NODE COL NO. SIZE 201.06 314.16 490.87 804.25 AST REQ AST PRO 201.06 314.16 490.87 804.25 AST REQ AST PRO
1375 C 29 400X600 8 4 1981 2865.133 8 4 2240 2865.1325
1417 C 77 400X600 8 4 1588 2865.133 8 4 2129 2865.1325
1423 C 83 400X600 4 8 1923 3317.522 4 8 2784 3317.5218
1426 C 86 400X600 8 4 1593 2865.133 8 4 2182 2865.1325
1351 C 01 400X600 8 4 2348 2865.133 8 4 2348 2865.1325
1432 C 36 250X450 8 2175 2513.274
1358 C 08 450X600 8 4 1799 2865.133 8 4 2606 2865.1325
1396 C 53 400X600 4 8 1903 3317.522 4 8 2788 3317.5218
1359 C 11 400X600 8 4 2567 2865.133 8 4 2222 2865.1325
1367 C 18 400X600 8 4 2617 2865.133 8 4 2495 2865.1325
1380 C 34 400X600 8 4 2688 2865.133 8 4 1587 2865.1325
1388 C 45 400X600 12 2899 3769.911 12 2611 3769.9112
1424 C 84 400X600 8 4 2692 2865.133 8 4 2507 2865.1325
1355 C 05 400X600 4 8 3072 3317.522 4 8 2018 3317.5218
1368 C 21 400X600 4 8 2899 3317.522 4 8 2721 3317.5218
1373 C 26 400X600 12 3497 3769.911 12 2716 3769.9112
1376 C 30 400X600 4 8 2964 3317.522 4 8 2513 3317.5218
1418 C 78 400X600 4 8 2971 3317.522 4 8 2310 3317.5218
1381 C 35 400X600 12 3465 3769.911 12 2304 3769.9112
1382 C 37 400X600 12 3291 3769.911 12 2377 3769.9112
1408 C 68 400X600 12 3658 3769.911 12 2576 3769.9112
1421 C 81 400X600 8 4 3725 4476.77 12 2799 3769.9112
1407 C 67 400X600 4 8 2890 3317.522 4 8 2150 3317.5218
1416 C 76 400X600 4 8 2844 3317.522 4 8 2281 3317.5218
1425 C 85 400X600 4 8 2761 3317.522 4 8 2787 3317.5218
1352 C 02 400X600 12 3415 3769.911 12 3051 3769.9112
1354 C 04 400X600 12 3456 3769.911 12 2733 3769.9112
1397 C 57 400X600 4 8 3108 3317.522 4 8 3022 3317.5218
1413 C 73 400X600 12 3474 3769.911 12 3064 3769.9112
1414 C 74 400X600 12 3247 3769.911 12 2855 3769.9112
1422 C 82 400X600 12 3268 3769.911 12 3345 3769.9112
1364 C 15 400X600 12 3135 3769.911 12 3660 3769.9112
1353 C 03 400X600 8 4 3699 4476.77 12 3440 3769.9112
1369 C 22 400X600 12 3652 3769.911 12 2837 3769.9112
1398 C 58 400X600 8 4 3883 4476.77 12 2828 3769.9112
1406 C 66 400X600 12 3348 3769.911 12 3053 3769.9112
1415 C 75 400X600 8 4 3703 4476.77 12 2637 3769.9112
1419 C 79 400X600 12 3448 3769.911 12 2450 3769.9112
1377 C 31 400X600 8 4 3961 4476.77 12 3076 3769.9112
1404 C 64 400X600 8 4 4010 4476.77 8 4 3676 4476.7695
1409 C 69 400X600 8 4 3883 4476.77 12 2529 3769.9112
1357 C 07 400X600 12 4508 5890.486 12 2985 5890.4862
1372 C 25 400X600 8 4 4362 4476.77 12 3650 3769.9112
1389 C 46 400X600 8 4 4351 4476.77 12 2418 3769.9112
1403 C 63 400X600 8 4 4298 4476.77 8 4 3841 4476.7695
1420 C 80 400X600 8 4 4254 4476.77 12 2237 3769.9112
1356 C 06 400X600 8 4 4008 4476.77 8 4 3344 4476.7695
1370 C 23 400X600 8 4 4320 4476.77 8 4 4336 4476.7695
1360 C 12 400X600 12 5184 5890.486 12 1869 5890.4862
1361 C 13 400X600 12 5376 5890.486 12 2837 5890.4862
1410 C 70 400X600 12 5483 5890.486 12 2813 5890.4862
