Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 13, 2024 Date: 13/3/2024
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-RE 500 V3 + HAS 8.8 M12
Item number: 2417171 HAS 8.8 M12x120 (element) / 2123406
HIT-RE 500 V3 (adhesive)
Effective embedment depth: hef,opti = 70.0 mm (hef,limit = 240.0 mm)
Material: 8.8
Evaluation Service Report: Hilti Technical Data
Issued I Valid: -|-
Proof: Design Method ACI 318-08 / Chem
Stand-off installation: eb = 0.0 mm (no stand-off); t = 12.0 mm
Anchor plate :
R lx x ly x t = 260.0 mm x 260.0 mm x 12.0 mm; (Recommended plate thickness: not calculated)
Application also possible with HIT-RE 500 V3 + HAS-U 8.8 M12 under the selected boundary conditions.
More information in section Alternative fastening data of this report.
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.91
www.hilti.co.th
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 13, 2024 Date: 13/3/2024
Fastening point:
3 4
Anchor reactions [kgf]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 128 125 0 -125
2 128 125 0 -125 x
3 128 125 0 -125
4 128 125 0 -125
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [kgf] Capacity f Nn [kgf] Utilization bN = Nua/f Nn Status
Steel Strength* 128 4,474 3 OK
Bond Strength** 510 2,666 20 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Failure** 510 5,336 10 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.91
www.hilti.co.th
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 13, 2024 Date: 13/3/2024
Fastening point:
Variables
2 2
Ase,N [mm ] futa [kgf/cm ]
84 8,158
Calculations
Nsa [kgf]
6,883
Results
Nsa [kgf] f steel f Nsa [kgf] Nua [kgf]
6,883 0.650 4,474 128
Nag = (AA ) y
Na
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ACI 318-11 Eq. (D-19)
f Nag ³ Nua ACI 318-11 Table D.4.1.1
ANa = see ACI 318-11, Part D.5.5.1, Fig. RD.5.5.1(b)
2
ANa0 = (2 cNa) ACI 318-11 Eq. (D-20)
t uncr
cNa = 10 da √ 1100
ACI 318-11 Eq. (D-21)
( )
1
'
y ec,Na = eN £ 1.0 ACI 318-11 Eq. (D-23)
1+
cNa
Na
ACI 318-11 Eq. (D-25)
= MAX(
c ) £
c c a,min Na
y cp,Na , 1.0 ACI 318-11 Eq. (D-27)
c ac ac
Nba = l a · t k,c · p · da · hef ACI 318-11 Eq. (D-22)
Variables
t k,c,uncr [kgf/cm ]
2
da [mm] hef [mm] ca,min [mm] aoverhead 2
t k,c [kgf/cm ]
190 12.0 70.0 130.0 1.000 98
Calculations
cNa [mm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na
187.0 243,762 139,879 0.909
Results
Nag [kgf] f bond f Nag [kgf] Nua [kgf]
4,102 0.650 2,666 510
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.91
www.hilti.co.th
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 13, 2024 Date: 13/3/2024
Fastening point:
Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-08 Eq. (D-5)
f Ncbg ³ Nua ACI 318-08 Eq. (D-1)
ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
2
ANc0 = 9 hef ACI 318-08 Eq. (D-6)
( )
1
'
y ec,N = 2 eN £ 1.0 ACI 318-08 Eq. (D-9)
1+
3 hef
ef
ACI 318-08 Eq. (D-11)
= MAX(
c ) £
c 1.5h a,min ef
y cp,N , 1.0 ACI 318-08 Eq. (D-13)
c ac ac
Nb = kc l √f'c h1.5
ef ACI 318-08 Eq. (D-7)
Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
70.0 0.0 0.0 130.0 1.000
'
cac [mm] kc l fc [psi]
117.1 17 1 4,551
Calculations
ANc [mm ]
2
ANc0 [mm ]
2
y ec1,N y ec2,N y ed,N y cp,N Nb [kgf]
152,100 44,100 1.000 1.000 1.000 1.000 2,380
Results
Ncbg [kgf] f concrete f Ncbg [kgf] Nua [kgf]
8,209 0.650 5,336 510
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.91
www.hilti.co.th
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 13, 2024 Date: 13/3/2024
Fastening point:
4 Shear load
Load Vua [kgf] Capacity f Vn [kgf] Utilization bV = Vua/f Vn Status
Steel Strength* 125 2,478 6 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength 500 5,743 9 OK
controls)**
Concrete edge failure in direction y-** 500 2,482 21 OK
Variables
Ase,V [mm ]
2
futa [kgf/cm ]
2
aV,seis
84 8,158 1.000
Calculations
Vsa [kgf]
4,130
Results
Vsa [kgf] f steel f Vsa [kgf] Vua [kgf]
4,130 0.600 2,478 125
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.91
www.hilti.co.th
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 13, 2024 Date: 13/3/2024
Fastening point:
