Professional Documents
Culture Documents
Refrigeration Basics PDF
Refrigeration Basics PDF
Refrigeration Basics PDF
We are offering a single source for one of the widest ranges of innovative refrigeration
and air conditioning components and systems in the world. And, we back technical
solutions with business solution to help your company reduce costs,
Refrigeration
streamline processes and achieve your business goals. - an introduction to the basics
Danfoss A/S • www.danfoss.com
REFRIGERATION &
DKRCC.PF.000.F2.02 Produced by Danfoss AC-DSL, HBS. 07.2007
AIR CONDITIONING DIVISION Lecture
Automatic Controls and Compressors for refrigeration
The contents of this book are intended to interest those who are not engaged every day with refrigeration
plant but who wish to extend their knowledge on the basic principles of appliances they see every day.
When compiling the material for the booklet a deliberate attempt was made to provide a thorough descrip-
tion of the elementary principles involved together with an explanation in everyday language of the practical
design of the individual components.
http://www.danfoss.com/BusinessAreas/RefrigerationAndAirConditioning
Nordborg, 2007
Contents
1. Introduction........................................................................................................................................................................................... 3
2. Fundamental terms............................................................................................................................................................................ 4
2.1 Unit systems..................................................................................................................................................................................................................................4
2.2 Temperature..................................................................................................................................................................................................................................4
2.3 Force and pressure......................................................................................................................................................................................................................5
2.4 Heat, work, energy and power...............................................................................................................................................................................................5
2.5 Substances and phase change...............................................................................................................................................................................................6
2.6 Latent heat.....................................................................................................................................................................................................................................7
2.7 Superheat.......................................................................................................................................................................................................................................7
2.8 Refrigerant diagrams.................................................................................................................................................................................................................8
3. Refrigerant circuit............................................................................................................................................................................... 9
3.1 Evaporator......................................................................................................................................................................................................................................9
3.2 Compressor...................................................................................................................................................................................................................................9
3.3 Compressor, method of operation........................................................................................................................................................................................9
3.4 Condenser................................................................................................................................................................................................................................... 10
3.5 Expansion process.................................................................................................................................................................................................................... 10
3.6 High and low pressure sides of the refrigeration plant......................................................................................................................................................10
Aa0_0002_00_A1
that removes heat.
R64-1866.10
were the first to find out that ice increased the life
Danfoss
and improved the taste of drinks and for centu-
ries Eskimos have conserved food by freezing it.
Aa0_0003_00_A1
As a consequence of this knowledge, it was now
possible to use refrigeration to conserve food-
stuffs and natural ice came into use for this pur-
pose.
Foodstuff conservation
Process refrigeration
Air conditioning plants
R64-1869.10
Drying plants
Danfoss
2. Fundamental terms On an international level, agreement has been Quantity SI-unit Alternative units
reached on the use of the Systeme International Time s (second) h (hour)
2.1 Unit systems d’Unités - often referred to as the SI-system. For a
Length m (meter) in (inch)
number of countries the implementation of the ft (foot)
SI-system is still an on-going process. Mass kg (kilogram) lb (pound)
Temperature K (Kelvin) °C (Celsius)
In this booklet the SI-system will be the primary °F (Fahrenheit)
unit system used. However, in many parts of the
Force N (Newton) kp (kilopond)
refrigeration community it is still practice to use
metric units or other alternative units. Therefore, Pressure Pa (Pascal) = N/m2 bar
the practically used alternative units will be given atm (atmosphere)
in parenthesis where needed. mm Hg (millimeter mercu-
ry column)
psi (pound per square inch)
The table shows the SI-units and the other often Energy J (Joule) = Nm kWh (kilowatt hour)
used alternative units for the quantities that are cal (calorie)
used in this booklet. Btu (British thermal unit)
Power W (Watt) = J/s calorie/h, Btu/h
The practical use of the SI-units is strongly associ- The choice of prefix is “free” but the best choice
ated with the use of the decadic prefixes to avoid will normally be the one where the value written
writing either very small or large numbers. A part will be in the range from 0.1 to 999.9.
of the prefixes used can be seen in the table be-
low. Prefixes should not be used for combined SI-units
- except when [kg] is used.
