Professional Documents
Culture Documents
ZhaoSubbarayanSoong PDF
ZhaoSubbarayanSoong PDF
ABSTRACT
Whether a landfill facility is conducting a bioreactor operation with large-scale liquid injection
or simply recirculating site-generate leachate, achieving uniform liquid distribution in the waste
mass is always a critical operational goal. Several methods of liquid introduction have been adopted
by the industry. Of these methods, subsurface lateral injection lines (including perforated plastic
pipes) have become “standard” design for many landfill engineers. The subsurface lateral injection
lines not only provide for safe liquid injection, they also allow for the introduction of a large volume
of liquid – even after the waste mass has reached its permitted grade.
This paper provides methodology for the design of subsurface lateral injection lines,
specifically the design of perforated pipes (pipe sizing, perforation sizing and the selection of
spacing between perforations). Essential design equations, design principle and criteria will be
presented. A design example will also be used to illustrate the step-by-step design procedures.
INTRODUCTION
During the lifespan of a landfill, moisture in the incoming waste as well as liquid entering the
waste mass (in forms of precipitation, snowmelt, surface runoff, and other liquid addition) generates
leachate. Leachate carries the characteristics of the waste constituents and needs to be properly
contained, collected, removed, treated, and ultimately disposed of safely, in order to protect human
health and minimize adverse effects to the environment. Due to the high cost of leachate treatment
and disposal, much research has been performed to find alternative uses for leachate that can reduce
amounts that must be removed from the landfill.
Since as-received waste typically still possesses additional moisture absorptive capacity, re-
introducing leachate back into the waste mass (commonly referred as “leachate recirculation”) offers
an effective way of reducing leachate treatment costs. The actual moisture absorptive capacity
remains in the waste mass (sometimes referred “moisture deficit”) varies greatly depending on the
geographic location, climate, type of waste and other pertinent factors. For landfill sites that are
located in arid or semi-arid areas and for landfills that receive large amount of incoming waste
volume, the remaining moisture absorptive capacity can be very significant. Such large amount of
absorptive capacity represents an immense cost-saving potential for landfill owners and operators
due to the circumvention of leachate disposal and treatment. In fact, reintroducing collected
leachate is widely practiced in the municipal solid waste (MSW) landfills in the United States
nowadays.
Recently, bioreactor landfills have been designed, constructed, and operated at a number of
commercial and municipal facilities throughout the United States. In bioreactor landfills, moisture
content in the waste material is quickly increased to an elevated level to allow for the initiation of
biological decomposition processes at a relatively early stage of waste filling. To achieve this goal,
a large amount of liquid is generally required and in some cases, addition of supplementary liquid is
necessary. Possible sources of supplementary liquids include leachate from other sites, storm water,
wastewater (including biosolid and septage), commercial liquids, animal manure, and others.
This paper provides design methodology for the design of subsurface lateral injection lines,
including pipe sizing, perforation sizing and the perforation interval determination. Essential design
equations will be presented first, followed by the design principle and criteria and the recommended
design procedures. A design example will also be presented to illustrate the step-by-step design
procedures.
“Trench” “Mound”
design design
Porous
Perforated
Media
Pipe
Porous
Media
MSW
Waste
50 – 200 ft
10 – 50 ft
Adequately designed lateral injection lines should carry the injected liquid to the end of the
perforated pipe and evenly discharge liquid along the entire line. Without proper engineering
design, un-even distribution, prolonged percolation time and excessive pressure buildup can be
expected. It is very common to see perforated injection pipe with relatively large perforations (e.g.,
½ inch or greater in diameter) drilled at a densely-spaced pattern (e.g., 4 perforations for every 6
inches). Such design minimizes the entrance pressure head hence results in a quick pressure drop
along the pipe. Consequently, vast majority of the injected liquid is discharged near the entrance of
the pipe. As illustrated in an example shown in Figure 3, ninety percent of the injected liquid is
discharged within the first 30 ft of the pipe and the discharge rate rapidly diminish beyond that point.
