You are on page 1of 7

CALCULATION OF LIGHTNING FLASHOVERS AND BACKFLASH LEVEL

ON 230kV TRANSMISSION LINES

Bander J. Al-Qahtani * M. H. Shwehdi

SAOO-NGPD-TSU Electrical Engineering Department


Saudi Aramco King Fahd University of Petroleum & Minerals
Abqaiq, Saudi Arabia Dhahran, Saudi Arabia
Bander.qahtani@aramco.com mshwehdi@kfupm.edu.sa

ABSTRACT indirect stroke. However, no two lightning strokes are the


Lightning has been one of the important problems for same. Therefore, the statistical variations of the lightning-
insulation design of power systems and it is still the stroke parameters must be taken into account in assessing
main cause of outages of transmission and distribution the severity of lightning strokes on the specific design of a
lines. Lightning caused outages can be reduced by power line or apparatus.
lightning protection devices such as ground wires and
lightning arresters. The lightning return-stroke current and the charge
delivered by the stroke are the most important parameters
This paper presents a comparative studies used to to assess the severity of lightning strokes to power lines
determine the lightning backflashovers level on 230kV and apparatus. The return-stroke current is characterized
transmission lines utilized by Saudi Electric Company by a rapid rise to the peak, I p, within a few microseconds
(SEC) in Saudi Arabia, using two well known and then a relatively slow decay, reaching half of the peak
approaches CIGRE, and the simplified method. The value in tens of microseconds. The return-stroke current is
studies include lightning flashovers, backflash specified by its peak value and its waveshape. The
analysis, as dependent on the tower design parameters waveshape, in turn, is specified by the time from zero to
which is considered the main parameters that reduce the peak value (tf, front time) and by the time to its
the rate of lightning bachflashovers in the subsequent decay to its half value (t h, tail time). The tail
transmission lines. The study results can be applied to time being several orders of magnitude longer than the
reduce the number lightning flashovers and therefore front time, its statistical variation is of lesser importance
reduce the transmission lines outages. in the computation of the generated voltage. The
generated voltage is a function of the peak current for
KEY WORDS both the direct and indirect strokes.
Lightning flashovers, backflashovers, simulation and
ground wires For backflashes in direct strokes and for indirect strokes
the generated voltage is higher the shorter the front time
of the return-stroke current [1]. The front time (and the
1. Introduction tail time, to a lesser extent), influence the withstand
capability (volt-time characteristics) of the power
A complete awareness of the parameters of lightning apparatus. The charge in a stroke signifies the energy
strokes is essential for the prediction of the severity of the transferred to the struck object. The ancillary equipment
transient voltages generated across power apparatus either (e.g., surge protectors) connected near the struck point
by a direct stroke to the power line/apparatus, or by an will be damaged if the charge content of the stroke

P.O.Box 66467, Dammam 31576, Kingdom of Saudi Arabia


2

exceeds the withstand capability of the equipment. The distribution lines to spark over causing a short circuit of
return-stroke velocity will affect the component of the the system. Thus, assuming the lightning channel to be a
voltage which is generated by the induction field of the current source, the transient voltages across the insulator
lightning stroke [1]. Field tests have shown that the of a phase conductor are generated in three ways: (i)
parameters of the first stroke are different from that of the lightning striking the phase conductor (shielding failure),
subsequent strokes. (ii) lightning striking the tower or the shield wire
(backflash), and (iii) lightning striking the nearby ground
(indirect stroke). The severity of these three types of
2. Lightning Flashes transient voltages is influenced by different lightning
parameters [2, 3].
Lightning damages a power apparatus in two ways: (i) it
raises the voltage across an apparatus such that the The significance of lightning parameters on power
terminals across the struck apparatus spark over causing a systems is gauged by the severity of the transient
short circuit of the system or the voltage punctures overvoltages they create and the consequent damages to
through the apparatus electrical insulation, causing the power system. As mentioned before, these
permanent damage. (ii) The energy of the lightning stroke overvoltages are generated by three different ways.
may exceed the energy handling capability of the
apparatus, causing meltdown or fracture.
3. Computation of Insulator Voltage
A lightning flash generally consists of several strokes
which lower charges, negative or positive, from the cloud The lightning return-stroke current is the most significant
to the ground. The first stroke is most often more severe parameter in the estimation of the response of electrical
than the subsequent strokes. Low current continues to apparatus and systems to lightning strikes. The return
flow between two strokes, thus increasing the total energy stroke current rises to its peak in a few microseconds and
injected to the struck object. The transient voltage from then decays to the half value in a few tens of
the lightning strike is generated by: (i) direct stroke and microseconds [4]. The return-stroke current is identified
(ii) indirect stroke. For direct strike, it can strike an by three parameters: peak value Ip, front time tf and time
apparatus. In that case, the apparatus will be permanently to half value th. The difficulty with the exponential
damaged. Most often, lightning strikes the phase function representing a return-stroke current is that it is
conductor of the power line. In that case, a traveling not easy to select the parameters of these analytical
voltage wave is generated on the line; it travels along the expressions to fit the three parameters (Ip, tf and th).
line and is impressed across the terminals of an apparatus However, this problem does not arise if the return-stroke
or most often the insulator between the phase conductor current is represented as linearly rising and linearly falling
and the cross-arm of the tower at the end of the span. If functions [4]:
the voltage is high enough, the insulator flashes over
causing a short circuit of the system. I (t )   1tu (t )   2 (t  t f )u (t  t f ) (1)

