A R T I C L E I N F O A B S T R A C T
Keywords: Loop heat pipe (LHP) is a high efficient and passive heat transfer device with long heat transfer distance and high
loop heat pipe cooling capacity. In this study, an advanced thermal management system based on a novel flat evaporator LHP
High-efficiency condenser with high-efficiency condenser was proposed to obtain high heat transfer capacity and low energy consumption.
Flat evaporator
Firstly, the cooling efficiency of two cooling heat sink units was evaluated by numerical analysis, and the
Numerical analysis
Heat transfer characteristics
optimization heat sink unit was applied in the LHP condenser. Then, the heat transfer characteristics of the flat
evaporator LHP with high-efficiency condenser were researched under different charging ratios, fan voltages and
LHP test directions. Finally, the energy consumption of the LHP cooling system was evaluated. The numerical
results showed that the novel louver folded fin heat sink unit has a better cooling efficiency than that of the
conventional straight fin heat sink unit. And the experimental results indicated that the flat evaporator LHP with
high-efficiency condenser exhibited better heat transfer characteristics at the input power range from 50 W to
450 W when the charging ratio of LHP was 33.1%. At the maximum input power of 550 W, the junction tem
perature of the flat evaporator LHP with high-efficiency condenser was 87.93 ◦ C at the fan voltage of 12 V, and
the junction temperature of this LHP at positive gravity direction of 30◦ was lower than that of other LHP test
directions. Additionally, the energy consumption of the efficient air-cooled LHP system was lower than one-
eighteenth of that of the water-cooled LHP system.
* Corresponding author.
E-mail address: sfwang@scut.edu.cn (S. Wang).
https://doi.org/10.1016/j.ijthermalsci.2023.108719
Received 18 January 2023; Received in revised form 5 September 2023; Accepted 12 October 2023
Available online 26 October 2023
1290-0729/© 2023 Elsevier Masson SAS. All rights reserved.
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
Nomenclature Subscripts
a ambient
cp constant-pressure specific heat J/(kg⋅K) c condenser
D diameter m cc compensation chamber
H height m e evaporator
ID inner diameter m j junction
L length m l liquid
OD outer diameter m sys system
P power W tot total
p pressure Pa v vapor
Q heat load W
R thermal resistance ◦ C/W Greek symbols
T temperature ◦ C α charging ratio %
t time s ρ density kg/m3
u, v, w x, y, z velocity components m/s μ viscosity kg/(m⋅s)
V volume m3 λ thermal conductivity W/(m⋅K)
W width m
x, y, z Cartesian coordinates
conventional heat pipe, micro-heat pipe, pulsating heat pipe (PHP), 24 V, the junction temperature of heating copper block was no more
sorption heat pipe (SHP), rotating heat pipe (RHP), loop heat pipe than 85 ◦ C when the input power reached 150 W (24 W/cm2).
(LHP), and so on [9–11]. Compared with other types of heat pipe, the Based on the previous studies of air-cooled LHP, it can be demon
LHP has some outstanding advantages, including strong anti-gravity strated that the air-cooled LHP are hard to limit the temperature of
ability, long distance heat transport, high heat transfer efficiency, electronic chips in a reasonable temperature range (normally < 85 ◦ C)
good thermal equilibrium and so on [12–14]. LHP is a long heat transfer when the power density was larger than 37 W/cm2 [23]. Compared to
distance, high cooling capacity phase change heat transfer equipment, liquid cooling technology, the air-cooled LHP have some advantages
which applying the capillary force of capillary wick to circulate the such as fewer auxiliary equipment, high safety, non-pollution and low
working medium, and the working medium transfers heat from the cost [6–8]. If the cooling capacity of the air-cooled LHP can be further
evaporator to the condenser in the cycle process [15–17]. At present, improved, it will have a broader prospect in electronic chip cooling.