2.50 250
1.00 100
0.50 50
0.00 0
0 10 20 30 40 50 60 70 80 90 100
Distance from End of Pipe (ft)
Figure 3 - Unit Discharge Rate and Flow Rate: the “Typical” Practice
In order to uniformly distribute the injected liquid along the entire pipe length, a “pressurized”
perforated pipe design is necessary, of which both the sizing and number of the perforations need to
be reduced. In an example illustrated in Figure 4, one ¼ inch perforation is drilled for every linear
foot of the pipe. As seen in the results, the perforated pipe is pressurized (entrance pressure head is
9 ft) and a relative uniform distribution of liquid along the entire length is achieved (between 2.2 and
1.8 gpm for any given perforation). The following sections will focus on the design of the
pressurized liquid injection pipes.
2.50 250
2.00 200
Unit Discharge Rate (gpm)
1.50 150
1.00 100
Figure 4 - Unit Discharge Rate and Flow Rate: the “Pressurized” Design
DESIGN METHOLOGY
Design Equations
The unit discharge rate (q) from each of the perforations is governed by the size of the
perforation and the static pressure at its respective location along the pipe:
q = BA 2 gP = 11.79d 2 P 1 / 2 (1)
According to Bernoulli’s equation, total head at any given point in liquid under motion is the sum of
pressure, velocity and elevation heads:
V2
h=P+ +Z (2)
2g
Where h = total head (feet)
P = pressure head (feet)
V = velocity (ft/sec)
g = gravitational acceleration (32.2 ft/s2)
Z = elevation head (feet)
Change of total head in pipes is primarily due to friction and other minor losses. Since perforated
pipes are typically constructed with straight sections with limited number of joints, minor losses are
generally considered negligible. Therefore, the friction loss along the pipe will determine the
change in total head. Friction loss in pipes can be calculation using Hazen-Williams equation as:
⎛ Q 1.85 ⎞
1.85
⎛ 100 ⎞
h f = 0.002082 L⎜ ⎟ ⎜⎜ 4.8655 ⎟⎟ (3)
⎝ C ⎠ ⎝D ⎠
Where hf = friction loss head (feet)
L = length of pipe (feet)
C = pipe friction factor (150 for HDPE pipes)
Q = flow rate in pipe (gpm)
D = nominal pipe size (inch)
Due to discharge at perforations, flow in perforated pipes varies along the pipe length (Figure 5).
Flow in perforated pipes can be obtained by summing discharges from all of the downstream holes:
i
Qi = ∑ q j (4)
j =1
Friction loss in each section between two perforations can be determined as:
⎛ 100 ⎞
1.85
⎛ Qi 1.85 ⎞
h f i = 0.002082∆L⎜ ⎟ ⎜ ⎟ (5)
⎝ C ⎠ ⎜ D 4.8655 ⎟
⎝ ⎠
Where “∆L” is the spacing between two adjacent perforations. “∆L” can be calculated based on total
number of perforations (“n”) as:
L
∆L = (6)
n −1
Based on the conservation of energy, the total head can be calculated as:
2 2
Vi V
h = Pi + + zi = Pi +1 + i+1 + zi+1 + h fi (7)
2g 2g
For low velocity flow (less than 5 ft/sec), the kinetic head is generally very low (less than 0.4 ft) and
is typically neglected. For horizontal-placed pipes, pressure at an upstream perforation can be
determined as:
Pi +1 = Pi + h f i (8)
⎛ 100 ⎞
1.85
⎛ Qi 1.85 ⎞
qi +1 = 11.79d 2
Pi + h f i = 11.79d 2
Pi + 0.002082∆L⎜ ⎟ ⎜ ⎟ (9)
⎝ C ⎠ ⎜ D 4.8655 ⎟
⎝ ⎠
The unit discharge rate at the end of the pipe (q1) can be calculated as:
q1 = 11.79d 2 P1 (10)
Note that the variation in the unit discharge rates is caused by the pressure change in the pipe
and the relative change of the discharge rate can be determined as:
q n − q1 Pn − P1
= (11)
qn Pn
Deriving from Equation (11), a correlation between the change in discharge rate and the change in
pressure can be developed as:
2
∆P ∆q ⎛ ∆q ⎞
=2 −⎜ ⎟ (12)
Pn q n ⎜⎝ q n ⎟⎠
where ∆q = qn - q1
∆P = Pn - P1
The correlation between the change in pipe pressure and the change in unit discharge rates can be
established using Equation (12), see Figure 6.
