DRAWING LIST OF SEB TYPICAL DETAILS

DRAWING No. DRAWING TITLE


SD/001D DRAWING LIST OF SEB TYPICAL DETAILS

SD/002A GENERAL NOTES

SD/003A CRANKING OF BARS, STANDARD HOOKS AND BENDS

· SD/004A STEEL REINFORCEMENT ANCHORAGE AND LAP LENGTH REQUIREMENT

SD/005B TYPICAL DETAIL OF SPACER BARS AND STIRRUPS AT BEAMS

SD/006B TYPICAL DETAIL OF TORSION STIRRUPS AND COLUMN BINDERS

SD/007 TYPICAL WALL JUNCTION DETAILS

SD/008 TYPICAL DETAIL OF BRICK OR R.C. PARTITION WALL AND WALL BASE

SD/009 TYPICAL DETAIL OF R.C. STRUCTURAL WALL

SD/010 TYPICAL DETAIL OF TRIMMING BARS FOR WALL OPENING

SD/011 TYPICAL DETAIL OF TRIMMING BARS FOR. PERMANENT SLAB OPENING

SD/012 TYPICAL DETAIL OF TRIMMING BARS FOR TEMPORARY SLAB OPENING

SD/013 TYPICAL DETAIL FOR TEMPORARY PIPE DUCT OPENING IN SLAB

SD/014 REQUIREMENT OF SPACER BLOCK, 'U' BARS AND STEEL CHAIRS FOR STRUCTURAL ELEMENTS

SD/015 CURTAILMENT OF LONGITUDINAL BARS IN BEAMS

SD/016 TYPICAL DETAIL OF BEAM AND BEAM 'L' JUNCTION

SD/017C TYPICAL DETAIL OF COLUMNS

SD/018 TYPICAL DETAIL OF ROOF BEAM & EXTERIOR COLUMN JUNCTION

SD/019B TYPICAL DETAIL OF 100 THICK GROUND SLAB ON GRADE

SD/020B TYPICAL DETAIL OF 150 THICK GROUND SLAB ON GRADE

SD/021B TYPICAL DETAIL OF 200 THICK GROUND SLAB ON GRADE

SD/022A TYPICAL DETAIL OF EXTERNAL DRIVEWAY AND ·CARPARK GROUND SLAB ON GRADE (1 OF 5)

SD/023A TYPICAL DETAIL OF EXTERNAL DRIVEWAY AND CARPARK GROUND SLAB ON GRADE (2 OF 5)

SD/024A TYPICAL DETA.IL OF EXTERNAL DRIVEWAY AND CARPARK GROUND SLAB ON GRADE (3 OF 5)

SD/025A TYPICAL DETAIL OF EXTERNAL DRIVEWAY AND CARPARK GROUND SLAB ON GRADE (4 OF 5)

SD/026B TYPICAL DETAIL OF EXTERNAL DRIVEWAY AND CARPARK GROUND SLAB ON GRADE (5 OF 5)

checked dote drawing no. rev. scale


drawing title

CSE/1 M.K. WONG I------=> DEC., 2014 SD/001 D N.T.S.


DRAWING LIST OF
SEB 1YPICAL DETAILS approved dote STRU. ENGG. BRANCH
AD(SE) K.T. LEUNG ~ DEC., 2014 ARCH. SERVICES DEPT.
NOTE : IN LIEU OF THE 1YPES OF BEAM STIRRUPS SHOWN ON THE R.C. DRAWINGS, THE CONTRACTOR
MAY PROPOSE FOR SO'S APPROVAL ALTERNATIVE TYPES OF BEAM STIRRUPS.

u· ~· J
(1YPE B)
11-----11+-- (1YPE C)
(1YPE E)

'-• • • •

SPACER BARS

lYPE D

u
lYPE F

E
E
si2
S: A\
,_
:::>
CD

10¢
BUT ~ 70mm

lYPE N
lYPE M (r) REFER TO TABLE 1 ( SD/003 )

FIG. 1 BEAM STIRRUPS ( *b1 )


Ab2
REFER TO TABLE 3 ( SD/006 )

checked dote drawing no. rev. , scale


dn;1wing title

CSE/1 M.K. WONG I DEC., 2014 SD/005 ,B N.T.s.


lYPICAL DETAIL OF
SPACER BARS AND approved dote STRU. ENGG. BRANCH
STIRRUPS AT BEAMS
AD(SE) K.T. LEUNG \uJ
u
DEC., 2014 ARCH. SERVICES DEPT.
50
TLL TLL

lit• • •
·11 •• • ·~·

• •

a •
\
• •

[]

• • [J
• • • • 0 • • • • • • • •
FIG. 2a TORSION STIRRUPS
NOTE : 1. IN LIEU OF THE TYPES OF COLUMN BINDERS SHOWN ON THE R.C. DRAWINGS, THE CONTRACTOR
MAY PROPOSE FOR SO'S APPROVAL ALTERNATIVE TYPES OF COLUMN BINDERS.
2. TYPE F CROSSTIES ENGAGING THE SAME LONGITUDINAL BAR SHALL HAVE THEIR 90-DEG HOOKS
ALTERNATIVELY FIXED ON OPPOSITE SIDES OF COLUMN.

