ABSTRACT To increase the reliability of aerospace electronics and reduce their overall power consumption,
we investigated the possibility of incorporating active thermoelectric cooling (TEC) solutions. The harsh
avionic environment demands sophisticated active control schemes that enable the achievement of high
coefficient of performance. The positive effect of active PWM control has been validated both in simulation
and on a working laboratory prototype that allowed us to clarify the pros and cons of the incorporation of
TEC techniques in avionics applications. This paper has been performed under the framework of CLEAN
SKY—THERMICOOL project.
I. INTRODUCTION thermoelectric cooler forces heat to flow from the cold sur-
Sustainable energy management has become an issue of grave face to the hot one, maintaining the junction temperature of
and global concern over the last two decades; the exploitation a device below a safe temperature, by pumping heat away
of renewable energy sources and the adaptation of energy from the device. In order to improve their performance, active
efficiency measures and practices, by incorporating smart thermoelectric cooling solutions have also been proposed,
energy management algorithms, are key technologies for the based on active PWM control of the supplying current [5]. To
reduction of fossil fuels share worldwide. To this direction, this direction, in the framework of CLEAN SKY – THERMI-
the complete electrification of aircrafts is of major impor- COOL project, the study and development of an innovative
tance; viable technologies for this purpose include devices thermoelectric cooling (TEC) solution for avionic applica-
and systems that take advantage of thermoelectricity. The tion with maturity level TRL5, low power consumption and
thermoelectric (TE) effect includes the transformation of heat high efficiency has been performed. The study focused on
to electric energy and vice versa and its applications can the incorporation of an active TEC solution to achieve high
consequently traverse two domains: (a) Electricity genera- coefficient of performance (COP) values. In addition, the
tion from heat sources such as power plants, factories and construction of a laboratory test bench took place, for the
motor vehicles, by exploiting the Seebeck effect; (b) cooling conduction of tests.
(or heating) using solid-state thermoelectric devices that can THERMICOOL is the acronym of the project entitled
exploit the Peltier effect [1]–[4]. The exploitation of this ‘‘Thermoelectric cooling using innovative multistage active
energy-conversion phenomenon allows the design of reliable control modules (Project number: 632436)’’ and it consists
systems, built with solid-state devices that enable long-life of three main technical Work Packages (WPs); WP1 was
operation, do not need any moving parts and leave any toxic entitled ‘‘Bibliographical Review’’ and included the bibli-
residuals, thus contributing to the goal of low environmental ographical review of thermoelectric materials and cooling
footprint. solutions, as well as a survey on the available commercial
Thermoelectric coolers have been successfully used in systems. The main theoretical analysis of the project was
commercial cooling applications with high heat dissipation implemented in WP2, which was entitled ‘‘Technology Selec-
requirements. In electronic applications, a well-designed tion’’; in more details, an extended finite element (FEM)
2169-3536
2017 IEEE. Translations and content mining are permitted for academic research only.
2288 Personal use is also permitted, but republication/redistribution requires IEEE permission. VOLUME 5, 2017
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
E. Karampasis et al.: Active TEC Solutions for Airspace Applications
modeling and simulation analysis has been carried out for the TABLE 1. Selected TE materials.
specific case study provided by the Topic Manager (Labinal
Power Systems) and the final technology selection has been
decided, based on the FEM analysis results. Finally, in WP3
entitled ‘‘Experimental Validation’’ the construction of the
laboratory test bench took place, as well as the conduction
of an extended series of evaluation tests.
In the following Sections the tasks performed in these WPs
will be analytically presented and the major project findings
will be discussed.
presented in Figs 2a-2h, assuming different values of Th extreme values, even greater than 2.0. However, efficiency
and Tc . Calculation of the ZTm value is made through spline degrades significantly as the temperature difference is fur-
interpolation of the known points for each material, for the ther increased. Regardless of the device temperature, there
mean temperature Tm = (Tc +Th )/2. Values of Tm that are out is always a hot ambient temperature, over which, selecting
of the range of values reported by the corresponding reference a high-ZT material makes negligible difference. Also, the
are omitted, resulting to interrupted COP plots. For each case system’s behavior in very low temperatures (<0◦ C) is of
study, a constant Tc is assumed, and COP is plotted for Th concern, since the number of efficient available materials is
values that vary from Tc + 10◦ C to a maximum of 160◦ C. limited in that range.