1383 C 38 400X600 12 4837 5890.486 12 2959 5890.4862
1405 C 65 400X600 12 4866 5890.486 12 3770 5890.4862
1411 C 71 400X600 12 5328 5890.486 12 3048 5890.4862
1412 C 72 400X600 12 4834 5890.486 12 3799 5890.4862
1386 C 41 400X600 12 5102 5890.486 12 5102 5890.4862
1399 C 59 400X600 12 4475 5890.486 12 4688 5890.4862
1362 C 14 400X600 12 5177 5890.486 12 4112 5890.4862
1395 C 52 400X600 12 5241 5890.486 12 4257 5890.4862
1390 C 47 400X600 4 8 7286 7690.619 4 8 7286 7690.6188
1371 C 24 400X600 8 4 6333 7143.982 4 8 3375 4731.2385
1401 C 61 400X600 8 4 6966 7143.982 12 5606 5890.4862
1392 C 49 600X725 16 7525 7853.982 8 8 2112 5535.4863
1393 C 50 600X725 16 5067 7853.982 8 8 3480 5535.4863
1400 C 60 600X650 16 7176 7853.982 8 8 3929 5535.4863
1678 C 87 450X700 16 7723 7853.982 4 12 5636 6694.7339
1391 C 48 650X725 20 9048 9817.477 8 12 3611 7498.9817
1378 C 32 600x600 8 4 3932 4476.77 8 4 3932 4476.7695
1523 C 33 600x725 12 5757 5890.486 12 2697 5890.4862
1402 C 62 600X600 12 5760 5890.486 4 8 3554 4731.2385
1385 C 40 600x725 8 4 6959 7143.982 12 4294 5890.4862
1384 C 39 600x650 8 4 6506 7143.982 12 4036 5890.4862
1428 C 09 400X600 8 8 4894 6440.265 8 8 4894 6440.2649
1429 C 10 400X600 8 8 6351 6440.265 8 8 6351 6440.2649
FDN-2ND REST
% Ast REQ % AstPRO % Ast REQ % AstPRO
0.825 1.194 0.933 1.194
0.662 1.194 0.887 1.194
0.801 1.382 1.16 1.382
0.664 1.194 0.909 1.194
0.978 1.194 0.978 1.194
0.906 1.047 0 0
0.75 1.194 1.086 1.194
0.793 1.382 1.162 1.382
1.07 1.194 0.926 1.194
1.09 1.194 1.04 1.194
1.12 1.194 0.661 1.194
1.208 1.571 1.088 1.571
1.122 1.194 1.045 1.194
1.28 1.382 0.841 1.382
1.208 1.382 1.134 1.382
1.457 1.571 1.132 1.571
1.235 1.382 1.047 1.382
1.238 1.382 0.963 1.382
1.444 1.571 0.96 1.571
1.371 1.571 0.99 1.571
1.524 1.571 1.073 1.571
1.552 1.865 1.166 1.571
1.204 1.382 0.896 1.382
1.185 1.382 0.95 1.382
1.15 1.382 1.161 1.382
1.423 1.571 1.271 1.571
1.44 1.571 1.139 1.571
1.295 1.382 1.259 1.382
1.448 1.571 1.277 1.571
1.353 1.571 1.19 1.571
1.362 1.571 1.394 1.571
1.306 1.571 1.525 1.571
1.541 1.865 1.433 1.571
1.522 1.571 1.182 1.571
1.618 1.865 1.178 1.571
1.395 1.571 1.272 1.571
1.543 1.865 1.099 1.571
1.437 1.571 1.021 1.571
1.65 1.865 1.282 1.571
1.671 1.865 1.532 1.865
1.618 1.865 1.054 1.571
1.878 2.454 1.244 2.454
1.818 1.865 1.521 1.571
1.813 1.865 1.008 1.571
1.791 1.865 1.6 1.865
1.773 1.865 0.932 1.571
1.67 1.865 1.393 1.865
1.8 1.865 1.807 1.865
2.16 2.454 0.779 2.454
2.24 2.454 1.182 2.454
2.285 2.454 1.172 2.454
2.015 2.454 1.233 2.454
2.028 2.454 1.571 2.454
2.22 2.454 1.27 2.454
2.014 2.454 1.583 2.454
2.126 2.454 2.126 2.454
1.865 2.454 1.953 2.454
2.157 2.454 1.713 2.454
2.184 2.454 1.774 2.454
3.036 3.204 3.036 3.204
2.639 2.977 1.406 1.971
2.903 2.977 2.336 2.454
1.73 1.806 0.486 1.273
1.165 1.806 0.8 1.273
1.84 2.014 1.007 1.419
2.452 2.493 1.789 2.789
1.92 2.083 0.766 1.724