many researchers have reported the application of air cooling LHP Therefore, in this work, a high-capacity air-cooled LHP with a new
technology in the thermal management challenge of electronic chips. condenser and flat evaporator was proposed for the first time to cool the
Maydanik et al. [18] provided a stainless steel-ammonia LHP with a high power density electronic chips. Firstly, the cooling efficiency of two
cylindrical evaporator measuring 8 mm (OD) × 59 mm (L) and equipped cooling heat sink units is evaluated by numerical simulation study, and
an effective heating area 40 × 40 mm2 for cooling the 1U server chip. the optimization heat sink unit is applied in the design of LHP
Their research conclusions showed that the LHP can effectively remove condenser. Then, the impact of charging ratios, fan voltages and LHP test
the heat power of 130 W by the forced air convection at the highest heat directions on the heat transfer characteristics of the air-cooled LHP with
source temperature of 70 ◦ C. And the corresponding minimum total heat a new condenser and flat evaporator are investigated in detail. Finally,
resistance was 0.33 ◦ C/W. Li et al. [19] presented and investigated a the energy consumption analysis of the air-cooled LHP system is pre
copper-water LHP with a plane, square evaporator measuring 30 × 30 × sented compared with the water-cooled LHP system. In summary, the
15 mm3 for thermal management of electronic cooling. Their research comprehensive study demonstrates that the novel air-cooled LHP can
results showed that the junction temperature of heating copper block become a promising, low-cost and high-efficiency technology for future
can be controlled at around 85 ◦ C when the input power was 350W. In high power density electronic chip cooling.
this study, the thermal properties of the LHP were researched in the
direction of positive gravity (+90◦ ). However, the thermal behavior of 2. Numerical analysis of heat sink
LHP in the conventional horizontal orientation has not been reported.
Liu et al. [20] demonstrated and studied a copper-acetone LHP with a 2.1. Model geometry
miniature plane type evaporator sizing 40 × 30 × 14.5 mm3 and also
equipped with a 4 mm thick stainless steel mesh wick of 82 layers 500 In order to reduce the computational burden, some simplified geo
grids. Their research results displayed that the junction temperature of metric units are often applied in numerical studies. In this work, two
heating copper block and the LHP heat resistance were 52 ◦ C and cooling heat sink units, conventional straight fin heat sink (Design 1)
0.45 ◦ C/W at the input power of 60 W, respectively. Xue et al. [21] and novel louver folded fin heat sink (Design 2), were used for numerical
developed and researched an aluminum-ammonia LHP with a plane type study and comparison of cooling efficiency in order to design the effi
evaporator sizing 54 × 44 × 12 mm3 and outfitted a ceramic heat source cient LHP condenser, as described in Fig. 1. The conventional straight fin
with 40 × 40 mm2 for cooling chip. And the volume of condenser fins for heat sink (Design 1) and novel louver folded fin heat sink (Design 2)
the air-cooled LHP was 150 × 80 × 23 mm3, with 0.5 mm thickness for were made of aluminum alloy. For the Design 2, the louver folded fin
each fin. Their research conclusions presented that at the highest input was welded to the middle of straight fins, and the detailed structure of
power of 513W (32.06 W/cm2), the surface temperature of ceramic the partially louver folded fin is presented in Fig. 2. Seen from Fig. 2, the
electrical heater was controlled at 72.3 ◦ C, and the LHP heat resistance folded fin unit was provided with louvers at angles of 45◦ and − 45◦ to
and the evaporator heat resistance were 0.058 ◦ C/W and 0.011 ◦ C/W, enhance the disturbance of the cooling air. In the length direction, every
respectively. Li et al. [22] devised a new plane type evaporator LHP with ten louvers with an angle of 45◦ and − 45◦ were arranged alternately,
a multi-porosity gradient sintered superhydrophilic wick structure, and a total of 140 louvers from a folded fin. Additionally, the main
without the reservoir to reduce the size of the evaporator as much as geometric dimensions of the conventional straight fin heat sink (Design
possible. A series of experimental studies found that under fan voltage of 1) and novel louver folded fin heat sink (Design 2) are given in Table 1.
