You are on page 1of 20

S70-400 OM/JUN 99

File: SERVICE MANUAL - Section 70


Replaces: NOTHING (New Information)
Dist: 3, 3a, 3b, 3c

OPERATION - MAINTENANCE

RXF
ROTARY SCREW COMPRESSOR UNITS
"MINI" MICROPROCESSOR CONTROL

THIS MANUAL CONTAINS RIGGING, ASSEMBLY, START-UP, AND


MAINTENANCE INSTRUCTIONS. READ THOROUGHLY BEFORE
BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN DAMAGE OR IMPROPER
OPERATION OF THE UNIT.
S70-400 OM RXF "MINI" MICROPROCESSOR CONTROL
Page 2 OPERATION - MAINTENANCE

Contents

"MINI" MICROPROCESSOR CONTROL PANEL ......................................................................................................................... 3


KEYS AND KEY FUNCTIONS ...................................................................................................................................................... 4
OPERATING DISPLAY .................................................................................................................................................................. 4
SETPOINTS DISPLAY .................................................................................................................................................................. 5
TO CHANGE THE ADJUSTABLE SETPOINTS: ........................................................................................................................... 6
HOW TO DETERMINE ADJUSTABLE SETPOINTS: ................................................................................................................... 6
SETPOINTS DISPLAY, Fixed, Page 1 * ........................................................................................................................................ 7
SETPOINTS DISPLAY, Fixed, Page 2 * ........................................................................................................................................ 7
ANNUNCIATOR DISPLAY ............................................................................................................................................................ 7
SECURITY DISPLAY * .................................................................................................................................................................. 9
COMMUNICATIONS DISPLAY * ................................................................................................................................................... 9
AUTO-CYCLE DISPLAY * ............................................................................................................................................................. 9
ANALOG OFFSET DISPLAY ........................................................................................................................................................ 9
HOW THE MICROPROCESSOR WORKS SUMMARY .............................................................................................................. 10
MULTIPLE COMPRESSOR SEQUENCING ............................................................................................................................... 11
MICROPROCESSOR OUTPUT DATA CODE ............................................................................................................................. 11
MICROPROCESSOR TELECOMMUNICATIONS ...................................................................................................................... 11
COMMUNICATIONS PROTOCOL SPECIFICATIONS: ............................................................................................................... 11
TROUBLESHOOTING THE RXF MICROPROCESSOR ............................................................................................................ 14
GENERAL INFORMATION ......................................................................................................................................................... 14
TROUBLESHOOTING FRICK SBC MICROPROCESSOR SYSTEM ........................................................................................ 14
EPROM MEMORY I/C CHIP REPLACEMENT ........................................................................................................................... 16
SBC BOARD REPLACEMENT ................................................................................................................................................... 16
MICROPROCESSOR DISPLAY REPLACEMENT ...................................................................................................................... 16
FUSE REPLACEMENT ............................................................................................................................................................... 16
MICROPANEL ASSEMBLY WIRING DIAGRAM ......................................................................................................................... 18
RECOMMENDED SPARE PARTS .............................................................................................................................................. 20

‡ - Designates changes or new information on referenced pages. See page and topic for matching symbol.
RXF "MINI" MICROPROCESSOR CONTROL S70-400 OM
OPERATION Page 3

"MINI" MICROPROCESSOR CONTROL PANEL

THE FOLLOWING MUST BE READ, In addition to the keyboard, there is an emergency stop but-
AND UNDERSTOOD, IN ADDITION ton. Pushing the emergency stop will bypass the computer
TO THE OPERATING AND START- and remove all power from the outputs. This will shut down
UP INSTRUCTIONS IN S70-200 IOM, BEFORE ATTEMPT- the compressor motor and all control power (120v) to the
ING TO START OR OPERATE THE UNIT. compressor auxiliary systems such as the oil pump and liq-
uid injection solenoid. THE EMERGENCY STOP BUTTON
The RXF compressor is controlled by a state-of-the-art mi- IS FOR EMERGENCY SHUTDOWN SITUATIONS ONLY
croprocessor control system. The microprocessor continu- AND MUST NOT BE USED TO ROUTINELY SHUT OFF
ously monitors the compressor unit’s condition and opera- THE COMPRESSOR.
tion. The microprocessor also directs instructions to the
various compressor unit subsystems. The microprocessor hardware contains an internal watch-
dog circuit. If the microprocessor should fail, this circuit will
The microprocessor has a membrane switch keyboard. disable (turn off) all outputs.
Pressing the keyboard in the area outlined as a key will cause
that function to be recognized by the microprocessor. The
keyboard has 32 membrane-type keys.
S70-400 OM RXF "MINI" MICROPROCESSOR CONTROL
Page 4 OPERATION

KEYS AND KEY FUNCTIONS


1. Operating display (5 Pages)
The [CHANGE] key rotates the display through the different 2. Setpoints display (7 Pages)
display screens. The [CHANGE] key is also used to change 3. Annunciator display (22 Pages)
the status of various setpoints. This key, when pressed, will 4. Communications display (1 Page)
cause the existing settings to be replaced with “#” symbol
for each number of the setting. To change from pounds per [F2] Security display
square inch (G) to inches of mercury (HG) press the [F4] Auto Cycle display
[CHANGE] key when the (G) or (HG) is flashing.

The [STEP] key steps or moves a set of flashing characters OPERATING DISPLAY
through the Adjustable setpoints on the Setpoints displays,
the Auto-cycle display and the Security display. The setpoint
replaced by the flashing “#” symbol may be changed or up- OPERATING DISPLAY, Page 1 *
dated. The [STEP] key is also used when the Annunciator
display is selected to step through the annunciator’s infor- SUCT DISH OIL mode
mation displays. // G ///G ///G state

NOTE: The [ * ] key is used to step or move to previous


screens, described above, one at a time. The Operating display is continuously updated and provides
a variety of information in regard to the current status of the
The [ENTER] key is used to change or enter new setpoints. compressor’s condition and performance.

The [CLEAR] key will reset an alarm or cutout indication on The information furnished by the Operating display is as fol-
the annunciator screen(s) and will clear the microprocessor lows:
to allow continued operation or restarting if all conditions
have returned to normal and no other control lockouts are in SUCT - Suction Pressure is measured at the compressor
force. inlet and is displayed in pounds per square inch gauge (G)
or in inches of mercury (HG).
The [NUMERIC KEYPAD] is used to introduce new setpoint
limits. DISH - Discharge Pressure is measured at the compressor
outlet and is displayed in pounds per square inch gauge
The [+/-] key will call up the Analog Offset display, page 1, (G).
then page 2.
OIL - Oil Pressure is measured prior to entering the com-
The [RUN], [STOP], and [REMOTE START] keys control pressor and is displayed in pounds per square inch gauge
the starting and stopping of the compressor unit. (G).

The [ALARM SILENCE] key will de-energize the alarm horn mode - mode displays the status of the compressor unit.
output. The mode of operation will be indicated as either manual
(MAN) when the [RUN] key has been pressed, automatic
The [AUTO], [REMOTE], and [MANUAL] keys control the (AUTO) when Auto Cycle has been activated, remote (RMT)
operation of the compressor slide valve. when the [RMT] key has been pressed, or off (OFF MODE).

The [AUTO], [MANUAL 2.2], [MANUAL 3.5], and [MANUAL state - state displays the current condition of the compres-
5.0] keys control the operation of the compressor slide stop. sor unit. The display will indicate if the unit is running (RUNG),
off (OFF), shutdown (SHUTD) because of some compres-
The [F1] function key will return the operator to the main sor or system condition or alarm (ALARM) when there is an
operating display. This function may be invoked at any time, alarm condition.
even during setpoint entry.
OPERATING DISPLAY, Page 2 *
The [F2] function key will call up the Security display. NOTE:
Press the [F2] key, as prompted by the display, to return DISCH OIL SEPARATOR
to the previously selected display. ///F ///F ///F
The [F3] function key is nonoperational.