1.092 1.244 1.092 1.244
1.323 1.354 0.62 1.354
1.6 1.636 0.987 1.314
1.6 1.642 0.987 1.354
1.668 1.832 1.035 1.51
2.039 2.454 2.039 2.454
2.646 2.977 2.646 2.977
COLUMN SCHEDULE
LONG. REINFORCEMENT TRANS. REINF.
COL. NO. SIZE L0 SC
FDN TO 2ND FL. LVL. 2ND FL. LVL. TO REST (10 T)
4 sets
C29,C77,C86 ,C01, C11, C18, C34, 400X600 8 - 16 T + 4 - 20 T 8 - 16 T + 4 - 20 T 675 75
C84
4 sets
C45, C26, C35, C37, C68, C02, C04, 400X600 8 - 20 T 8 - 20 T 675 75
C73, C74, C82, C15, C22, C66, C79
4 sets
C81, C03, C58, C75, C31, C69, C25, 400X600 8 - 20 T + 4 - 25 T 12 - 20 T 675 75
C46, C80
4 sets
C16, C27, C54, C56 L - 625 X 625 X 250 18 - 25 T 18 - 25 T 625 75
6 sets
C43, C20 T - 1300 X 1300 X 250 35 - 20 T + 4 - 12 T 35 - 20 T + 4 - 12 T 1300 75
3 Cross Tie
6 sets
C19, C55 T - 1000 X 1000 X 250 25 - 25 T + 10 - 20 T 25 - 25 T + 10 - 20 T 1000 75
3 sets
C51 T - 525 X 525 X 250 9 - 20 T + 6 - 12 T 9 - 20 T + 6 - 12T 625 75
SN
200
200
200
200
200
200
200
200
200
300
300
300
200
300
300
300
300
300
200
200
300
300
300
300
300
300
CALCULATION OF Ash
SECTION- 250 X 450
Larger Dimension = 450 mm
Shorter Dimension = 250 mm
Strps. Dia = 12 mm
Area of stirrup = 113.10 mm2
Clear Cover = 40 mm
Core Dimension
Lc = 346 mm
Bc = 146 mm
h= 116 mm
Spacing of hoops S = 75 mm
Grade of Concrete Fck = 25 MPa
Grade of Steel Fy = 500 MPa
Gross Area Ag = 112500 mm2
Core Area Ak = 50516 mm2
Ash = 0.18 x S x h x fck/fy x
[Ag/Ak -1 ] = 96.08 mm2 <113.1 sq.mm Hence Ok
SECTION- 450 X 600
Larger Dimension = 600 mm
Shorter Dimension = 450 mm
Strps. Dia = 10 mm
Area of stirrup = 78.54 mm2
Clear Cover = 40 mm
Core Dimension
Lc = 500 mm
Bc = 350 mm
h= 167 mm
Spacing of hoops S = 90 mm
Grade of Concrete Fck = 25 MPa
Grade of Steel Fy = 500 MPa
Gross Area Ag = 270000 mm2
Core Area Ak = 175000 mm2
Ash = 0.18 x S x h x fck/fy x
[Ag/Ak -1 ] = 73.29 mm2 <78.54 sq.mm Hence Ok
SECTION- 400 X 600
Larger Dimension = 600 mm
Shorter Dimension = 400 mm
Strps. Dia = 10 mm
Area of stirrup = 78.54 mm2
Clear Cover = 40 mm
Core Dimension
Lc = 500 mm
Bc = 300 mm
h= 167 mm
Spacing of hoops S = 75 mm
Grade of Concrete Fck = 25 MPa
Grade of Steel Fy = 500 MPa
Gross Area Ag = 240000 mm2
Core Area Ak = 150000 mm2
Ash = 0.18 x S x h x fck/fy x
[Ag/Ak -1 ] = 67.50 mm2 <78.54 sq.mm Hence Ok
SECTION- 600 X 725
Larger Dimension = 725 mm
Shorter Dimension = 600 mm
Strps. Dia = 10 mm
Area of stirrup = 78.54 mm2
Clear Cover = 40 mm
Core Dimension
Lc = 625 mm
Bc = 500 mm
h= 158 mm
Spacing of hoops S = 100 mm
Grade of Concrete Fck = 25 MPa
Grade of Steel Fy = 500 MPa
Gross Area Ag = 435000 mm2
Core Area Ak = 312500 mm2
Ash = 0.18 x S x h x fck/fy x
[Ag/Ak -1 ] = 55.57 mm2 <78.54 sq.mm Hence Ok
SECTION- 450 X 700
Larger Dimension = 700 mm
Shorter Dimension = 450 mm
Strps. Dia = 10 mm
Area of stirrup = 78.54 mm2
Clear Cover = 40 mm
Core Dimension
Lc = 600 mm
Bc = 350 mm