8~ '\o\1;
~

TYPE C
TYPE D

BOND LENGTH
FOR REBARS TO CS2 : 1995 CS2 : 2012
4¢ 5¢
~1 BUT 2 50mm BUT 2 50mm
6¢ 6¢
~ BUT 2 60mm BUT 2 60mm

TABLE 3
8 BOND LENGTH FOR HOOKS AND BENDS
REQUIREMENT FOR BEAM STIRRUPS
AND COLUMN BINDERS
~150mm

(TYPE D)
OR

FIG. 2b TYPICAL DETAIL OF COLUMN BINDERS


FOR COLUMN BINDERS : ( r ) REFER TO TABLE 1 ( SD/003 )
checked dote drawing no. rev. scale
drawing title

CSE/1 M.K. WONG / - ) • DEC., 2014 SD/006 8 N.T.S.


lYPICAL DETAIL OF
TORSION STIRRUPS AND approved dote STRU. ENGG. BRANCH
COLUMN BINDERS
AD(SE) K.T. LEUNG [MU DEC., 2014 ARCH. SERVICES DEPT.
50
TLL
I· ·1
: } { : : :
11 s
i i s
OR
'I
TLL
I· ·1

If i i s
:
s
: } { : :: : : )1

S = SPACING OF BARS
WAll END

<: n
.. :<
~-

..
0- 0
"., .," 5"'<1 "., ?
OR < , 0

o 0
-.J
-.J
....:
o

1\
0

]
~ e 10 c

o e ~ c
.JV- l..;y.

../'y-
TEE JUNCTION rV'-

o 0 ., 0

-'r-- " e 9 ~
~
.-
8 TWO BARS SHOULD BE PLACED WITHIN LOOP en
-=- Ul

-.J FOR WAlL THICKNESS ~ 200mm. -'


-'.,.- ole -.J -' 10
....: FOUR BARS SHOULD BE INCLUDED AS SHOWN ~ 0 t---'Ic-

- FOR WALL THICKNESS OVER 200mm.


Ul \ I en
.,
- -' ~
0
.
0
..
v
..
v
< OR ~
u

c>
"
~

"-
0
ft ',/
7-
1----' ..-

-
s l
'1
s
'1
l s 1
'1
s 1
'1
T.L.L. TLL
S = SPACING OF BARS
-
0
~
l" JUNCTION
-
FIG. 3 TYPICAL WALL JUNCTION DETAILS (PLAN)

checked date drawing no. scale


drawing title
-
lYPICAl WALL JUNCTION CSE/l C.T. WONG ~tX<f JULY. 2008 SD/007 N.T.S.

DETAilS approved date STRU. ENGG. BRANCH


Wd
-:
...:
AO(SE) W,W. U JULY. 2008 ARCH. SERVICES DEPT.
0 'I' 'I I I I 50
1 0 10 20 30 40 50 mm A4 210 x 297
11111111111 I I I I
1 : 1 SCALE BAR
VERT. REINF'T HORI. REINF'T
WALL THICKNESS, h COMPARTMENT WAll WITH
NO FRP FIRE RESISTING PERIOD (FRP) REQUIREMENTS
( mm ) REQUIREMENT
ALL CASES
1 HOUR 2 HOUR 4 HOUR
100 ~ h < 120 T10-250 Tl0-250

120 ~ h < 160 T10-300 EF T10-300 EF

160 ~ h < 180 T10-300 EF Tl0-300 EF Tl0-300 EF T10-250 EF

180 ~ h < 200 T10-250 EF T10-250 EF T10-250 EF T10-250 EF

200 ~ h < 240 T10-200 EF T10-200 EF T10-200 EF T10-200 EF

240 ~ h ~ 250 T10-200 EF T10-200 EF T10-200 EF T10-200 EF

INDICATES THAT WAlL THICKNESS IS NOT PREFERRED AS 1% REINFORCEMENT OF


THE MIN. WAlL THICKNESS IS NEEDED FOR THE FRP REQUIREMENT. WAlL THICKNESS SHOULD BE
INCREASED IN THIS CASE IF POSSIBLE SO THAT NORMAl REINFORCEMENT RATIO COULD BE USED.

TABLE 3 BAR SIZES AND SPACING FOR NON-LOADBEARING PARTITION WALL


It 300 It It 300 (,

1 1 1 1
NOTES:
1. PARTITION WALLS WITH NOMINAL REINFORCEMENT
ARE NOT CONSIDERED AS LOAOBEARING
STRUCTURAl MEMBERS AND HENCE
REINFORCEMENT WILL NOT BE MEASURED
SEPARATELY, BUT DEEMED INCLUDED IN THE
RATES AS FOR OTHER ARCHITECTURAL
FEATURES.
h h
2. SLAB THICKNESS & REINFORCEMENT APPUCABLE
TO BRICK PARTITION WAlL BASES.
6T10

600 POLYTHENE SHEETING 600

~- 50 BUNDING LAYER - - - - '

100 ~ h < 120 WALL 120 ~ h ~ 250 WALL

FIG. 4 1YPICAL DETAIL OF BRICK OR R.C. PARTITION WALL & WALL BASE
drawing title checked date drawing no. scale

TYPICAL DETAIL OF BRICK GSEll CJ. WONG ~ JULY, 2008 SD/008 N.T.S.