2
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
And the relative parameters in the model are written in Table 2. In order
to facilitate the numerical simulation process, the following assumptions
were considered:
The governing equations for the heat sink unit design were presented
as bellows:
Continuity equation:
∂u ∂ν ∂w
+ + =0 (1)
∂x ∂y ∂z
3
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
4
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
5
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
6
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
Fig. 7. Temperature contour of Design 1 and Design 2 at different inlet water temperatures.
temperature. In the height direction, the temperature difference be that at same inlet water temperature Design 2 has lower outlet water
tween the bottom and top of Design 2 is larger than that of Design 1, temperature and better cooling efficiency. Additionally, the out water
which indicated that the Design 2 has more efficient cooling capacity temperature difference between Design 2 and Design 1 was gradually
than the Design 1. Therefore, the Design 2 can remove more heat at the improved with the increasing of inlet water temperature from 40 ◦ C to
same height of heat sink. The inlet water temperature dependence of the 80 ◦ C. At the inlet water temperature of 40 ◦ C, 50 ◦ C, 60 ◦ C, 70 ◦ C and
temperature difference between inlet water temperature and outlet 80 ◦ C, the outlet water temperature (temperature difference (Tinlet -
water temperature (Tinlet - Toutlet) for the Design 1 and Design 2 is Toutlet)) of Design 2 were 39.15 ◦ C (0.85 ◦ C), 48.72 ◦ C (1.28 ◦ C), 58.30 ◦ C
demonstrated in Fig. 8. As noticed from Fig. 8, the temperature differ (1.7 ◦ C), 67.81 ◦ C (2.19 ◦ C) and 77.44 ◦ C (2.56 ◦ C), respectively.
ence (Tinlet - Toutlet) of Design 2 was larger than that of Design 1 at the Similarly, the corresponding outlet water temperature(temperature
inlet water temperature range from 40 ◦ C to 80 ◦ C, which also illustrated difference (Tinlet - Toutlet)) of Design 1 were 39.36 ◦ C (0.64 ◦ C), 49.04 ◦ C
7
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
Fig. 9. Startup process under different input power for a 33.1 % charging ratio.
8
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
Fig. 10. Startup process under different input power for a 46.1 % charging ratio.
working medium in the LHP. Finally, the temperatures, working me temperature Tv2 was the most obvious compared with other tempera
dium circulation and pressure drop of LHP gradually reached a steady tures of the LHP, and corresponding oscillation amplitude was more
state. Moreover, all startup processes of the novel air-cooled LHP with than 25 ◦ C. And highest oscillating temperature of junction tempera
33.1 % charging ratio at the input power of 20 W, 30 W, 40 W and 50 W tures Tj at input power of 20 W and 30 W were no more than 55.60 ◦ C
can reach a stable running stage before 2500s, and the corresponding and 59.89 ◦ C. These results explained that the working medium circu
steady-state temperatures were 40.87 ◦ C, 43.07 ◦ C, 44.56 ◦ C and lation of the air-cooled LHP with 46.1 % charging ratio at input power of
46.19 ◦ C, respectively. In comparison to the results of Fig. 9, the startup 20 W and 30 W was intermittent, and intermittent time of working fluid
characteristics of the air-cooled LHP with 46.1 % charging ratio (Fig. 10) circulation was reduced with the enhancing of input power from 20 W to
presented a pseudo-startup phenomenon at input power of 20 W and 30 30 W. Under the input power of 40 W and 50 W, the startup processes of
W. And the startup processes of the air-cooled LHP at input power of 20 the novel air-cooled LHP with 46.1 % charging ratio can reach a rela
W and 30 W displayed the regular oscillation phenomenon when the test tively stable running stage when the test time was more than 3000 s and
time was more than 4750 s and 2150 s, respectively. Based on the results 1250 s, respectively. And the LHP temperature at the relatively stable
of Fig. 10(a–b), the regular oscillation amplitude of the condenser inlet running stage also showed small fluctuations, which main reason may be
Fig. 11. LHP operating characteristics vs input power under different charging ratios: (a) 33.1 %; (b) 46.1 %.