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ] ACI 318-11 Eq. (D-41)
f Vcpg ³ Vua ACI 318-11 Table (D.4.1.1)
ANa see ACI 318-11, Part D.5.5.1, Fig. RD.5.5.1(b)
2
ANa0 = (2 cNa) ACI 318-11 Eq. (D-20)
t uncr
cNa = 10 da √ 1100
ACI 318-11 Eq. (D-21)
( )
1
'
y ec,Na = eN £ 1.0 ACI 318-11 Eq. (D-23)
1+
cNa
ac
ACI 318-11 Eq. (D-25)
= MAX(
c ) £
c c a,min Na
y cp,Na , 1.0 ACI 318-11 Eq. (D-27)
c ac ac
Nba = l a · t k,c · p · da · hef ACI 318-11 Eq. (D-22)
Variables
kcp aoverhead t k,c,uncr [kgf/cm ]
2
da [mm] hef [mm] ca,min [mm]
2 1.000 190 12.0 70.0 130.0
t k,c [kgf/cm ]
2
ec1,N [mm] ec2,N [mm] cac [mm] la
98 0.0 0.0 117.1 1.000
Calculations
cNa [mm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na
187.0 243,762 139,879 0.909
Results
Vcpg [kgf] f concrete f Vcpg [kgf] Vua [kgf]
8,204 0.700 5,743 500
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.91
www.hilti.co.th
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 13, 2024 Date: 13/3/2024
Fastening point:
Vcbg = (AA ) y
Vc
Vc0
ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-08 Eq. (D-22)
f Vcbg ³ Vua ACI 318-08 Eq. (D-2)
AVc see ACI 318-08, Part D.6.2.1, Fig. RD.6.2.1(b)
2
AVc0 = 4.5 ca1 ACI 318-08 Eq. (D-23)
( )
1
'
y ec,V = 2ev £ 1.0 ACI 318-08 Eq. (D-26)
1+
3ca1
a1
ACI 318-08 Eq. (D-28)
= (7 ( ) √ d ) l
0.2
l
Vb e
a √f'c c1.5
a1 ACI 318-08 Eq. (D-24)
d a
Variables
ca1 [mm] ca2 [mm] ecV [mm] y c,V ha [mm]
130.0 - 0.0 1.000 440.0
'
le [mm] l da [mm] fc [psi] y parallel,V
70.0 1.000 12.0 4,551 1.000
Calculations
AVc [mm ]
2
AVc0 [mm ]
2
y ec,V y ed,V y h,V Vb [kgf]
111,150 76,050 1.000 1.000 1.000 2,426
Results
Vcbg [kgf] f concrete f Vcbg [kgf] Vua [kgf]
3,545 0.700 2,482 500
z z
bNV = bN + bV <= 1
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.91
www.hilti.co.th
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 13, 2024 Date: 13/3/2024
Fastening point:
6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the
potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or
where pullout or pryout strength governs.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions.
• The present version of the software does not account for special design provisions for overhead applications. Refer to related approval (e.g.
section 4.1.1 of the ICC-ESR 2322) for details.
• For additional information about ACI 318 strength design provisions, please go to
https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.91
www.hilti.co.th
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 13, 2024 Date: 13/3/2024
Fastening point:
7 Installation data
Anchor type and diameter: HIT-RE 500 V3 + HAS 8.8 M12
Profile: H-Sections, 100x100x6; (L x W x T x FT) = 100.0 mm x 100.0 mm x 6.0 Item number: 2417171 HAS 8.8 M12x120 (element) /
mm x 8.0 mm 2123406 HIT-RE 500 V3 (adhesive)
Hole diameter in the fixture: df = 14.0 mm Maximum installation torque: 40 Nm
Plate thickness (input): 12.0 mm Hole diameter in the base material: 14.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 70.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 98.0 mm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required
Hilti HAS-U threaded rod with HIT-RE 500 V3 injection mortar with 70 mm embedment h_ef, M12, Steel galvanized, Hammer drilled
installation per instruction for use
y
130.0 130.0
40.0
3 4
130.0
180.0
x
130.0
1 2
40.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
Hilti PROFIS Engineering 3.0.91
www.hilti.co.th
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 13, 2024 Date: 13/3/2024
Fastening point:
8 Alternative fastening
8.1 Alternative fastening data
Anchor plate :
R lx x ly x t = 260.0 mm x 260.0 mm x 12.0 mm; (Recommended plate thickness: not calculated)
Hilti HAS-U threaded rod with HIT-RE 500 V3 injection mortar with 70 mm embedment h_ef, M12, Steel galvanized, Hammer drilled
installation per instruction for use
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
Hilti PROFIS Engineering 3.0.91
www.hilti.co.th
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Mar 13, 2024 Date: 13/3/2024
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
11