Example:
The atmospheric air pressure is 101325 Pa. Using Example:
the decadic prefixes from the table below the 2000 W/m2 K should be written as 2.000 × 103
best way of writing this would be 101.325 kPa. W/m2 K and not as 2 kW/m2 K.
Name pico nano micro mili kilo Mega Giga Tera Peta
Prefix p n m m k M G T P
Factor 10-12 10-9 10-6 10-3 103 106 109 1012 1015
2.2 Temperature Temperature is a very central property in refriger- temperature scale because its reference point
ation. Almost all refrigeration systems have the (0 °C) is defined by the freezing point of water
purpose of reducing the temperature of an (equal to 273.15 K).
object like the air in a room or the objects stored
in that room. The only difference between Kelvin and Celsius is
the difference in reference point. This means that
The SI-unit for temperature Kelvin [K] is an abso- a temperature difference of 1 °C is exactly the
lute temperature because its reference point [0 K] same as a temperature difference of 1 K.
is the lowest temperature that it in theory would
be able to obtain. In the scientific part of the refrigeration commu-
nity temperature differences are often described
When working with refrigeration systems the using [K] instead of [°C]. This practice eliminates
temperature unit degree Celsius [°C] is a more the possible mix-up of temperatures and temper-
practical unit to use. Celsius is not an absolute ature differences.
Fundamental terms The SI-unit for force is Newton (N) which is actual-
ly a [kg m/s2].
2.3 Force and pressure
A man wearing skis can stand in deep snow with-
out sinking very deep - but if he steps out of his
skis his feet will probably sink very deep into the
snow. In the first case the weight of the man is
distributed over a large surface (the skis). In the
second case the same weight is distributed on
the area of his shoe soles - which is a much small-
er area than the area of the skis. The difference
between these two cases is the pressure that the
man exerts on the snow surface.
2.4 Heat, work, energy and Heat and work are both forms of energy that can a lower temperature than that of the object you
power be transferred between objects or systems. The wish to cool. Putting these two objects into con-
transfer of heat is closely connected to the tem- tact will cause a transfer of heat away from the
perature (or temperature difference) that exists object you wish to cool and, consequently, its
between two or more objects. By itself heat is al- temperature will decrease. In other words, cooling
ways transferred from an object with high tem- an object is the same as transferring energy (heat)
perature to objects with lower temperatures. away from the object.
Heating of water in a pot on a stove is a good
everyday example of the transfer of heat. The The transfer of work is typically connected to the
stove plate becomes hot and heat is transferred use of mechanical shafts like the one rotating in
from the plate through the bottom of the pot and an electric motor or in a combustion engine.
to the water. The transfer of heat to the water Other forms of work transfer are possible but the
causes the temperature of the water to rise. In use of a rotating shaft is the primary method
other words, heating an object is the same as trans- used in refrigeration systems.
ferring energy (heat) to the object.
As mentioned both heat and work are forms of en-
In many practical applications there is a need to ergy. The methods of transfer between objects are
reduce the temperature of an object instead of different but for a process with both heat and work
increasing it. Following the example above this transfer it is the sum of the heat and work transfer
can only be done if you have another object with that determines the outcome of the process.
R64-1850.10
o
2.4 Heat, work, energy and increase the temperature of 1 kg of water from 15 15 C
Danfoss
power (cont.) to 16 °C is 4.187 kJ. The 4.178 kJ can be trans-
ferred as heat or as work - but heat would be the
most used practical solution in this case.
2.5 Substances and phase All substances can exist in three different phases:
change solid, liquid, and vapour. Water is the most natural
example of a substance that we use almost every-
day in all three phases. For water the three phases
have received different names - making it a bit
confusing when using it as a model substance.
The solid form we call ice, the liquid form we just
call water, and the vapour form we call steam.
