Presented by:

Richard Crossley CSSW, WDS


Technical Director

Newton House, 17-19 Sovereign Way, Tonbridge, Kent TN9 1RH


T: 01732 360095| E: info@newtonwaterproofing.co.uk| Certificate ISO 9001
W: www.newtonwaterproofing.co.uk Number: ISO 14001
12252 OHSAS 18001

10/10/2016 Newton Waterproofing Systems © 2


2
Newton Waterproofing Systems head office, Tonbridge
“To provide an overview on the types of systems
utilised to provide protection to
below ground structures from water from
the ground in the UK.”

 The importance of BS 8102:2009 and how to


design waterproofing systems

 Types of waterproofing systems used to


protect structures internally and externally

 Different levels of waterproofing protection


in the UK explained

 Failed basements – why failures happen and


how to deal with the problem using Cavity
Drain Membrane Systems

 The importance of using a professional


waterproofing contractor (NSBC) for design
and installation who can offer a
guarantee for their work

Newton have extensive training facilities

10/10/2016 Newton Waterproofing Systems © 4


10/10/2016 Newton Waterproofing Systems © 5
10/10/2016 Newton Waterproofing Systems © 6
Three Defining Factors

When looking at waterproofing solutions


there are three defining factors:

 Consideration to the
recommendations of BS 8102:2009
 What form of structure you are
intending to use
 What is the internal space going to
be used for

10/10/2016 Newton Waterproofing Systems © 7


BS 8102:2009

The Code of Practice for the Protection of Below Ground


Structures Against Water From the Ground

10/10/2016 Newton Waterproofing Systems © 8


Reference Material

 BS 8102:2009: Code of Practice for the


protection of structures against water from
the ground

 ICE: Reducing The Risk Of Leaking


Substructures (A Clients Guide)

 CIRIA 139/140: Water Resisting


Basement Construction

10/10/2016 Newton Waterproofing Systems © 9


NHBC: Chapter 5.4 ‘Waterproofing of Basements and
other Below Ground Structures’

The National House Building Council (NHBC)


have clarified the recommendations of
BS 8102:2009 with the introduction of the new
Chapter 5.4 ‘Waterproofing of basements and
other below ground structures’.

The new Chapter introduces meaningful


benchmarks and supporting technical guidance
for a range of situations where the structure is
required to resist the ingress of water from the
ground and other sources, where ‘normal’
waterproofing arrangements are not considered
appropriate.

10/10/2016 Newton Waterproofing Systems © 10


Design Philosophy and Design Team

 The Standard recognises that, for a below ground


project to be successful, strategies for dealing with
groundwater, soil gases and contaminants are
considered from the very earliest stages of the
design process

 A “Waterproofing Specialist” should be included


as a part of the design team so that an
integrated waterproofing solution is created

 All design decisions made by others that might


have an impact on the waterproofing design
should be brought to the attention of the
waterproofing/ specialist designer and installing
contractors. Final decisions and any
recommendations should be approved by the
designer.

If a Waterproofing Design Specialist is not involved in the design, the designer is culpable

10/10/2016 Newton Waterproofing Systems © 11


Design To Expect A High Water Table

A risk assessment should be carried out which considers the long term pressures, the effects of surface water infiltration and
the use of external drainage, cut-off walls and the local geology and topography both recent and historical.

In addition, consideration should be made for:


burst water mains and sewers, adjacent trees,
sulphates, radon, methane and other ground
gases and contaminates.

“Even when the site investigation indicates dry


conditions, the risk of some waterlogging in the
future should be assumed.”

“Even in a permeable subsoil, ground water


requires time to drain away and this can result in
limited pressure periodically coming to bear
against the structure.”

Waterproofing measures should be designed on the basis of water to the full height of the retained
ground at some point in the structure’s life.