60%
50%
Change in Entrance Pressure
40%
30%
20%
10%
0%
0% 5% 10% 15% 20% 25% 30%
Change in Unit Discharge Rate
Figure 6 – Correlation between Change in Unit Discharge Rate and Change in Entrance Pressure
As previously discussed, pressure change in pipe is primarily due to friction loss:
n −1
∆P = ∑ h f i (13)
i =1
The total friction loss in perforated pipes can be estimated using Equation (14):
∆P = ∆P * F (14)
Note that “F” is a correction factor and “∆P*” is the friction loss calculated for a solid wall pipe
having same diameter, length, and total flow rate. Equations (15) and (16) depict the determinations
for “F” and “∆P*”, respectively. Note that the correlation shown in Equation (15) is established
based on an assumption that the change of unit discharge rate is less than 20%.
n −1
∑i 1.85
F= i =1
(15)
(n − 1)n1.85
⎛ 100 ⎞
1.85
⎛ Qn 1.85 ⎞
∆P = 0.002082 L⎜
*
⎟ ⎜ ⎟ (16)
⎝ C ⎠ ⎜ D 4.8655 ⎟
⎝ ⎠
As shown in Equation (15), the correction factor “F” is a function of the number of
perforations along the pipe. As the number of perforations increases, the correction factor decreases
and ultimately levels off at a value of 0.36 (Figure 7). For most design with more than 100 holes
along the pipe, a correction factor “F” of 0.36 can be used.
0.65
0.60
0.55
F=hf/hf*
0.50
0.45
0.40
0.35
0.30
0 50 100 150 200
Number of Hole on Perforated Pipe (n)
Finally, by combining and rearranging Equations (14) and (16), the required pipe diameter can be
determined as:
0.2055 0.3802
⎛ LF ⎞ ⎛ Qn ⎞
D = 1.6193⎜ ⎟ ⎜ ⎟ (17)
⎝ ∆P ⎠ ⎝C ⎠
Design Procedures
Uniform liquid distribution along the perforated liquid injection pipes can be achieved by
proper selection of pipe diameter, size of perforations, and spacing between perforations. A
systematic procedure can be presented in a flowchart format as shown in Figure 8. Individual steps
will be discussed in detail in the following subsections.
Input
Pipe length (L) and linear discharge rate (q*)
Calculation
Total flow rate (Q)
Design
Pumping system
and entrance pressure
Change linear discharge rate (q*)
Select
Perforation diameter (d) and unit discharge rate (q)
Calculate
Number of perforations (n) and spacing (∆L)
Satisfied?
No
YES
Calculation Input
Pressure difference between first and last perforations Allowed variation
Eq. 17 and Fig. 7 for unite discharge rate
Calculation
Determine pipe diameter
Satisfied?
No
YES
Output
Perforation diameter (d), spacing (∆L),
pipe diameter (D) and entrance pressure (Pn)
The linear discharge rate (q*) should also be pre-selected. The actual value is controlled by the
infiltration capacity of the waste. Reinhart and Townsend (1998) suggested that injection rates
between 25- to 50 gpd/ft are adequate. To further promote lateral distribution and minimize
biological clogging, intermittent liquid injection should also be considered (Reinhart and
Townsend, 1998). Generally speaking, selecting linear discharge rate between 0.2- to 0.4 gpm/ft
seems appropriate.
2. Determining total flow rate
The total flow rate (Q) can be calculated as:
Q = Lq * (18)
Note that this total flow rate is identical to the entrance flow rate (Qn).
20
18
d=1/8 in
16
d=3/16 in
Maximum Recommended Entrance Pressure 11.5 ft
14
Pressure (ft)
d=1/4 in
12
d=5/16 in
10
d=3/8 in
8
d=7/16 in
6
d=1/2 in
4
2
0
0 2 4 6 8 10 12
Unit Discharge Rate (gpm)
Figure 9 – Unit Discharge Rate vs. Entrance Pressure for Different Sizes of Perforation
5. Calculating number and spacing of perforations
Number of perforations (n) can be calculated as:
Q
n= (19)
q
Spacing between perforations (∆L) can be calculated as:
L
∆L = (20)
n −1
In most cases, the number of perforations (n) should be greater than 50 (i.e., q/Q < 2%) and
spacing between perforations (∆L) should be less than 2% of the length of perforated section (L).