R64-1851.10
What is common to these three phases is that the
Danfoss
water molecules remain unchanged, meaning
that ice, water, and steam all have the same
chemical formula: H2O.
When taking a substance in the solid to the liq- taking a substance from the vapour to the liquid
uid phase the transition process is called melting phase the transition process is called condens-
and when taking it further to the vapour phase ing and when taking it further to the solid phase
the transition process is called boiling (evapora- the transition process is called freezing (solidifi-
tion). When going in the opposite direction cation).
At constant pressure the transition processes dis- temperature increases until it reaches 100 °C -
play a very significant characteristic. When ice is then evaporation starts. During the evaporation
heated at 1 bar its temperature starts rising until process the temperature remains at 100 °C. When
it reaches 0 °C - then the ice starts melting. all the liquid water has evaporated the tempera-
During the melting process the temperature does ture of the steam left in the pot will start rising.
not change - all the energy transferred to the
mixture of ice and water goes into melting the ice The temperature and pressure a substance is ex-
and not into heating the water. Only when the ice posed to determine whether it exists in solid, liq-
has been melted completely will the further uid, or vapour form - or in two or all three forms
transfer of energy cause its temperature to rise. at the same time. In our local environment iron
The same type of behaviour can be observed appears in its solid form, water in its liquid and
when water is heated in an open pot. The water gas forms, and air in its vapour form.
R64-1852.10
2.5 Substances and phase chocolate at 26 °C and most refrigerants melt at
Danfoss
change (cont.) temperatures around -100 °C!
2.6 Latent heat Going back to the process of ice melting it is im-
portant to note that the amount of energy that
335 kj
must be transferred to 1 kg of ice in order to melt
it is much higher than the energy needed to (80 kcal)
change the temperature of 1 kg of water by say
1 K. In section 2.4 the specific heat capacity of
R64-1853.10
water was given as 4.187 kJ/kg K. The energy
Danfoss
needed for melting 1 kg of ice is 335 kJ. The same
amount of energy that can melt 1 kg of ice can
increase the temperature of 1 kg of water by
(335 kJ/4.187 kJ/kg K) = 80 K!
When looking at the boiling process of water the ice and while the ice melts the temperature stays
energy needed for evaporating 1 kg of water is at 0 °C.
2501 kJ. The same amount of energy that can
evaporate 1 kg of water can increase the tempe- The refrigerating effect in refrigeration systems is
rature of not 1 but 6 kg of water by 100 K! based on the use and control of the phase transi-
tion processes of evaporation. As the refrigerant
These examples show that energy transfer relat- evaporates it absorbs energy (heat) from its sur-
ed to the transitional processes between phases roundings and by placing an object in thermal
is significant. That is also why ice has been used contact with the evaporating refrigerant it can be
for cooling - it takes a lot of energy to melt the cooled to low temperature.
2.7 Superheat Superheat is a very important term in the termi- mined from a single measurement of tempera-
nology of refrigeration - but it is unfortunately ture alone - a measurement of pressure or satura-
used in different ways. It can be used to describe tion temperature is also needed. When superheat
a process where refrigerant vapour is heated is quantified it should be quantified as a tempera-
from its saturated condition to a condition at ture difference and, consequently, be associated
higher temperature. The term superheat can also with the unit [K]. If quantified in [°C] it can be the
be used to describe - or quantify - the end condi- cause of mistakes where the measured tempera-
tion of the before-mentioned process. ture is taken for the superheat or vice versa.
Superheat can be quantified as a temperature dif- The evaporation process in a refrigeration system
ference - between the temperature measured is one of the processes where the term superheat
with a thermometer and the saturation tempera- is used. This will be explained further in the next
ture of the refrigerant measured with a pressure chapter.
gauge. Therefore, superheat can not be deter-
Fundamental terms The characteristics of a refrigerant can be illustrat- content). In between you find the mixture region.
ed in a diagram using the primary properties as The regions are bounded by a curve - called the
2.8 Refrigerant diagrams abscissa and ordinate. For refrigeration systems saturation curve. The fundamental processes of
the primary properties are normally chosen as evaporation and condensation are illustrated.