h= 150 mm
Spacing of hoops S = 100 mm
Grade of Concrete Fck = 25 MPa
Grade of Steel Fy = 500 MPa
Gross Area Ag = 315000 mm2
Core Area Ak = 210000 mm2
Ash = 0.18 x S x h x fck/fy x
[Ag/Ak -1 ] = 67.50 mm2 <78.54 sq.mm Hence Ok
SECTION- 650 X 725
Larger Dimension = 725 mm
Shorter Dimension = 650 mm
Strps. Dia = 10 mm
Area of stirrup = 78.54 mm2
Clear Cover = 40 mm
Core Dimension
Lc = 625 mm
Bc = 550 mm
h= 158 mm
Spacing of hoops S = 100 mm
Grade of Concrete Fck = 25 MPa
Grade of Steel Fy = 500 MPa
Gross Area Ag = 471250 mm2
Core Area Ak = 343750 mm2
Ash = 0.18 x S x h x fck/fy x
[Ag/Ak -1 ] = 52.58 mm2 <78.54 sq.mm Hence Ok
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
COL.SIZE
C45, C26, C35, C37,
C68, C02, C04, C73,
C74, C82, C15, C22,
C66, C79 400X600
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
2390 2391 2392 2393 2394
c 22 1369 2513.2741228718 1.047197551 2395
187.811 279.03
2715 2716 2717 2718 2719
c 79 1419 2513.2741228718 1.047197551 2720 2720
2299 2300 2301 2302 2303
c 02 1352 2513.2741228718 1.047197551 2304
Spacing s = 641.8017 mm
COL.SIZE
C83, C53, C05, C21,
C30, C78, C67, C76,
C85, C57 400X600
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
2739 2740 2741 2742 2743
C83 1423 3317.5218421908 1.382300768 2744
2570 2571 2572 2573 2574
C53 1396 3317.5218421908 1.382300768 2575
2432 2433 2434 2435 2436
C05 1355 3317.5218421908 1.382300768 2437
2703 2704 2705 2706 2707
C21 1368 3317.5218421908 1.382300768 2708
2757 2758 2759 2760 2761
C30 1376 3317.5218421908 1.382300768 2762
158.3 279.03
2293 2294 2295 2296 2297
C78 1418 3317.5218421908 1.382300768 2298
2378 2379 2380 2381 2382
C67 1407 3317.5218421908 1.382300768 2383
2697 2698 2699 2700 2701
C76 1416 3317.5218421908 1.382300768 2702
2751 2752 2753 2754 2755
C85 1425 3317.5218421908 1.382300768 2756
2576 2577 2578 2579 2580
c 57 1397 3317.5218421908 1.382300768 2581
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
2345 2346 2347 2348 2349
C81 1421 3769.9111843078 1.570796327 2350
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 1.047
Ꞇc = 0.65
Vus = 152023.9 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 584.3064 mm
COL.SIZE
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
2323 2324 2325 2326 2327
c 06 1356 4476.7695313655 1.865320638 2328
2396 2397 2398 2399 2400
c 23 1370 4476.7695313655 1.865320638 2401
260.859 279.03
2621 2622 2623 2624 2625
c 64 1404 4476.7695313655 2626 2627 2628
2613 2868 2615 2616 2617
C 63 1403 4476.7695313655 1.865320638 2618 2619 2620
BEAM L/C NODE FX FY FZ MX MY MZ
Max Fx 2613 7 1.5(DL+LL) 1403 3046.89 -0.286 12.145 -0.285 -11.848 -1.733
Min Fx 2396 5 SLZ 1370 -455.21 -104.914 -0.642 0.142 1.044 -218.859
Max Fy 2623 13 0.9DL+1.5SL-X 506 922.313 156.493 2.802 -2.741 -6.573 262.549
Min Fy 2398 10 1.5(DL+SLZ) 426 1062.122 -221.175 35.786 1.526 -65.141 -392.297
