APPLICATION NOTE

YS170 Boiler Combustion Control


OVERVIEW load range is difficult. Refer to the SAMA diagram below.
This configuration is called a cross
The boiler combustion control PARALLEL POSITIONING limited or lead-lag system. If an
system is designed to maintain a increase in firing rate is needed due
proper air/fuel mixture under varying This system uses a master pressure to an increasing steam demand, the
load conditions and within safe controller to position the fuel valve(s) air flow leads the fuel. As the load
limits. The system should provide and air damper. An air/fuel ratio curtails, the fuel decreases first,
nearly complete fuel combustion as station is placed in the air damper followed by a decrease in
efficiently as possible. Discussions circuit. Advantages are low installed combustion air flow. A low limiter is
here are limited to oil and/or natural cost and simplicity with only one used in the air controller to prevent
gas fired industrial boilers. Control controller to manipulate. The the air flow set point to be reduced
systems that perform these functions disadvantage is that it is not fail-safe. less than 25% of full span. This
can be classified as positioning or There is no inherent fuel cut back or minimum setting is required by
metering systems. Positioning air tracking the fuel if either drive NFPA code and ensures safe
combustion systems use mechanical were to fail. operation in the event of loss of
linkages between the fuel control signals.
valve and air damper to adjust for PARALLEL
the proper ratio. Both single point METERED FT From Pressure
Controller
FT
positioning and parallel position
systems are common. CROSS Fuel Flow
Firing Rate
Air Flow
Demand
LIMITED √ √
Low
SINGLE POINT SYSTEM Select 25%

POSITIONING
In this combustion
< High
> A f(x)

One of the most common system, the air and Select

combustion control system on oil fuel flows are


and/or gas fired boilers is the single measured and are
K ∫ K ∫
point positioning system, commonly the process
referred to as a jackshaft. Refer to variables of two
the drawing below. The fuel valve(s) controllers. The air T A T A
and air damper are mechanically and fuel controllers
linked to a common rotating drive receive a setpoint f(x) f(x)
mechanism controlled by a master value from a master
drive unit. Simple and safe, but steam pressure Fuel Air

requires a constant fuel pressure controller. In the Valve Damper

and BTU content. Maintaining the fuel controller, this


optimum air/fuel ratio throughout the value is compared to a modified air The YS170 Dual Loop
flow signal in a low signal Programmable Controller is the
Automatic Adjustment of
Blower Side of Shaft
selector. The lower value logical choice for boiler combustion
is selected as the remote control. The controllers can be
set point of the fuel flow easily implemented to perform the
Jackshaft controller. full metering cross limited system
configuration. The YS170 fuel
Conversely, the pressure controller can transmit the fuel signal
controller output is as an analog output to the air
compared to the fuel flow controller for the cross limiting
using a high signal action. Conversely, the YS170 air
Combustion Air Fuel Valve
selector in the air flow controller can transmit the air flow to
controller. The higher the fuel controller. The limiting
Single Point Positioning signal is selected.
1 CCYS-G-01A
03-99
APPLICATION NOTE
signal selectors reside in each A load index is created from the SUMMARY
controller. firing rate demand signal. The
amount of excess oxygen varies YS170 Programmable Loop
Using discrete inputs and outputs, inversely with steam demand, i.e., Controllers can be installed in a
the fuel controller can track the air low loads have a higher excess variety of applications. As discussed
control MANUAL status and logic oxygen. The operator can apply a here, boiler combustion control can
can be incorporated to not permit manual bias to the index set point be implemented easily and cost
automatic fuel control until the air without changing the index slope or effectively. Multiple analog and
controller is in AUTO. These shape. Refer to the SAMA diagram discrete inputs/outputs permit
signals can be hard-wired between below. interaction with burner management
controllers or an optional peer-to- equipment. YS170 controllers have
Air Flow FT Firing Rate AT Percent
peer digital communications Demand Oxygen been installed in dozens of boiler
network can transfer analog and installations. Users are glad they
status information over a single √ selected this versatile easy-to-use
pair of twisted wires. f(x)
controller.
K ∫
f(x) Operator
Diagnostics of flow inputs allows Bias YS170 - The Logical Choice in
the controllers to transfer the fuel Combustion Control!
A T A
and air outputs to safe conditions X
in the event of transmitter failure. To Air
The controllers can be forced into Controller
K +
MANUAL mode (holding the last
calculated output) and discrete
outputs are available to activate
an annunciator or other alarm The output of the percent oxygen
device. controller is adjusted for gain and
bias and applied to the combustion
If the YS170 controller were to fail, air flow signal. Additionally, low and
an integral hard manual station high limits are used to ensure
allows immediate backup. By raising continued operation during analyzer
the front panel assembly of the outage.
instrument, the manual station can
be activated by a slide switch. A The YS170 can be programmed to
knurled thumb wheel can be perform two independent P+I+D
adjusted to provide the appropriate control algorithms. This is ideal to
output to the control element. A incorporate the combustion air and
FAIL discrete output can be wired to oxygen trim controls into one
an alarm device. instrument. The multiple
input/output capabilities permit air
FLUE GAS ANALYSIS flow, percent oxygen, and firing rate
demand inputs. Function generators
Flue gas analysis is a method of residing in the microprocessor-based
providing a more precise control of controller allow calculation of the
the air/fuel ratio. The intent is to load index described above and
minimize the amount of excess air characterization of the air flow
rising through the stack which results measurement. By implementing
in lower operating costs by using these two control strategies in one
less fuel. An oxygen trim controller device, the purchase cost is lowered
can be used to bias or trim the and installation costs are reduced.
combustion air controller.

2 CCYS-G-01A
03-99