energy content and pressure. Energy content is re-
presented by the thermodynamic property of spe- The idea of using a refrigerant diagram is that it
cific enthalpy - quantifying the change in energy makes it possible to represent the processes in the
content per mass unit of the refrigerant as it un- refrigeration system in such a way that analysis
dergoes processes in a refrigeration system. An ex- and evaluation of the process becomes easy.
ample of a diagram based on specific enthalpy When using a diagram determining system oper-
(abscissa) and pressure (ordinate) can be seen be- ating conditions (temperatures and pressures) sys-
low. For a refrigerant the typically applicable inter- tem refrigerating capacity can be found in a rela-
val for pressure is large - and therefore diagrams tively simple and quick manner.
use a logarithmic scale for pressure.
Diagrams are still used as the main tool for analysis
The diagram is arranged so that it displays the liq- of refrigeration processes. However, a number of
uid, vapour and mixture regions for the refriger- PC programmes that can perform the same analy-
ant. Liquid is found to the left (with a low energy sis faster and with more details have become gen-
content) - vapour to the right (with a high energy erally available.
Pressure
Liquid
Condensation
Mixture of
Liquid + Vapour
(saturated)
Evaporation Vapour
Specific enthalpy
(energy content)
3. Refrigerant circuit The physical terms for the refrigeration process A simple refrigerant circuit is built up as shown in
have been dealt with previously, even though for the sketch below. In what follows, the individual
practical reasons water is not used as a refrige- components are described to clarify a final overall
rant. picture.
Ahead of the expansion valve the liquid will be a uid begins to boil and evaporate. This evapora-
little under boiling point. By suddenly reducing tion takes place in the evaporator and the circuit
pressure a conditional change will occur; the liq- is thus complete.
3.6 High and low pressure sides There are many different temperatures in-
of the refrigeration plant volved in the operation of a refrigeration
plant since there are such things as sub-
cooled liquid, saturated liquid, saturated va-
pour and superheated vapour. There are how-
ever, in principle, only two pressures; evapo-
rating pressure and condensing pressure. The
plant then is divided into high pressure and
low pressure sides, as shown in the sketch.
4. Refrigeration process, The condensed refrigerant in the condenser is in point C1 there is super-heated vapour which
pressure/enthalpy condition A which lies on the line for the boiling means that the suction gas is heated to a higher
diagram point of the liquid. The liquid has thus a tempera- temperature than the saturated temperature.
ture tc, a pressure pc also called saturated temper- Pressure and temperature are the same at point B
ature and pressure. and at outlet point C1 where the gas is super-heat-
ed the evaporator has absorbed heat from the
The condensed liquid in the condenser is further surroundings and the enthalpy has changed to h1.
cooled down in the condenser to a lower temper-
ature A1 and now has a temperature tl and an en- When the refrigerant passes through the com-
thalpy h0. The liquid is now sub-cooled which pressor its condition changes from C1 to D.
means that it is cooled to a lower temperature Pressure rises to condensing pressure pc. The
than the saturated temperature. temperature rises to thot-gas which is higher than
the condensing temperature tc because the va-
The condensed liquid in the receiver is in condi- pour has been strongly superheated. More ener-
tion A1 which is sub-cooled liquid. This liquid gy (from the electrical motor) in the form of heat
temperature can change if the receiver and liquid has also been introduced and the enthalpy there-
is either heated or cooled by the ambient tem- fore changes to h2.
perature. If the liquid is cooled the sub-cooling
will increase and visa versa. At the condenser inlet, point D, the condition is
thus one of superheated vapour at pressure pc.
When the liquid passes through the expansion Heat is given off from the condenser to the sur-
valve its condition will change from A1 to B. This roundings so that the enthalpy again changes to
conditional change is brought about by the boil- main point A1. First in the condenser there occurs
ing liquid because of the drop in pressure to p0. a conditional change from strongly superheated
At the same time a lower boiling point is pro- vapour to saturated vapour (point E), then a con-
duced, t0, because of the drop in pressure. densation of the saturated vapour. From point E
to point A the temperature (condensing tempera-
In the expansion valve the enthalpy is constant ture) remains the same, in that condensation and
h0, as heat is neither applied nor removed. evaporation occurs at constant temperature.