OR R.C. PARTITION WALL


& WALL BASE
approved date STRU. ENGG. BRANCH
AD(sE) W.W. LI JULY. 2008 ARCH. SERVICES DEPT.
50 o 10 20 30 40 50 mm 297~
'"" I",,' I !
1 : 1 SCAt! BAR
I I A4 210 x
VERT. REINF'T HOR!. REINF'T
WALL THICKNESS, h I--N-O-F-R-P---r"F-IR-E-R-ES-ISTI-N-G-P-E-RI-OD-(FR-P-)-R-EQ-U-IRE-M-EN-T-St - - - - - - t
( mm ) REQUIREMENT 1 HOUR 2 HOUR 4 HOUR ALL CASES

150 ~ h < 160 nO-300 EF

160 ~ h < 180 T10-200 EF T10-200 EF Tl0-200 EF nO-250 EF

180 ~ h < 200 T12-250 EF T12-250 EF T12-250 EF Tl0-250 EF

200 ~ h < 240


240 ~ h ~ 250 T12-170 EF T12-170 EF T12-170 EF T12-170 EF n2-250 EF
INDICATES THAT WALL THICKNESS IS NOT PREFERRED AS 170 REINFORCEMENT OF
THE WALL THICKNESS IS NEEDED FOR THE FRP REQUIREMENT. WALL THICKNESS SHOULD BE
INCREASED IN THIS CASE IF POSSIBLE SO THAT NORMAL REINFORCEMENT RATIO COULD BE USED.

TABLE 4 BAR SIZES AND SPACING FOR R.C. STRUCTURAL WALL


( SEE ALSO DETAIL DRAWINGS WHICH SHALL TAKE PRECEDENCE OVER THIS TABLE.)
300 ..
FL LEV' MIN
"V'
I I
? ?

~.

-'
-'
I-
FL LEV
-~
? ?

FOR SIZE AND REINFORCEMENT


OF WALL REFER TO TABLE 4 OR
AS SPECIFIED ON THE DETAIL DRAWINGS.
~
t- h

-'
-'
I-
GRD LEV

l
"V'
• l
V~/(', ~ V ~/:"-J

HARDCORE J . V
REFER RELEVANT
.
r-....l~
~
/
STR UCTURAL DRAWINGS

GROUND BEAM OR FOOTING


FER RELEVANT STRUCTURAL DRAWINGS)
~300 /] (RE
It 'I

FIG. 5 1YPICAl DETAil OF R.C. STRUCTURAL WALL


drawing title checked dote drawing no. scale

lYPICAL DETAIL OF CSE/1 C.T.WONG ~. JULY. 2008 SD/009 N.T.S.

R.C. STRUCTURAL WALL approved dote STRU. ENGG. BRANCH


AD(SE) W.W. LI Wd JULY. 2008 ARCH. SERVICES DEPT.
50 0 10
11111111111
20
I
30
I
40
I
50 mm
I M 210 x 297~
1 : I SCAlE BAR
, . . - - - - WAll REINFORCEMENT - - - - - ,
r-tY ,h .,

TRIMMING BARS
(TYING WIRE AT ALL INTERSECTIONS)

h < 120 120 ~ h < 200 200 ~ h ~ 250

SEC. A - A
ELEVATION TRIMMING BARS
(TYING WIRE AT ALL INTERSECTIONS)
r- ..-- TRIMMING BARS
(TYING WIRE AT AlL INTERSECTIONS)

I .
~
~ L..------L... WALL REINFORCEMENT
75
- - WALL REINFORCEMENT

h < 120 120 ~ h ~ 250


SEC. B - B
1. TABLE 5 AND FIG. 6 ARE APPLICABLE FOR NON-LOADBEARING WALLS WHERE OPENING WIDTH (L 1) ~ 2m.

TRIMMING BARS TO OPENING


WALL THICKNESS, h (mm)
L1 < 1m 1m < L1 ~ 2m
h < 120 1T12 ( SINGLE LAYER ) 2T12- 75 (SINGLE LAYER)

120 ~ h < 200 1T12 EF 2T12 - 75 EF

200 ~ h ~ 250 1T16 EF 2T16 - 75 EF

TABLE 5 TRIMMING BARS FOR WALL OPENING AT NON-LOADBEARING WALLS

2. FOR NON-LOADBEARING WALLS WHERE OPENING WIDTH (L1) > 2m, OR FOR ALL SIZE OF OPENING IN
STRUCTURAL WALLS, THE LOCATION AND SIZE OF THE OPENING SHALL BE APPROVED BY THE PROJECT
STRUCTURAL ENGINEER. DETAILS AND AMOUNT OF TRIMMING BARS SHALL BE SPECIFIED BY THE PROJECT
STRUCTURAL ENGINEER. REFER ALSO TO WALL DETAIL DRAWINGS.

3. UNDER NORMAL SITUATION, IF OPENING WIDTH (L1) < BAR SPACING, NO TRIMMING BAR IS REQUIRED.

FIG. 6 TYPICAL DETAIL OF TRIMMING BARS FOR WALL OPENING

drawing title checked date drawing no. scale

TYPICAL DETAIL OF CSEll C.T. WONG ~. JULY. 2008 SO/OlO N.T.s.

TRIMMING BARS FOR approved date STRU. ENGG. BRANCH


WALL OPENING

50
AO(sE)
0
'1LW. LI
10
rdd20 30 40
JULY. 2008
50 mm
ARCH. SERVICES DEPT.
A4 210 x 297~
11111111111 I I I I
1 : 1 SCAI.£ BAR
-r
2 )( 1T16 T 8£ B
~
/

- ~~ ......
f~"""
IY ~ \.::J

I ill II II
I II '-2 )( 1T16 T 8£ B

AFFECTED BARS

PLAN
300

II
LL AND ~ 2h
U-BARS TO LAP THjE U-BARS TO LAP THE 1 r- Tl0 EXTRA BARS
AFFECTED BARS --:: AFFECTED BARS

~:: :~:::::::;:::::: ~ T
t=;:::::t: -"
B~: ~ -? ..c1
1T16 T 8£ B ~ 1. 1T16 T 8£ • --

