You are on page 1of 8

www.hilti.it Profis Anchor 2.9.

1
Company: Page: 1
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 13.8.2022
E-Mail:

Specifier's comments:

1 Input data
Anchor type and size: HST3 M10 hef2
Return period (service life in years): 50
Effective embedment depth: hef = 60 mm, hnom = 68 mm
Material:
Approval No.: ETA-98/0001
Issued I Valid: 02/10/2019 | -
Proof: Design method EN 1992-4, Mechanical
Stand-off installation: eb = 0 mm (no stand-off); t = 6 mm
Baseplate: lx x ly x t = 120 mm x 100 mm x 6 mm; (Recommended plate thickness: not calculated
Profile: Rectangular hollow, 50 x 30 x 2,9; (L x W x T) = 50 mm x 30 mm x 3 mm
Base material: uncracked concrete, C45/55, fc,cyl = 45,00 N/mm2; h = 200 mm, partial material safety factor gc = 1,500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid baseplate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.it Profis Anchor 2.9.1
Company: Page: 2
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 13.8.2022
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads

Anchor reactions [kN] 2


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 12,283 0,735 -0,735 0,015
2 12,283 0,715 -0,715 0,015 x
Compression Tension
max. concrete compressive strain: 0,67 [‰]
max. concrete compressive stress: 20,02 [N/mm2]
resulting tension force in (x/y)=(20/0): 24,566 [kN] 1
resulting compression force in (x/y)=(-52/0): 24,926 [kN]

Anchor forces are calculated based on the assumption of a rigid baseplate.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.it Profis Anchor 2.9.1
Company: Page: 3
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 13.8.2022
E-Mail:

3 Tension load (EN 1992-4, Section 7.2.1)


Load [kN] Capacity [kN] Utilisation bN [%] Status
Steel failure* 12,283 23,214 53 OK
Pull-out failure* 12,283 22,000 56 OK
Concrete cone failure** 24,566 27,831 89 OK
Splitting failure** 24,566 35,092 71 OK
* most unfavourable anchor **anchor group (anchors in tension)

3.1 Steel failure


NRk,s [kN] gM,s NRd,s [kN] NEd [kN]
32,500 1,400 23,214 12,283

3.2 Pull-out failure


NRk,p [kN] yc gM,p NRd,p [kN] NEd [kN]
22,000 1,500 1,500 22,000 12,283

3.3 Concrete cone failure


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm] fc,cyl [N/mm2]
40.800 32.400 90 180 45,00
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
0 1,000 0 1,000 0,967 1,000
z [mm] y M,N k1 N0Rk,c [kN] gM,c NRd,c [kN] NEd [kN]
72 1,000 11,000 34,295 1,500 27,831 24,566
Group anchor ID
1, 2

3.4 Splitting failure


Ac,N [mm2] A0c,N [mm2] ccr,sp [mm] scr,sp [mm] y h,sp fc,cyl [N/mm2]
40.800 32.400 90 180 1,310 45,00
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1
0 1,000 0 1,000 0,967 1,000 11,000
N0Rk,sp [kN] gM,sp NRd,sp [kN] NEd [kN]
33,000 1,500 35,092 24,566
Group anchor ID
1, 2

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.it Profis Anchor 2.9.1
Company: Page: 4
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 13.8.2022
E-Mail:

4 Shear load (EN 1992-4, Section 7.2.2)


Load [kN] Capacity [kN] Utilisation bV [%] Status
Steel failure (without lever arm)* 0,735 18,880 4 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout failure* 0,735 37,154 2 OK
Concrete edge failure in direction x-** 1,450 15,303 10 OK
* most unfavourable anchor **anchor group (relevant anchors)

4.1 Steel failure (without lever arm)


V0Rk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
23,600 1,000 23,600 1,250 18,880 0,735

4.2 Pryout failure


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm] fc,cyl [N/mm2] k8
20.400 32.400 90 180 45,00 2,670
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N
0 1,000 0 1,000 0,967 1,000 1,000
k1 N0Rk,c [kN] gM,c,p VRd,cp [kN] VEd [kN]
11,000 34,295 1,500 37,154 0,735
Group anchor ID
1, 2

4.3 Concrete edge failure in direction x-


lf [mm] dnom [mm] k9 a b fc,cyl [N/mm2]
60 10,0 2,400 0,087 0,066 45,00
c1 [mm] Ac,V [mm2] A0c,V [mm2]
80 36.000 28.800
y s,V y h,V y a,V ec,V [mm] y ec,V y re,V
1,000 1,000 1,000 0 0,997 1,000
V0Rk,c [kN] kT gM,c VRd,c [kN] VEd [kN]
18,423 1,0 1,500 15,303 1,450

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.it Profis Anchor 2.9.1
Company: Page: 5
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 13.8.2022
E-Mail:

5 Combined tension and shear loads ( EN 1992-4, Section 7.2.3)

Steel failure
bN bV a Utilisation bN,V [%] Status
0,529 0,039 2,000 29 OK

baN + baV ≤ 1,0

Concrete failure
bN bV a Utilisation bN,V [%] Status
0,883 0,095 1,000 82 OK
(bN + bV) / 1.2 ≤ 1,0

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 9,098 [kN] dN = 0,287 [mm]
VSk = 0,545 [kN] dV = 0,101 [mm]
dNV = 0,305 [mm]
Long term loading:
NSk = 9,098 [kN] dN = 0,479 [mm]
VSk = 0,545 [kN] dV = 0,149 [mm]
dNV = 0,502 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7 Warnings
• The anchor design methods in PROFIS Anchor require rigid baseplates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the baseplate are not considered - the baseplate is assumed to
be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required
baseplate thickness with FEM to limit the stress of the baseplate based on the assumptions explained above. The proof if the rigid baseplate
assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions
and for plausibility! 
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters
of the clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• For the determination of the Psi_re,v (concrete edge failure) a concrete cover of the edge reinforcement c = 30 mm is assumed
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.it Profis Anchor 2.9.1
Company: Page: 6
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 13.8.2022
E-Mail:

8 Installation data
Baseplate, steel: - Anchor type and size: HST3 M10 hef2
Profile: Rectangular hollow, 50 x 30 x 2,9; (L x W x T) = 50 mm x 30 Installation torque: 0,045 kNm
mm x 3 mm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 10 mm
Plate thickness (input): 6 mm Hole depth in the base material: 78 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 120 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions
for use is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Hilti SIW 6AT-A22 + SI AT-A22
• Properly sized drill bit • Torque wrench
• Hammer
y

60 60

20
2

50
60

x
50

1
20

80 40

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 20 -30 80 - - -
2 20 30 80 - - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.it Profis Anchor 2.9.1
Company: Page: 7
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 13.8.2022
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
HST3 (-R) subject to:
Anchor size M8 M10 M12 M16 M20 M24
Hammer drilling*

TE2(-A) – TE30(-A) TE40 – TE70

Diamond core drilling*

DD-30W, DD-EC1

Setting tool*
Setting tool HS-SC -

Hollow drill bit drilling*

- TE-CD, TE-YD

Seismic Set/ Filling Set**

Seismic/Filling Set M8-M20 (Carbon and Stainless Steel A4) -

*Installation methods provided in ETA-98/0001


**Seismic set needed to fill the annular gap between anchor and fixture:
No annular gap, double design resistance (αgap=1)

You might also like