Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/31/2019
E-Mail:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-HY 200 + HIT-Z 1/2
Effective embedment depth: hef,opti = 70 mm (hef,limit = 143 mm)
Material: DIN EN ISO 4042
Evaluation Service Report: ESR-3187
Issued I Valid: 3/1/2018 | 3/1/2020
Proof: Design method ACI 318-08 / Chem
Stand-off installation: eb = 0 mm (no stand-off); t = 8 mm
Anchor plate: lx x ly x t = 585 mm x 105 mm x 8 mm; (Recommended plate thickness: not calculated
Profile: Flat bar; (L x W x T) = 585 mm x 8 mm x 0 mm
Base material: uncracked concrete, C25/30, fc' = 3,626 psi; h = 200 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Seismic loads (cat. C, D, E, or F) no
R
- The anchor calculation is based on a rigid baseplate assumption.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.8.0
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/31/2019
E-Mail:
3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 5.651 38.678 15 OK
Pullout Strength* 5.651 33.884 17 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 8.322 25.199 34 OK
* anchor having the highest loading **anchor group (anchors in tension)
Variables
Ase,N [mm2] futa [N/mm2]
92 649.48
Calculations
Nsa [kN]
59.504
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
59.504 0.650 38.678 5.651
Variables
Np [kN]
52.129
Calculations
-
-
Results
Npn [kN] f concrete f Npn [kN] Nua [kN]
52.129 0.650 33.884 5.651
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.8.0
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/31/2019
E-Mail:
Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-08 Eq. (D-5)
f Ncbg ≥ Nua ACI 318-08 Eq. (D-1)
ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-08 Eq. (D-6)
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-08 Eq. (D-9)
1+
3 hef
y ed,N = 0.7 + 0.3 (ca,min
1.5hef )
≤ 1.0 ACI 318-08 Eq. (D-11)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-08 Eq. (D-13)
1.5
Nb = kc l √fc hef
'
ACI 318-08 Eq. (D-7)
Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
70 36 11 ∞ 1.000
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
86,432 43,911 0.745 0.901 1.000 1.000 29.316
Results
Ncbg [kN] f concrete f Ncbg [kN] Nua [kN]
38.767 0.650 25.199 8.322
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.8.0
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/31/2019
E-Mail:
4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 6.748 15.709 43 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Concrete Breakout 6.748 40.393 17 OK
Strength controls)*
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)
Variables
Ase,V [mm2] futa [N/mm2] (0.6 Ase,V futa) [kN]
92 649.48 26.182
Calculations
Vsa [kN]
26.182
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
26.182 0.600 15.709 6.748
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-08 Eq. (D-9)
1+
3 hef
y ed,N = 0.7 + 0.3 (ca,min
1.5hef )
≤ 1.0 ACI 318-08 Eq. (D-11)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-08 Eq. (D-13)
1.5
Nb = kc l √fc hef
'
ACI 318-08 Eq. (D-7)
Variables
kcp hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm]
2 70 0 0 ∞
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
43,216 43,911 1.000 1.000 1.000 1.000 29.316
Results
Vcp [kN] f concrete f Vcp [kN] Vua [kN]
57.704 0.700 40.393 6.748
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.8.0
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/31/2019
E-Mail:
6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
• The ACI 318-08 version of the software does not account for adhesive anchor special design provisions corresponding to overhead
applications.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.8.0
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/31/2019
E-Mail:
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-HY 200 + HIT-Z 1/2
Profile: Flat bar; 585 x 8 x 0 mm Installation torque: 0.040 kNm
Hole diameter in the fixture (pre-setting) : df = 14 mm Hole diameter in the base material: 14 mm
Hole diameter in the fixture (through fastening) : df = 16 mm Hole depth in the base material: 95 mm
Plate thickness (input): 8 mm Minimum thickness of the base material: 127 mm
Recommended plate thickness: not calculated
Drilling method: Hammer drilled
Cleaning: No cleaning of the drilled hole is required
293 293
21
2 53
64
x
53
1
21
Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y
1 -100 -32 - - - -
2 100 32 - - - -
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.8.0
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/31/2019
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan