Penentuan koefisien h

Diagram penentuan FT untuk Multipass 1-2 dan 1-4

Diagram penentuan FT untuk Multipass 2-4


 Counterflow Exchanger Co-Current

Beberapa nilai koefisien fouling

𝑾 𝒃𝒕𝒖
𝒉𝒅 ( 𝟐 ) 𝒉𝒅 ( )
𝒎 .𝑲 𝒉. 𝒇𝒕𝟐 .𝒐 𝑭

Distilled and Sea Water 11.350 2000

City Water 5680 1000

Muddy Water 1990 – 2840 350 - 500

Gases 2840 500

Vaporizing Liquid 2840 500

Vegetable and Gas oil 1990 350

Beberapa nilai koefisien perpindahan panas overall

𝑾 𝑾𝒃𝒕𝒖
𝑼( ) 𝑼 ( )
𝒎𝟐 . 𝑲 𝒉. 𝒇𝒕𝟐 .𝒐 𝑭

Water to Water 1140 – 1700 200 - 300

Water to Brine 570 – 1140 100 – 200

Water to Organic Liquids 570 - 1140 100 - 200

Water to Condensing Steam 1420 – 2270 250 - 400

Water to Gasoline 340 – 570 60 - 100

Water to Gas Oil 140 – 340 25 - 60


Water to Vagetable Oil 110 - 285 20 - 50

Gas oil to Gas oil 110 - 285 20 - 50

Steam to boilling Water 1420 – 2270 250 - 400

Water to Air (finned tube) 110 – 230 20 - 40

Light Organic to Light Organic 230 – 425 40 - 75

Heavy Organic to Heavy Organic 55 – 230 10 - 40