~FFECTED BARS I. .TLL .1 LAFFECTED BARS

SLAB WITH TOP REINFORCEMENT SLAB WITHOUT TOP REINFORCEMENT


SEC. A - A

NOTES:
1. FIG. 7 IS APPLICABLE FOR OPENINGS THAT :-
o. WITH SLAB THICKNESS ~ 200mm
b. HAVE OPENING SIZE NOT MORE THAN 600mm OR 0.25 x SPAN LENGTH OF SLAB
c. DETAIL NOT APPLICABLE TO OPENINGS IN CANTILEVER SLABS

8
-=. 2. IF SIZE OF OPENING < 200mm, DISPLACE BARS TO SIDES OF OPENING, NO EXTRA TRIMMING BARS
REQUIRED.
-
3. FOR SIZE OF OPENING BETWEEN 200mm & 600mm, ADD TRIMMING BARS AS STATED IN THE FIGURE,
- OR THE AREA OF TRIMMING BAR ON ONE SIDE EQUAL TO HALF THE AREA OF THE AFFECTED BARS IN
THE CORRESPONDING DIRECTION CUT BY THE OPENING, WHICHEVER IS THE GREATER.
- 4. FOR LARGER SIZE OF SLAB OPENING, DETAILS OF STEEL ARRANGEMENT SHALL BE SPECIFIED BY THE
PROJECT STRUCTURAL ENGINEER. REFER ALSO TO SLAB DETAIL DRAWINGS.
-

- FIG. 7 lYPICAl DETAil OF TRIMMING BARS FOR PERMANENT SLAB OPENING

drawing title checked date drawing no. scale


-
lYPICAl DETAIL OF CSE/l C.T. WONG ~ur JULY, 2008 SO/011 N.T.S.

TRIMMING BARS FOR approved date STRU. ENGG. BRANCH


Wd
..."
PERMANENT SLAB OPENING
-= AO(SE) W.W. LI JULY, 2008 ARCH. SERVICES DEPT.
0 'I' 'I 1 1 1 150 0
11111111111
10 20
I
30
I
40
I
50 mm
I A4 210 )( 297~
1 : 1 SCAl£ BAR
,I ,I
,,

,,
1----.-,""T,-t--L-- TRIMMING BAR TO BE SPECIFIED BY
THE PROJECT TRUCTURAL ENGINEER
IF NEEDED
SlAB REINFORCEMENT --'----------t-i

I I

TRIMMING BARS TO BE SPECIFIED BY


THE PROJECT STRUCTURAL ENGINEER IF NEEDED

FORMWORK TO BE SLOTTED FOR PASSAGE OF BARS

L--'- SLAB REINFORCEMENT

SEC. A - A

NOTES:
THE FIGURE IS APPLICABLE TO TEMPORARY SLAB OPENING THE SIZE AND LOCATION OF WHICH
SHALL BE APPROVED BY THE PROJECT STRUCTURAL ENGINEER BEFORE CONSTRUCTION.

FIG. 8 TYPICAL DETAIL OF TRIMMING BARS FOR TEMPORARY SLAB OPENING

drawing title checked date drawing no. scale

lYPICAL DETAIL OF CSE/I C.T. WONG ~. JULY. 2008 SD/012 N.T.S.

TRIMMING BARS FOR approved date


TEMPORARY SLAB OPENING STRU. ENGG. BRANCH
AD(SE) W.W. LI JULY. 2008 ARCH. SERVICES DEPT.
50 o 10
I""',,,,! 20
I 30
!
40
I
50 mm
I A4 210 x 297~
1 : 1 SCAlI lIAR
PIPE DUCT OPENINGS TO BE CONCRETED -
AFTER INSTAlLATION OF PIPS

r-- . .
SLAB REINF'T.
I
1
I
I 1',,,- <""" //

I
I
I ~
I',
DIA & SPACING SAME AS LAB REINF'T.
//~
I I
I I ', -I
F= /
/
~
'L... t:z
E I . G:i
o
o
E
It: I
I
I ' ',-'\;- //
/ 0:::
Vl~
0:::
Lf)
I~
v 10::: IIt I m~' ' / / I,TlL~
C,!)
:z I~ I I 1 'x/ '1I
C5
0...
I 1 ~ /,
o
lL.
--------~I-+--I~I--~I------- //', ~
o
I I I / / -'", , <0...(3
I I / ,Vl

I II I / / -I 'O'd
,~

-------
F=
I
I I 1// '~
I I-~----- - - - -
I 1//1 "
~----------~

TRIMMING BARS TO BE SPECIFIED BY


THE PROJECT STRUCTURAL ENGINEER
IF NEEDED.
J SLAB REINF'T.

WALL - - t -

WIDTH OF OPENING < 1500mm

CD
:5
en
8
-=-
-
~r=f : .• .•
:z
~
u
~
-

- SEC. A - A
- NOTES:
THE FIGURE IS APPLICABLE TO TEMPORARY SLAB OPENING THE SIZE AND LOCATION OF WHICH
SHALL BE APPROVED BY THE PROJECT STRUCTURAL ENGINEER BEFORE CONSTRUCTION.

-
FIG. 9 1YPICAL DETAIL FOR LARGER TEMPORARY PIPE DUCT OPENINGS

drawing title checked date drawing no. scale

- lYPICAL DETAIL FOR CSE/l C.T. WONG JULY. 2008 SO/013 N.T.S.