9
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
the effect of heat leakage for the reservoir and fan frequency fluctuation. on the results of Fig. 12, the thermal performance of the air-cooled LHP
The mean steady-state junction temperatures Tj for the novel air-cooled with the 33.1 % charging ratio was better than that of the 46.1 % air-
LHP with 46.1 % charging ratio were 56.91 ◦ C and 58.25 ◦ C corre cooled LHP in the input power range of 50–450W. And the junction
sponding to 40 W and 50 W, respectively. temperature difference of air-cooled LHP between 33.1 % charging ratio
Fig. 11 displays the steady-state operating characteristics of the and 46.1 % charging ratio constantly reduced with the enhancing of the
novel air-cooled LHP with charging ratios of 33.1 % and 46.1 % at input power from 50 W to 450 W. The reason for this result was that the
different input power, including the different testing point temperatures working medium of reservoir for the air-cooled LHP with a high
Tj, Te, Tr, Tv1, and condenser cover plate average temperature‾Tc. As charging ratio will absorb more leakage heat, which will result in a
shown in Fig. 11(a), the pattern of the curve Tr = f (Q) displayed a near higher junction temperature. However, the increase circulation rate and
flattened LHP operating curve, which included a variable conductance quantity of working medium will decrease the influence of heat leakage
mode (VCM) and a constant conductance mode (CCM). When the with the enhancing of input power. At the maximum of input power of
operating power did not surpassed 250 W, the temperature Tr of the 550 W, the junction temperature of the air-cooled LHP with 33.1 % and
novel air-cooled LHP with 33.1 % charging ratio was operating in VCM 46.1 % charging ratio were 92.09 ◦ C and 90.93 ◦ C, respectively. Simi
stage, which mainly reason may be the impact of heat leak for the larly, the heat transfer performance of the water-cooled LHP with the
reservoir and working medium circulation. However, the temperature Tr 33.1 % charging ratio was also better than that of the 46.1 % water-
exhibited a linear increasing trend when the input power was increasing cooled LHP when the input power did not exceed 500 W. However,
from 300 W to 550 W. In the whole input power range, the temperature the junction temperature of the water-cooled LHP with a 46.1 %
Tj, Te, and‾Tc was also shown the near linear increasing trend with the charging ratio was lower than that of the water-cooled LHP with a 33.1
enhancing of input power. At the maximum input power of 550 W, the % charging ratio in the input power range from 500 W to 750 W. In
steady-state temperature Tj and Te were 92.09 ◦ C and 82.21 ◦ C, addition, the thermal characteristics of the water-cooled LHP at the
respectively. As demonstrated from Fig. 11(b), the pattern of the curve same filling ratio were better than that of the air-cooled LHP. And the
Tr = f (Q) for the air-cooled LHP with 46.1 % charging ratio exhibited a junction temperature difference between water-cooled LHP and air-
near U-shaped LHP operating curve. And the temperature Tr presented a cooled LHP gradually increased with the increase of the input power.
near decreasing trend with the enhancing of input power from 50 W to The principal reason can be that the most of the condensing line of the
250 W, while it was constantly gone up as input power was higher than air-cooled condenser and water-cooled condenser were in sub-cooled
300 W. The main reason was that the low circulation rate and quantity of stage at low input power. In comparison to the water-cooled
working fluid under low heat loads were difficult to weaken the influ condenser, the sub-cooled area of air-cooled condenser was signifi
ence of heat leakage for the reservoir. And the circulation rate and cantly reduced with the enhancing of heat load due to low condensing
quantity of working medium were continuously rose with the improving efficiency. Many factors, including cooling requirements, economic
of input power, which will result in the decrease of reservoir tempera costs and spatial layout, should be considered for the use of the type of
ture. However, when the increased input power reached a higher value, condenser. Based on some literature reports, the temperature of elec
the effect of the circulation rate and quantity of working medium will tronic chip should not exceed 85 ◦ C to guarantee the stable and safe
not increase due to the limitation of pipe diameter and charging ratio. operation of the electronic chip. Therefore, the air-cooled LHP with 33.1
Therefore, the reservoir temperature Tr was constantly gone up when % and 46.1 % charging ratio can meet the cooling requirements of 450
the input power is more than 300 W. At the maximum input power of W and 500 W electronic chips, respectively. Similarly, the water-cooled
550 W, the steady-state temperature Tj and Te of the air-cooled LHP with LHP with 33.1 % and 46.1 % charging ratio can efficiently dissipate the
46.1% charging ratio were 90.93 ◦ C and 77.20 ◦ C, respectively. In input power of 600 W and 700 W, respectively. Compared with the
comparison to the results of Fig. 11(a) and (b), the temperature Te, Tr water-cooled LHP, the air-cooled LHP has some advantages in the
and Tv1 of the air-cooled LHP with 46.1% charging ratio presented a acceptable range of electronic chip temperature such as less auxiliary
more obvious U-shaped curve. The reason for this phenomenon was that equipment, save energy consumption and low cost. Comprehensive
the higher charging ratio will result in higher steady-state operating consideration of the cooling requirements and cooling costs of electronic
temperature at low input power. chips, the air-cooled LHP with 33.1 % charging ratio was a better cooling
The operating characteristics of the air-cooled LHP and the water- solution when the thermal design power of electronic chips was less than
cooled LHP at different charging ratios are illustrated in Fig. 12. Based 500 W. On the contrary, only the water-cooled LHP with 46.1 %
charging ratio can meet the heat dissipation requirements of the elec
tronic chips when the thermal design power of the electronic chip was
500–700 W.
