BD201506-MYTHLTD - Preliminary Engineering Assesment of Two Storied Residential Building
BD201506-MYTHLTD - Preliminary Engineering Assesment of Two Storied Residential Building
DELIVERABLE:
PRELIMINARY ENGINEERING ASSESMENT OF 2 STORIED RESIDENTIAL
BUILDING AT BANANI
PREPARED BY:
INDUSTRIAL BUILDING CONSULTANTS
SECTION: 1
INTRODUCTION
Industrial Building Consultants (IBC) has been asked by Myth Ltd to Design the
extension of existing two storied residential building at Banani.
However, as per information provided by the client/owner there is no detail
structural drawing available for the existing building. Considering the structural safety
of the existing building IBC has tentatively analyzed the building and generated a
preliminary structural assessment report.
Also we have evaluated the building in light of different codes from BNBC 2006. Our
preliminary assessment report shall deliver the following facts
1. Preliminary structural assessment report.
2. Code requirements for masonry structures.
3. Recommendation.
SECTION: 2
2.0 Project Information
The client has provided us with the following information of the project.
Basis of analysis:
The analysis was conducted based on available data from site visit &
architectural drawing shared by client. Furthermore the missing information was
considered as from worst case scenario.
Required STRENGTH OF
DETAIL DESIGN OF SLAB
data MATERIAL
Conclusion: Perform NDT/DT on brick wall. Increased load may cause bearing
wall to crack under increased load.
COMPLIENCE
POSSIBILITY
BNBC CODE BRIEF WITH THE
FOR
REFERANCE DESCRIPTION EXISTING
COMPLIANCE
BUILDING
3.8.1 Dimension of
Failed NO
Footing
4.2.2 Masonry Units Date is Not
YES
( Brick Type) Available
4.2.3 Mortar and Date is Not
NO
Grout Available
4.3.2 Compressive
Date is Not
strength of NO
Available
Masonry
4.3.4 Quality Date is Not
NO
Compliance Available
4.4.2.1 Design Date is Not
NO
Consideration Available
4.4.4.1 (A) Height to
Available YES
width ratio
4.4.4.1 (C) Anchorage
Date is Not
with cross NO
Available
wall
4.4.5 Structural Date is Not NO
Continuity Available
4.8.3 Earthquake
Date is Not
resistance for NO
Available
Zone 2
4.8.4 Wall
reinforcement Date is Not
NO
for Seismic Available
Zone 2
4.8.6 (b) Wall openings Does not
NO
Comply
4.8.6.2 Strengthening Data is not
NO
Arrangements Available
4.8.6.3 Bands Data is not
NO
Available
4.8.6.4 (a-b) Strengthening
Data is not
of corner and NO
Available
Junctions
PROJECT ID: BD201506 CLIENT: MYTH LTD DELIVERABLE ID: 20150601
As per analysis & discussion carried on above it can be summarized that key fact/data that is
needed to be addressed before conducting any further alteration and modification is absent
for this residential building. Moreover as a masonry structure it needs special arrangement
and consideration for lateral stability as per BNBC.
Considering requirement chart stated above it can be concluded that the structure is
“NOT SAFE FOR VERTICAL EXTENSION”.