Max Fz 2619 10 1.5(DL+SLZ) 857 403.171 0.11 260.859 -2.884 -132.968 -34.724
Min Fz 2325 11 1.5(DL+SL-Z) 377 1388 4.617 -133.383 2.365 236.649 8.271
Max Mx 2619 13 0.9DL+1.5SL-X 857 247.377 63.331 85.977 16.748 -51.577 -10.658
Min Mx 2627 10 1.5(DL+SLZ) 858 311.341 -72.583 61.11 -22.826 -77.861 -28.41
Max My 2623 10 1.5(DL+SLZ) 612 1270.269 -24.823 159.093 -2.256 273.039 45.26
Min My 2623 10 1.5(DL+SLZ) 506 1299.533 -24.823 159.093 -2.256 -275.83 -40.38
Max Mz 2397 10 1.5(DL+SLZ) 426 1205.066 -192.393 19.76 -0.012 46.474 396.712
Min Mz 2398 10 1.5(DL+SLZ) 426 1062.122 -221.175 35.786 1.526 -65.141 -392.297
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 1.865
Ꞇc = 0.80
Vus = 123334.7 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 720.2232 mm
COL.SIZE
C07, C12, C13, C70,
C38, C65, C71, C72,
C59, C14, C52 400X600
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
COL.SIZE
C10, C09
400X600
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 2.683
Ꞇc = 0.89
Vus = 104571 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 849.4566 mm
COL.SIZE
C47
400X600
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
2529 2530 2531 2532 2533
c 47 1390 7690.62 3.204424507 2534 3004
196.85 279.03
COL.SIZE
C24
400X600
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
c 24 1371 4731.24 1.97134939
256.466 279.03
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 1.971
Ꞇc = 0.82
Vus = 120026.6 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 740.0736 mm
COL.SIZE
C61
400X600
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
c 61 1401 5890.49 2.454369261
187.932 279.03
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 2.454
Ꞇc = 0.87
Vus = 108500.5 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 818.6925 mm
COL.SIZE
C49, C50
600X725
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
2541 2542 2543 2544 2545
c 49 1392 5535.49 1.272525576 2546 3008
2547 2548 2549 2550 2551 327.2 279.03
c 50 1393 5535.49 2.306452607 2552 2553 2993
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 1.273
Ꞇc = 0.70
Vus = 189997.2 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 467.5255 mm
COL.SIZE
C41
400X600
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 2.306
Ꞇc = 0.86
Vus = 111961.7 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 793.3829 mm
COL.SIZE
C60
600X650
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
c 60 1400 5535.49 1.41935545 2594 - 2599, 3005
337.782 279.03
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 1.419
Ꞇc = 0.73
Vus = 195998.1 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 453.2112 mm
COL.SIZE
C87
C87
450X700
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
c 87 1678 6694.73 2.125312363 3335 - 3340
260.076 279.03
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 2.125
Ꞇc = 0.84
Vus = 116200.4 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 764.4425 mm
