Feasibility Analysis of The Positioning of Superconducting Fault Current Limiters For The Smart Grid Application Using Simulink and Simpowersystem
Feasibility Analysis of The Positioning of Superconducting Fault Current Limiters For The Smart Grid Application Using Simulink and Simpowersystem
Abstract—One of the most important topics regarding the ap- But, superconducting fault current limiter (SFCL) is inno-
plication of superconducting fault current limiters (SFCL) for up- vative electric equipment which has the capability to reduce
coming smart grid is related to its possible effect on the reduction fault current level within the first cycle of fault current [2]. The
of abnormal fault current and the suitable location in the micro
grids. Due to the grid connection of the micro grids with the cur- first-cycle suppression of fault current by a SFCL results in an
rent power grids, excessive fault current is a serious problem to increased transient stability of the power system carrying higher
be solved for successful implementation of micro grids. However, a power with greater stability [3].
shortage of research concerning the location of SFCL in micro grid Smart grid is the novel term used for future power grid which
is felt. In this work, a resistive type SFCL model was implemented integrates the modern communication technology and renew-
by integrating Simulink and SimPowerSystem blocks in Matlab.
The designed SFCL model could be easily utilized for determining able energy resources for the 21st century power grid in order
an impedance level of SFCL according to the fault-current-limita- to supply electric power which is cleaner, reliable, resilient and
tion requirements of various kinds of the smart grid system. In ad- responsive than conventional power system [4].
dition, typical smart grid model including generation, transmission One of the key elements of the smart grid is decentralization
and distribution network with dispersed energy resource was mod- of the power grid network into smaller grids, which are known
eled to determine the location and the performance of the SFCL.
As for a dispersed energy resource, 10 MVA wind farm was con- as micro grids, having distributed generation sources (DG) con-
sidered for the simulation. Three phase faults have been simulated nected with them. These micro grids may or may not be con-
at different locations in smart grid and the effect of the SFCL and nected with conventional power grid, but the need to integrate
its location on the wind farm fault current was evaluated. Conse- various kinds of DGs and loads with safety should be satisfied
quently, the optimum arrangement of the SFCL location in Smart [2]. However, newly emerging problems due to these integra-
Grid with renewable resources has been proposed and its remark-
able performance has been suggested. tions are also of severe nature and needs to be taken care of. Two
major challenges expected by direct connection of DGs with the
Index Terms—Fault current, micro grid, smart grid, supercon-
power grid are the excessive increase in fault current and the is-
ducting fault current limiter, wind farm.
landing issue which is caused when, despite a fault in the power
grid, DG keeps on providing power to fault-state network [5].
I. INTRODUCTION Up to now, there were some research activities discussing the
fault current issues of smart grid [6], [7]. But the applicability
C ONVENTIONAL protection devices installed for protec-
tion of excessive fault current in electric power systems,
especially at the high voltage substation level, are the circuit
of a SFCL into micro grid was not found yet. Hence, solving
the problem of increasing fault current in micro grids by using
SFCL technology is the main concern of this work. In this paper,
breakers tripped by over-current protection relay which has a
the effect of SFCL and its position was investigated considering
response-time delay that allows initial two or three fault current
a wind farm integrated with a distribution grid model as one of
cycles to pass through before getting activated [1].
typical configurations of the smart grid. The impacts of SFCL
on the wind farm and the strategic location of SFCL in a micro
Manuscript received August 02, 2010; accepted October 18, 2010. Date of grid which limits fault current from all power sources and has
publication December 03, 2010; date of current version May 27, 2011. This
work was supported by the research fund of Hanyang University (HY-2010-N). no negative effect on the integrated wind farm was suggested.