The [F4] function key will call up the Auto Cycle display. DISCH - Discharge Temperature in degrees Fahren-
NOTE: To exit the Auto Cycle display, press the [F1] key heit is displayed.
as prompted by the display.
OIL - Oil Temperature is displayed in degrees Fahrenheit.
The microprocessor has a liquid crystal display in a 2 line
by 20 character format, for a total of 40 characters. There SEPARATOR - Separator displays the oil separator temper-
are 6 different display modes with a total of 36 possible dis- ature in degrees Fahrenheit.
plays. When power is first applied to the control panel, the
unit will be in the Operating display mode. To change to a
different display mode, press the [CHANGE] key. The dis-
play modes in their order of rotation are: * Display for illustrative purposes only.
RXF "MINI" MICROPROCESSOR CONTROL S70-400 OM
OPERATION Page 5

OPERATING DISPLAY, Page 3 * low this, an information space has been provided to indi-
cate whether V ratio is in the automatic (AUTO) or the manual
COMP-mode FLA HEATER (MAN) mode.
state ///% OFF
RECYCLE - A Recycle Delay message indicates that the
compressor has started and has shut down within the time
delay setpoint period. The Recycle Delay will prevent the
COMP - Compressor mode indicates whether the compres-
sor is in automatic (AUTO), remote (RMT), or manual (MAN) compressor from starting until the delay time expires and is
intended to prevent damage to the compressor motor from
operating mode.
successive restarts. During Recycle Delay, the micro-
STATE - state indicates the unit operating condition when processor will alternatively flash “RECYCLE DELAY” and
the remaining delay time in minutes. The (RECYCLE . . .)
running (RUNG), off (OFF), shutdown (SHUTD), or (ALARM).
message appears only when the compressor is in the re-
FLA - Percent Full-Load Amps displays the percentage of cycle mode.
the drive motor full-load amperage rating that the motor is
NOTE: Consult Motor Manufacturer for the recom-
currently using.
mended duration of the Recycle Delay.
HEATER - Heater displays the condition of the oil separator
If the [RUN] key is pushed while
heater(s), indicating ON or OFF.
the unit is in Recycle Delay, the
compressor will start at the end of
OPERATING DISPLAY, Page 4 * the delay period.
S.V.///% CAP.CON=//G SETPOINTS DISPLAY
AUTO-L SUCT.P.=//G
SETPOINTS DISPLAY, Adjustable, Page 1 *
S.V. % - Slide valve position is displayed as a percentage.
This percentage reflects the mechanical position of the slide CCSP=//G LPCO=//G
valve and does not reflect the percentage of full-load opera- LPA =//G
tion. Immediately below this information, space has been
provided to indicate whether the S.V. % is in the automatic
The information furnished by the Adjustable Setpoints of
(AUTO), manual (MAN), or remote (RMT) mode. The micro-
the Setpoints display is as follows.
processor will control this function in the automatic mode.
To the right of the mode indicator, three other messages
CCSP - The Capacity Control Setpoint, reported in pounds
may appear:
per square inch gauge (G) or inches of mercury (HG), con-
trols the loading and unloading of the compressor when S.V.
L - indicates Slide Valve loading.
is in the automatic (AUTO) mode.
U - indicates Slide Valve unloading.
FU - indicates Slide Valve forced unloading.
LPCO - The Low Suction Pressure Cutout, reported in
pounds per square inch gauge (G) or inches of mercury
A Forced Unload (FU) message indicates that the percent-
(H), will shut down the compressor if the suction pressure
age of motor full-load amps has exceeded the maximum
drops to this limit or lower, for 90 seconds or longer.
limit and the microprocessor is unloading the compressor
until the percentage FLA falls back to normal limits.
LPA - The Low Suction Pressure Alarm, reported in pounds
per square inch gauge (G) or inches of mercury (HG), will
CAP CON - The Capacity Control setpoint, reported in
trigger a prealarm if the suction pressure drops to this limit
pounds per square inch gauge (G) or inches of mercury
or lower.
(HG), controls the loading and unloading of the compressor
when S.V. is in the automatic (AUTO) mode.
SETPOINTS DISPLAY, Adjustable, Page 2 *
SUCT.P. - Suction Pressure is measured at the compressor
inlet and is displayed in pounds per square inch gauge (G) PB DB CT
or in inches of mercury (HG). This is the same value as shown 15 1.0 10
on “Operating Display, Page 1.”
PB - The Proportional Band (PB) is used to determine the
OPERATING DISPLAY, Page 5 * amount of time the load/unload solenoid is energized, ac-
cording to how far away from the setpoint the actual control
VOLUME RATIO - /./ pressure or temperature is. The smaller the number, the
AUTO RECYCLE 30 MIN more load/unload will be sent. A PB of 10% is default. It is
adjustable to 2, 5, 10, 15, 20, or 25 percent.

VOLUME RATIO - Volume Ratio is the ratio selected by the DB - The Dead Band (DB) is a + (plus) or - (minus) value
microprocessor to provide the highest efficiency at any given above or below the setpoint at which the compressor will
suction and discharge pressure condition. Immediately be- neither load nor unload. It is adjustable between .5 and 5.0
psig or degrees, in increments of .5 units.

* Display for illustrative purposes only.


S70-400 OM RXF "MINI" MICROPROCESSOR CONTROL
Page 6 OPERATION

CT - The Cycle Time (CT) setpoint is the amount of time MLC FORCE UNLD - The Motor Load Control Force Un-
between the beginning of each load/unload response. It is load (MLFU), reported as a percentage of the motor full-
adjustable to 5, 10, 15, 20, 25, or 30 seconds. load amps (FLA), will force the compressor to unload until
the motor full-load amps (FLA) falls to less than the stop
Use the [STEP] key to step to the desired setpoint, then load setpoint. MLFU will show on display when active. NOTE:
press the [CHANGE] key to change the CC, PB, DB, and Consult motor manufacturer for recommended setpoint.
CT values. Enter the desired value for the remaining set-
points and press [ENTER] when complete. TO CHANGE THE ADJUSTABLE SETPOINTS:
SETPOINTS DISPLAY, Adjustable, Page 3 * Adjustable Setpoints are stored in memory and are easily
changed in the field.
HPCO=///G AUX1-A-NC Although the Adjustable Setpoints
HPA =///G AUX2-S-NO are not lost if power is interrupted,
we suggest that a list of Adjustable
Setpoints be affixed to one end of the microprocessor
HPCO - The High Discharge Pressure Cutout, reported in cabinet for reference.
pounds per square inch gauge (G), will shut down the com-
pressor if the discharge pressure equals or exceeds this NOTE:The following procedure also applies to the chang-
setpoint. ing of the Security and Auto Cycle display setpoints.

HPA - The High Discharge Pressure Alarm, reported in 1. Press the [CHANGE] key to rotate the display to any of
pounds per square inch gauge (G) will trigger a prealarm if the Adjustable Setpoints displays (Pages 1, 2, 3, 4, or 5).
the discharge pressure equals or exceeds this setpoint.
2. Press the [STEP] key to move or step through the various
AUX 1 and AUX 2 - May be configured for either an alarm or setpoints. A setpoint is selected for change or update when
shutdown and with either a normally closed (NC) or nor- it is flashing.
mally open (NO) contact.
3. Having selected the setpoint to be changed, the [NU-
SETPOINTS DISPLAY, Adjustable, Page 4 * MERIC KEYPAD] may be used to enter the new setpoint.
NOTE: All digits must be entered, including zeros. For
RECYCLE DELAY=30 MIN example, (01.0).
C.T. FACTOR =///
NOTE: The AUX 1 and AUX 2 setpoints, once selected,
are changed or updated by pressing the [CHANGE] key.
RECYCLE DELAY - The Recycle Delay displays the cur-
rent recycle delay setpoint in minutes. NOTE: Consult mo- NOTE: Certain setpoints may be reported in either
tor manufacturer for recommended setpoint. pounds per square inch gauge (G) or inches of mercury
(HG). Having selected the setpoint, press the [CHANGE]
CT FACTOR - The Current Transformer Factor records the key to toggle between (G) and (HG).
proper current transformer factor to match the compressor
motor FLA rating to the current transformer primary amp 4. In the event that an incorrect setpoint is keyed in, press
rating. The CTF factor is programmable and its correct value the [CLEAR] key to restore the original setpoint. Pressing
is determined by the following formula: the [CLEAR] key a second time will eliminate the flashing
characters.
1024 x FLA (Full Load Amps *)
CTF = 5. Having keyed in the desired setpoint, press the [ENTER]
10x CT (Current Transformer Primary Amps **)
key. The new setpoint will be entered and the next adjust-
* See motor nameplate. able setpoint will begin flashing.
** See CT located in starter panel.
NOTE: A setpoint entry outside the parameters of the
EXAMPLE: FLA = 230 Amps Adjustable Setpoint display will be refused.
CT = 300 (300:5)
1024 x 230 HOW TO DETERMINE
CTF = = 80 (Round to whole number)
10 x 300 ADJUSTABLE SETPOINTS:
Adjustable Setpoints should reflect values compatible with
SETPOINTS DISPLAY, Adjustable, Page 5 * normal system operation. Too high a Low Suction Pressure
Alarm setpoint may cause nuisance prealarms. Similarly,
MLC STOP LOAD=/// % cutout setpoints should not fall within what are considered
normal plant operation. As a rule of thumb, set the Low Suc-
MLC FORCE UNLD=/// %
tion Pressure Alarm 5 PSIG lower than the lowest normal
suction pressure. The Low Suction Pressure Cutout should
MLC STOP LOAD - The Motor Load Control Stop Load
be 5 to 10 PSIG lower than the Low Suction Pressure Alarm
(MLSL), reported as a percentage of the motor full load amps
setpoint.
(FLA), will prevent the compressor capacity control from load-
ing when the setpoint is equaled or exceeded. NOTE: Con-
sult motor manufacturer for recommended setpoint.
* Display for illustrative purposes only.
RXF "MINI" MICROPROCESSOR CONTROL S70-400 OM
OPERATION Page 7

