You are on page 1of 31

3M Electrical Markets Division

Electrical Products
Selvakumar – Application Development Engineer

Medium Voltage
Termination Theory

© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Definition

To Terminate a MV
Shielded Power Cable
Means, ………………
To Discontinue, or End,
The Cable Insulation
Shield System.

2
© 3M 2010. All Rights Reserved.

1
3M Electrical Markets Division

Basic Functions of Cable Terminations

 Distribution of Voltage Stress


 Elimination of Voids
 Conduction of Charging/Faults Currents
 Adequate tracking distance
 Environmental Seal
 UV Protection

3
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Definition – Based on Required Functions

Class I Termination
Electric Stress Control
@ Cable Shield Terminus

External Leakage Current Protection


Between H.V. Conductor & Ground
( Tracking Protection )

A Seal
To the External Environment

4
© 3M 2010. All Rights Reserved.

2
3M Electrical Markets Division

Common Termination Standards

 IEEE-48
 VDE 0278
 CENELEC HD629.1 S2
 IEC 60502-4

5
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Performance Standards Comparison


3.6/6(7.2) kV Indoor Termination

6
© 3M 2010. All Rights Reserved.

3
3M Electrical Markets Division
Electric Stress Control
@ Cable Shield Terminus

Why Do We Need
Stress Control??

7
© 3M 2010. All Rights Reserved.

Distribution of Voltage Stress


3M Electrical Markets Division

Equipotential
Lines
Electrical Flux
Lines

8
© 3M 2010. All Rights Reserved.

4
3M Electrical Markets Division

When Preparing For Splicing or Terminating,


…………….

Cable Shield System


Must Be Partially Removed
WHY??

9
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Flux
Line
Separate HV Conductor From Grounded Shield

Potential
Line

10
© 3M 2010. All Rights Reserved.

5
3M Electrical Markets Division

Possible Voltage Stress


100 V/Mil ( 4 kV/mm )

Air Breakdown Strength


76 V/Mil ( 3 kV/mm )

11
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division


Insulation Damage - No Stress Control

Semi-con Removed - For Visual Clarity


12
© 3M 2010. All Rights Reserved.

6
3M Electrical Markets Division

No Stress Control

13
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Geometric Stress Control

Semi-conductive layer Stress Cone

14
© 3M 2010. All Rights Reserved.

7
3M Electrical Markets Division

Geometric Stress Control

Improved Shape

Increased Distance

Additional Insulation
15
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division


Geometric Stress Control

Concentrated
Voltage
Distribution

16
© 3M 2010. All Rights Reserved.

8
3M Electrical Markets Division

Refractive Stress Control

 Law of Refraction
 High-K (high dielectric constant) material is used to reduce stress at the shield
discontinuity by field refraction due to different K values of two adjacent dielectric
layers
 Dielectric Constant - A measurement of the ability of a material to store a charge

Material K
Air 1
Cable Insulation 3
Splicing Tape 3
Hi-K Material 30

17
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Refractive Stress Control

High Dielectric Constant ( High K )


Stress Relief Tube

Based on Theory of Field Refraction

18
© 3M 2010. All Rights Reserved.

9
3M Electrical Markets Division

Flux Line Refraction @ Dielectric Interface

K2 > K1

Insulation
K2 θ2

θ1 Insulation
K1

19
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Refractive Stress Control

 Different K values of two neighboring dielectric layers.

20
© 3M 2010. All Rights Reserved.

10
3M Electrical Markets Division
Result

Voltage Gradient

21
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Geometric Method Vs Refractive Stress Control

Geometric Refractive
Stress stress
Control Control
Method Method

22
© 3M 2010. All Rights Reserved.

11
3M Electrical Markets Division
II. External Leakage Current Protection
Between Conductor & Ground

Flashover Protection Tracking Resistance

Insulator
Material Selection
Can Be Critical

Non-Organic? Organic?

23
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Tracking – Definition

The decomposition of electrical


insulation caused by passage of
electrical current resulting in
the progressive formation of a
conducting carbon path.

