You are on page 1of 6

PROTECTION RELAY SETTING

Company : Candra Asri Switchboard Neutral Gnd :


Plant : PBI Name : Voltage0.38kV
: NGR 400A
Location : 0.38kV PBI I Rating1250
: A

OVER CURRENT (51/50) and GROUND FAULT (51N/50N)


ANSI : 51 ANSI: 50 ANSI : 51N ANSI: 50N
No Feeder Name Type CT ratio
I> I> Curve TD I> Curve Delay 3Io > Curve TD 3Io >>3Io >> Curve
1a PN-201 (Inc.6kV) PAC-T100 1200:5 1200 IEC-NI 0.05 NA 120 IEC-NI 0.26 360 DT
1b PN-201 (Inc.6kV) PAC-T100 1200:5 1380 5.75 IEC-NI 0.43 8000 33.33 INST 0.45 120 IEC-SI 0.23 Not active

2a PN-202A (GAM-8123A, 310kW)


PAC-M100 60:5, ZCT=100/5 (SLD) 40.8 IEC-LTI 0.26 504 INST 0.05 40 IEC-NI 0.33 320 INST
2b PN-202A (GAM-8123A, 310kW)
PAC-M100 60:5, ZCT=100/5 (SLD) 45 3.75 IEC-LTI 0.26 504 42 INST 0.05 Not active 50 2.5 DT

3a PN-202B (GAM-8123S, 310kW)


PAC-M100 60:5, ZCT=100/5 (SLD) 40.8 IEC-LTI 0.26 504 INST 0.05 40 IEC-NI 0.33 320 INST
3b PN-202B (GAM-8123S, 310kW)
PAC-M100 60:5, ZCT=100/5 (SLD) 45 3.75 IEC-LTI 0.26 504 42 INST 0.05 Not active 50 2.5 DT

4a PN-203A (GAM-8233A, 560kW)


PAC-M100 100:5, ZCT=100/5 (SLD) 66 IEC-LTI 0.35 820 INST 0.05 40 IEC-NI 0.33 320 INST
4b PN-203A (GAM-8233A, 560kW)
PAC-M100 100:5, ZCT=100/5 (SLD) 75 3.75 IEC-LTI 0.35 820 41 INST 0.05 Not active 50 2.5 DT
5a PN-203B (GAM-8233S, 560kW)
PAC-M100 100:5, ZCT=100/5 (SLD) 66 IEC-LTI 0.35 820 INST 0.05 40 IEC-NI 0.33 320 INST
5b PN-203B (GAM-8233S, 560kW)
PAC-M100 100:5, ZCT=100/5 (SLD) 75 3.75 IEC-LTI 0.35 820 41 INST 0.05 Not active 50 2.5 DT

6a PN-204 (GBM-8231, 1MW) PAC-M100 200:5, ZCT=100/5 (SLD) 120 IEC-LTI 0.34 1080 INST 0.05 40 IEC-NI 0.33 320 INST
6b PN-204 (GBM-8231, 1MW) PAC-M100 200:5, ZCT=100/5 (SLD) 150 3.75 IEC-LTI 0.34 1080 27 INST 0.05 Not active 50 2.5 DT

7a PN-205A (GAM-8122A, 230kW)


PAC-M100 50:5, ZCT=100/5 (SLD) 29 IEC-LTI 0.26 353 INST 0.05 40 IEC-NI 0.33 320 INST
7b PN-205A (GAM-8122A, 230kW)
PAC-M100 50:5, ZCT=100/5 (SLD) 32 3.2 IEC-LTI 0.26 353 35.3 INST 0.05 Not active 50 2.5 DT

8a PN-205B (GAM-8122S, 230kW)


PAC-M100 50:5, ZCT=100/5 (SLD) 29 IEC-LTI 0.26 353 INST 0.05 40 IEC-NI 0.33 320 INST
8b PN-205B (GAM-8122S, 230kW)
PAC-M100 50:5, ZCT=100/5 (SLD) 32 3.2 IEC-LTI 0.26 353 35.3 INST 0.05 Not active 50 2.5 DT

9a PN-206A (GAM-8130A, 210kW)


PAC-M100 40:5, ZCT=100/5 (SLD) 26.4 IEC-LTI 0.26 320 INST 0.05 40 IEC-NI 0.33 320 INST
9b PN-206A (GAM-8130A, 210kW)
PAC-M100 40:5, ZCT=100/5 (SLD) 28.8 3.6 IEC-LTI 0.26 320 40 INST 0.05 Not active 50 2.5 DT

10a PN-206B (GAM-8130S, 210kW)


PAC-M100 40:5, ZCT=100/5 (SLD) 26.4 IEC-LTI 0.26 320 INST 0.05 40 IEC-NI 0.33 320 INST
10b PN-206B (GAM-8130S, 210kW)
PAC-M100 40:5, ZCT=100/5 (SLD) 28.8 3.6 IEC-LTI 0.26 320 40 INST 0.05 Not active 50 2.5 DT
11a PN-207A (GAM-8801A, 400kW)
PAC-M100 75:5,ZCT=100/5 (SLD) 48 IEC-LTI 0.26 600 INST 0.05 40 IEC-NI 0.33 320 INST
11b PN-207A (GAM-8801A, 400kW)
PAC-M100 75:5, ZCT=100/5 (SLD) 53 IEC-LTI 0.26 600 INST 0.05 Not active 50 DT
11c PN-207A (GAM-8801A, 460kW)
PAC-M100 75:5, ZCT=100/5 (SLD) 57.5 3.83 IEC-LTI 0.35 600 40 INST 0.05 Not active 50 2.5 DT

