You are on page 1of 2

STANDARDS

Concrete specification and testing –


is BS EN 206 fit for purpose?
review belongs to the same population as B.1 states that the probability of
A new edition of BS EN 206, the that verified as conforming via conformity conforming concrete being rejected is
Standard for concrete specification assessment by the producer’. A translation only 1%; no figure is given for the
and testing, was published in of this clause into plain UK English would probability of the customer having to
December 2013(1). Does it address be helpful – one assumes it means ‘testing to accept non-conforming concrete.
previous criticisms(2,3)? Is the establish whether concrete supplied to site Annex J states that more stringent
new edition now ‘fit for purpose’? complies with the specification’. criteria may be applied in Spain because
Alasdair N Beal of Thomasons According to Cl. B.2, the ‘volume of of its legal requirement that the risk to
concrete under review’ for ‘identity testing’ customers of defective concrete being
reports. may be anything from a single batch to accepted should not exceed 50%.
400m³ of concrete. Very little is said about Therefore presumably under the
sampling rates. According to Cl. B.3.1, if standard BS EN 206 rules the risk to the
S EN 206:2013 covers concrete from there is product control certification, one to customer of having to accept defective

B strength class C8/10 to C100/115


(characteristic cube strengths
10–115MPa).
six test results may be used for conformity
assessment:
• individual tests fci ≥ (fck – 4) MPa

concrete is more than 50%.
If one test per sample is acceptable for
producers, then it should also be
Cl. 3.1.5.4 defines concrete ‘characteristic • for a group of two to four tests fcm ≥ (fck acceptable for customers. Requiring
strength’ as the ‘value of strength below + 1) MPa, or group of five to six tests fcm customers to carry out twice as many
which 5% of the population of all possible ≥ (fck + 2) MPa). tests simply increases costs and
strength determinations of the volume of discourages testing.
concrete under consideration are expected Although concrete producers checking • On a small project with concrete from a
to fall’. This is a strangely abstract definition: concrete are permitted by Section 8 to only non-certified supplier, the requirement
instead of real strength measurements test one cube/cylinder from each concrete for a minimum of six tests regardless of
it is based on expected values of possible sample, if a customer wants to check the volume involved is simply absurd.
strength determinations. In addition, no concrete Annex B would require him to • The BS EN 206 compliance rules
lower limits are placed on the strength of the carry out twice as many tests – two cube/ appear to be based on analysis from
5% of tests that are allowed to fall below the cylinder tests from every concrete sample. ‘large number’ probability theory,
specified strength, so if a customer specifies No explanation is given as to why the where a small number of random
30MPa concrete and receives 20 batches requirement for customer tests is different samples is used to estimate the
with strengths of 30–45MPa and one batch from producer tests. characteristics of random variations in
of 20MPa, the supplier could claim that this Where the concrete has no product a quasi-infinite population. However,
complies with a specification. control certification, Cl. B.3.2 imposes concrete is delivered to construction
more stringent requirements for assessing sites in batches, so its strength
‘Volume of concrete under conformity: at least three test results are variations are ‘quantised’ and although
consideration’ and test criteria required and the strength requirements are: large variations are possible between
Most of the recommendations in BS EN 206 • individual tests fci ≥ (fck – 4) MPa batches, the variations within a batch
concern statistically based control criteria for • group of three to six tests fcm ≥ (fck + 4) of properly-mixed concrete are usually
concrete producers. According to Cl. 8.2.1.2, MPa. small. ‘Large number’ probability
concrete in continuous production by a theory does not apply in this situation
producer with product control certification Thus at least six cubes/cylinders must be unless the sampling rate is very low
shall be sampled at a rate of at least one per tested, even if only a single batch of concrete (1/10 or less)(5).
400m³, or per five production days or per is being considered. • The compliance rules ignore the effect
month (whichever is greatest). Test results of sampling rate on customer and
can be based on one test cube/cylinder per Analysis producer risk. If the entire concrete for
sample. The acceptance criteria are: The compliance rules in BS EN 206 have a project is assessed on the basis of a
• individual tests (fci ≥ (fck – 4) MPa) some odd features: single test result, or the combined
• tests are also assessed either in groups • As can be seen, the criteria for ‘identity results of a single group of test results,
of three (mean fcm ≥ fck + 4) MPa) or testing’ are more lenient than those for this creates a high risk for both the
groups of at least 15 (mean fcm ≥ fck + production control. They are also producer and the customer. However,
1.48σ) MPa, where σ is the standard lenient compared with past UK practice; these risks can be reduced by increasing
deviation). although the definition of the sampling rate. If every batch of
‘characteristic strength’ is similar to concrete is sampled and tested, so that
Annex B covers ‘identity testing’, in that in the old BS 5328(4), the allowable only good batches are accepted and bad
which clause B.1 states, ‘indicates whether limits on test results in BS EN 206 are batches rejected, the risk for both
the defined volume of concrete under generally 1MPa lower. The Note to Table producer and customer falls to 0%.