TEMPORARY PIPE DUCT approved date


- OPENING IN SLAB STRU. ENGG. BRANCH
-:: AD(SE) W.W. LI JULY, 2008 ARCH. SERVICES DEPT.
o 'I ·1 I I I o w
'""',,,,'
~
I
~
I
~
!
50 mm
I A4 210 x 297~
1 : 1 SCAlE BAR
T12 STEEL CHAIR
@1500 clc MAX.

COVER SPACERS FORMWORK

~
@600 clc MAX.
SECTION OF SLAB
( :
FORMWORK T12 "u" BAR
COVER SPACERS MAX. SPACING: 1500 c/c B.W.

T12 -U- BAR WALL REINFORCEMENT


@1500 clc MAX.
WALL PLAN

SPACERS WITH
TIE WIRES
)§§~- FORMWORK
COVER SPACERS

SECTION OF BEAM

NOTES:
THE DIAMETER AND SPACING OF CHAIRS ARE GIVEN AS MINIMUM REQUIREMENT,
THE CONTRACTOR HAS TO PUT IN ADDITIONAL CHAIRS WHERE NECESSARY TO SUPPORT
THE REINFORCEMENT FROM SAGGING OR DISPLACEMENT.

FIG. 10 REQUIREMENT OF SPACER BLOCK. "Un BARS AND


STEEL CHAIRS FOR STRUCTURAL ELEMENTS

drawing title checked dote drawing no. scale

REQUIREMENT OF SPACER
BLOCK, 'u' BARS AND
CSE/l C.T. WONG ~ JULY, 2008 SD/014 N.T.S.

STEEL CHAI RS FOR approved dote STRU. ENGG. BRANCH


STRUCTURAL ELEMENTS AO(SE) W.W. LI JULY, 2008 ARCH. SERVICES DEPT.
50 o
I"" I",,'
10
I
20 30
!
40
,
50 mm
!
A4 210 x 297~
1 : 1 SCAlE BAR
100

I J
I I
TAL I ~ O.lSl1 ~ O.25L j;J O.25L ~ 0.15L2
AND ~ 45(1\1 AND ~ 45(1\3 AND ~ 45¢3 AND ~ 45¢4
TAL +
~~ LES ER (O.5h 0R 8(4)
r ~ r ~
Q
'" -
~ L BEAM BAR OF DIA, ~1 - L BEAM BAR OF DIA, ~3 BEAM BAR OF DIA, ~4 ~ -
(") 0 -r-- ,-
~ a V1 J
Vi'
,..., CD LANTI-CRACK WEB BARS OF DIA ¢s, FOR BEAM DEPTH> 750 BEAM BAR OF DIA, ~5 --.
........ 0 -'-
0 7':'
""., S
0 CD -'-
("")
<
III
~ CD a. 12(1\s L BEAM BAR OF DIA, ~2 ~ 0.75h
a. ;-t ~ BEAM
~ 12!11~- ~ ~
:::E
DEPTH LAP
0 0 12¢5
:z
G") I- Lf
FLOOR BEAM FLOOR BEAM h
.. N
0
- SPAN L1 SPAN L2
I I I

~ ~
NOTE: L = THE GREATER OF 11 AND L2
~
I t 1
is
<- <-
c: c:
E< a. E< a.
U! a N a
0 ~ CD 800 CD
3 ~ - -
3
c..
a
!.
::l NOTES:
<0
~~ ::l
.:I:c:
. ? 1. FOR ARRANGEMENT OF REINFORCEMENT IN EXTERIOR COLUMN AND BEAM JUNCTION
U)r'Tl AT ROOF LEVEL REFER TO ORG No. 50/018.
r'Tlz U)
~C') a
("')!"> "'-
0
"'m (]'I FIG. 11 CURTAILMENT OF LONGITUDINAL BARS IN BEAM
~ ~~
r'Tl
~ n
z: CIl
0 ~:I: (")
;-t 0
x ~ ii>
N
cD

L
L_r
.h
r
111-_--::£---- .... --j--------...,
J~/ I ;
SEE NOTE 1

I
ANTICRA.CK WEB BAR REQUIRED
.IF BEAM DEPTH > 750mm

1 I ; I
iJ-J------ -J-----------
I_ 1U. .1 ~ ElfAII U.N R8NFORCEMENT

ELEVATION

"'V
T 1
1 1
1 1
1 I
1 I
1 I
1 I
1 I

[ ----I
I
I
I
j
BEAM MAIN REINFORCEMENT

I I 7
~.... ~ J.

J
SEE NOTE 1
~
PLAN
8
....=:

- NOTES:

- 1. FOR ANTIC RACK BARS AT THE CORNER OF L JUNCTION USE T12 - 250 c/c (MIN.) OR
IF BEAM DEPTH GREATER THAN 750mm. USE ANTICRACK BARS AS SPECIFIED ON BEAM
DETAIL DRAWING.
-

FIG. 12 lYPICAl DETAil OF BEAM AND BEAM 'L' JUNCTION


-

drawing title checked date drawing no. scale

- lYPICAL DETAIL OF BEAM CSE/1 C.T.WONG ~. JULY. 2008 SD/016 N.T.S.