12a PN-207B (GAM-8801B, 400kW)


PAC-M100 75:5, ZCT=100/5 (SLD) 48 IEC-LTI 0.26 600 INST 0.05 40 IEC-NI 0.33 320 INST
12b PN-207B (GAM-8801B, 400kW)
PAC-M100 75:5, ZCT=100/5 (SLD) 53 IEC-LTI 0.26 600 INST 0.05 Not active 50 DT
12c PN-207B (GAM-8801B, 460kW)
PAC-M100 75:5, ZCT=100/5 (SLD) 57.5 3.83 IEC-LTI 0.35 600 40 INST 0.05 Not active 50 2.5 DT

13a PN-207C (GAM-8801S, 400kW)


PAC-M100 75:5, ZCT=100/5 (SLD) 48 IEC-LTI 0.26 600 INST 0.05 40 IEC-NI 0.33 320 INST
13b PN-207C (GAM-8801S, 400kW)
PAC-M100 75:5, ZCT=100/5 (SLD) 53 IEC-LTI 0.26 600 INST 0.05 Not active 50 DT
13c PN-207C (GAM-8801S, 460kW)
PAC-M100 75:5, ZCT=100/5 (SLD) 57.5 3.83 IEC-LTI 0.35 600 40 INST 0.05 Not active 50 2.5 DT
14a PN-208A (GBM-8501AX, 220kW)
PAC-M100 60:5, ZCT=100/5 (SLD) 25.6 IEC-LTI 0.22 314 INST 0.05 40 IEC-NI 0.33 320 INST
14b PN-208A (GBM-8501AX, 220kW)
PAC-M100 60:5, ZCT=100/5 (SLD) 27.6 IEC-LTI 0.22 314 INST 0.05 Not active 50 DT
14c PN-208A (GBM-8501AX, 300kW)
PAC-M100 40:5, ZCT=100/5 (SLD) 39.2 4.90 IEC-LTI 0.35 314 39.20 INST 0.05 Not active 50 2.5 DT

15a PN-208B (GBM-8501BX, 220kW)


PAC-M100 60:5, ZCT=100/5 (SLD) 25.6 IEC-LTI 0.22 314 INST 0.05 40 IEC-NI 0.33 320 INST
15b PN-208B (GBM-8501BX, 220kW)
PAC-M100 60:5, ZCT=100/5 (SLD) 27.6 IEC-LTI 0.22 314 INST 0.05 Not active 50 DT
15c PN-208B (GBM-8501BX, 300kW)
PAC-M100 40:5, ZCT=100/5 (SLD) 39.2 4.90 IEC-LTI 0.35 314 39.20 INST 0.05 Not active 50 2.5 DT

16a PN-209A (GAM-8701A, 165kW)


PAC-M100 30:5, ZCT=100/5 (SLD) 20.4 IEC-LTI 0.26 252 INST 0.05 40 IEC-NI 0.33 320 INST
16b PN-209A (GAM-8701A, 165kW)
PAC-M100 30:5, ZCT=100/5 (SLD) 22.2 3.7 IEC-LTI 0.26 252 42 INST 0.05 Not active 50 2.5 DT

17a PN-209B (GAM-8701S, 165kW)


PAC-M100 30:5, ZCT=100/5 (SLD) 20.4 IEC-LTI 0.26 252 INST 0.05 40 IEC-NI 0.33 320 INST
17b PN-209B (GAM-8701S, 165kW)
PAC-M100 30:5, ZCT=100/5 (SLD) 22.2 3.7 IEC-LTI 0.26 252 42 INST 0.05 Not active 50 2.5 DT

18a PN-210 (GAM-8231A, 200kW)


PAC-M100 100:5, ZCT=50/5 (SLD) 27.6 1.38 IEC-LTI 0.38 237 23.7 INST 0.05 Not active 50 2.5 DT

19a PN-211 (GAM-8231B, 200kW)


PAC-M100 100:5, ZCT=50/5 (SLD) 27.6 1.38 IEC-LTI 0.38 237 23.7 INST 0.05 Not active 50 2.5 DT
20a PN-212 (to MCC 301) PAC-F100 350:5, ZCT=100/5 (SLD) 343 IEC-NI 0.05 3430 INST 0.05 40 IEC-NI 0.33 320 INST
20b PN-212 (to MCC 301) PAC-F100 350:5, ZCT=100/5 (SLD) 343 4.9 IEC-NI 0.25 3500 50 INST 0.25 Not active 50 2.5 DT

21a PN-213 (Cap. Bank) PAC-F100 200:5, ZCT=100/5 (SLD) 208 IEC-NI 0.05 4000 INST 0.05 40 IEC-NI 0.33 320 INST
21b PN-213 (Cap. Bank) PAC-F100 200:5, ZCT=100/5 (SLD) 208 5.2 IEC-NI 0.05 4000 100 INST 0.05 Not active 50 2.5 DT

22a PN-214
23a PN-215
24a PN-216 P 632 400:5 7200 IEC-SI NA 200 DT 1.8 NA
ANSI: 50N
Delay
1
Not active
0.05
0.8
0.05
0.8
0.05
0.8
0.05
0.8
0.05
0.8
0.05
0.8
0.05
0.8
0.05
0.8
0.05
0.8
0.05
0.8
0.8
0.05
0.8
0.8
0.05
0.8
0.8
0.05
0.8
0.8
0.05
0.8
0.8
0.05
0.8
0.05
0.8
0.8
0.8
0.05
1
0.05
0.8
NA