According to the derived COP trends, a COP factor above Therefore, according to the target specifications, especially
unity can be obtained at certain temperature ranges, for every concerning operating temperatures, guaranteeing a constant
material. In fact, for small ambient-to-device temperature satisfactory behavior in terms of performance (COP>1),
differences, around 10-20◦ C, COP can theoretically reach is not a straightforward task. The final material selection
fact that the thermal sources in the experimental setup were In summary, the temperature measurements at +95◦ C envi-
not uniformly distributed throughout the mezzanine and the ronmental temperature highlighted also the fact, that in the
copper layer (PCB) surfaces (as in the simulated model). For experimental setup the temperature values at the mezzanine
the same reason, there were also notable differences between surface are in line with the corresponding simulated values.
the experimental and the simulation results concerning the On the other hand, higher divergence was observed for the
maximum and minimum temperature values on the copper average temperature value on the copper layer (PCB) sur-
layer surface. Nevertheless, the average temperature value on face, as a result of the heat sources distribution. Finally, the
the copper layer surface was close enough to the simulation enclosure temperature values were now in line with the cor-
results, having a small divergence of 5.9%. Finally, higher responding simulated values (although its thermal resistance
differences between the measured and the simulated temper- was higher than in the simulation process).
ature values on the enclosure surface existed; the fact that the Hence, the experimental results without any TEC operation
measured temperatures were much smaller than the simulated have shown that the experimental setup was valid for the
ones can be justified by the air velocity due to the blower study of TECs’ operational characteristics, despite the fact
operation. Nevertheless, this part of the experimental setup that there were some divergences between the experimental
is of lower importance. In summary, the temperature mea- and the simulated temperature values.
surements at +63◦ C environmental temperature highlight the After the experiments without utilizing any TEC mod-
fact, that this is the critical condition for the average tempera- ule, the first thermoelectric cooling experiment took place,
ture value at the mezzanine surface. It is also deduced, that in namely Case 2, considering the series connection of TECs.
the experimental setup the average temperature values at the The electric power supply was regulated by means of a con-
mezzanine and the copper layer surface are in line with the trol loop that minimized the average TEC temperature value;
corresponding simulated values, although small divergences for this purpose, the use of the Maximum Power Point Track-
exist between maximum and minimum temperature values. ing (MPPT) control loop that was developed in the context of
Next, Case 1 has been tested at +95◦ C environmental CLEAN SKY – RENERGISE project [36], has been modified
temperature, which is the worst case scenario for the envi- and incorporated into the experimental process. It is noted
ronmental temperature conditions. According to the obtained that the MPPT controller time constant (averaging period)
results we may conclude that the difference between the was set to 1sec, in order to account for the thermal inertia
experimental and the simulated average temperature values of the system. According to the obtained results, we may
at the mezzanine surface was 3.3%, while the difference conclude that the series TEC connection was not suitable for
between minimum and maximum temperature values at the the specific application. This was due to the fact that the total
mezzanine surface was quite smaller than in the case where series resistance was very high (4 × 1.58 Ohm) and so the
the environmental temperature was +63◦ C; this can be jus- Joule effect restricted drastically the supplying current range,
tified by the fact that at such high temperatures the mezza- that leads to COP values greater than 1.0. Consequently,
nine surface was heated in a more uniformly way. On the the provided cooling power, Pc , was limited below 4W and
other hand, the difference between the experimental and the consequently the TEC system managed to keep the average
simulated average temperature values was increased for the temperature value of the mezzanine surface below +95◦ C up
copper layer surface, reaching 11.4%. It is noted however, that to 78◦ C – 80◦ C ambient temperature values.
the difference at the minimum temperature value has been Next, Case 3.1 was evaluated, where the series TEC con-
drastically decreased, being only 3.1%. Once again, these nection was subject to classical active PWM control (SPC
results for the copper layer surface can be justified by the pattern). Various tests were performed in order to identify
fact that the thermal sources in the experimental setup were the most suitable switching frequency; however, it seemed
not uniformly distributed throughout the mezzanine and the that frequency values between 500Hz and 1kHz had simi-
copper layer surfaces (as in the simulated model). Finally, the lar results, while higher frequencies increased notably the
differences between the measured and the simulated tempera- electric power consumption. This was due to the high series
ture values on the enclosure surface have been also decreased resistance and the skin effect that becomes dominant as fre-
drastically, below 3%; it has to be noted that the average tem- quency rises. It is noted that all measurements in this Case
perature value on the enclosure surface is higher than in the stand for steady state conditions (i.e. the MPPT controller is
simulation results, leading to the conclusion that the enclose in steady state). Moreover, the temperature control loop was
thermal resistance was considerably higher than the one in also active, by regulating the duty cycle value Df . According
the simulation process (taking also into account the positive to the obtained results, we may conclude that the use of the
presence of the air velocity due to the blower operation). SPC pattern in series TEC connection improves its cooling
This can be justified by the differences in the material used capability; ,the critical temperature becomes as high as 83◦ C
(AlMgSi-0.5 F22 aluminum alloy) as well as its higher thick- due to the higher COP values at higher ambient tempera-
ness (in order to ensure the static safety of the thermal closet). tures. This is due to the lower electric power consumption,
As it will be shown onwards, the higher thermal resistance Pel , thanks to the switching supplied current. It is noted
affects also the operation of TECs – leading to higher tem- that even at +95◦ C ambient temperature, the classical active
perature differences between the cold and the hot sides (1T ). PWM method improved the temperature conditions on the
FIGURE 13. Pc as a function of Df , with I, fs being parameters (Parallel FIGURE 14. COP as a function of Df , with I, fs being parameters (Parallel
TEC connection). TEC connection).