AND BEAM 'L' JUNCTION approved date STRU. ENGG. BRANCH


...:

0""1' 'I I 1 I ISO


AD(SE) W. W. LI
0 10
hid
20 30 40
JULY. 2008
50 mm
ARCH. SERVICES DEPT.
A4 210 x 297~
11111111111 1 1 1 I
1 : 1 SCALE BAR
I I LESSER ( 0.5h OR 80b1 ) + TAL
I
BEAM BAR (01) OF DIA = 01,1 1 I

-
I

.' (

J ROOF BEAM
(02) "1:>
,...
U')

ci
A\
I

I
I
1--H+---I--1I---f--
-~

BINDERS WITH
SPACING EO 200mm
(SEE DETAIL DRG)
BEAM BAR OF DIA = £Ib2 J I ~ 0.75h I
+
II 1 ....... 1 .r:
I .§, I
U')
-'- .8--....
L
I I
I I
114---,------t~- COLUMN BAR (02) OF DIA = 0c
I hi J
f,,--1
COL~MN

I
FIG. 14.1 ROOF BEAM & EXTERIOR COLUMN JUNCTION
- TYPICAL DETAIL (I)

TLL

BEAM BAR (01) OF DIA = £Ib1 1 II


~±=~1(0=2)====~~~~~~~~~
~ -r-
ROOF BEAM I - - I t - I - - - I - - - BINDERS WITH
SPACING EO 200mm
(SEE DETAIL DRG)
BEAM BAR OF DIA = £Ib2 J [I > 0.75h.1 +
8
-=- If I II
!I I
I I

-
I : COLUMN BAR (02) OF DIA = £Ie
- I
.1

-
COL~MN
-

- FIG. 14.2 ROOF BEAM & EXTERIOR COLUMN JUNCTION


- TYPICAL DETAIL (II)
drawing title checked date drawing no. scale

- lYPICAL DETAIL OF CSE/l C.T. WONG ~. JULY. 2008 SD/018 N.T.S.

ROOF BEAM & approved date STRU. ENGG. BRANCH


~
-:
EXTERIOR COLUMN JUNCTIO~
- AD(S[) w.w. LI JULY. 2008 ARCH. SERVICES DEPT.
'I Iso 297~
0 'I 1 1 1 0 :lID 1000 1300 2100 2500nmm
11111111111 I I I I A4 210 x
1 1 j 1SCJtII.III!I\R
100
Q(")f'Tl--1
z:)>X-<
::;o--1-o aa.
,......""T"1f'Tl- ~ KERB (IF ANY)
" ' )::. ::::o o . ::r
~::::oz)>"'
O:;::o;;:)>'. ;::(:
f'T1 I 0 co i:n
0orrl EXPANSION JOINT CONTRACTION JOINT
~:r:
::::O::;o~ ::21- EXPANSION JOINT
Cl
0-- ~ g;=
c<r w N
Cl ~><
6~o <( <( CONTRACTION JOINT LONGITUDINAL JOINT
C2 ::2
(/)~"Tl cc
<(

s;:)> u
~ -4t
u_ i:n
coz 0
0 ~:r: SINGLE LAYER OF STEEL FABRIC
:r:
,_ ::21-
Cl Cl
REINFORCEMENT TO BS 4483 ~. ~·
;: g;: WITH 450mrn LAP MINIMUM DIRECTION OF TRAFFIC
N ~~
~>< (SEE TABLE 7 FOR MESH TYPE)
0 {"') 0 <(
t; (/) ::::r ::2
(/) (1)
0
.!:]. ""0 s
< (1)
(1) "
a.
:;:><;: a. :;:::::
;..., ?"
r-
fT1
c::: 0
==
:z: :z: 20000 MAX. 20000 MAX. 20000 MAX.
GJ GJ

.... 60000 MAX.

j AREAS
~
,.,0 0
,., NOTES:
f' a. f' a.
1. . DRAWINGS No. SD/022 TO SD/026 ARE NOT APPLICABLE TO WORKS
0
N N ~
0 ro- 0 (1) THAT WILL BE HANDED OVER TO HIGHWAYS DEPARTMENT.
-l>- -l>-
--- MAX. SLAB WIDTH BETWEEN
STEEL MESH 2. CONCRETE TO BE GRADE 40/20 MIN.
a. LONGITUDINAL JOINTS,
a TO BS 4483
~ 'B'
:;·
(/) 3. LONGITUDINAL JOINTS SHOULD BE PROVIDED SO THAT SLABS ARE NOT WIDER THAN
~~ 0 "'
::J THE MAX. WIDTH IN TABLE 7.
.:::I:c
. ............ !:l C503
0 4.5 m
N (4.34 kg/sq. m)
VJrr~ N 4. EVERY THIRD JOINT IN THE TRANSVERSE DIRECTION SHOULD BE AN EXPANSION JOINT,
rrlz
~<i) B503 THE REMAINDER BEING CONTRACTION JOINTS.
(")~ ·6.0 m
(5.93 kg/sq. m)
rr1
VJ m •--- 5. CONTRACTOR IS REQUIRED TO SUBMIT LAYOUT OF JOINTS FOR PSE'S APPROVAL PRIOR
c $2 I
TO CONSTRUCTION OF THE EXTERNAL SLABS ON GRADE.
rr1 z I
~(")
• :I: 6. GRANULAR SUB-BASE MATERIAL REFER TO TABLE 8 ON DRG No. SD/026.
100