www.concrete.org.uk APRIL 2014 concrete 35


STANDARDS

Therefore with a high sampling rate, • When there is more than one test rules should be revised to take into account:
the risk for both producer and customer result, the rules mean that the entire • the difference between within-batch
is low. Reducing the sampling rate cuts concrete on a project may be rejected and between-batch strength variations
testing costs but for the producer it even if all the test results exceed the • the effect of different sampling rates on
increases the volume of concrete at risk specified strength (iii), (v), (viii), (x). risks to both customers and producers.
on a single decision and for the On the other hand, on another project
customer it increases the risk of concrete could be accepted even when The lower limit for individual test results
defective concrete being accepted. the results show that 10% or more was of 4MPa below characteristic strength is
• For the producer, a criterion based on below the specified characteristic too low, particularly for lower-strength
the mean of a group of test results strength (eg, iv, ix). concretes.
leads to a large volume of concrete • The rules for concrete from non- Assessment based on the average of
being put at risk on a single decision. certified suppliers give even stranger a group of test results puts an excessive
It can also lead to good batches of results: if there is only a single batch of volume of concrete at risk on a single
concrete with perfectly satisfactory test concrete, this would be rejected unless decision.
results being rejected because a bad the test results exceeded the specified Assessment based on the average of a
batch has been included in their strength by 4MPa (x). On a larger group of test results also creates a risk that
group. However, group criteria also project, concrete could be rejected good concrete may be rejected because a
mean that customers may be expected when the tests clearly show that all of low-strength batch has been included in
to accept bad batches of concrete if the concrete supplied exceeds the the group, or substandard concrete may be
they are assessed alongside other specified characteristic strength (xii). accepted because it has been assessed in a
better batches. On the other hand, on another project group that contains better batches. ●
concrete might be accepted even
Table 1 shows the results from the BS though the tests show that more than
EN 206 ‘identity testing’ assessment rules 5% fell below the specified
in various situations. As can be seen, strict characteristic strength (xi).
application of the BS EN 206 rules would
lead to some very peculiar decisions. Concluding remarks
• Where there is only a single batch of The concrete strength rules in BS EN 206
concrete (i, vi), the results are bizarre: are unsatisfactory. References
if the producer is certified, individual The definition of ‘characteristic strength’
test results 4MPa below the specified is abstract and impractical. The assessment 1. BRITISH STANDARDS INSTITUTION, BS EN 206.
Concrete. Specification, performance, production
strength are accepted. Therefore, rules in later parts of the code are not and conformity, BSI, London, 2013.
although Cl.3.1.5.4 only permits 5% consistent with the definition and can lead 2. TOPLIS, P. Concrete compressive strength testing –
defective concrete, under the BS EN to concrete that complies with the definition is the industry getting it right? The Structural
206 assessment rules concrete may be being rejected and concrete that does not Engineer, Vol.86, No.23/24, 2 December 2008,
pp.43.
judged ‘acceptable’ even when 100% of comply being accepted. 3. BEAL, A.N. Viewpoint: Concrete strength testing –
it is below the specified strength. If the The risk to the customer of substandard are the code writers getting it right? The Structural
specified strength is 10MPa, the concrete being deemed ‘acceptable’ is too Engineer, Vol.87, No.10, 19 May 2009, pp.12–13.
strength of the concrete that is high. This is recognised in Annex J, which 4. BRITISH STANDARDS INSTITUTION, BS 5328.
Concrete. Guide to specifying concrete. BSI,
accepted might be only 60% of what permits more stringent acceptance rules to London, 1997, superseded.
was specified. be used in Spain. 5. BEAL, A.N. Concrete cube strengths – what use are
• Some 400m³ of concrete in a structure It is unreasonable to require customers to statistics? ICE Proceedings, Vol.71, Issue 4, 1
could be accepted on the basis of a test two cubes/cylinders from each sample December 1981, pp.1037–1048 and Vol.73, Issue
2, 1 June 1982, pp.515–532, Institution of Civil
single test result 4MPa lower than the when producers are allowed to use single Engineers, London.
specified strength (ii, vii). tests. The statistical analysis of acceptance

Table 1 – Results from BS EN 206 ‘identity testing’ assessment rules

Certified Non-certified Specified No. of No. of Results (MPa) Pass/fail?


production production strength batches tests
(MPa)
(i) / 10 1 1 6 Pass
(ii) / 50 1 6 Pass
(iii) / 2 2 11, 10 Fail
(iv) / 50 2 7, 15 Pass
(v) / 5 5 10, 13, 11, 12, 13 Fail
(vi) / 30 1 1 26 Pass
(vii) / 50 1 26 Pass
(viii) / 2 2 30, 31 Fail
(ix) / 50 2 26, 36 Pass
(x) / 5 5 30, 34, 31, 32, 33 Fail
(xi) / 30 1 3 33, 34, 34 Fail
(xii) / 50 3 26, 36, 40 Pass
(xiii) / 5 5 30, 34, 40, 32, 33 Fail

36 concrete APRIL 2014 Find concrete on : pinterest.com/concretemag/boards

You might also like