The High Discharge Pressure Cutout should be set at 90% Alarm will occur if oil pressure is 25 lb below discharge pres-
of the setting of the lowest high side relief valve. The High sure or within 10 lb of suction pressure for 30 seconds.
Discharge Pressure Alarm should be set 10 PSIG lower than Cutout occurs if oil pressure is 30 lb below discharge pres-
the Cutout. sure or if oil pressure is within 7 lb of suction pressure for 10
seconds and alarm has already been set.
The Capacity Control setpoint should be the equivalent of
the normal suction condition.
ANNUNCIATOR DISPLAY
SETPOINTS DISPLAY, Fixed, Page 1 * When a prealarm or cutout occurs, a flashing ALARM or
SHUTD (shutdown) indicator will appear in the lower right
HDTC=212 HOTC=167 hand corner of the “Operating Display, Page 1” and in the
HDTA=194 HOTA=159 lower left hand corner of “Operating Display, Page 3”. To
determine the fault, rotate to the Annunciator display by pres-
HDTC - The High Discharge Temperature Cutout, reported sing the [CHANGE] key.
in degrees Fahrenheit, will shut down the compressor if the
discharge temperature equals or exceeds this setpoint. The Annunciator display will show all failures, individually. If
there is only one failure, the annunciator display will appear
HDTA - The High Discharge Temperature Alarm, reported as shown on the following “Annunciator Display's”. When
in degrees Fahrenheit, will shut down the compressor if the the system has failed for more than one condition, (USE
oil temperature equals or exceeds this setpoint. STEP) will appear in the upper right side of the display. The
applicable failure displays will be individually rotated through
HOTC - The High Oil Temperature Cutout, reported in de- by pressing the [STEP] key. Continued pressing of the
grees Fahrenheit, will shut down the compressor if the oil [STEP] key will result in the applicable failure displays re-
temperature equals or exceeds this setpoint. peating.
Pressing the [CLEAR] key while at the Annunciator display
HOTA - The High Oil Temperature Alarm, reported in de- will clear all alarms and/or cutouts.
grees Fahrenheit, will trigger a prealarm if the oil tempera-
ture equals or exceeds this setpoint. In order to restore the Annunciator display and resume nor-
mal operation, it will be necessary to go through the follow-
SETPOINTS DISPLAY, Fixed, Page 2 * ing steps:

LOTC=49 HON =113 1. Correct the conditions causing the alarm.


LOTA=58 HOFF=122
2. Press the [ALARM SILENCE] key. (This action may pre-
cede correcting the conditions causing the alarm).
LOTC - The Low Oil Temperature Cutout, reported in de-
grees Fahrenheit, will shut down the compressor if the oil
3. To clear or reset the Annunciator pages, press the
temperature equals or falls below this setpoint.
[CLEAR] key. This will also clear the ALARM, SHUTD, or
CUTOUT indicator from the Operating display.
LOTA - The Low Oil Temperature Alarm, reported in degrees
Fahrenheit, will trigger a prealarm if the oil temperature
4. Press [F1] to call up the Operating display. If the condi-
equals or falls below this setpoint.
tions causing the alarm have not been corrected or a new
fault has occurred, the ALARM, SHUTD, or CUTOUT mes-
HON - The setpoint, in degrees Fahrenheit, to turn on the oil
sage will appear.
heater when the oil temperature in the oil separator equals
or falls below this setpoint.
NOTE: Use of the Emergency Stop Button may trip one
or more alarm setpoints.
HOFF - The setpoint, in degrees Fahrenheit, to turn off the
oil heater when the oil temperature in the oil separator equals
5. After all failures have been corrected and the [CLEAR]
this setpoint.
key has been pressed and if there are no failures, the An-
nunciator display will show (NO FAILURES).
Compressor Differential Cutout between Suction and
Discharge - The differential cutout has been lowered from
55 lb to 25 lb. Cutout will occur after five minutes. To allow ANNUNCIATOR DISPLAY, NO FAILURES*
operation at low differential pressures, the micro will take
the following steps: ANNUNCIATOR
NO FAILURES
A. Force unload the compressor to 50% and display an "F
Unload" when the oil pressure is within 10 lb of the main oil
injection port pressure and the slide valve position is greater ANNUNCIATOR DISPLAY, 1 FAILURE*
than 50%.
ANNUNCIATOR
B. Prohibit the compressor from loading and display a "Ld HIGH PRESSURE CUTOUT
Inhib" message when the differential is within 15 lb of the
main oil injection port pressure.

Oil Pressure Alarm and cutout - Logic has been revised


to same logic as currently used on RXB/RXF. The new logic
is as follows: * Display for illustrative purposes only.
S70-400 OM RXF "MINI" MICROPROCESSOR CONTROL
Page 8 OPERATION

ANNUNCIATOR DISPLAY, ANNUNCIATOR DISPLAY*


MULTIPLE FAILURES*
ANNUNCIATOR
ANNUNCIATOR USE STEP DISCH TEMP ALARM
HIGH PRESS ALARM
ANNUNCIATOR DISPLAY*
The remaining screens show additional
failure messages that may appear. ANNUNCIATOR
COMPRESSOR AUXILIARY
ANNUNCIATOR DISPLAY*
ANNUNCIATOR ANNUNCIATOR DISPLAY*
LOW PRESS CUTOUT
ANNUNCIATOR
OIL LEVEL
ANNUNCIATOR DISPLAY*
ANNUNCIATOR ANNUNCIATOR DISPLAY*
LOW PRESS ALARM
ANNUNCIATOR
COMP DIFFERENTIAL
ANNUNCIATOR DISPLAY*
ANNUNCIATOR ANNUNCIATOR DISPLAY*
OIL PRESS CUTOUT
ANNUNCIATOR
AUX #1 ALARM
ANNUNCIATOR DISPLAY*
ANNUNCIATOR ANNUNCIATOR DISPLAY*
OIL PRESS ALARM
ANNUNCIATOR
AUX #1 SHUTDOWN
ANNUNCIATOR DISPLAY*
ANNUNCIATOR ANNUNCIATOR DISPLAY*
HI OIL TEMP CUTOUT
ANNUNCIATOR
AUX #2 ALARM
ANNUNCIATOR DISPLAY*
ANNUNCIATOR ANNUNCIATOR DISPLAY*
HI OIL TEMP ALARM
ANNUNCIATOR
AUX #2 SHUTDOWN
ANNUNCIATOR DISPLAY*
ANNUNCIATOR ANNUNCIATOR DISPLAY*
LO OIL TEMP CUTOUT
ANNUNCIATOR
BAD E2PROM CHIP
ANNUNCIATOR DISPLAY*
ANNUNCIATOR ANNUNCIATOR DISPLAY*
LO OIL TEMP ALARM
ANNUNCIATOR
SENSOR FAULT
ANNUNCIATOR DISPLAY*
ANNUNCIATOR
DISCH TEMP CUTOUT
* Display for illustrative purposes only.
RXF "MINI" MICROPROCESSOR CONTROL S70-400 OM
OPERATION Page 9

SECURITY DISPLAY * AUTO-CYCLE DISPLAY *

KEYBD ENTRY ENABLED START=//G MIN.SV.=//


ENTER CODE ***** STOP =//G ENABLE=YES

The [F2] function key will call up the Security display. The The Auto Cycle display is accessed by pressing [F4]. The
Security display allows the operator to either enable or dis- Auto Cycle display provides for independently adjustable
able the microprocessor’s keyboard to prevent unauthorized setpoints to turn the compressor on and off in response to
tampering with the various adjustable setpoints. When en- the suction pressure or as an adjustable setpoint to limit the
abled, the microprocessor keyboard is fully operative and minimum slide valve position.
the security lockout is not in effect. When disabled, the key-
board is rendered partially nonfunctional. All displays will NOTE: To change the Auto Cycle setpoints, refer to “TO
still be accessible through the keyboard. If any attempt is CHANGE THE ADJUSTABLE SETPOINTS”.
made to enter new adjustable setpoints, however, the mi-
croprocessor will default to the Security display. START - Compressor Start-up will bring the compressor
back on line when the suction pressure rises to the dis-
played setpoint.
TO ENABLE THE KEYBOARD, press the [STEP] key so
that the Enter Access Code asterisks (*****) flash, key the STOP - Compressor Stop will shut down the unit if the
proper five digit access code, and press [ENTER]. The Set- suction pressure drops to or below the displayed setpoint
points Access will toggle from disabled to enabled and adjus- limit. NOTE: This limit must be set higher than Low Suc-
table setpoint entry is now possible. tion Pressure Cutout and the Low Suction Pressure
Alarm setpoints.
TO DISABLE THE KEYBOARD, press the [F2] function
key to call up the Security display. Press the [STEP] key MIN. SV - Minimum Slide Valve Position, shown as a per-
until the Enter Access Code asterisks (*****) flash, key the centage, will limit the slide valve position to the displayed
proper five digit access code, and press [ENTER]. Now, setpoint.
press the [STEP] key until ENABLED/DISABLED beside
KEYBD ENTRY flash and press the [CHANGE] key to toggle ENABLE - Indicates whether Auto Cycle is active (YES) or
from enabled to disabled. not active (NO). Press the [CHANGE] key while at this set-
point to change the status. Upon deactivation, the com-
TO CHANGE THE ACCESS CODE, press the [F2] func- pressor will return to the previous mode of operation.
tion key to call up the Security display. Press the [STEP] key
until the Enter Access Code asterisks (*****) flash, key the The Analog Offset Display is accessed by pressing [+/-]
proper five digit access code, and press [ENTER]. Now, key.
select the Enter Access Code a second time by pressing
the [STEP] key until the asterisks flash, key in the new five ANALOG OFFSET DISPLAY, PAGE 1 *
digit access code, and press [ENTER].
SUCT DISCH OIL TEMP.
NOTE: Power loss will not affect the Security display. +0 +1 -1
NOTE: IF NO ACCESS CODE WAS ENTERED AND THE
DISABLED COMMAND WAS SELECTED, THE ACCESS
CODE IS [00000].
ANALOG OFFSET DISPLAY, PAGE 2 *

LOST OR FORGOTTEN ACCESS CODE: Consult Frick DISCH OIL SEP TEMP.
Company for assistance. +0 +0 +2

COMMUNICATIONS DISPLAY *
All analog values can be offset + or - 5 units, depending on
which value is being adjusted. Use the [STEP] key to step
COMMUNICATIONS through the desired setpoint. Press the [CHANGE] key to
ID# = 33 BAUD = 9600 change the value of the offset by 1. The actual analog value
will be displayed under the word “PRESS” or “TEMP”.
ID - The ID number is a programmable identification code
used in telecommunications to access a specific compres-
sor.