10/10/2016 Newton Waterproofing Systems © 12


Protection against
water ingress by a
‘barrier membrane’
applied to the structure

Type A Protection

‘Structurally integral’
joint seals and
maintainable interjoint
protection against
water transmission

Type B Protection

An
An
Aninternally
internally
internally
maintainable
maintainable
maintainable‘drained
‘drained
‘drained
system’
system’
system’with
with
withdedicated
dedicated
dedicated
ground
ground
groundwater
water
water
discharge
discharge
dischargemanagement
management
management

Type
Type
TypeCCCProtection
Protection
Protection

10/10/2016 Newton Waterproofing Systems © 13


Type A (Barrier Protection)

Has no integral protection against water


penetration and relies totally on a waterproofing
membrane to keep water out.

Liquid Waterproofing Membranes

External Waterproofing and Drainage Membranes

Multilayer
systems

Can be one or
two part systems

10/10/2016 Newton Waterproofing Systems © 14


Type A
(Barrier/Tanked Protection)

Newton System 200

10/10/2016 Newton Waterproofing Systems © 15


Type B (Integral Protection)

Requires that the structure itself be constructed as


an integral water-resistant shell.

Waterbars, Waterstops and Waterplugs

10/10/2016 Newton Waterproofing Systems © 16


Type B
Waterbars provide Type B protection

One-part system

10/10/2016 Newton Waterproofing Systems © 17


Type B
(Structurally Integral Protection)

10/10/2016 Newton Waterproofing Systems © 18


Type C (Drained Cavity Protection)

Incorporating a drained cavity within the


structure.

Cavity Drain Waterproofing

 Professionally installed internally after


construction of basement

 Provides zones of depressurisation at


strategic points in the structure

 The most effective and trouble free


standalone waterproofing system

10/10/2016 Newton Waterproofing Systems © 19


Type C
(Drained) Protection: Cavity Drain Waterproofing

10/10/2016 Newton Waterproofing Systems © 20


Combination Waterproofing Systems

BS 8102:2009 advises that a Combined Waterproofing


System be considered where:

A. The likelihood of leaking is high


B. The consequences of leakage is
unacceptable
C. Unacceptable water vapour transmission
could otherwise occur

Consideration should be given to the


type of combined protection i.e.

 Type A and Type B


 Type A and Type C or
 Type B and Type C

A typical combination waterproofing design showing


Newton System 500 cavity drain system internally (Type C) and Newton
System 400 membrane externally (Type A)

10/10/2016 Newton Waterproofing Systems © 21


10/10/2016 Newton Waterproofing Systems © 22
10/10/2016 Newton Waterproofing Systems © 23
Outwing vs Weatherald

A very high profile case which has set a precedent in the


waterproofing industry. The end ruling of the case states that it is
not reasonable for a tanking system to be applied 100% defect
free.

This means that if you are using a system which has to be 100%
defect free as your only waterproofing system, and it fails, you
can be held responsible.

10/10/2016 Newton Waterproofing Systems © 24


Case Study: Tanking System Failure

Project Overview: £12m house in Fulham

Scenario Builder installed a cheap waterproofing


solution

Why It Went Wrong: Wrong product, installed in


the wrong place – on the inside rather than the
outside. Areas such as wall/floor junction ignored

Consequences of Failure: Burst water main led to


water pouring into the property. Tens of thousands
of pounds of damage

Could Have Been Avoided: If a Cavity Drain


Membrane System had been installed to manage
ingressing water

10/10/2016 Newton Waterproofing Systems © 25


10/10/2016 Newton Waterproofing Systems © 26
Case Study: Type A ‘Sandwiched’ Design Failure

Project Overview: Existing Commercial Project

Scenario: A single Type A waterproofing system was installed here.

Why It Went Wrong: No consideration was given to the ‘form and


feasibility of remedial treatment’

Consequences of Failure: When the system failed, there was no way


to detect where the failure so there was a great deal of disruption
caused by trying to locate and fix the problem.

Could Have Been Avoided: Installation of a Cavity Drain System


would have included specially designed inspection ports to locate
any problems. In addition, the Cavity Drain System would have
depressurised the water meaning that water ingress would be
minimal, even if the system was damaged

10/10/2016 Newton Waterproofing Systems © 27


Case Study: Multiple System Failure

Project Overview: Large Scale Multi-Level New-


Build Basement, London

Scenario: The two forms of waterproofing system


used here were Type A ‘Barrier’ Protection and
Type B ‘Integral’ Protection

Why It Went Wrong: Failure of Type A system and


caused flooding, water level rose to 5 feet
internally!