mezzanine surface; notably, its ambient temperature value 1.0 whereas Pc decreased – although it remained at the range
was reduced by 12.5◦ C. Nevertheless, the experiments so of 7W – for I > 1A. It is noted that the current-switching fre-
far have highlighted that the series TEC connection was not quency combinations in Figs 13, 14 cover almost any possible
able to meet the project requirements and so the parallel operational condition; as it has been experimentally deduced,
connection had to be employed. higher current and switching frequency values deteriorate
After the experiments considering the series connection, the system operation. In conclusion, classical active PWM
the parallel connection of TEC modules was established, control is able to exploit the cooling capabilities of the parallel
initially driven by constant current, i.e. Case 3.2; as it was connected TEC system by increasing the switching frequency
expected, constant current supply had similar results with the at the range of 10 kHz or higher. On the other hand, at higher
ones presented for the series TEC connection, supplied also ambient temperature values (like the one during the test) the
by a constant current, i.e. the cooling power capability was achievement of high COP values, becomes more difficult
reduced very quickly due to the rise of 1T . due to the high current pulses that are required to keep Pc
Case 4 was a much more interesting case than the previ- high enough. A solution to this issue is the proposed active
ous one, due to the classical SPC pattern that incorporated. PWM control (DPC pattern), that has been developed in
Because of the parallel TEC connection, the Joule effect the context of THERMICOOL project and the experimental
was less dominant, due to the drastically reduced equiva- verification of which, will be presented next. Nevertheless,
lent resistance (1.58 / 4 Ohm) and so a wider switching according to the obtained results in Case 4, we may con-
frequency range could be exploited. In order to study the clude that the parallel TEC connection manages to operate
cooling behavior of the parallel connected system, a test was at higher 1T values than the ones in series connection, due
carried out; during this test, Pc ad COP values were measured to the positive effect of the high switching frequency that has
with the switching frequency, fs , Df , as well as the total been discussed. As a result, the mezzanine surface is more
average supplying current, I , being variable parameters. The effectively cooled, with its average temperature being slightly
test was performed at 83◦ C average temperature value on the higher (+3.4◦ C) than the target, only at very high ambient
mezzanine surface. The results of this test are depicted in temperatures.
Figs 13 and 14, showing clearly the cooling potential of PWM Last, Case 5 is the most ambitious one, because it incor-
pattern in the parallel connected TEC system. In more details porated the proposed double carrier frequency DPC pattern.
as Df decreased (narrower current pulses) and fs increased, Pc As presented, a fast switching frequency (higher than 1 kHz)
became adequately high for the specific application (higher that determined Pc and a slow switching frequency (lower
than the 7W target); it could have reached values even higher than 1 kHz) that determined COP factor (by means of elec-
than 10W, as long as I became higher than 1.5 A. On the other trical consumption regulation) were used. The novel active
hand, for such high Pc and small Df values, COP became PWM control method was tested in the parallel TEC connec-
lower than 1.0; this was due to the extremely high peak tion, with the following technical characteristics:
current pulses, that seriously affect the electric consumption. • Fast switching frequency: 50 kHz
Moreover, as Df became higher, Pc value moderated under • Fast switching frequency duty cycle: 30% - 80%
any fs value (the operation converged towards continuous • Slow switching frequency: 0,.1 Hz
current supply operation); the COP factor became higher than • Slow switching frequency duty cycle: 70%
[22] N. Shutoh and S. Sakurada, ‘‘Thermoelectric properties of the DIONISIS VOGLITSIS received the Dipl.Eng. degree in electrical engineer-
Tix (Zr0.5 Hf0.5 )1−x NiSn half-Heusler compounds,’’ in Proc. 22nd ing from the Democritus University of Thrace, Xanthi, Greece, in 2008,
Int. Conf. Thermoelectrics (ICT), La Grande-Motte, France, 2003, pp. and the M.Sc. degree in electrical engineering from the Delft University of
312–315. Technology, The Netherlands, in 2014. He is currently pursuing the Ph.D.
[23] D. M. Rowe, V. S. Shukla, and N. Savvides, ‘‘Phonon scattering at grain degree in grid-tied inverters for distributed generation with the Democritus
boundaries in heavily doped fine-grained silicon–germanium alloys,’’ University of Thrace. He joined the Electrical and Computer Engineering,
Nature, vol. 290, pp. 765–766, Apr. 1981. Democritus University of Thrace, in 2014.