24
© 3M 2010. All Rights Reserved.

12
3M Electrical Markets Division
What Causes Elect. Discharges?

 Voltage Gradient Required To Cause


Electrical Discharging in Air is Approx.
76 Volts/Mil ( 3 kV/mm ).

 Average Voltage Gradient on The Surface


Typical Termination Surface is Approx.
1 Volt/Mil ( 39.5 V/mm ).

 So, What’s The Problem?

25
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Tracking

Three Conditions Must Exist:

• CONTAMINATION • MOISTURE
- Dust - Humidity
- Chemicals - Fog
- Salt - Condensation
- Other Airborne Particles - Mist
- Snow
• VOLTAGE - Rain
- Surface Stress (V/mil)

26
© 3M 2010. All Rights Reserved.

13
3M Electrical Markets Division

Discharge
Formation Surface Resistance
Reduced When Wet

DRY BANDS
(Areas of Higher
Surface Resistance)
ELECTRICAL
&
DISCHARGES
Concentrated
Voltage Gradient (Generated in
Dry Band Areas)

27
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division


Ways to Control
Tracking
 Increase Distance from HV
to Ground
 Rain Shed (Insulator Skirts)
 Track Resistant Materials
 Porcelain
 Inorganic Fillers in
Rubber
 Inorganic Fillers in EVA
(Heat Shrink)
 Silicone Rubber

28
© 3M 2010. All Rights Reserved.

14
3M Electrical Markets Division

3
Silicone Rubber
Cold Shrink Terminations

29
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Silicone Rubber

 Silicone is Hydrophobic
 Silicone Can Recover Its Hydrophobicity
 Silicone is Inherently UV-Stable
 Silicone is Mostly Inorganic (No Conducting Carbon Path)
 Silicone Has a Smooth Surface

30
© 3M 2010. All Rights Reserved.

15
3M Electrical Markets Division

Hydrophobic vs Hydrophilic

HYDROPHOBIC HYDROPHILIC

Contact Angle

Water “balls” up Surface “wets” out

Energy from leakage current can cause


insulator surfaces to become hydrophilic

31
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Hydrophobic vs Hydrophilic – Actual Example


SILICONE RUBBER PORCELAIN

Hydrophobic Hydrophilic
(Water “Balls-up”) (Surface “Wets”)

32
© 3M 2010. All Rights Reserved.

16
3M Electrical Markets Division
Silicone Rubber
Termination Skirt
Water Beads-Up When New

33
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

SILICONE RUBBER INSULATOR


Coated with ASTM D-2132 Contaminant

Surface remains “Hydrophobic”

34
© 3M 2010. All Rights Reserved.

17
3M Electrical Markets Division

EPDM INSULATOR

UV Damage

35
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Silicone Rubber Advantages

 Silicone Insulators are superior to EPDM, EVA and porcelain


insulators
 Silicone is more hydrophobic than other polymers or
porcelain
 Silicone has the ability to regenerate its hydrophobicity in
the event that high-leakage current changes its state
 Silicone Insulators are inherently stable to UV due to its high
backbone bond energy

36
© 3M 2010. All Rights Reserved.

18
3M Electrical Markets Division
III - Seal to The Environment

Moisture Must Be Kept Out Of Terminations


In Order To, ……

 Maintain The Desired Creepage Distance

 Prevent Corrosion of Metallic Components

 Prevent Degradation of Insulations Affected By


Moisture

37
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division


III - Seal to The Environment

Top Seal
Conductor
Connection Top Seal
Conductor
Connection

Bottom Seal Bottom Seal


Jacket Seal Jacket Seal
Ground Seal Ground Seal

38
© 3M 2010. All Rights Reserved.

19
3M Electrical Markets Division
Normal
Creepage
Environmental
Path
&
Electrical
Sealing
Example Shown:
Porcelain
Normally
Compound-Filled

39
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division


Sealing - Design Considerations

 Sealing Pressure Vs. Adhesive Seal


 Pressure / Adhesive Combination
 Expansion & Contraction of Cable
 Conformability to Cable & Lug
 Cable Application Range
 Ease of Installation
 Product Life

40
© 3M 2010. All Rights Reserved.

