6 Walls
6.1 General
Walls are defined as being vertical elements whose lengths are four times greater than
their thicknesses. Their design does not differ significantly from the design of columns in
that axial loads and moments about each axis are assessed and designed for.
Generally, the method of designing walls is as follows:
1. Determine design life. <BS EN 1990 & NA Table NA 2.1>
2. Assess actions on the column. <BS EN 1991 (10 parts) & UK
NAs>
3. Determine which combinations of actions <BS EN 1990 & NA Tables NA
apply. A1.1 & NA A1.2(B)>
4. Assess durability requirements and determine <BS 8500–1>
concrete strength.
5. Check cover requirements for appropriate fire <Approved Document B
resistance period. BS 1992–1–2>
6. Determine cover for fire, durability and bond. <BS EN 1992–1–1 Cl. 4.4.1>
7. Analyse structure for critical combination <BS EN 1992–1–1 Section 5>
moments and axial forces.
8. Check slenderness and determine design <BS EN 1992–1–1 Section 5.8>
moments.
9. Determine area of reinforcement required. <BS EN 1992–1–1 Section 6.1>
10. Check spacing of bars <BS EN 1992–1–1 Sections 8 & 9>
Example 6.2 shows the design of a simple linear shear wall as typically used in medium rise
buildings. Similar principals may be applied to walls that are shaped as C, L, T, Z and rectangles
in-plan but issues of limiting flange dimensions and shear at corners need be addressed. The
example shows only ULS design as, apart from minimum areas of steel to control cracking, SLS
issues are generally non-critical in medium-rise structures. For shear walls in high-rise
structures, reference should be made to specialist literature (ref to CIRIA R102 Design of shear
wall buildings).
Figure 6.1
Typical floor plan
Qk = αn × 196.1
where
αn = 1.1 – n / 10
where
n =no. of storeys qualifying for reduction* <BS EN 1991-1-1 6.3.1.2(11) & NA>
=3
= 1.1 – 3 / 10 = 0.8
∴Qk = 0.8 × 196.1 = 156.9 kN Qk /m = 156.9 / 4.4 = 35.7 kN /m
Check relative stiffness of lift shaft and wall A to determine share of load on wall A.
Lift shaft: ILS = 2.44 / 12 – 2.04 / 12 – 0.2 × 1.63 / 12
= 1.36 m4
Wall A: IWallA = 0.2 × 4.43 / 12
= 1.41 m4
∴ Wall A takes = 1.41 / (1.41 + 1.36) = 51% of wind load.
Check shear centre to resolve the effects of torsion.
Determine centre of reaction of lift shaft
Area x Ax
2.4 × 2.4 = 5.76 1.2 6.912
–2.0 × 2.0 = –4.00 1.2 –4.800
–1.6 × 0.2 = –0.32 2.3 –0.732
1.44 1.38
*
Includes storeys supporting Categories A (residential & domestic), B (office), C (areas of
congregation) and D (shopping) but excludes E (storage and industrial), F (traffic), G (traffic) and H
(roofs).
†
Assuming centreline of wall A is 50 mm to right hand side of grid.
‡
For medium rise shear walls there are a number of methods of design. Cl. 9.6.1 suggests strut-and-
tie (see Section xx). Another method [ref to Concrete Buildings Design manual] is to determine elastic
tensile and compression stresses from NEd/bL +/– 6MEd/bL2 and determine reinforcement
requirements based on those maxima. The method used here assumes a couple, consisting of 1.0 m of
wall either end of the wall. The reinforcement in tension is assumed to act at the centre of one end and
the concrete in compression (with a rectangular stress distribution) acts at the centre of the other
end. The forces generated by the couple add or subtract from the axial load in the 1 m ends of the
walls. The method is useful for typical straight shear walls of say 2.5 to 5.0 m in length.
§
As Hi derives mainly from permanent actions its resulting effects are considered as being a
permanent action too.
Figure 6.8 Plan of wall A and location of sections Figure 6.9 Section A – A
A – A and B – B
Section A – A @ 1st floor.
The slab frames into the wall. For the purposes of assessing fixed end moments, the width of slab
contributing to the moments in the wall is assumed to be the length of the wall plus distances half
way to adjacent supports either end. Therefore, consider the fixed end moment for 1.50/2 + 4.40 +
1.30/ 2 = 5.8 m width of adjoining slab framing into the 4.4 m long shear wall (see Figure 6.8).
**
FEM Fixed End Moment for 1 m width of adjoining slab.
FEM
Assuming variable action is a leading action:
= 302.8 / 2 = 151.4 kNm
kw =I/l
= 2200 × 2003 / (12 × 1650) = 8.88 × 105
††
Ignoring effect of landing.
‡‡
Assuming wind load is lead variable action.
§§
Strictly incompatible with Qk = 0. However, allow Qk= 0.
Figure 6.12 Stresses and strains in wall subject to tension and out of plane moment
Restoring moment
Mk = (1021.0 + 5.0 x 1.2 x 0.9 x 25 + 0 x 225.1 ) x (0.3 + 2.2)
= 2890 kNm
At ULS of EQU,
Overturning moment
= fn(γQ,1Qk1 + γG,supGk) <BS EN 1990 Table
= 1.5 x 1057.5 + 1.1 x 211.0 = 1818.4 kNm A1.2(A) & NA>
Restoring moment
= fn(γG,infGk) <BS EN 1990 Table
= 0.9 x 2890 = 2601 kNm i.e. > 1818.4 kNm A1.2(A) & NA>
∴ OK