From point A to point A1 in the condenser the
At the evaporator inlet, point B, there is a mixture condensed liquid is further cooled down, but the
of liquid and vapour while in the evaporator at C pressure remains the same and the liquid is now
there is saturated vapour. At the evaporator outlet sub-cooled.
tc = condensing temperature
pc = condensing pressure
tl = liquid temperature
t0 = evaporating temperature
p0 = evaporating pressure
5. Refrigerants During the examination of the refrigeration process To avoid heavy refrigerator design the pres-
the question of refrigerants was not discussed since sure, which corresponds to normal con-
5.1 General requirements it was not necessary to do so in connection with the densing pressure, must not be too high.
basic physical principles of the conditional change Relatively high evaporating temperature is
of substances. It is well known, however, that in required so that heat transmission can occur
practice different refrigerants are used according to with least possible circulating refrigerant.
the specific application and requirements. The most Refrigerant vapour ought not to have too
important factors are as follows: high a specific volume because this is a de-
terminant for compressor stroke at a partic-
The refrigerant ought not to be poisonous. ular cold yield.
Where this is impossible, the refrigerant must The refrigerant must be chemically stable at
have a characteristic smell or must contain a the temperatures and pressures normal in a
tracer so that leakage can quickly be observed. refrigeration plant.
The refrigerant ought not to be flammable The refrigerant ought not to be corrosive
nor explosive. Where this condition cannot and must not, either in liquid or vapour
be met the same precautions as in the first form, attack normal design materials.
point must be observed and local legisla- The refrigerant must not break down lubri-
tions must be followed. cating oil.
The refrigerant ought to have reasonable The refrigerant must be easy to obtain and
pressure, preferably a little higher than at- handle.
mospheric pressure at the temperatures re- The refrigerant must not cost too much.
quired to be held in the evaporator.
5.2 Fluorinated refrigerants Fluorinated refrigerants always carry the designa- R143a (CH3CF3) with a boiling point at (–46.7 °C)
tion “R” followed by a number, e.g. R22, R134a, which is slightly lower than for R22. Its thermody-
R404A and R407C. Sometimes they are met bear- namic properties makes it suitable as a refrigerant
ing their trade names. The fluorinated refrigerants for low and medium temperature applications in
all have the following features: commercial refrigeration (e.g. supermarkets).
Vapour is smell-free and non-irritant. R407C, which is a mixture of the refrigerants R32
Extensively non-poisonous. In the presence (CH2F2), R125 (CHF2CF3) and R134a (CH2FCF3) with
of fire the vapour can give off fluoric acid a boiling point at (–43.6 °C) which is slightly lower
and phosgene, which are very poisonous. than for R22. Its thermodynamic properties make
Non-corrosive. it suitable as a refrigerant for medium and high
Non-flammable and non-explosive. temperature applications in residential and com-
mercial air conditioning.
The most common fluorinated refrigerants are:
R410A, which is a mixture of the refrigerants R32
R134a, which is a substance of the ethane group (CH2F2) and R125 (CHF2CF3) with a boiling point at
with the formula CH2FCF3 and has a normal boiling (–51.4 °C) which is lower than for R22. Its thermo-
point of –26.1 °C. Its thermodynamic properties dynamic properties make it suitable as a refriger-
make it suitable as a refrigerant for medium temper- ant for medium and high temperature applications
ature applications such as domestic refrigerators. in residential and commercial air conditioning.
