, M_ r ; at various conden- perature. In view of this, the discrepancy between the two
sation temperature differences, DTs. It is evident that at the compared results may be attributed to differences in the
same value of DTs, the condensation HTC increases with test saturation temperature, measurement accuracy and
the increase of M_ r : For instance, at DTs = 12°C, ac test section dimensions. It is considered of a practical and
enhances by a factor of about two as M_ r rises from 100 to theoretical interest to compare the present data with
700 kg/m2s. In the fact, for a high refrigerant mass flux, the straight tube data. For this purpose, data measured by
vapour velocity is also high. Hence, the vapour shear on the Cavallini et al. [22] in a straight plain tube at test satu-
condensate layer formed on the tube wall becomes high ration temperature of 40°C are plotted in the same Fig. 7.
resulting in a high condensation HTC. In addition, as the Here, it is important to point out that the data of Cavallini
mass flux rises, the secondary flow created by the centri- et al. are average values calculated from local data mea-
fugal force due to the tube curvature becomes more sured at mean vapour quality of 0.5. The comparison
effective in mixing the two refrigerant phases, and indicates that the helical tube gives a relatively higher
enhances the condensation HTC. condensation HTC by about 30–50% compared with the
The results of Fig. 6 show that condensation HTC de- straight tube. This may be attributed to the fact that the
pendences on average condensation temperature difference condensation flow mechanism in a helical tube is different
DTs. At the same mass flux, ac decays with a rise in DTs. from that in a straight tube. The secondary flow created in
Similar trend for the effect of wall subcooling was the helical tube due its curvature increases the dynamic

123
1114 Heat Mass Transfer (2009) 45:1107–1115

interaction between the vapour phase flowing in the tube 6 Conclusions


core and the condensate film formed on the wall. This
means that the secondary flow generated in the helical In this study, the condensation heat transfer and pressure
tube acts as a turbulence source, which increases the drop characteristics of saturated R-134a vapour in a coiled
interfacial heat transfer surface between the two fluid double tube were investigated at inlet pressure of
phases and, consequently, enhances the condensation heat 815 ± 5 kPa. All test runs were carried out under the
transfer coefficient compared with an equivalent straight condition that the refrigerant enters the test section as
tube. saturated vapour and leaves as saturated liquid. The
The pressure drop of R-134a across the test section is obtained results show that the condensation and overall
plotted versus the refrigerant mass flux in Fig. 8. It is clear heat transfer coefficients increase with the increase of
that the pressure drop rises by a factor of about two as M_ r refrigerant mass flux, and decrease with the rise of con-
increases from 100 to 710 kg/m2s. A comparison of present densation temperature difference. Similar to the behaviour
data with other relevant data measured by Han et al. [13] in of condensation HTC, the pressure drop across the test
a helical tube of 9.4-mm inner diameter at a relatively section rises with the increase of refrigerant mass flux.
higher saturation temperature of 45°C is displayed in the Condensation Nusselt number correlation was obtained by
same graph. The comparison indicates that the present data fitting experimental data set of 283 points within ±20%.
are somewhat higher than those of Han et al. Zaki et al. However, further investigations are still needed to extend
[23] experimentally proved that the pressure drop decays as this correlation to account for the effects of condensation
the condensation temperature rises. It is also considered of pressure and coil dimensions. In addition, studying the flow
a practical interest to compare the present helical-tube data and condensation heat transfer characteristics of R-407C in
with straight-tube data. For this purpose, the total pressure helical double-tube condensers can be recommended for a
drops per 1-m tube length measured by Cavallini et al. [22] future work.
in a straight smooth tube at test saturation temperature of
40°C and mean vapour quality of 0.5 are plotted in the Acknowledgments This work was supported by the Public
Authority for Applied Education and Training (PAAET) of Kuwait
same figure. The comparison indicates that the pressure through a research grant number: Ts 03-06. This financial support is
drop in the helical tube is much higher than that in the greatly appreciated.
straight tube because the flow pattern in a helical tube is
different from that in a straight tube. For the same mass
flux and tube diameter, the secondary flow generated in a
References
helical tube creates swirls and turbulence raising the
pressure drop compared with a straight tube. 1. Copenhagen Amendments to Montreal Protocol, 25 Nov 1992
The mean condensation Nusselt numbers, Nuð¼ac di =kl Þ, 2. Yan Y-Y, Lin T-F (1999) Condensation heat transfer and pressure
calculated for 283 data points, could be fitted within ±20% drop of refrigerant R-134a in a small pipe. Int J Heat Mass Transf
by 42:697–708
3. Coleman JW, Garimella S (2003) Two-phase flow regimes in
"   # round, square and rectangular tubes during condensation of
Nu DTs 0:9 refrigerant R-134a. Int J Refrig 26:117–128
¼ 6:39 1  0:85 ;
 0:4 1=3 Ts 4. Jung D, Song K, Cho Y, Kim S (1972) Flow condensation heat
Re Prl transfer coefficients of pure refrigerants. Int J Refrig 26:4–11
DTs 5. Samuel MS, Maltais H (2000) Experimental investigations of two
0:3  Ts  0:6
for ð6Þ phase flow condensation inside enhanced surface tubing. Appl