If these requirements are met, the design procedure can continue. Otherwise, a new perforation
size shall be selected and Step 4 shall be repeated until all design requirements are met.
6. Selecting the allowable variation for unit discharge rate and calculating the corresponding
allowable pressure difference
Friction loss along the perforated pipe can be minimized but can not be completely eliminated.
In other words, some differences in the unit discharge rate will always exist. A tolerable
variation should be pre-determined for each project. To maintain a reasonable pipe size, the
tolerance (∆q/qn) can be set between 10% and 20%. The corresponding variance in pressure
between the two extreme ends of the perforated pipe can be calculated using Equation (12) or
Figure 6. Subsequently, the allowable pressure drop (∆P) in the perforated pipe can be
calculated based on the entrance pressure.
The diameter of the perforated pipe should be rounded to higher standard size. If the result is not
satisfactory, a new linear discharge rate can be selected and the entire design procedure can be
repeated. The following example illustrates the use of the above-mentioned design procedures.
DESIGN EXAMPLE
A landfill plans to install several leachate recirculation lines on the active surface. Based on
the geometry of the lift boundary, three subsurface leachate injection lines will be installed (Figure
11). Leachate will be pumped from the storage facility, through a forcemain, into a control vault
located at the base of the northeastern slope. Designated transmission lines will direct leachate from
the vault into the perforated pipes. Only one line will be used during each injection event.
0.08 0.010
0.009
0.07
0.008
0.06
0.007
Unit Friction Loss
0.00 0.000
0 50 100 150 200 0 50 100 150 200 250 300 350 400
Flowrate in Pipe (gpm) Flowrate in Pipe (gpm)
Leachate Leachate
Storage Transmission
Facility Control Lines Lift Boundary
Vault
cem
300 ft
For
600 ft
Leachate
Recirculation
Lines
6. Selecting the allowable variation for unit discharge rate and calculating the corresponding
allowable pressure difference
The allowable variation in the unit discharge rate is pre-selected as 20%. With that, the
allowable pressure drop can be calculated using Equation (12).
Line Length Total Flow Allowed No. of Pipe Diameter Pipe Diameter
(ft) Rate Pressure Drop Perforations - Calculated - Selected
(gpm) (ft) (inch) (inch)
1 600 90 0.90 135 4.11 4
2 300 90 1.22 121 3.35 4
3 150 90 1.55 101 2.77 3
Note that the pipe diameter can also be selected based on the unit friction loss and the total
flow rate using Figure 10.
8. Results verification
Based on output of the design procedures (i.e., pipe size, perforation size and spacing,
entrance pressure, etc.), three simulations were executed using a spreadsheet program that
incorporates Equations (4), (9) and (10). Results of the simulation illustrate the predicted
discharge rate at each of the perforations along the entire perforated sections, see Figure 12.
Further examining the results shown in Figure 12 reveals that the actual variations of unit
discharge flow rates (changes between the first and the last perforations) are 18%, 7% and
10% for Lines 1, 2 and 3, respectively. All of which are less than the pre-selected maximum
allowable variation (20%, see Step 6 in the previous section). Therefore the design is
verified as appropriate. Otherwise different pipe sizing may be considered and the
procedures can be repeated until the result is successfully verified.
1.0
0.9
(gpm)(gpm)
0.8
0.7
Hole Rate
0.6
Flow per Flow
0.5
Unit Discharge
0.4
0.3
0.2
0.1
0.0
0 100 200 300 400 500 600
Length
Distance fromfrom distal
the end of(ft)
pipe (ft)
Figure 12 – Predicted Discharge Flow Rate along the Perforated Pipes (Example Problem)
To demonstrate this fact, two design charts were developed and shown in Figures 13 and 14.
Both charts assumed a 5-ft spacing between perforations and an entrance pressure of 5-ft of water
column. Additionally, both charts correlate the perforation size with the maximum pipe length and
the corresponding discharge flow rates for different pipe sizes. The only difference between Figures
13 and 14 is the allowable variation among the unit discharge rates – a maximum variation of 10%
and 20% were assigned in Figures 13 and 14, respectively.
