Cooling Load Check Figure: (Based On The AIRAH Handbook 3rd Edition)
Cooling Load Check Figure: (Based On The AIRAH Handbook 3rd Edition)
Only use these figures for preliminary estimates or to check a full load estimate.
406762490.xlsx
DUCT SIZE - 3.0m/sec AIR QUANTITY - l/sec DUCT
150 0- 60
200 51 -100
250 101 -160
300 161 -250 Outlet Supply Duct
350 251 - 400
400 401 - 450
450 451 -500
DUCT SIZE - 4.0m/sec AIR QUANTITY - l/sec DUCT
200 130
250 200
300 280
350 380 Branch Duct - two or
400 480 more diffusers
450 630
500 750
550 1000
DUCT SIZE - 5.0m/sec AIR QUANTITY - l/sec DUCT
300 350
350 485
400 650
Main Duct - Main SA
450 780
off fan coil
500 1100
550 1250
600 1500
Refrigerated Systems
Low Average High Very High
Litres/m2 7.1 7.8 8.5 9.5
watts/m2 95-100 130 - 155 160 - 175 180 -200
Evaporative Cooling
Low Average High Very High
Litres/m2 18.5 20.3 21.1 24.7