1200  Re  95000 Therm Eng 20:1113–1126
  pffiffiffiffiffiffiffiffiffiffiffi 6. Liu X (1997) Condensing and evaporating heat transfer and
where Re¼M_ r ð1xm Þþxm ql =qv di =ll and Pr¼Cpl ll =kl : pressure drop characteristics of HCF-134a and HCF-22. ASME J
Heat Transf 119:158–163
The symbol DTs is the average condensation tempera-
7. Nualboornueng T (2004) Two-phase condensation heat transfer
ture difference, and xm refers to the mean vapour quality. coefficients of HFC-134a in smooth and micro-fin tubes at high
The above helical-tube correlation is based on own data, mass flux. Int Commun Heat Mass Transf 31:991–1004
and does not explain for the effects of condensation 8. Nualboornueng T, Wongwises S (2003) Two-phase flow pressure
drop of HFC-134a during condensation at high mass flux in
pressure and coil dimensions. Therefore, other studies are
smooth and micro-fin tubes. Int Commun Heat Mass Transf
still need to extend this correlation to account for these 30:577–590
effects. Figure 9 displays the comparison between present 9. Kumar R, Gupta A, Vishvakarma S (2005) Condensation of
experimental and predicted Nusselt numbers. Here, it is R-134a vapour over single horizontal integral-fin tubes: effect of
fin height. Int J Refrig 28:428–435
important to point out that correlation (6) is only valid for
10. Rennie JT, Raghavan GSV (2005) Experimental studies of a
the studied configuration and cannot be considered as double-pipe helical heat exchanger. Exp Therm Fluid Sci J
universal. 29:919–924

123
Heat Mass Transfer (2009) 45:1107–1115 1115

11. Uddin M, Patrik J, Newlin A (1994) Variation of local conden- 18. Moffat RJ (1988) Describing uncertainties in experimental
sation heat transfer for R-134a in helically coiled tubes. In: results. Exp Therm Fluid Sci J 1:3–7
International mechanical engineering congress and exhibition, 19. Cavallini A, Del Col D, Doretti L, Longo GA, Ressetto L
Winter Annular Meeting, Chicago, pp 6–11 (2000) Heat transfer and pressure drop during condensation
12. Kang HJ, Lin CX, Ebadian MA (2000) Condensation of R-134a of refrigerants inside horizontal enhanced tubes. Int J Refrig
flowing inside helical pipes. Int J Heat Mass Transf 43:2553–2564 23:4–25
13. Han JT, Lin CX, Ebadian MA (2000) Experimental investigation of 20. Longo GA, Gasparella A, Sartori R (2004) Experimental heat
condensation heat transfer of refrigerant R-134a in helicoidal pipe. transfer coefficients during refrigerant condensation inside her-
In: Proceeding of ASME heat transfer division, HTD-4, pp 95–101 ringbone-type plate heat exchangers with enhanced surfaces. Int J
14. Yu B, Han JT, Kang HJ, Lin CX, Awwad A, Ebadian MA (2003) Heat Mass Transf 47:4125–4136
Condensation heat transfer of R-134a flow inside helical pipes at 21. Honda H, Takata N, Takamatsu H, Kim JS, Usami K (2002)
different orientations. Int Commun Heat Mass Transf 30:745–754 Condensation of downward-flowing HFC134a in a staggered
15. Wongwises S, Polsongkram M (2006) Condensation heat transfer bundle of horizontal finned tubes. Int J Refrig 25:3–10
and pressure drop of HFC-134a in a helically coiled concentric 22. Cavallini A, Censi G, Del Col D, Doretti L, Longo GA, Ressetto
tube-in-tube heat exchanger. Int J Heat Mass Transf 49:4386–4398 L (2001) Experimental investigation on condensation heat
16. Garimella S, Richerds DE, Christensen RN (1998) Experimental transfer and pressure drop of new HFC refrigerants (R134a,
investigation of heat transfer in coiled annular ducts. ASME J R125, R32, R410A, R236ea). Int J Refrig 24:73–87
Heat Transf 110:329–336 23. Zaki M, Liu YZ, Dong ZF, Ebadian MA (1997) Condensation
17. Gnielinski V (1986) Heat transfer and pressure drop in helically heat transfer of R-134a in helical pipes. In: Proceeding of ASME
coiled tubes. In: Proceeding of international meeting on reactor heat transfer division, HTD-351, pp 141–148
heat transfer, Karlsruhe, pp 351–372

123

View publication stats

You might also like