OOrrl=< 0.
:z>X;;o---1""0 0
G) ""0 rrl (") :§.
~?0~)>-E ONE LAYER OF 125 J..im POLYTHENE SHEET 25 x 15 SEALING GROOVE SAWN OR WET FORMED AT A POSITION VERTICALLY
o:A>' ;:;: WITH 150mm LAP MIN. WHERE REQUIRED. ABOVE THE CRACK-INDUCER TO WITHIN A TOLERANCE OF ±10mm
rr1 ' o ro
G)o~
:::0:::0)> STEEL FABRIC REINFORCEMENT APPROVED POLYSULPHIDE I
0-- POLYURETHANE JOINT SEALANT
c<• ( SEE DRG No. SDI022 )
~~0
(/)~.,
BOND BREAKER
s;:>
rnZ
0
'I 350 300 CD
~ 5Vl
> 0 0
0 -o (./)
",..., ::r I.Cljw
Nt;:;
Ui' -o No:;
0
-!:!. 0< ~ "' u
0.
"'"' z
:;><; "'0. 0
~ u
;...; ?"
r-
25mm DIA 650mm LONG MILD STEEL DOWEL BARS PREFORMED PVC TIGHT FITIING
rr1 ::::;: AT MID-DEPTH AND AT 300mm CENTRES
c::: . 0:z: DOWEL SLEEVE
:z:
G") G")

...... 0
lCl
GRANULAR SUB-BASE
ROAD FORMATION

BOTIOM CRACK-INDUCER ( OF TIMBER, STEEL OR SYNTHETIC MATERIAL )


SECURELY FIXED TO THE BASE. THE COMBINED DEPTH OF DISCONTINUITY
,0 ,0 PROVIDED BY THE CRACK-INDUCER AND THE SEALING GROOVE AT THE TOP
0 f'
0. 0. OF THE SLAB SHOULD BE AT LEAST 1I 4 OF THE THICKNESS OF THE SLAB
N ~ N ~
0 0 "'
~
"' ~

0..
0 FIG. 16.2 SEC. A-A DETAIL OF CONTRACTION JOINT
:§.
::::0
(/)<Q IN EXTERNAL DRIVEWAY AND CAR PARKING AREAS
~~ 0 ::::0