COL.SIZE
C48
650X725
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
c 48 1391 5180.49 1.099307435
363.221 279.03
COL.SIZE
C32
600X600
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
2450 2451 2452 2453 2454
c 32 1378 4476.77 1.243547092 2455
234.337 279.03
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 1.244
Ꞇc = 0.70
Vus = 142834.7 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 621.8973 mm
COL.SIZE
C62
C62
600X600
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
c 62 1402 4731.24 1.314232927
315.258 279.03
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 1.314
Ꞇc = 0.71
Vus = 176753.9 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 502.5548 mm
COL.SIZE
C40
600X725
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
c 40 1385 5890.49 1.354134764
294.237 279.03
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 1.354
Ꞇc = 0.72
Vus = 154488 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 574.9866 mm
COL.SIZE
C33
600X725
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
c 33 1523 5890.49 1.354134764
264.769 279.03
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 1.047
Ꞇc = 0.65
Vus = 244691.2 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 363.0231 mm
COL.SIZE
C08
450X600
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
2335 2336 2337 2338 2339
c 08 1358 2865.13 1.061160185 2340 116.065 279.03
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 1.061
Ꞇc = 0.65
Vus = 151370.4 N
Dia of Hoop = 10 mm
Using 4-legged Hoop
Area = 78.53982 mm2
Spacing s = 586.8288 mm
COL.SIZE
C39
600X650
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
c 39 1384 5890.49 1.510381083 2490 - 2495
371.7 279.03
L&T SECTIONS
COL.SIZE
C17,C28,C42,C44
775X775X250
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
COL.SIZE
C16,C27,C54,C56
625X625X250
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
C 16 1629 5655.00 2.262 3099 - 3106
C 27 1628 5655.00 2.262 3091 - 3096, 3060, 3061
192.622 279.03
C 54 1605 5655.00 2.262 3056 - 3058, 3065, 3060 - 3063
3070 - 3072, 3326, 3074, 3075,
C 56 1614 5655.00 3346, 3347
BEAM L/C NODE FX FY FZ MX MY MZ
Max Fx 3056 9 1.5(DL+SL-X) 1605 2453.56 -51.127 110.514 1.07 -420.373 -159.869
Min Fx 3056 3 SLX 1605 -708.351 36.191 -74.14 -1.286 280.893 104.559
Max Fy 3062 19 1.2(DL+LL+SL-Z) 1319 351.98 192.622 98.073 -0.039 55.757 38.781
Min Fy 3092 13 0.9DL+1.5SL-X 92 544.335 -106.331 163.946 1.655 -350.067 -207.616
Max Fz 3091 9 1.5(DL+SL-X) 1628 1074.287 -104.923 168.295 4.781 -508.119 -215.658
Min Fz 3071 11 1.5(DL+SL-Z) 200 591.9 124.065 -165.554 -2.991 377.793 241.31
Max Mx 3346 11 1.5(DL+SL-Z) 1320 -62.16 35.631 24.765 30.236 -99.695 9.472
Min Mx 3346 14 0.9DL+1.5SLZ 1320 226.217 5.401 13.954 -20.647 74.687 28.543
Max My 3091 12 0.9DL+1.5SLX 1628 839.247 109.248 -163.823 -4.868 501.366 220.993