10
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
affected by gravity. In this study, the impact of the LHP test directions on
the thermal performance of the air-cooled LHP was studied at the fan
voltage of 12V. The steady-state of junction temperature Tj and the Tj,
Direction i - Tj, Direction 4 are plotted as the function of the input power in
Fig. 16(a) and (b) for the seven LHP test directions, respectively. It can
be found from Fig. 16(a) and (b) that in the input power range of 50
W–250 W, the junction temperature Tj and Tj, Direction i - Tj, Direction 4 of the
air-cooled LHP at the test directions 1–3 is lower than that of the other
LHP test directions due to gravity assisting the return of the working
medium to the reservoir. However, the superiority of thermal perfor
mance of the air-cooled LHP at the positive gravity test directions 1–3
gradually weakens with the enhancing of the input power. The analysis
for the phenomenon can be that the working medium of reservoir at the
positive gravity test directions 1–3 may not directly contact the capillary
wick, and only relies on sintering copper powder on the inside wall of
the reservoir for the transfer of the working medium. For the anti-gravity
test direction 5, the junction temperature Tj and Tj, Direction i - Tj, Direction 4
of the air-cooled LHP at the test direction 5 is higher than that of the
other LHP test directions at the low input power (≤100 W). This is
Fig. 13. Junction temperature vs input power at different fan voltages.
because under anti-gravity test direction 5 and low input power, low
vapor evaporation makes it more difficult to push the working medium
voltage of 6 V, 8 V, 10 V and 12 V. The relationship between the RLHP,
from the pipeline into the reservoir. However, with the increasing of
Rsys and input power at different fan voltages were exhibited in Fig. 14
input power, the influence of the anti-gravity test direction 5 on the
(a) and (b), separately. The result of Fig. 14 was displayed that the RLHP
thermal performance of the air-cooled LHP gradually decreases due to
was obviously lower than the Rsys. And the RLHP and Rsys were illustrated
the increasing vapor evaporation capacity and low anti-gravity angle
a trend of declining obviously at first and then tending to a constant
(only 5◦ ). On the other hand, the circulation rate of the working medium
value with the increasing of input power. At the input power range from
increases at the relatively high input power. And the working medium of
50 W to 350 W, the RLHP at fan voltage of 6 V was lower than that at
the reservoir was more conducive to transfer to the capillary wick at the
other fan voltages. When the input power was more than 400 W, the
anti-gravity test directions. In the entire input power range from 50 W to
minimum RLHP value of 0.028 ◦ C/W was gained at the input power of
750 W, the thermal performance of the air-cooled LHP at the test di
500 W and fan voltage of 12 V. At the entire input power range from 50
rections 6, 7 is generally worse than that of the horizontal position due
to 550 W, the Rsys of 0.123 ◦ C/W at fan voltage of 12 V was lower than
to the influence of gravity. At the largest input power of 550 W, the
that at other fan voltages. At the largest input power of 550 W, the Rsys
junction temperature of the air-cooled LHP at LHP test directions 1–7 are
values of 0.154 ◦ C/W, 0.136 ◦ C/W, 0.131 ◦ C/W and 0.123 ◦ C/W were
arranged from small to large as follows: LHP direction 3 < LHP direction
achieved at the fan voltage of 6 V, 8 V, 10 V and 12 V, respectively.