.::J:c
. ............. ?
0
N NOTES
(/)f'Tl
f'TlZ 0J 1. ALL THE FILLING MATERIALS FOR ROAD FORMATION SHALL BE COMPACTED IN COMPLIANCE WITH CLAUSE 3.19(vi) OF THE
~8 GENERAL SPECIFICATION; OR, AS APPROVED BY THE SO, CLAUSE 3.20 OF THE GENERAL SPECIFICATION.
2. IMMEDIATELY PRIOR TO LAYING THE SUB-BASE, CARRY OUT PREPARATION AND SURFACE TREATMENT OF THE ROAD
~~~ FORMATION IN ACCORDANCE WITH CLAUSE 3.26 OF THE GENERAL SPECIFICATION.
3. UNLESS OTHERWISE SPECIFIED, SUB-BASE SHALL BE COMPACTED IN ACCORDANCE WITH CLAUSE 3.20 OF THE GENERAL
~~-~
~::I: z:
.
(J)
0
SPECIFICATION OR AS APPROVED BY THE SO.
--l 0
$n ro
Oloootiuul I J lso I I I I 1100
0 (") rrl --I
:z: )>X-<
:::u --I -o aa.
j G) -o rrl (") ~
;:;u )> ;:;u )> ~.
)>:::U:Z:
o="')>' e:
-1 rrl I 0 iif
§cio~
o:::U)>
c:<r .---- ONE lAYER OF 125 J.Jm POLYTHENE SHEET
- :z:rrl WITH 150mm LAP MIN. WHERE REQUIRED. .-- APPROVED SEALING STRIP GLUED TO EDGE OF FIRST SLAB
o~O CAST PRIOR TO POURING THE SECOND SLAB
(/)-<.,
- ,..... );: )> .- STEEL FABRIC REINFORCEMENT
VI OJ :Z: ( SEE DRG No. SD/022 )
0 0
~:
.........
> 0 0
0 Ul
",..., ::r
<n <I>
0 ~ r-- ---·--- --- --- ---
-::::::-
""
5 0
< <I> I_ 50 _
;:><;
<I>
a_
"""
a_

~
s::::
?-:
-~J--- -·-- _J!
llYiJ :5
(/)
r-
fTl ::E L(')lw
c:: 0
:z: :z: ~~
C) G) u
I I 75 75 _I z
I 0
I 12mm DIA. MILD STEEL DOWEL BARS, 1.1m IN LENGTH u
AND SPACED AT 600mm CENTRES AT MID-DEPTH
150mm LONG PREFORMED PVC TIGHT FITTING SLEEVE -

I~ J v 0
L(1
GRANULAR SUB-BASE
0 0 ROAD FORMATION
,..., ,..., . '5:2'.
f' a_ f' a_ ~ ~
0 0
N c;; N c;;
0 0
.j>. .j>.

a_
a
!.
FIG. 16.3 SEC. B-B DETAIL OF LONGITUDINAL JOINT
::>
(/)<O IN EXTERNAL DRIVEWAY AND CAR PARKING AREAS
~~ 0 ::>
:::I:c
. . .............. p
0 NOTES :
UlrTt N
rTt:z ~ 1. ALL THE FILLING MATERIALS FOR ROAD FORMATION SHALL BE COMPACTED IN COMPLIANCE WITH CLAUSE 3.19(vi) OF THE
~8 GENERAL SPECIFICATION; OR, AS APPROVED BY THE SO, CLAUSE 3.20 OF THE GENERAL SPECIFICATION.
(")
. 2. IMMEDIATELY PRIOR TO LAYING THE SUB-BASE, CARRY OUT PREPARATION AND SURFACE TREATMENT OF THE ROAD
rTtCDI I
Cil
FORMATION IN ACCORDANCE WITH CLAUSE 3.26 OF THE GENERAL SPECIFICATION.
)>
:" 3. UNLESS OTHERWISE SPECIFIED, SUB-BASE SHALL BE COMPACTED IN ACCORDANCE WITH CLAUSE 3.20 OF THE GENERAL
~~
rTt(") -
z (/)
SPECIFICATION OR AS APPROVED BY THE SO.
~:I: 0
;-t 0
!I'
'"
100
OOrrl:(!
:z):>X ~
::::0 --I """0 0
G') """0 rr1 0 !.
:;;o):>::::0):>-.5
):> ::::0 ~I ,....
CJA ;::;:
rr1 ' o <n
GJo~
::::O:;;o)>
0-- - ONE LAYER OF 125 um POLYTHENE SHEET
c<r - LJ 1\ I..J ..J/"\YYI'\1 VI\ YYLI rVf\IVI[.U \Jf\VVVL

z~o WITH 150mm LAP MiN. WHERE REQUIRED.


o)>""Tl
(/)=-<
);:l> - STEEL FABRIC REINFORCEMENT APPROVED POLYSULPHIDE /
c:o:Z ( SEE DRG No. SD/022 ) I 51 POLYURETHANE JOINT SEALANT
0
1
' I Vj
~
~ mf-
I '=-f-
a C) n BOND BREAKER
E;; -.::> Vl :T
-.::> CD ~
8..!:].• n ""- ~
s - ---·- -- -- -- -- - --,50 ~ ---- -- -- -- -- --
CD
0<
CD "
0.
;:;><;; 0. s::: I 350 I TYP 0: 300 125 I :5
~ I ~ I Vl
?"
r- I L{)lw
rr1 ==: ·_·.·. . ,., I < N W
c: 0 I I N 0::
:z: :z: u
C) C) :z
0
25
~~ u
HOLES DRILLED IN THE FILLER TO GIVE ~ L PREFORMED PVC TIGHT FITIING
A DOWEL BAR SLEEVE A "PUSH FIT" ~ DOWEL SLEEVE

I
J / - 25mm DIA 650mm LONG MILD STEEL DOWEL BARS 0
L{)
GRANUlAR SUB-BASE AT MID-DEPTH AND AT 300mm CENTRES. <
0
, ,0 HALF LENGTH PAINTED WITH BOND PREVENTING COMPOUND. ROAD FORMATION
!="' !="'
0. 0. ~
N ~ N ~ - APPROVED POLYETHYLENE FOAM
0 CD 0 CD
.j>. .j>. JOINT FILLER

0.
a
FIG. 16.4 SEC. C-C DETAIL OF EXPANSION JOINT
........._g
;:cc
~~181
. 0 . IN EXTERNAL DRIVEWAY AND CAR PARKING AREAS
(/) fT1 N NOTES :
fT1 z ()1
1. ALL THE FILLING MATERIALS FOR ROAD FORMATION SHALL BE COMPACTED IN COMPLIANCE WITH ClAUSE 3.19( vi) OF THE
~C)
oP GENERAL SPECIFICATION; OR, AS APPROVED BY THE SO, ClAUSE 3.20 OF THE .GENERAL SPECIFICATION.
r'TltD 2. IMMEDIATELY PRIOR TO lAYING THE SUB-BASE, CARRY OUT PREPARATION AND SURFACE TREATMENT OF THE ROAD
):> (il FORMATION IN ACCORDANCE WITH ClAUSE 3.26 OF THE GENERAL SPECIFICATION.
~~I :<
r'Tl(") 3. UNLESS OTHERWISE SPECIFIED, SUB-BASE SHALL BE COMPACTED IN ACCORDANCE WITH ClAUSE 3.20 OF THE GENERAL
:z (/J SPECIFICATION OR AS APPROVED BY THE- SO.
~ :I: I n
;-t a
Yl ;;-
RANGE OF GRADING '

B. S. SIEVE SIZE PERCENTAGE BY WEIGHT PASSING


75 mm 100

37.5 mm 85 rv 1QQ

20 mm 60 rv 85 ·

10 mm 40 rv 70

5 mm 25 rv 45

600 J.lm 8 rv.22

75 J.lm Q rv 10

a. GRANULAR SUB-BASE MATERIAL SHALL BE COMPRISED OF CRUSHED ROCK, RE-CYCLED


AGGREGATE OR APPROVED RE-CYCLED SUB-BASE MATE~IAL. THE MATERIAL SHALL BE
WELL -GRADED AND LIE WITHIN THE ABOVE GRADING LIMITS. THE PARTICLE SIZE SHALL
0
0 BE DETERMINED IN ACCORDANCE WITH THE REQUIREMENTS OF CS3.
-=
b. THE MATERIAL PASSING THE B.S. SIEVE 425 J.lm WHEN TESTED IN ACCORDANCE WITH
- GEOSPEC 3, TEST METHOD 6.1 SHALL BE NON-PLASTIC.

c. THE MATERIAL SHALL BE LAID AND COMPACTED TO THE. REQUIREMENTS OF


- CLAUSE 3.20 OF THE GENERAL SPECIFICATION.

- TABLE 8 GRANUlAR SUB-BASE MATERIAL


0
~

checked date drawing no. rev. scale


drawing title
-
TYPICAL DETAIL OF I
CSE/1 M.K. WONG
I
... DEC., 2014 SD/026 B N.T.S.

EXTERNAL DRIVEWAY AND


- approved date STRU. ENGG. BRANCH
CARPARK GROUND SLAB
-

0
ON GRADE
'I 'I I
(5 OF
I I
5)
150
AD(SE) K.T. LEUNG
WJ DEC., 2014 ARCH. SERVICES DEPT.
/