2000
1800
1600
1400
Max Pipe Length (ft)
D=6 in
1200
D=5 in
1000 D=4 in
D=3 in
800
D=2 in
600
400
200
0
1/8 3/16 1/4 5/16 3/8 7/16 1/2
Orifice Diameter (in)
400
350
300
Total Flowrate (gpm)
250 D=6 in
D=5 in
200 D=4 in
D=3 in
150 D=2 in
100
50
0
1/8 3/16 1/4 5/16 3/8 7/16 1/2
Orifice Diameter (in)
Figure 13 – Correlation between Size of Perforation, Maximum Pipe Length and Discharge Flow
Rates for Different Pipe Sizes (maximum allowable difference on unit discharge rate = 10%)
2500
2000
Max Pipe Length (ft)
D=6 in
1500
D=5 in
D=4 in
D=3 in
1000
D=2 in
500
0
1/8 3/16 1/4 5/16 3/8 7/16 1/2
Orifice Diameter (in)
500
450
400
350
Total Flowrate (gpm)
D=6 in
300
D=5 in
250 D=4 in
D=3 in
200
D=2 in
150
100
50
0
1/8 3/16 1/4 5/16 3/8 7/16 1/2
Orifice Diameter (in)
Figure 14 – Correlation between Size of Perforation, Maximum Pipe Length and Discharge Flow
Rates for Different Pipe Sizes (maximum allowable difference on unit discharge rate = 20%)
As clearly indicated in Figures 13 and 14, all of the design parameters are interrelated and no
“typical” perforated pipe design is universally applicable. Design engineers should have a thorough
understanding of both the project requirements and the design mechanism in order to provide an
effective design of liquid injection system.
PARAMETRIC ANALYSES AND OBSERVATIONS
This section presents the results of a series of parametric analyses. The parametric analyses
were designed to demonstrate the sensitivity embedded in various design parameters in the design of
perforated liquid injection pipes. Four critical design parameters including size of perforation, size
of pipe, spacing between perforations, and the entrance pressure were evaluated. Table 1
summarizes the results of the parametric analyses and the authors’ observations and comments.
CONCLUSIONS
One of the essential goals when designing liquid injection lines is to uniformly distribute liquid
into the waste mass. According to the information documented in literature and the authors’ past
project experiences, the most effective injection method is the use of lateral injection lines (trenches
or mounds). However, an improperly-designed lateral injection line can still result in an uneven
liquid distribution, which may eventually lead to issues such leachate outbreaks, differential
settlements, unstable working surface, or even slope instability.
A systematic design procedure is recommended and presented in this paper, following which
will allow the engineers to properly select system parameters (e.g., pipe size, perforation size,
perforation spacing, and entrance pressure) and meet their project-specific requirements.
600 120
Entrance Pressure = 5 ft W.C.
500 Pipe ID = 3 inches 100
Perforation: 1 hole every 5 ft
300 60
200 40
100 20
0 0
1/8 3/16 1/4 5/16 3/8 7/16 1/2
Hole Size (inch)
800 240
Entrance Pressure = 5 ft W.C.
700 Perforation: 1 hole every 5 ft 210
Hole size = ¼ inch
600 180
500 150
400 120
300 90
200 60
100 30
0 0
2 3 4 5 6
Pipe ID (inch)
100
80
60
40
20
0
1 2 3 4 5 6 7 8 9 10
Spacing between Holes (ft)
dq/q=10% dq/q=20%
350
300
250
200
150 Hole size = ¼ inch
100 Spacing = 5 ft
50 Pipe ID = 3 inch
0
1 2 3 4 5 6 7 8 9 10
160
Entrance Pressure (ft W.C.)
140
Total Flowrate (gpm)
dq/q=10% dq/q=20%
Reinhart, D.R. and T.G. Townsend (1998). “Landfill Bioreactor Design and Operation”, published
by Lewis Publishers, New York
Bachus, R.C., M.F. Houlihan, E. Kavazanjian, R. Isenberg, and J.F. Beech (2004). “Bioreactor
landfill stability: key considerations”, in MSW Management, September/October,
http://www.mswmanagement.com/mw_0409_biostability.html