5 < LHP direction 4 < LHP direction 7 < LHP direction 2 < LHP di
rection 6 < LHP direction 1, and corresponding junction temperature
4.2.3. Effect of LHP test direction
values were 87.27 ◦ C, 87.63 ◦ C, 87.93 ◦ C, 89.36 ◦ C, 91.36 ◦ C, 93.81 ◦ C
The study of LHP test directions is crucial to the thermal performance
and 94.50 ◦ C. Fig. 17(a) and (b) display the relationship between ther
of the LHP, which can effectively determine the range of the working
mal resistance (RLHP and Rsys) and input power at seven different LHP
position of the LHP and avoid the operation of the LHP in the non-
test directions and the fan voltage of 12 V. It is found here that the RLHP
working range. Seven different air-cooled LHP test directions are illus
and Rsys shown a tendency of increasing first and then approaching a
trated in Fig. 15. When the position of evaporator is lower than that of
constant value at all LHP test directions. The effect of LHP test directions
condenser, the LHP test directions 1–3 are regarded as the positive
on thermal resistance (RLHP and Rsys) was significant when the input
gravity directions. On the contrary, the LHP test direction 5 is consid
power was less than 300W. However, when the input power was more
ered as the anti-gravity test direction. The LHP test direction 4 is the
than 300 W, the effect of LHP test directions on thermal resistance (RLHP
horizontal position without gravity assistance. And the LHP test di
and Rsys) gradually decreased. For the LHP test directions 1–7, the
rections 8 and 9 are the horizontal side directions, which may be
minimum RLHP values of 0.037 ◦ C/W, 0.038 ◦ C/W, 0.025 ◦ C/W,
Fig. 14. The input power dependences of (a) RLHP and (b) Rsys at different fan voltages.
11
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
Fig. 16. (a) Junction temperature Tj and (b) Tj, Direction i – Tj, Direction 4 as a function of input power at different LHP test directions.
Fig. 17. (a) RLHP and (b) Rsys as a function of input power at different LHP test directions.
0.028 ◦ C/W, 0.024 ◦ C/W, 0.031 ◦ C/W and 0.029 ◦ C/W were reached at 4.3. Comparison of thermal characteristics
the input power of 400 W, 550 W, 550 W, 500 W, 550 W, 500 W and 550
W, respectively. And the minimum Rsys values of 0.135 ◦ C/W, 0.131 ◦ C/ At present, many researchers were devoted to the research of LHP for
W, 0.121 ◦ C/W, 0.123 ◦ C/W, 0.124 ◦ C/W, 0.135 ◦ C/W and 0.128 ◦ C/W cooling high power density electronic chips. Compared with the
were reached at the input power of 500 W, 550 W, 550 W, 550 W, 550 research of water-cooled LHP, the research of air-cooled LHP is less due
W, 550 W and 550 W, respectively. to low heat transfer capacity. However, as a traditional and cheap
cooling technology, some researchers still insist on strengthening the
12
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
Q
COPwater− cooled = (14)
Pcompressor + Ppump + Pfan
where Pfan, Pcompressor, and Ppump are the power of fan, compressor and
pump, respectively.
The COP value of the air-cooled LHP system and water-cooled LHP
system at different operating heat loads for the air cooling condition of
fan voltage 12 V, and the water cooling condition of temperature of
20 ◦ C and volume flow speed of 4 L/min are displayed in Fig. 19. It was
obviously found that the COP value of the air-cooled LHP system was
much larger than that of water-cooled LHP system in the entire input
power range from 50 to 550 W, which indirectly indicated the air-cooled
LHP system was more efficient and energy-saving than the water-cooled
Fig. 20. Total energy consumption in a 5-year period for different LHP cool
LHP system. At the highest input power of 550 W, the COP value of the
ing systems.
air-cooled LHP system and water-cooled LHP system were 20.37 and
Fig. 18. Comparison of thermal characteristics between this study and other literatures: (a) Junction temperature vs input power; (b) Junction temperature vs power
density. { , the data from references [27,28]; , the data from reference [29]; , the data from reference [22]; , the data from reference [30]; , the data from
reference [31]; , the data from reference [21]; , the data in this work}.
13
K. Xiong et al. International Journal of Thermal Sciences 196 (2024) 108719
14