BAUD - Shows the baud rate of the RS-422 communication


port. Both ports are configured as follows: word = 8 bit,
parity = none or even, stop = 1 bit. The communications port
is programmable from 300 to 19200 baud.

* Display for illustrative purposes only.


S70-400 OM RXF "MINI" MICROPROCESSOR CONTROL
Page 10 OPERATION - MAINTENANCE

HOW THE MICROPROCESSOR WORKS A typical example of how the microprocessor responds can
SUMMARY be illustrated by the responses generated by the micropro-
cessor as oil temperature increases. Assume that the ambi-
ent temperature and compressor unit temperature is 45OF,
The Frick microprocessor has 3 major components and a
liquid injection, R-22 refrigerant and you have just pressed
variety of sensors. The major components are the SBC
the [RUN] key to start the compressor unit:
(single board computer) 1 display screen, and the keyboard.
AT 45OF
The SBC can be considered the brain of the microprocessor
Microprocessor receives information that the oil tempera-
control console. The SBC contains the logic center which
ture is below 49OF, the low oil temperature cutout setpoint,
provides the rules by which the microprocessor will oper-
and triggers a cutout. The microprocessor will prevent the
ate, the integrated circuit chips which store the burned in
compressor package from being started. The microproces-
memory of how the compressor unit is to behave, an analog
sor also instructs the oil heater(s) output to energize the oil
input to convert Volts DC from the various sensors into com-
heater(s).
puter binary language, and RAM (random access memory)
integrated circuit chips to store information which can be
AT 50OF
readily changed by the microprocessor or, as in the case of
When the oil temperature reached 50OF the microprocessor
adjustable setpoints, by the operator. The SBC collects
would allow the Low Oil Temperature Cutout to be cleared
information, processes the information, and delivers instruc-
and the compressor unit could now be started. (Assume that
tions to the displays and to the output modules.
the [RUN] key has been pressed and that the compressor
has now started.) The low oil temperature alarm would still
The SBC gathers information from several sources on the
be engaged and cannot be cleared until oil temperature
compressor unit. Pressure transducers sense changes in
exceeds 58OF. The oil heater(s) shut off on compressor start.
pressure and return a variable DC voltage of 1 to 5 VDC to
the SBC. The signals are converted into binary code which
AT 113OF
the microprocessor understands. The microprocessor scans
The microprocessor instructs the liquid injection solenoid
the incoming data many times per second and compares
output to deenergize the liquid injection solenoid.
the information it receives with the instructions programmed
in the PROM chips, information stored in the RAM chips,
AT 122OF
and instructions it has received from the console keyboard.
The microprocessor instructs liquid injection solenoid out-
As operating conditions change, the microprocessor also
put to energize and the oil heater(s) output to deenergize
forwards the information it is receiving to the display screen.
(This is a fail-safe. The heater(s) should already be
When an operating condition or conditions develop which
deenergized due to compressor running.)
the microprocessor program identifies as requiring a spe-
cific action, the microprocessor generates an instruction
AT 50O TO 157OF
which is forwarded to the output modules. The instruction
Normal operating range. The microprocessor continues
triggers a solid state output device capable of handling con-
monitoring oil temperature and reporting this information on
trol voltage and the instruction is executed.
the Operating display.
If the microprocessor receives information that indicates an
AT 158OF
abnormal operating condition has been reached or is
The microprocessor triggers the High Oil Temperature Alarm
present, it will generate one or more of the following instruc-
and displays the alarm on the Operating display and the
tions:
Annunciator display.
1. If a subsystem on the compressor unit, such as the oil
AT 167OF
heater(s) or liquid injection, can correct the problem, the
The microprocessor instructs the compressor motor to shut
microprocessor will energize or deenergize this system.
down and displays a SHUTD indication on the Operating
display. Information regarding the cutout will also be retained
2. If an alarm setpoint has been reached,the microprocessor
by the Annunciator display(s).
will trigger the alarm and display this information on the
Operating display and the Annunciator display.
NOTE: If the operator makes an error by attempting to
start the compressor under conditions outside safe
3. If a cutout setpoint has been reached,the microprocessor
normal operating conditions, the microprocessor will
will trigger the cutout and shut down the compressor. The
prevent start-up and advise the operator of the fault.
microprocessor will indicate CUTOUT on the Operating dis-
play. Information will be available through the Annunciator
display.
RXF "MINI" MICROPROCESSOR CONTROL S70-400 OM
OPERATION - MAINTENANCE Page 11

MULTIPLE COMPRESSOR SEQUENCING MICROPROCESSOR


FOR RXF COMPRESSOR UNITS WITH MI- TELECOMMUNICATIONS
CROPROCESSOR CONTROLS
The Frick RXF Microprocessor comes with an onboard tele-
A - The standard microprocessor panel includes: communications interface. The telecommunications feature
permits interfacing the microprocessor with a modem, re-
1. Remote Run Input mote data communications terminal, or master computer via
2. Remote Load Input RS-422 protocol. In the case of a modem, telephone lines
3. Remote Unload Input are used for the actual transmission of data permitting
communications from a remote location.
The remote run input is only recognized when the remote
run mode has been selected by pressing the “remote start” The components necessary to utilize the telecommunica-
key on the front panel of the microprocessor. tions feature will vary with the application. Information
concerning these items may be obtained from Frick Com-
The remote load and unload inputs can only be recognized pany, Waynesboro, Pa.
when the [remote] key in the slide valve column on the front
panel of the microprocessor has been pressed. COMMUNICATIONS PROTOCOL
SPECIFICATIONS:
B - A master sequence controller must be installed to pro-
vide the signals to remote start and stop the compressors All commands must be in ASCII (CAPS) to be recognized. A
and remote load and unload the compressors based on compressor with an ID code of [00] is considered disabled.
the common suction pressure or other parameter. The cus- ID Codes from [01] thru [99] are valid and are recognized by
tomer may supply his own master sequencer panel (usually the microprocessor.
a programmable controller) or Frick can supply this se-
quencer, if desired (contact Frick Company for pricing).
The following is a complete list of available command types:

COMMAND CODE and DESCRIPTION


I = Returns compressor status information.
R = Compressor start command.
S = Compressor stop command.
V = Compressor capacity control command.
P = Return Pressures information.
T = Return Temperatures information.
A = Return full load amps information.
C = Enter Change setpoints mode.

The following is a detailed description of each command:


RETURN COMPRESSOR STATUS INFORMATION: #01I

# Start of command sequence.


01 Compressor ID code.
I Return Status information command.

RETURNED ANSWER, ie: 090RRRN340

Character Description
MICROPROCESSOR OUTPUT DATA CODE Position of returned data

1,2,3 Capacity control position.


A 3.5 K OHM, 10 watt resistor (RES) must be field installed, 4 Remote, Auto, Manual (Cap control)
as shown below, when the 120 VAC outputs of the RXF are 5 Delay-recycle, Running, Off.
6 Rem, Man, Off, Auto (Compressor mode)
driving 120 VAC solid state input devices such as program- 7 Cutout, Alarm, Normal.
mable controllers. 8,9,10 Suction in PSIA.
(Carriage return, line feed.)

COMPRESSOR START COMMAND: #01R01

# Start command sequence.


01 Compressor ID code.
R Start compressor command.
01 ID code repeated for verification
NOTE: The compressor must be in the remote
start mode for this command to be executed.
Returned answer: A01

Character Description
Position of returned data

1 Acknowledge of command sent.


2,3 ID code of compressor.
(Carriage return, line feed.)
S70-400 OM RXF "MINI" MICROPROCESSOR CONTROL
Page 12 OPERATION - MAINTENANCE

COMPRESSOR STOP COMMAND: #01S01 RETURN PRESSURES COMMAND: #01PX


# Start command sequence. # Start command sequence.
01 Compressor ID code. 01 Compressor ID code.
S Stop compressor command. P Return pressures command.
01 ID code repeated for verification
X = S Return suction pressure (PSIA).
NOTE: The compressor must be in the remote X = D Return discharge pressure (g/hg).
start mode for this command to be executed. X = O Return oil pressure (g).
X = A Return all pressures.
RETURNED ANSWER: A01
If the command was #01PS, then the micro-
Character Description processor would dump the suction pressure.
Position of returned data
RETURNED ANSWER:
1 Acknowledge of command sent.
2,3 ID code of compressor. XXX = 3 characters followed by a carriage
(Carriage return, line feed.) return, line feed.