Gratitude is expressed to Higher Education Commission Government of Pak-
istan for sponsoring the studies of Mr. Umer Amir Khan. II. SIMULATION SET-UP
U. A. Khan, J. K. Seong, and S. H. Lee are with the Department of Elec-
tronics, Electrical, Control & Instrumentation Engineering of Hanyang Univer- Matlab/Simulink/SimPowerSystem was selected to design
sity, Ansan 426-791, Korea. and implement the SFCL model. A complete smart grid power
S. H. Lim is with the School of Electrical Engineering, Soongsil University,
(156-743)511 Sangdo-Dong, Dongjak-Gu, Seoul, Korea.
network including generation, transmission, and distribution
B. W. Lee is with the School of Electrical Engineering & Computer Science, with an integrated wind farm model was also implemented in it.
Hanyang University, Ansan 426-791, Korea (e-mail: bangwook@hanyang.ac. Simulink/SimpowerSystem has number of advantages over its
kr). contemporary simulation software (like EMTP, PSPICE) due
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. to its open architecture, a powerful graphical user interface and
Digital Object Identifier 10.1109/TASC.2010.2089591 versatile analysis and graphics tools. Control systems designed
1051-8223/$26.00 © 2010 IEEE
2166 IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, VOL. 21, NO. 3, JUNE 2011
Fig. 1. Power system model designed in Simulink/SimPowerSystem. Fault and SFCL locations are indicated in the diagram.
Fig. 3. SFCL performance evaluation graph indicating the relationship Fig. 4. Comparison of the wind farm fault currents for four SFCL locations in
between SFCL impedance and reduction in fault current. case of fault in distribution grid (Fault 1).
Fig. 7. Comparison of the reduction in wind farm fault current for four SFCL
installation scenarios.
Fig. 6. Comparison of the wind farm fault currents for four SFCL locations in
case of fault in transmission line (Fault 3).
TABLE I
PERCENTAGE CHANGE IN WIND FARM FAULT CURRENT DUE TO
SFCL LOCATIONS
are similar to what were observed in the case of distribution grid
(Fault 1) as explained in Section III-A.
Once again the best results are obtained when a single SFCL
is located at Location 3, which is the integration point of the
wind farm with the distribution grid.
[2] T. Jamasb, W. J. Nuttall, and M. G. Pollitt, Future Electricity Tech- [6] J. Driesen, P. Vermeyen, and R. Belmans, “Protection issues in micro-
nologies and Systems. Cambridge: Cambridge Univ. Press, 2006, pp. grids with multiple distributed generation units,” in Power Conversion
83–97, 235–246. Conf., Nagoya, April 2007, pp. 646–653.
[3] B. C. Sung, D. K. Park, J. W. Park, and T. K. Ko, “Study on a series [7] W. Friedl, L. Fickert, E. Schmautzer, and C. Obkircher, “Safety and re-
resistive SFCL to improve power system transient stability: Modeling, liability for smart-, micro-, and islanded grids,” presented at the CIRED
simulation and experimental verification,” IEEE Trans. Industrial Elec- Seminar: SmartGrids for Distribution, Jun. 2008, Paper 107.
tron., vol. 56, no. 7, pp. 2412–2419, Jul. 2009. [8] L. Dessaint, K. Al-Haddad, H. Le-Huy, G. Sybille, and P. Brunelle, “A
[4] Litos Strategic Communication, “The Smart Gird: An Introduction,” power system tool based on simulink,” IEEE Trans. Industrial Elec-
2008 [Online]. Available: http://www.oe.energy.gov/SmartGridIntro- tron., vol. 46, no. 6, pp. 1252–1254, Dec. 1999.
duction.htm, Prepared for U.S. Department of Energy. [9] K. Maki, S. Repo, and P. Jarventausta, “Effect of wind power based
[5] R. Strzelecki and G. Benysek, Power Electronics in Smart Electrical distributed generation on protection of distribution network,” in IEEE
Energy Networks. London, U.K.: Springer-Verlag London Ltd., Developments in Power System Protection, Dec. 2004, vol. 1, pp.
2008, pp. 203–213. 327–330.