R22, which is a substance of the methane group Apart from these fluorinated refrigerants there is
with the formula CHF2CI and has a boiling point of a long series of others not seen very often today:
–40.8 °C. Its thermodynamic properties make it R23, R123, R124 and R218.
suitable as a refrigerant for a wide range of applica-
tions in commercial refrigeration and air condition- Except for R22, systems with fluorinated hydro-
ing. R22 is being phased out as refrigerant in many carbons are in general lubricated with polyol es-
countries due to its ozone depleting potential. ter oils (POE). These oil types are much more sen-
sitive to react chemically with water, the so-called
R404A/R507A (also known as R507), which is a “hydrolysis” reaction. For that reason systems to-
mixture of the refrigerants R125 (CHF2CF3) and day are kept extremely dry with filter driers.
5.3 Ammonia NH3 Ammonia NH3 is used extensively in large indus- burn, but it is moderately explosive when mixed
trial refrigeration plants. Its normal boiling point with air in a volume percentage of 13 to 28%.
is –33 °C. Ammonia has a characteristic smell Because of corrosion, copper or copper alloys
even in very small concentrations in air. It cannot must not be used in ammonia plants.
5.4 Secondary refrigerants The refrigerants mentioned above are often de- ings to the evaporator, the so-called “secondary
signated “primary refrigerants”. As an interme- refrigerants” can be used, e.g. water, brine, atmos-
diate link in heat transmission from the surround- pheric air etc.
The refrigerant condensate flows through the water so that it circulates several times through
cylinder, the cooling water through the tubes. the condenser. As a rule, the water becomes
The end covers are divided into sections by ribs. heated 5-10 °C when it has passed through a
The sections act as reversing chambers for the condenser.
Refrigeration plant main If it is desirable or necessary to cut down on the Water distribution tubes with nozzles are placed
components amount of water an evaporating condenser can be over the condensing coil so that water is spread
used instead. This type of condenser consists of a over and runs down the coil. The fans direct a
6.2 Condenser (cont.) housing in which there is a condensing coil, water strong flow of air across the condensing coil.
distribution tubes, deflection plates and fans. When the falling drops of water meet the up-
ward air flow some of the water will evaporate.
The warm refrigerant vapour is led to the top of This absorbs the necessary evaporating heat
the condensing coil after which it condenses from the refrigerant vapour and causes it to con-
and runs from the bottom of the coil as liquid. dense.
1. Fan
2. Deflector plate
3. Outer covering
4. Superheat remover
5. Condenser tubing
6. Air intake
7. Collecting tray
8. Overflow pipe
9. Water distribution pipe
10. Water circulation pump
11. Air intake
The principal involving water evaporation is but instead of condensing elements there
also used in connection with cooling towers. are deflector plates. Air is heated on its way
These are installed when the most practical is through the tower by direct contact with the
to place a shell and tube condenser near a trickle of water travelling downwards and
compressor. The water is then circulated in a is, therefore, able to absorb an increasing
circuit between condenser and cooling tower. amount of moisture coming from part-
evaporation. In this way, the cooling water
In principle, the cooling tower is built up loses heat. Water loss is made up by supplying
the same as the evaporating condenser, more water.
1. Fan
2. Deflector plate
3. Outer covering
4. Nozzle
6. Air intake
7. Collecting tray
8. Overflow pipe
9. Cooling water from condenser
10. Air intake
11. Cooling water return to condenser
6.3 Expansion valve The main purpose of the expansion valve is to en- cause it is not capable of regulating the amount
sure a sufficient pressure differential between the of liquid that is injected into the evaporator. A
high and low pressure sides of the plant. The sim- regulating valve must be used for this process,
plest way of doing this is to use a capillary tube the most usual being the thermostatic expan-
inserted between the condenser and evaporator. sion valve, which consists of a valve housing,
capillary tube and a bulb. The valve housing is
The capillary tube is, however, only used in fitted in the liquid line and the bulb is fitted on
small, simple appliances like refrigerators be- the evaporator outlet.
Refrigeration plant main The degree of opening of the valve is determined –10 °C evaporating temperature the bulb tem-
components by: perature could be 0 °C.