[24] G. Joshi et al., ‘‘Enhanced thermoelectric figure-of-merit in nanostruc-
His research interests include the analysis, design, simulation, and con-
tured p-type silicon germanium bulk alloys,’’ Nano Lett., vol. 8, no. 12,
struction of dc/dc and dc/ac converters for use in renewable energy systems,
pp. 4670–4674, 2008.
[25] L.-D. Zhao, V. P. Dravid, and M. G. Kanatzidis, ‘‘The panoscopic approach waste heat recovery systems, and aeronautics applications.
to high performance thermoelectrics,’’ Energy Environ. Sci., vol. 7, no. 1, Mr. Voglitsis is a member of the Technical Chamber of Greece.
pp. 251–268, 2014.
[26] F. P. Pierre Poudeu et al., ‘‘High thermoelectric figure of merit and nanos-
tructuring in bulk p-type Na1−x Pbm Sby Tem+2 ,’’ Angew. Chem. Int. Ed.,
vol. 45, no. 23, pp. 3835–3839, 2006.
[27] K. F. Hsu et al., ‘‘Cubic AgPbm SbTe2+m : Bulk thermoelectric materials MICHAEL LOUPIS (M’08–SM’10) received the Dipl.Eng. degree in electri-
with high figure of merit,’’ Science, vol. 303, pp. 818–821, Feb. 2004. cal engineering from the Aristotelian University of Thessaloniki, Greece, the
[28] J. He, Y. Liu, and R. Funahashi, ‘‘Oxide thermoelectrics: The challenges, M.Sc. degree in microprocessor engineering from the University of Bradford,
progress, and outlook,’’ J. Mater. Res., vol. 26, no. 15, pp. 1762–1772, U.K., the Ph.D. degree in electrical engineering from the National Technical
Aug. 2011. University of Athens, Greece, and the M.Sc. degree in quality assurance from
[29] K. Fujita, T. Mochida, and K. Nakamura, ‘‘High-temperature thermo- the Greek Open University.
electric properties of Nax CoO2−δ single crystals,’’ Jpn. Soc. Appl. Phys., He is the Technical Manager of ITC S.A., being the coordinator of various
vol. 40, no. 7, pp. 4644–4647, 2001. EU funded research programs and also an Assistant Professor with the
[30] M. Shikanoa and R. Funahashi, ‘‘Electrical and thermal properties of Technological Educational Institute of Central Greece.
single-crystalline (Ca2 CoO3 )0.7 CoO2 with a Ca3 Co4 O9 structure,’’ Appl. Dr. Loupis is a member of the Technical Chamber of Greece, the Associ-
Phys. Lett., vol. 82, pp. 1851–1853, Mar. 2003. ation of Mechanical and Electrical Engineers, the Association of Computer
[31] R. Funahashi and M. Shikano, ‘‘Bi2 Sr2 Co2 Oy whiskers with high ther- Engineers, and the Greek Computer Society, a Fellow Member of the Society
moelectric figure of merit,’’ Appl. Phys. Lett., vol. 81, pp. 1459–1461, for Industrial Robotics and Expert Systems, and a member of the Institution
Aug. 2002.
of Engineering and Technology.
[32] G. J. Snyder and E. S. Toberer, ‘‘Complex thermoelectric materials,’’
Nature Mater., vol. 7, pp. 105–114, Feb. 2008.
[33] D.-Y. Chung et al., ‘‘CsBi4 Te6 : A high-performance thermoelectric mate-
rial for low-temperature applications,’’ Science, vol. 287, pp. 1024–1027,
Feb. 2000.
[34] B. Wölfing, C. Kloc, J. Teubner, and E. Bucher, ‘‘High performance ANASTASIOS PSARRAS received the Diploma degree in electrical and
thermoelectric Tl9 BiTe6 with an extremely low thermal conductivity,’’ computer engineering and the master’s degree from the Democritus Univer-
Phys. Rev. Lett., vol. 86, pp. 4350–4353, May 2001. sity of Thrace, Xanthi, Greece, in 2012 and 2013, respectively, where he is
[35] O. Yamashita, S. Tomiyoshi, and K. Makita, ‘‘Bismuth telluride com- currently pursuing the Ph.D. degree. His current research interests include
pounds with high thermoelectric figures of merit,’’ J. Appl. Phys., vol. 93, low power system-on-chip design, and particularly on on-chip interconnec-
pp. 368–374, Jan. 2003. tion networks.
[36] G. C. Christidis et al., ‘‘Innovative waste heat recovery systems in rotor-
crafts,’’ in Proc. Elect. Syst. Aircraft, Railway Ship Propuls. (ESARS),
2012, pp. 1–4. [Online]. Available: http://10.1109/ESARS.2012.6387452