Consequences of Failure: Very high cost of


remedial work, plus project delayed by many
months

Could Have Been Avoided: A Waterproofing


Specialist would have designed a Combination
Waterproofing System to negate any risk of water
ingress – probably a Type A, B and C System for a
project of this size

10/10/2016 Newton Waterproofing Systems © 28


Case Study: Standalone System

Project Overview: Existing Building, Basement Conversion


to Office Space

Scenario: Installation of a Type A System – consideration


has not been given to the type of structure to which it was
applied

Why It Went Wrong: Water pressure created tensile


bending stresses causing the internal floor slab to lift and
break

Consequences of Failure: Damage was extensive and


costly – both in the cost of remediation work and due to
the fact that the office needed to be out of service until it
was fixed.

Could Have Been Avoided: A Type C Drained Cavity


System should have been used to depressurise water, and a
supporting Type A system would have been recommended
to give even more robust protection.

10/10/2016 Newton Waterproofing Systems © 29


This flow chart from BS 8102:2009
outlines the principal factors and stages
that need to be addressed in order to
produce a robust waterproofing
solution for a below ground structure

10/10/2016 Newton Waterproofing Systems © 30


A Type C maintainable solution is ideal for new-build basements and refurbishment projects.
The System comprises four components: Cavity Drain Membranes, Drainage, Pumps and Control Systems.

10/10/2016 Newton Waterproofing Systems © 31


Type C cavity drain system internally, Type B waterbars to construction joints

10/10/2016 Newton Waterproofing Systems © 32


Type A bonded sheet membranes externally, Type C cavity drain system internally

10/10/2016 Newton Waterproofing Systems © 33


Type A bonded sheet membranes externally, Type B waterbars in the construction joints
Type C cavity drain system internally,

10/10/2016 Newton Waterproofing Systems © 34


10/10/2016 Newton Waterproofing Systems © 35
Listed Building Requirements

Section 7 of the Planning (Listed Buildings


and Conservation Areas) Act 1990, states
that ‘no person shall execute or cause to be
executed any works for the demolition of a listed building or for
its alteration or extension in any manner which would affect its
character [emphasis added] as a building of special architectural
or historic interest, unless the works are authorised’.

The fundamental challenge when dealing with buildings of


special architectural or historic interest is therefore to maintain
structural and aesthetic integrity, whilst remaining sympathetic
in the product application and still achieving the desired effect.

Damp proofing and cavity drain membranes can be


sympathetically applied with little or no preparation at all and
depending on the chosen wall finish, often only require the very
minimum of strategically placed fixings to hold the membrane in
place. They could – if ever required – be removed at a later date
so the building could be restored to the original condition, which
also meets Listed Building recommendations for being a Damp proof membranes are installed throughout Windsor Castle
reversible solution.

10/10/2016 Newton Waterproofing Systems © 36


Case Study: The Royal Courts of Justice

This Grade I listed structure had a labyrinth of unused


basement areas. With space at a premium, a large part of the
brick basement area was converted into habitable space.

A full Type C Cavity Drain System was installed by a Specialist


Waterproofing Contractor. The System was quick to install and
sympathetic to the structure, making it the ideal
waterproofing solution.

The convoluted Victorian Bird Beak Arches were


sympathetically waterproofed whilst retaining the original
features of this historic property, thus meeting Listed Building
Requirements. The vaults are now fully refurbished and
provide a habitable area to Grade 3 of the environmental
table within BS 8102:2009

Following the success of this project, the Specialist


Waterproofing Contractor was commissioned to complete a
second area to the same specification, with plans to renovate
further areas of the immense below ground infrastructure in Type C cavity drain system installed internally
the future.