If using the "A" command, then the returned


data would be:
COMPRESSOR SLIDE VALVE #01VLXX
CONTROL COMMANDS: #01VUXX XXXXXXXXX = 9 characters followed by a
#01VS carriage return, line feed.
#01VP
# Start command sequence.
01 Compressor ID code. RETURN TEMPERATURES COMMAND: #01TX
V Compressor control command.
L Load Slide valve command. # Start command sequence.
U Unload slide valve command. 01 Compressor ID code.
XX = 00 Turns selected output off. T Return temperature command.
XX = 01 to 15 Turns selected output on
for XX seconds. X = D Return discharge temperature.
XX = 99 Turns selected output on. X = O Return oil temperature.
S Return slide valve position value. X = P Return separator temperature.
P Return slide stop position value. X = A Return all temperatures as a string
of data.
If the command was #01VL00, then the load
slide valve output on compressor #1 would be If the command was #01TS, then the micro-
turned off. If the command was #01VL05, then processor would dump the suction temperature.
the load slide valve output on compressor #1
would be turned on for 5 seconds, and would RETURNED ANSWER:
then automatically turn off. NOTE: the slide
valve must be in the remote mode for this XXXX = 4 characters followed by a carriage
command to be executed. return, line feed for suction.
XXX = 3 characters followed by a carriage
RETURNED ANSWER (for L or U commands): A01 return, line feed for discharge, oil,
and separator.
Character Description If using the "A" command, then the returned
Position of returned data data would be:
1 Acknowledge of command sent. XXXXXXXXX = 9 characters followed by
2,3 ID code of compressor. carriage return, line feed.
(Carriage return, line feed.)
RETURNED ANSWER (for S command), ie: 090 COMPRESSOR DISPLAY SCREENS COMMAND: #01DX
1,2,3 Slide valve position.
RETURNED ANSWER (for P command), ie: 2.2 # Start command sequence.
(Carriage return, line feed) 01 Compressor ID code.
D Compressor control command.
X = O Operating display (Page 1,2,3,4, & 5
CHANGE SLIDE VALVE MODE #01MVR will be dumped consecutively)
X = S Adjustable Setpoints display
# Start command sequence (Page 1 through 5)
01 Compressor ID Code X = X Fixed Setpoints display (Page 1 & 2)
MV Change slide valve mode + ID X = C Autocycle display.
X = P Security display.
X = A Auto mode.
X = R Remote mode. If the command was #01D0, then the micropro-
cessor would dump the operating display.
If the command #01MVRID was sent, the slide
valve mode would change to Remote and
the returned answer would be A01 followed RETURN FULL LOAD AMPS COMMAND: #01A
by carriage return, line feed.
# Start command sequence.
01 Compressor ID code.
A Return full load amps command.
If the command was #01A, then the micro-
processor would dump the full load amps value.
RETURNED ANSWER:

XXX = 3 characters followed by a carriage


return, line feed.
RXF "MINI" MICROPROCESSOR CONTROL S70-400 OM
OPERATION - MAINTENANCE Page 13

READ FAILURES COMMAND: #01F READ INPUT/OUTPUT COMMAND #01X


# Start command sequence. # Start command sequence.
01 Compressor ID Code. 01 Compressor ID Code.
F Read Failures command. X Read Input/Output(s) command.
Returned Answer: Returned Answer:
00000000000000000000000 1000001100000000
Character Description Character Description
Position Position
1 High Press Cutout 1 Oil Level Input 1
2 High Press Alarm 2 Remote Run Input 2
3 Low Press Cutout 3 Remote Load Input 3
4 Low Press Alarm 4 Remote Unload Input 4
5 Oil Press Cutout 5 Compressor Aux Input 5
6 Oil Press Alarm 6 Aux 1 Input 6
7 Hi Oil Temp Cutout 7 Aux 2 Input 7
8 Hi Oil Temp Alarm 8 Compressor Run Output 1
9 Lo Oil Temp Cutout 9 Slide Valve Load Output 2
10 Lo Oil Temp Alarm 10 Slide Valve Unload Output 3
11 Disch Temp Cutout 11 Slide Stop Increase Output 4
12 Disch Temp Alarm 12 Slide Stop Decrease Output 5
13 Comp Auxiliary 13 Liquid Injection Output 6
14 Pump Auxiliary 14 High Vi Liquid Injection
15 Oil Level Output 7
16 Comp Differential 15 Oil Heated Output 8
17 Aux. #1 Alarm 16 Alarm Output 9
18 Aux. #1 Shutdown
19 Aux. #2 Alarm Example:
20 Aux. #2 Shutdown If the answer returned was
21 Bad E2Prom Chip U6
22 Sensor Fault 1000001100000000
Example: the inputs/outputs on compressor #1
If the answer returned was which are energized are:
00000100000000000000000, Oil Level Input 1
Aux 2 Input 7
compressor #2 has an Oil Press Alarm. Compressor Run Output 1

CHANGE SETPOINTS COMMAND: #01C RETURN FAIL LIST: #01L


# Start command sequence. #
01 Compressor ID code. 01
C Change setpoint command. L Return Fail List
xxx New setpoint
xx New setpoint Will return a descriptive comment for
y g or h for gauge or inches each fail that is currently active, each
line is terminated by a carriage return,
The following is the complete list of the line feed if there are no failures active.
setpoints that may be changed while in the No response is given.
change setpoints command:

01xxxy Capacity Control Setpoint


02xxxy Change Low Pressure Cutout Setpoint. CHANGE COMPRESSOR MODE #01MCR
03xxxy Change Low Pressure Alarm Setpoint.
04xxx Change High Pressure Cutout Setpoint # Start command sequence
05xxx Change High Pressure Alarm Setpoint. 01 Compressor ID Code
06xxx Change MLC Stop Load Setpoint. MC Change compressor mode + ID
07xxx Change MLC Force Unload Setpoint.
08xx Change Recycle Delay Setpoint. X = O Off mode.
09xxx Change CTF Setpoint. X = A Auto mode.
X = R Remote mode.
01 Compressor ID code.
If the command #01MCRID was sent, the com-
RETURNED ANSWER: pressor mode would change to Remote and
the returned answer would be A01 followed
Axxxx The new setpoint which was sent by carriage return, line feed.
followed by a carriage return, line
feed.
CLEAR FAILURE COMMAND #01KF
If the command was sent #01C01300g01, the
capacity control setpoint would be changed # Start command sequence
to 30.0g and the returned answer is A300g 01 Compressor ID Code
followed by a carriage return, line feed. K Clear command + ID
If the command sent was #01C0711001, the MLC
force unload setpoint would be changed to X = F Clear fails.
110% and the returned answer is A110 fol- X = R Clear recycle delay.
lowed by a carriage return, line feed.
If the command sent was #01C0520002, the If the command #01KFID was sent, the
returned answer is “BAD” followed by the ID compressor cutout would clear and
number and a carriage return, line feed. the returned answer would be A01 followed
by carriage return, line feed.
g or h : must be lower case - exception to "All commands
must be caps" statement at beginning of section.
S70-400 OM RXF "MINI" MICROPROCESSOR CONTROL
Page 14 MAINTENANCE

TROUBLESHOOTING or failure of a peripheral control such as a solenoid coil or a


THE RXF MICROPROCESSOR pressure transducer. Faults in the computer, while possible,
are unlikely. If a fault develops in the computer, the prob-
ability is that all functions will cease and the display screen
This section contains information on troubleshooting and
will go blank.
making corrections to the microprocessor and control cir-
cuits of the RXF unit. This section is composed of four parts:
The control system of the RXF compressor consists of a
a general information section, a troubleshooting guide, a
120 volt AC (high voltage) side and a DC (low voltage) side.
repair procedure guide, and a section with illustrative sche-
The 120 volt side actuates solenoids, relays, alarms, and
matics and data.
other electromechanical functions. The DC side operates
the computer and its various sensors. The microprocessor
GENERAL INFORMATION console contains the SBC (single board computer) and one
display screen.
THE COMPONENTS WITHIN THE
MICROPROCESSOR CONSOLE When working within the micropro-
CAN BE INADVERTENTLY DAM- cessor console, 120 VOLTS CAN
AGED BY STATIC ELECTRICITY OR MISHANDLING. CAUSE INJURY OR DEATH.
ONLY QUALIFIED TECHNICIANS SHOULD DIRECTLY
HANDLE THESE COMPONENTS. To troubleshoot the low voltage side of the RXF control cir-
cuits, it is necessary to have the following tools:
1. DO NOT REMOVE the microprocessor console cover or
attempt to make corrections to the microprocessor power 1. Accurate digital multimeter.*
supply without shutting off the control power. Accidental 2. Small wire stripper.
shorts can irreparably damage the SBC (single board com- 3. Small screwdriver.
puter) or the display screen. 4. Small snip nose pliers.
5. 15 watt soldering iron (no larger).
2. DO NOT HANDLE the SBC or the display screen board 6. .032,60/40 rosin core solder.
when their cables are disconnected without first attaching a 7. IC chip extraction and insertion tools.*
ground strap to prevent static electrical discharge from your 8. Grounding strap.*
body. 9. Static-free grounded work surface.
Most problems encountered with the microprocessor and * Available from Frick. Order kit 451862, P/N 111Q0451862.
control circuits will be the result of a wiring fault, blown fuse,

TROUBLESHOOTING FRICK SBC MICROPROCESSOR SYSTEM


(Refer to wiring diagrams)
NOTE: Before proceeding, check all wiring connections, wire nuts, terminal strips, etc. Also, make sure operating condi-
tions are calling for change.