Min My 3091 9 1.5(DL+SL-X) 1628 1074.287 -104.923 168.295 4.781 -508.119 -215.658
Max Mz 3326 11 1.5(DL+SL-Z) 1671 303.312 157.692 -141.58 0.116 222.701 287.293
Min Mz 3072 11 1.5(DL+SL-Z) 1671 429.132 158.211 -135.099 0.868 -213.478 -284.303
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 2.262
Ꞇc = 0.85
Vus = 113001.9 N
Dia of Hoop = 12 mm
Using 4-legged Hoop
Area = 113.0973 mm2
Spacing s = 1131.955 mm
COL.SIZE
C43,C20
1300X1300X250
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
3110, 3118, 3119, 3113, 3114,
C 43 1632 11447.96 1.949 3122, 3116, 3117
C 20 1647 11447.96 1.949 3136 - 3143 375.128 279.03
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 1.949
Ꞇc = 0.81
Vus = 216832 N
Dia of Hoop = 12 mm
Using 4-legged Hoop
Area = 113.0973 mm2
Spacing s = 589.9179 mm
COL.SIZE
C19,C55
1000X1000X250
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
C 19 1648 15413.44 3.523 3144 - 3149, 3358, 3359
3.523 3123 - 3125, 3324, 3127, 3128,
C 55 1639
15413.44 3348, 3351 320.78 279.03
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 3.523
Ꞇc = 0.90
Vus = 145639.9 N
Dia of Hoop = 12 mm
Using 4-legged Hoop
Area = 113.0973 mm2
Spacing s = 878.2831 mm
COL.SIZE
C51
525X525X250
MAX MAXIMUM
CALCULATED FACTORED
COLUMN NO. NODE MIN. AST PRO % Pt MEMBERS IN STAAD SF S.F
C 51 1648 3506.02 1.753 2554 - 2561
180.447 279.03
FACTORED
MAX AST MOMENT OF RESISTANCE OF S.F = 1.4 x
.PROVIDED BEAMS CORRESPONDING TO [Mu1+Mu2]/
BEAMS SECTIONS USED GROSS AREA 4% 4% REINFORCEMENT hst
500 250 125000 5000 108.75 KN-m 92.27272727 KN
600 300 180000 7200 219.24 KN-m 186.0218182 KN
600 250 150000 6000 182.7 KN-m 155.0181818 KN
700 300 210000 8400 328.86 KN-m 279.0327273 KN
650 300 195000 7800 271.44 KN-m 230.3127273 KN
600 400 240000 9600 292.32 KN-m 248.0290909 KN
750 250 187500 7500 326.25 KN-m 276.8181818 KN
CALCULATION OF TIES
% Of Reinf. Provided = 1.753
Ꞇc = 0.78
Vus = 126838.9 N
Dia of Hoop = 12 mm
Using 4-legged Hoop
Area = 113.0973 mm2
Spacing s = 1008.469 mm
Total Height = 23.25 M
Thickness of the wall provided= 250 mm > 150 mm Hence OK
Min Ast required = 14531.25 mm2 [ As per IS 13920 : 1993, Clause: 9.1.4
Min. reinf. Ratio shall be 0.0025 of the
gross area in each direction]
Horizontal length of the wall = 1200 mm
Min Ast required = 14531.25 mm2 [ As per IS 13920, Clause: 9.1.4 Min.
reinf. Ratio shall be 0.0025 of the gross
area in each direction]
Horizontal length of the wall = 1037 mm
[ As per IS 13920,Clause 9.1.7 The maximum spacing of reinf. In either direction shall not
exceed the smaller of lw/5 , 3tw and 450 mm ]
lw = the horizontal length of the wall = 1037 mm
tw = thickness of the wall = 250 mm
Max. Spacing = 207.4 mm
Dia. of bar provided = 12 mm
Area = 113.0973 mm2
No. Of bars required = 128 Nos.
Spacing required = 181 mm
Spacing provided = 100 mm
Hence Provide 12 T @ 100 c/c