The pressure produced by the bulb temper-
6.3 Expansion valve (cont.) ature acting on the top surface of the dia- If the evaporator receives too little refrigerant the
phragm. vapour will be further superheated and the tem-
The pressure under the diaphragm, which is perature at the outlet pipe will rise. The bulb tem-
equal to the evaporating pressure. perature will then also rise and with it the vapour
The pressure of the spring acting on the un- pressure in the bulb element since more of the
derside of the diaphragm. charge will evaporate. Because of the rise in pres-
sure the diaphragm becomes forced down, the
During normal operation, evaporation will cease valve opens and more liquid is supplied to the
some distance up in the evaporator. evaporator. Correspondingly, the valve will close
more if the bulb temperature becomes lower.
Then, saturated gas appears which becomes su-
perheated on its way through the last part of the Thermostatic expansion valves are produced in
evaporator. The bulb temperature will thus be several versions and of course there are many
evaporating temperature plus superheat, e.g. at variants within each type.
As the name implies, a chiller cools down liquid. Ribbed tube evaporator
The simplest method is to immerse a coil of tube
in an open tank. Closed systems are coming into
use more and more. Here, tube coolers made simi-
lar to shell and tube condensers are employed.
7. The practical build-up Figure A shows the principle build-up of a refrig- From the receiver, an uninsulated line, the liquid
of a refrigeration plant eration plant for a simple cold store - much like line, is taken out to the cold store where it is con-
those that can be seen in butchers’ shops and su- nected to the thermostatic expansion valve at
permarkets. the evaporator inlet. The evaporator is built up
with close-pitch fins attached to tubes. It is also
The compressor unit can, for example, be in- equipped with a fan for forced air circulation and
stalled in an adjacent storage room with an outlet a drip tray.
to fresh air. Such a unit consists of a compressor
driven by V-belt and electric motor. Additionally, From the outlet side of the evaporator a line,
the base frame carries an air-cooled condenser the suction line, is led back to the compressor.
and a receiver. A fan is mounted on the shaft of The diameter of the suction line is somewhat
the electric motor to force air through the con- larger than the liquid line because it carries
denser and ensure the necessary degree of cool- vapour. For this reason the suction line is as a
ing. The line between compressor and condenser rule insulated.
is known as the discharge line.
Fan
Evaporator
Drip tray
Cold store
Compressor
Base frame
Compressor unit
Fig. A
The practical build-up of a Figure B gives details of momentary temperatures static expansion valve bulb becomes +2 °C, corre-
refrigeration plant in a refrigeration plant. At the compressor outlet sponding to the superheat set on the valve.
the pressure is 7.6 bar and the temperature is 60 °C
because of the presence of superheated gas. The As illustrated below, air temperature will vary, in
temperature in the upper part of the condenser that the air will take up heat on its way round the
will quickly fall to saturation temperature, which store from products, walls, ceiling, etc. The tem-
at the pressure concerned will be 34 °C, because perature of the air blown across the condenser
superheat is removed and condensation begins. will also vary with the time of year.
Pressure at the receiver outlet will remain more or A refrigeration plant must then be dimensioned
less the same, while subcooling of the liquid be- according to the largest load it will be subjected
gins because the temperature has fallen by 2 °C to. To be able to accommodate smaller loads, fa-
to 32 °C. cilities must exist in the plant for altering yield.
The process of making such alterations is called
In the evaporator a pressure of 1 bar and an evap- regulation and it is precisely regulation that
orating temperature of –10 °C are indicated. In the Danfoss’ automatic controls are made for. But that
last part of the evaporator the vapour becomes is a subject, which is outside the scope of this
superheated so the temperature at the thermo- publication.
Fig. B R134a
19
Notes
20
Automatic Controls and Compressors for refrigeration
We are offering a single source for one of the widest ranges of innovative refrigeration
and air conditioning components and systems in the world. And, we back technical
solutions with business solution to help your company reduce costs,
Refrigeration
streamline processes and achieve your business goals. - an introduction to the basics
Danfoss A/S • www.danfoss.com
REFRIGERATION &
DKRCC.PF.000.F2.02 Produced by Danfoss AC-DSL, HBS. 07.2007
AIR CONDITIONING DIVISION Lecture