SYMPTOM PROBABLE CAUSES and CORRECTIONS

DISPLAY IS INOPERATIVE Check the 10 amp fuse (2FU) which controls all voltage going to the microprocessor.

Check F1 on SBC, F2 if 230 VAC.

Shut off power to the microprocessor and confirm that all cable and wire connections are made.

COMPRESSOR AUXILIARY Output 1 controls the Compressor Start Relay (2CR). If the compressor does not start and
SHUTDOWN the LED for Output 1 is on, check the fuse FU1 (5 amp). If the problem persists,
check the interposing relay (2CR). Check Wire 28 before fuse. If fuse ok, then possible bad output.

The Compressor Starter Auxiliary Contacts turn on Input 5 when they are closed.
These contacts are located on the Compressor Starter.Check terminal 20 for voltage input.

OIL HEATERS DO NOT The oil heaters should operate only when the compressor is NOT running and the oil in the
OPERATE separator sump is cold.

If the oil heaters do not work, check between wires 25 and 2 for voltage. If none, check fuse FU1
(15 amp). If the fuse is not blown, check between Wires 11 and 2. If 120VAC is not found, check
output 8 to ensure it is energized. Check fuse FU8 if output is on. If there is voltage, check between
Wires 26 and 2. If no voltage, then replace CR1.

SLIDE VALVE DOES NOT LOAD Verify that the Slide Valve is in the AUTO mode and that capacity control is calling for loading
and/or UNLOAD or unloading (AUTO L or AUTO U will appear on the Operating display).

If 120VAC is not found when the LED for Output 2 is on, check the fuse (FU2).

Output 2 controls the Slide Valve Load Solenoid. If 120VAC is found across Wires 17 and 2, the
Slide Valve Load Solenoid should be energized. If not, the solenoid is defective or neutral
wiring from coil is loose.
RXF "MINI" MICROPROCESSOR CONTROL S70-400 OM
MAINTENANCE Page 15

TROUBLESHOOTING FRICK SBC MICROPROCESSOR SYSTEM (Continued)


SYMPTOM PROBABLE CAUSES and CORRECTIONS

SLIDE VALVE DOES NOT LOAD Output 3 controls the Slide Valve Unload Solenoid. If 120VAC is found across Wires 16 and 2, the
and/or UNLOAD (Continued) Slide Valve Unload Solenoid should be energized. If not, the solenoid is defective. If 120VAC is
not found across Wires 16 and 2 when the LED for Output 3 is on, check the fuse (FU3).

Check for Motor Load Control Stop Load (MLSL) and Motor Load Control (Forced Unload) (MLFL);
Check Autocycle-minimum Slide Valve position;manually cycle to check for bad pot or that rod is
hung. If all ok, Hydraulic System Troubleshooting.

NOTE: Verify that the proper setpoint has been programmed into C.C. (Capacity Control) on
theAdjustable Setpoints display.

SLIDE STOP DOES NOT Output 4 controls the Slide Stop 3.5 Vi Solenoid. If 120VAC is found across Wires 15 and 2, the
INCREASE and/or DECREASE Slide Stop 3.5 Vi Solenoid should be energized. If not, the solenoid is defective. If 120VAC is not
found across Wires 15 and 2 when the LED for Output 4 is on, check the fuse (FU4).

Outputs 4 and 5 control the Slide Stop 2.2 Vi Solenoid. If 120VAC is found across Wires 14 and 2,
the Slide Stop 2.2 Vi Solenoid should be energized. If not, the solenoid is defective. If 120VAC is
not found across Wires 14 and 2 when the LED for Output 5 is on, check the fuse (FU5).

LIQUID INJECTION SOLENOID Verify that the Liquid Injection TXV is modulating properly and not feeding excessive liquid to
DOES NOT ENERGIZE (LICO the compressor. When oil temperature drops too low, the microprocessor SHOULD deenergize
ONLY) this solenoid.

Output 6 controls the Liquid Injection Solenoid. If 120VAC is found across Wires 13 and 2, the
Liquid Injection Solenoid should be energized. If not, the solenoid is defective. If 120VAC is not
found when the LED for Output 6 is on, check the fuse (FU6).

HI Vi LIQUID INJECTION PORT Output 7 controls the Hi Vi Liquid Injection Port solenoid. If 120VAC is found across Wires 12 and
SOLENOID DOES NOT 2, the Hi Vi Liquid Injection Port Solenoid should be energized. If not, the solenoid is defective.
ENERGIZE If 120VAC is not found when the LED for output 7 is on, check the fuse (FU7).

NOTE: This output should only be on when the Vi is at 5.0.

ALARM CIRCUIT DOES NOT Output 9 controls the Alarm Circuit. The Alarm should turn on only when there is a prealarm or
ENERGIZE shutdown. If the Alarm does not sound when these conditions are found, check for 120VAC
across Wires 10 and 2. If 120VAC is not found, check the fuse (FU9).

CONTROL PANEL DOES NOT Inputs 2 through 4 can be used to operate the compressor from a remote location.
RESPOND TO REMOTE
CONTROL SIGNALS NOTE: Check the Operating display to verify that the compressor and the Slide Valve
are in the REMOTE MODE.

If 120VAC is found (across Wires 21 and 2, 22 and 2, and 23 and 2) and the input does not turn
on, and after checking for bad input and loose wires, consult Frick Company.

MOTOR LOAD CONTROL The current transducer is used to convert the AC motor amps to a DC voltage signal for the
(FORCED UNLOAD) OCCURS microprocessor. If the %FLA reading from the Operating display is incorrect, consult Frick Co.

PRESSURES ON THE TEST 1 - Shut down the compressor and allow pressures to equalize. Discharge pressure
OPERATING DISPLAY and oil pressure should have the same reading.
DO NOT APPEAR CORRECT
TEST 2 - If either oil pressure or discharge pressure read different pressures, one or both
transducers are at fault. Valve off the suction transducer from the unit and open the vent
valve on transducer manifold to atmosphere. If the suction transducer reads atmospheric
pressure, then the suction transducer is correct.

NOTE: A 1% tolerance is allowed for all transducers.

COMPRESSOR DOES NOT Verify that the [AUTO] key has been pressed and AUTO appears under SV Pos on the
AUTOMATICALLY Operating display #4.
LOAD OR UNLOAD
If the problem persists, see the Troubleshooting section SLIDE VALVE DOES NOT LOAD
and/or UNLOAD.

DISPLAY SCREENS DISPLAY A loose or improper connection between the displays and the SBC is indicated. Remove fuse
SCRAMBLED PATTERN OR (2FU, 10 amp) for 15 seconds, then restore to reset the displays.
LIST ALPHABET

ANNUNCIATOR DISPLAY E2PROM chip malfunction or bad. The system may still be run by resetting all Adjustable Setpoints
MESSAGE “BAD E2PROM and clearing Annunciator Display. If condition repeats, replace E2PROM chip in slot U6.
CHIP U6”
S70-400 OM RXF "MINI" MICROPROCESSOR CONTROL
Page 16 MAINTENANCE

EPROM MEMORY I/C CHIP REPLACEMENT Pay particular attention to the ori-
entation of the notch(es) on the
Microprocessor EPROM memory I/C chip is located inside end of the chip(s). Install the
the microprocessor console on the SBC board. A special chip(s) on the replacement board in exactly the same
tool is required to remove this chip to prevent damaging it position as they were on the defective board.
(See Troubleshooting The Microprocessor). The procedure
to replace the EPROM memory chip is outlined below: 4. Then install the modified replacement board in the panel.

