6.2(W6.2.)AC-AC átalakítók.

Háromfázisú váltakozó áramú


szaggatók, háromfázisú
takarékkapcsolások. Alkalmazás.

Kósáné Kalavé Enikő

1
Háromfázisú váltakozó áramú
szaggatók

2
Táp oldal Terhelési oldal

3
Three-phase Y-connected type ACVCs

three-phase full-wave controllers three-phase half-wave controllers =


Ellenpárhuzamosan kapcsolt tirisztor párok =három fázisú félig vezérelt kapcsolás
alkalmasak a háromfázisú terhelés be- és kikapcsolására. Ellenpárhuzamosan kapcsolt tirisztor-dióda párok
alkalmasak a háromfázisú terhelés be- és kikapcsolására.
4
Three-phase Y-connected type ACVCs

Figures (a) and (b) show three-phase full-wave and half-wave controllers respectively con-
nected to Y- or delta-connected loads in which the neutral point is not accessible. Half-wave
controller shown in Figure (b) economizes in the cost of devices and does not give rise to dc
components in any part of the system unlike its single-phase counterpart. However, it introduces
more harmonics into the line current than does the full-wave controller, and this is a serious
disadvantage. 5
Háromfázisú félig vezérelt kapcsolás
Félvezető elemek fele vezérelhető. A terhelés akár csillagba akár deltába kapcsolható.

Ellenpárhuzamosan kapcsolt tirisztor-dióda párok


alkalmasak a háromfázisú terhelés be- és kikapcsolására.

6
Háromfázisú takarékkapcsolások

7
Háromfázisú takarékkapcsolás

Táp oldal

Terhelési oldal

Két fázisban van csak vezérelhető kapcsolóelem, a harmadik fázis közvetlenül a terhelésre
csatlakozik.
Előny: Kevesebb vezérelhető eszköz és vezérlő áramkör szükséges.
Hátrány: a kapcsolóelemek szimmetrikus vezérlésekor a terhelés egyes fázisaira jutó
feszültségek, ill a fázisáramok nem azonos alakúak, effektív értékük jelentősen eltér.
A tirisztorok aszimmetrikus vezérlésével az egyes fázisok fesz-e szimmetrikussá tehető.
8
Háromfázisú takarékkapcsolás 2

Táp oldal

Terhelési oldal

A csillagpontot, három deltába kapcsolt tirisztorral alakítottuk ki.


Csak akkor megvalósítható, ha a terhelés csillagpontja bontható.

9
Three-phase neutral point ACVC

Táp oldal Terhelési oldal (Load)

For Y-connected load circuits in which the neutral point is accessible and can be opened, we can
use the neutral point controller which reduces the number of thyristors required to three and
considerably simplifies the control circuitry.
10
Three-phase delta-connected type ACVC

Táp oldal Terhelési oldal

If the terminals of a three-phase system are accessible, the control elements (or power devices)
and load may be connected in delta.
Since the phase current in a normal three-phase system is only 1/√3 of the line currents, the
current ratings of thyristors would be less than that if thyristors (or control elements) were
placed in the line.
For delta-connected load circuits in which each end of each phase is accessible, we can use a
delta-connected ACVC. This circuit has the advantage of reducing the current rating of the
11
devices. (Remember that Phase Current=Line Current/√3.)
Alkalmazás

12
Váltakozóáramú szaggatók alkalmazása
• Kontaktor jellegű és szabályozott kapcsolóként
pl:
– hevítőberendezésekben pl háztartási fűtő-és
főzőberendezésekben
– Pont- és vonal-hegesztő berendezésekben
– Egy- és háromfázisú váltakozóáramú motorok
kapcsolására, fordulatszám-, ill nyomaték-
változtatására

13
Váltakozó áramú szaggatók
alkalmazása szabályozott kapcsolóként
• Váltakozó feszültségű fogyasztó
teljesítményének folyamatos változtatására pl
fényerősség szabályozó berendezésekben,
fűtőberendezésekben, pont- és vonalhegesztő
berendezésekben, és váltakozó áramú
motorok fordulatszám- ill nyomaték
változtatására.

14
Applications
• Domestic and industrial heating
• Induction heating in metallurgical industries
• Illumination control
• Speed control of induction motors in pumps
and fans etc.

15