10/10/2016 Newton Waterproofing Systems © 37


Rapid Reoccupation Following Flooding

Lord Deben, Chairman of the Committee on Climate Change recently


stated: “climate change is expected to increase the frequency and
magnitude of severe flooding across the UK”

Defences that might historically have provided protection against a


1 in 100 year flood will, with climate change, provide a much lower
level of protection and be overtopped more frequently. The latest
projections suggest periods of intense rainfall could increase in
frequency by a factor of five this century as global temperatures rise.

A saturated wall can take up to a month per inch of its thickness to


dry out and even with dehumidifiers, heaters and air changing units
this process can still be painfully slow and inhibit any successful
reoccupation for a prolonged period of time.

The installation of cavity membranes can speed up the reoccupation


of flood affected buildings as they can be installed while the wall is
still damp. The membrane will form an impermeable barrier which
separates new finishes from the damp structure so the new wall Flood rescue by the British Army and the Mountain Rescue at Queens
finishes will not be affected by the salts and staining which could Staith Road near the Ouse Bridge in York City Centre after heavy rain,
occur during the drying process. on 27th December 2015

10/10/2016 Newton Waterproofing Systems © 38


Case Study: Designing A Flood Mitigation System

South Hinksey, Oxfordshire suffers from high flood risk. In 2007, a major
flood engulfed the village with devastating results.
A full Cavity Drain System was installed in five properties in the village.
Sump and pumps were installed to manage any ingression of water
through the building fabric and through the floor to the sump and pump
systems so problem water could be evacuated in the event of ingress.

With the major flood in Oxfordshire in November 2012 these systems


were tested to the extreme, with 500 to 800mm of water engulfing the
village completely. The Cavity Drain System protected all the properties it
was installed in, while houses all around were flooded and in some cases
families were evacuated from their homes.

“My friends and family were amazed how well the system did exactly what
it was supposed to. Following the event, I have not had to claim on my
insurance, I have not had to clean up or had any stress put on me, as my
home was saved. My neighbours whom had not installed the flood
protection were devastated at the amount it is going to cost them to
repair the damage caused by the flooding, the stress it caused and is
Ingressing water is expelled using a sump and pump
causing and the sheer turmoil it leaves behind” – Detective Sgt Maria
system - and the homeowner could stay in his property
Banks, Local CID, Oxford Police Station.

10/10/2016 Newton Waterproofing Systems © 39


 Newton Specialist Basement Contractors (NSBC)
are an elite group of professional structural
waterproofing contractors who work in
partnership with Newton Waterproofing Systems
to provide the specifier and their clients with the
highest quality products, design and installation
available in all aspects of domestic and
commercial basement waterproofing

 NSBC contractors can offer peace of mind to the


designer and the client by taking full design
liability on the project, and can fulfil the role of
‘waterproofing design specialist’ as recommended
by BS 8102:2009

 All members of the scheme adhere to very strict


membership criteria. NSBCs are required to
demonstrate the ability to deliver quality design
and workmanship, resulting in a meaningful
scheme where all members provide a level of
superior technical excellence unsurpassed within
the industry

10/10/2016 Newton Waterproofing Systems © 40


 At Newton Waterproofing Systems we take our
responsibility to protect and preserve the
environment very seriously and are committed to
the prevention of pollution. Therefore we strive to
use the most environmentally friendly materials and
processes in all of our activities.

 We are committed to being compliant with all


environmental legal requirements, any other
requirements to which we subscribe, to using all our
resources wisely and to disposing of waste
responsibly.

 Planning and control of our processes is


documented in our quality and environmental
management system in line with ISO 9001:2008
(Quality) and ISO 14001:2004 (Environmental)
Standards.

 Newton Waterproofing Systems are the first


construction industry supplier to gain full
membership into RECOUP, the UK’s leading
authority on plastics waste and resource
management.

10/10/2016 Newton Waterproofing Systems © 41


 In-house CAD design service

 3D sections and details available

 BIM objects for insertion into your project

 NBS Create and NBS Building used


in-house to produce bespoke specifications
tailored to your project

 Newton Waterproofing APP features all our


product datasheets, case studies and
technical drawings