1. Shut off control power. MICROPROCESSOR DISPLAY REPLACEMENT


2. Open console cover. The procedure to replace the microprocessor display is out-
lined below:
3. Using a chip extraction tool, remove old and install new
chip. NOTE: The chip must be inserted into socket U3. 1. Shut off control power.
The notched end of the chip must 2. Remove the defective display(s).
be up when the chip is inserted to
match the notch on the U3 chip 3. Install the new display(s).
socket.
FUSE REPLACEMENT
SBC BOARD REPLACEMENT 1. Shut off control power.
The procedure to replace SBC boards is outlined below: 2. Open console cover.
1. Shut off control power. 3. Identify faulty fuse.
2. Remove the old board from the machine and the new 4. Use voltmeter to verify that no voltage is present on either
board from its packing and place both on an antistatic sur- side of the fuse.
face.
5. Remove faulty fuse using fuse puller.
3. Remove the program chip(s) from the defective board and
install them in the replacement board. 6. Install new plug-type fuse.
FRONT PANEL (REAR VIEW) CUST'S HEATER
CONNECTION IF
CUST SEPARATE FROM CUSTOMER'S
SECURE CABLES WITH
GROUND LUG CONTROL POWER CONNECTION
DISPLAY CABLE CLAMP ON DOOR
AT STOCK LEVEL PLACE 120
WITH SLACK TOWARD KEYPAD PLACE 230 VOLT LABEL
1/4 STAR WASHER VOLT LABEL HERE.
HERE IF 230 VOLT
UNDER SCREW REMOVE IF 230 VOLT CONTROL
GREEN WIRE HEATERS OR CONTROL

1 FU
REPLACEMENT 2 FU
TYPE BAF 15 AMP 230 VOLTS REPLACEMENT 120 VOLTS
12 COND 250 VOLTS TYPE FNM 10 AMP L1 L2
SBC POWER 14 COND GND LUG 250 VOLTS

CSA ONLY
WARNING AVERTISSEMENT ANALOG
TOROID MORE THAN ONE CET EQUIPMENT
LIVE CIRCUIT RENFERME PLUSIEURS
SEE DIAGRAM CIRCUITS SOUS TENSION. DRAIN WIRES
VOIR LE SCHEMA
TERMINAL SCREW
1A 1 2 TIGHTENING TORQUE
GND #22-#8 AWG
1
2
2
2
2

P1 20 LB.IN (2.3Nm)

25
26
27

1A
2A
2A
LUG FU FU SPARE
FU
SPARE
SPARE

115V

230
115
NEU
GND
F2 F1
C.T.

CH 2 TO STUD ON REAR GREEN


AT PACKAGE ASSEM. 3
CH 3 OF FRONT PANEL GREEN
FEED ANALOG RXF REV D 4
CH 4 & SBC P1 CONN.
CABLES BACK OF CH 5 GND 5
SWING-OUT CH 6 LUG 5
CH 7 6

ANALOGS
PANEL MTG. BRKT. CH 8 TO 10
DISPLAY POT 4 1CR
11
CABLE CLAMP U6 12
P6 J1 EEPROM
FOR ANALOG 13
1
14

64
32
CHANNELS POT 3
2 TO 8 PIN 1 2CR 15
0% TO UV
16
100% PROM
KEYPAD P7
COPPER CONDUCTORS ONLY

17
POT 2 18
MAINTENANCE

20
CR
9 20
21 26
IN 1-7 OUT 1-9 22

422
CR
TERMS
23
3 24
28
FU1-FU9
CR 29
30
1 7 INPUTS 14 15 9-OUTPUTS 32
36
RXF "MINI" MICROPROCESSOR CONTROL

42
CR
SPARE
.

.
MICRO COMPONENT PLACEMENT DIAGRAM

SWING-OUT PANEL
13" X 13"
THROUGH-HOLE FOR ALL AC WIRES TO SBC FIXED OR BOTTOM PANEL
AND DOOR EXCEPT P1 CONNECTION ON SBC 14.75" X 12.88"
SEE 640D0028 (PAGES 42 & 43) FOR STANDARD WIRING DIAGRAM RXFMCPD
INDICATES DEVICES SUPPLIED ONLY WHEN OPTIONAL OR REQUIRED
Page 17
S70-400 OM
S70-400 OM RXF "MINI" MICROPROCESSOR CONTROL
Page 18 MAINTENANCE

MICROPANEL ASSEMBLY WIRING DIAGRAM

CUSTOMER SUPPLIED 115 OR 230 VAC CONTROL TRANSFORMER POWER SOURCE IS REQUIRED
ALL POWER SOURCES SHALL BE GROUNDED ON ONE SIDE NEUTRAL
-ISOLATED AND SEPARATED FROM OTHER INDUCTIVE LOADS SUCH AS LIGHTING CIRCUITS POWER SOURCE
-OR FROM FRICK SUPPLIED OR SPECIFIED STARTER, USE MINIMUM #12 AWG FOR FEED

HOT NEUTRAL ALL NEUTRALS ENTERING


IF SEPARATE FEED OR VOLTAGE FOR HEATER CIRCUIT IS DESIRED, THIS ENCLOSURE SHALL
REMOVE JUMPERS 1 TO 1A & 2 TO 2A & CONNECT BE TIED TOGETHER AT
01 A SEPARATE 115 OR 230 VAC SOURCE TO 1A & 2A SOURCE, NOT IN THIS
ENCLOSURE
02 FOR (2) 115V-1KW HTR'S, MOVE TIE NEUTRAL TO GROUND
1 FU WIRE TO 1A FU & NUMBER 25A 1CR AT SOURCE
03 15 HEATER GROUND BAR IN MICRO
1 1A 25 26 2A 2
1A FU 1CR SEPARATOR OIL HEATERS
ADD 1A FU FOR 115V-1KW HTR'S
04 15 HEATER 5 KW HTR
25A 27
1 KW HTR OPTIONAL
2nd HEATER WHEN REQUIRED
05 #14
RED ALL HEATER WIRING
TO BE #14 AWG
06
ALL NEUTRAL (EXP: 2 & 2A)
DIGITAL I/O WIRING TO BE WHITE
07 10 EXCEPT WHERE NOTED

1 LSL SEPARATOR OIL


08 2 1 1
24 LEVEL SAFE
(SAFE) N.O.-HELD CLOSED
09
REMOTE START/RUN/STOP
10 4 2 3 REMOTE START/RUN/STOP
23
REMOTE LOAD
11 6 3 5 REMOTE LOAD
22
REMOTE UNLOAD
12 8 4 7 REMOTE UNLOAD
21
LIQ. INJ. PRESS. REG.
13 SEE NOTE LN. 39 IF ADDING OIL PUMP (ONLY ON BOOSTERS WITH LIQ. INJ.)
OIL PUMP AUX
14 ECONOMIZER (IF APPLICABLE)
5 19
COMPR. AUX.
15 10 5 9 COMPR. AUX.
5 20 20
REMOVE IF OIL PUMP REQ'D
16 COMPR. RUN TIME METER

17 12 6 11 AUX 1 (SEE NOTE B)


30

18

19 14 7 13 AUX 2 (SEE NOTE B)


29

20

21

22

23 EMERGENCY P4
STOP FU1
2 COMPRESSOR START/RUN
24 16 1 15 CR
6 28
FU2 SLIDE VALVE LOAD
2 YY
25 18 2 17
<b>COIL SHOWN WITH SOL. ON COMPR.
17 <a>COIL WITH SOL ON BASE
FU3
1 YY SLIDE VALVE UNLOAD
26 20 3 19
<a>COIL SHOWN WITH SOL. ON COMPR.
16
FU4 <b>COIL WITH SOL. ON BASE
4 YY
27 22 4 21 DECREASE TO 3.5 Vi
15
FU5
3 YY
28 24 5 23 DECREASE TO 2.2 Vi
14
FU6
7 YY
29 26 6 25 LIQUID INJECTION
13 (IF REQ'D)
FU7
9 YY
30 28 7 27 LIQUID HI Vi LIQ. INJ.
12 (IF REQ'D)
FU8
1
31 30 8 29 CR OIL HEATER
5 11 2 03
32 SEE NOTE C
FU9 ALARM
33 32 9 31
10 (OPT) RELAY OR LAMP

34

35

HOT WIRING IF ISOLATED NEU


36 2CR CONTACT IS USED
JUMP TO 6 SEE NOTE A COMPR MOTOR STARTER
(Y) 2CR OL IF STARTER CONTAINS MULTIPLE
IF REQ'D (Y) (Y)
37 SEE NOTE A JUMPER MS CONTACTORS, RELAYS, & TIMERS,
36 SEE NOTE B 42 18 18 ADD SUPPRESSORS OR VARISTORS
AT EACH COIL (SEE NOTE C)
38
NOTE: IF OIL PUMP IS REQ'D, WIRE OIL PUMP STARTER AS SHOWN.
OIL PUMP AUX & COMPR AUX MUST BE WIRED IN SERIES. OL
OIL PUMP STARTER
39 IF FRICK STARTER IS SUPPLIED, MODIFY STARTER AUX'S. MS SUPPRESSOR OR VARISTOR
5 H-O-A SWITCH IS NOT SUPPLIED. 8 2
INSTALLED AT OIL PUMP
RXFMIWD1
STARTER COIL (SEE NOTE C)
RXF "MINI" MICROPROCESSOR CONTROL S70-400 OM
MAINTENANCE Page 19