20
3M Electrical Markets Division
III - Seal to The Environment

Material
Technology
Options

41
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division


SEALING with TAPE

42
© 3M 2010. All Rights Reserved.

21
3M Electrical Markets Division
POTTING with RESIN

43
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division


SEALING
with
HEAT SHRINK

44
© 3M 2010. All Rights Reserved.

22
3M Electrical Markets Division

SEALING
with
45
© 3M 2010. All Rights Reserved.
COLD SHRINK

3M Electrical Markets Division

Termination Technologies

 Taping Method
 Heat Shrink
 Cold Shrink
 Push-on

46
© 3M 2010. All Rights Reserved.

23
3M Electrical Markets Division

Heat Shrink Termination - An Example

47
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Heat Shrink Termination - Installation


(1)
Stress Relief
Material
(Semi-con Step
Filler)

(2)
Stress Control
Tube

48
© 3M 2010. All Rights Reserved.

24
3M Electrical Markets Division

Heat Shrink Termination - Installation


(3)
Top
Seal

(4)
Jacket
Seal

49
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Heat Shrink Termination - Installation

(5)
Separate
Insulator
Tube
Allow Tube
To Cool (6)
Before Separate Shrink
Proceeding Insulator Evenly
Skirts With no
Tilt or Sag

50
© 3M 2010. All Rights Reserved.

25
3M Electrical Markets Division

Completed Termination

Outdoor Termination
(with skirts)

Indoor Termination
(same, but without skirts)

51
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Cold Shrink Termination

52
© 3M 2010. All Rights Reserved.

26
3M Electrical Markets Division

Examples of Cold Shrink Termination Kits


3M™ QT-II Termination 3M™ QT-III Termination
Integrated 1-Piece

Silicone
Tape
Top Seal

Silicone
Grease

53
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Cold Shrink Termination - Installation

Apply mastic
seal around jacket
& neutral wires

Apply filler to fill


semi-con step

54
© 3M 2010. All Rights Reserved.

27
3M Electrical Markets Division

Cold Shrink Termination - Installation


Install termination
by removing
supporting core

Complete top seal


with application
of silicone rubber
tape

55
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Completed Cold Shrink Termination

Outdoor Termination
(With Skirts)

Indoor Termination
(Tubular, without Skirts)

56
© 3M 2010. All Rights Reserved.

28
3M Electrical Markets Division

3™ QT-III Termination
Integrated 1-Piece Design
Silicone Sealing Silicone Rubber Stress Control
Compound Insulator Compound

High Dielectric Constant Step Core


Stress Relief Tube

57
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Improvement QTII vs QTIII

Improvements QT III vs QT II

58
© 3M 2010. All Rights Reserved.

29
3M Electrical Markets Division

Benefits of Cold Shrink

• No Tools for Installation

• Low Installation Force

• Good Interfacial Pressure

• Live Seal

• Broad Application Range

• Environmentally Stable Materials

59
© 3M 2010. All Rights Reserved.

3M Electrical Markets Division

Phase Clearance

 Refer to the phase spacing guide handout to determine the


minimum recommended clearance between phases and
ground.
 In accordance with National Electrical Code (N.E.C).
 Phase clearance is not required between the same phases
for level connections. However it is still recommended to
maintain 5mm distance as a good engineering practice.

60
© 3M 2010. All Rights Reserved.

30
3M Electrical Markets Division

Phase Spacing Guide

d = Cable Jacket O.D. for single conductor cables.


= Insulator O.D. for 3-conductor cables.
r = Bending radius is suggested to correspond to
the industry norm for the specific power cable
utilized. For tape shielded cables the recommended
min. radius is 12x the overall diameter of the cable.

61
© 3M 2010. All Rights Reserved.

31

You might also like