MICROPANEL ASSEMBLY WIRING DIAGRAM - continued

C.T. MOUNTED IN STARTER OR


40 MOTOR JUNCT. BOX (BY OTHERS)
5 2
P2
41 - (CHANNEL 1)
0-5 AMP AC 4
0-5 AMP AC
SECONDARY COMPR MOTOR AMPS
42 +
ONE PHASE 3 SEE IOM MANUAL
OF MOTOR FOR C.T. WIRE SIZING
43
+ (CHANNEL 2)
TE-4 BLACK SEP TEMP
44 -
CABLE #2
45 + (CHANNEL 3)
TE-2 BLACK DISCH TEMP
-
46 CABLE #3
+ (CHANNEL 4)
TE-3 BLACK OIL TEMP
47 -
CABLE #4
BLACK
48 - - (CHANNEL 5)
PE-4 WHITE
S S 1-5 VDC
RED SUCTION PRESS
49 + +
CABLE #5
BLACK
50 - - (CHANNEL 6)
PE-3 WHITE
S S 1-5 VDC
RED DISCH PRESS
51 + +
CABLE #6
BLACK
52 - - (CHANNEL 7)
PE-1 WHITE
S S 1-5 VDC
RED OIL PRESS
53 + +
CABLE #7
RED
54 3 +
SLIDE VALVE 2 WHITE (CHANNEL 8)
POSITION S
POTENTIOMETER BLACK
55 1 -
CABLE #8 ALL ANALOG LOW VOLTAGE WIRING TO BE RUN
IN SEPARATE CONDUIT FROM ALL OTHER WIRING
56
TEMPERATURE WIRING SPECIFICATIONS
TEMPERATURE SENSOR WIRING TO BE #8760 BELDEN CABLE
57 OR EQUAL. GROUND DRAIN WIRE AT PANEL ONLY ON 4"
SENSORS. GROUND AT SENSOR END ONLY ON 1" SENSORS.
PORT 1 INSULATE DRAIN WIRE AT OPPOSITE END. 2000 FT. MAX. DISTANCE.
58 P5
RS 422 NOTE A:
IF COMPR. MOTOR STARTER IS A FRICK SUPPLIED STARTER
FRONT OR CONFORMS TO FRICK STARTER SPECS, WIRE AS SHOWN
59 PANEL P6
RXF SBC ON LINE 37 ONLY. JUMP 6 TO 36.
DISPLAY IF 2CR IS USED AS A ISOLATED CONTACT, WIRE AS SHOWN
60 1 14 COND RIBBON CABLE 1 BETWEEN THE HOT & NEUTRAL LINES ON LINE 37.
P7 NOTE B:
1 FOR OPTIONAL ALARMS & SHUTDOWNS:
61 KEY (HIGH LEVEL SHUTDOWN ETC.)
PAD 12 COND RIBBON CABLE WHEN REFERENCING MICRO POWER TO OPERATE COMPR.
NO CONNECTION ON 230 MOTOR STARTER (PARAGRAPH 1-NOTE A), REMOVE JUMPER
62 FOR GROUNDED CIRCUITS 36 TO 42 & INSERT ISOLATED CONTACT(S). JUMP 42 TO
GREEN WIRE GND
STUD POWER EITHER 29 OR 30 (AUX 1 OR AUX 2). PROGRAM AUX TO
STUD SUPPLY F1 SHUTDOWN-NORMALLY CLOSED.
63 F2
P1 WHEN USING 2CR AS A ISOLATED CONTACT (PARAGRAPH 2,
NOTE A), REMOVE JUMPER 36 TO 42 & INSERT ISOLATED
SW1
115
230

115 GND NEU 230


64 CONTACT(S). A SEPARATE ISOLATED CONTACT SHOULD BE
GREEN INSERTED BETWEEN 5 & 29 OR 30. PROGRAM AUX AS
ABOVE.
SET SW 1 TO CORRECT VOLTAGE AUX 1 & AUX 2 CAN BE PROGRAMMED TO ALARM OR
65 TOROID
WRAP WIRES THROUGH TOROID TWO (2) SHUTDOWN, NOR. OPEN OR NOR. CLOSED.
FERRITE
TIMES, ALL IN THE SAME DIRECTION RING NOTE C:
66 A SURGE SUPPRESSOR OR MOV TO BE INSTALLED ACROSS
5 2 ALL INDUCTIVE LOADS IN CONTROL CENTER.
67 SURGE SUPPRESSOR
SUPPRESSOR SPECIFICATIONS:
RC NETWORK CONSISTING OF A .1 MFD CAPACITOR, 600
68 VDC IN SERIES WITH A 47 OHM RESISTOR.
USE ELECTROCUBE #RG2031-3-6 OR EQUAL.
69 VARISTOR
METAL OXIDE VARISTOR (MOV) SPECIFICATIONS:
GE #V130LA10A OR EQUAL FOR 115 VOLTS
70 GE #V250LA10A OR EQUAL FOR 230 VOLTS
CUSTOMER'S CONNECTIONS TO CONTROL CIRCUIT *INDICATES FURNISHED OR REQUIRED WITH OIL PUMP ONLY
71 LINE NO. TERM NO. CIRCUIT DESCRIPTION INDICATES DEVICES SUPPLIED ONLY
3 1,2,GND CONTROL POWER WHEN OPTIONAL OR REQUIRED
72 3 1A,2A,GND OIL HEATER POWER (IF REQ'D) WIRING BY OTHERS- ALL WIRING ENTERING CONTROL
37 18,2 OIL PUMP STARTER (SEE NOTE A) OR CENTER (INCLUDING GROUND & NEUTRAL) TO BE #14
* (IF REQ'D) AWG STRANDED WIRES UNLESS SPECIFIED OTHERWISE.
73 37 36,18 OIL PUMP STARTER ISOLATED CONTACT
37 18,2 COMPR. STARTER (SEE NOTE A) OR TERMINALS IN CONTROL CENTER
37 36,18 COMPR. STARTER ISOLATED CONTACT NO THREE PHASE WIRING SHALL ENTER OR LEAVE MICRO PANEL
74 OR BE RUN IN SAME CONDUIT AS ANY MICRO CONTROL WIRING
19 5,29 AUX 2 (IF REQ'D) ENTERING OR LEAVING MICRO PANEL
75 17 5,30 AUX 1 (IF REQ'D) NO SINGLE PHASE OVER 300 VOLTS SHALL ENTER OR LEAVE MICRO PANEL
* 14 (IF REQ'D) FOR PROPER INSTALLATION OF ELECTRONIC EQUIPMENT,
15 5,20 COMPRESSOR AUX SEE FRICK PUBLICATION S90-400 SB/ SERVICE MANUAL.
12 5,21 REMOTE UNLOAD (IF REQ'D) ALL CONTROL CENTER WIRING TO BE #16 AWG
11 5,22 REMOTE LOAD (IF REQ'D) STRANDED WIRE UNLESS SPECIFIED OTHERWISE.
10 5,23 REMOTE START/RUN/STOP (IF REQ'D) FOR RXF PACKAGE/MICROPROCESSOR
41,42 3,4 CURRENT TRANSFORMER TEST PROCEDURE, SEE MMIB NO. 4.11.10.9
FOR INSTALLATION OF MICROPROCESSOR BOARD
AND EPROMS, SEE MMIB NO. 4.11.10.11
FOR HIGH POT TEST PROCEDURE, SEE MMIB NO. 4.11.10.7
RXFMIWD2
SEE 640D0029 FOR STANDARD CONTROL CENTER ASSEMBLY
S70-400 OM RXF "MINI" MICROPROCESSOR CONTROL
Page 20 MAINTENANCE

RECOMMENDED SPARE PARTS


(Current Design)
ITEM
DESCRIPTION QTY MODELS NUMBER
Microprocessor Cover and Keypad 1 ALL 640D0010H01
Gasket for 640D0010H01 1 ALL 649A0162H01
Display (Standard) 1 ALL 111Q0281048
Output Module 2 ALL 111Q0281061
Input Module 1 ALL 333Q0000116
SBC Board (Standard) 1 ALL 333Q0000549
3 PDT Relay 1 ALL 333Q0000206
Base for 333Q0000206 1 ALL 333Q0000207
Fuse - 5 AMP 5 ALL 333Q0000117
Cable Assy. - 14 Conductor, SBC to Display (Standard) 1 ALL 640A0019H01
Cable Assy. - 12 Conductor, SBC to Keypad 1 ALL 640B0019H03
Suppressor 3 ALL 111Q0280958
Fuse 2 AMP 2 ALL 333Q0000573
Temperature Probe 3 12–101 640A0035H01
Pressure Transducer 0–100 PSIA 1 ALL 333Q0000426
Pressure Transducer 0–300 PSIA 2 ALL 333Q0000427
Float Switch 1 12–50 913A0086H01
Float Switch 1 58–101 913A0086H02
Emergency Stop Operator Latch 1 ALL 111Q0280832
Contact Block for Above 1 ALL 111Q0280833
Fuse - 15 AMP 2 ALL 111Q0281053
Microprocessor Service Tool Kit 1 ALL 111Q0451862
Includes: CMOS Extractor Tool
CMOS Insertion Tool
Digital Multimeter
Wrist Grounding Strap
Antistatic Pad

York Refrigeration Group - Frick


100 CV Avenue, P.O. Box 997 Waynesboro, Pennsylvania USA 17268-0997
Phone: 717-762-2121 • Fax: 717-762-8624
Printed in U.S.A. SUBJECT TO CHANGE WITHOUT NOTICE

You might also like