Many overhead power lines are equipped with shield Where α1 = Ip/tf, and α2 = (2th–If)Ip/2tf (th–If). For short tf in
wires to shield the phase conductors. Even then, shielding the order of a few microseconds, eqn. 1 seems to work
failures occur when lightning bypasses the shield wires very well. With eqn. 1, the three parameters of the return-
and strikes a phase conductor. When lightning strikes a stroke current can be varied very easily. Starting with the
tower, a traveling voltage is generated which travels back return-stroke current, the various voltage components
and forth along the tower, being reflected at the tower across the insulator were computed.
footing and at the tower top, thus raising the voltages at
the cross-arms and stressing the insulators. The insulator
will flash over if this transient voltage exceeds its 3.1 First and Second Voltage Components
withstand level (backflash). Even if lightning strikes a
shield wire, the generated traveling voltage wave will To compute the first voltage component, i.e. the cross-arm
travel to the nearest tower, produce multiple reflections voltage Vca, the tower was assumed to be a vertical
along the tower, causing backflash across an insulator. transmission line of a fixed surge impedance Zt. The
voltage and current waves were assumed to travel along
When lightning hits the ground several hundred meters the tower with a constant p.u. velocity of β t. The first
away from the line (indirect stroke), the electric and reflections from the adjacent towers for the shield-wire
magnetic fields of the lightning channel can induce high voltages were also included in the computation. The tower
voltage on the line for the insulators of the low-voltage footing resistance was assumed to be constant, Rtf. The
3

tower-top was terminated by shield wire(s) and the where r and r ‫ ׳‬are field and source points, respectively: I
lightning channel of constant surge impedance Zch. The is the return-stroke current: q0 is the constant linear charge
cross-arm voltage due to the multiply reflected voltage density of the leader stroke: hc is the cloud height: and is
waves along the struck tower was computed by following the instantaneous height of the upward-moving head of
a previous method as shown in [4]. Although Z t, βt, Rtf the return stroke above ground. For a stroke to ground, z ‫׳‬
and Zch were assumed as constant, they were used as input increases as a function of time and the return-stroke
variables which could be changed for parametric analysis. velocity, with its lower and upper limits 0 and h c. For a
stroke to tower of height hc, the lower and the upper limits
The second voltage component is the voltage induced on of z ‫ ׳‬are ht and hc. Thus, for a stroke to tower, the
the phase conductor due to electromagnetic coupling with voltages induced on the phase conductor were computed
the shield wire. This voltage is equal to k cf Vt, where Vt is for two different cloud heights (h c and ht), and then the
the tower-top/shield-wire voltage and the coupling factor second induced voltage (for ht) was subtracted from the
kcf is equal to Zps/Zsh. Zps is the mutual surge impedance first induced voltage (for hc).
between the phase conductor and the shield wire; Z sh is
the shield-wire surge impedance [4]. The tower-top
voltage was computed following the same procedure as 4. Computation of Backflash Rate
for Vca. The insulator-string voltage due to the first and
second voltage components is: The overhead ground wires or shield wires have been
located so as to minimize the number of lightning strokes
Vins  Vca  kcf Vt (2) that terminate on the phase conductor. The remaining and
vast majority of strokes and flashes now terminate on the
overhead ground wires. A stroke that so terminate forces
3.2 Third Voltage Component current to flow down the tower and out on the ground
wires. Thus voltage are built up across the line insulation.
The third voltage component is the voltage induced on the If these voltages equal or exceed the line CFO, flashover
phase conductor due to the electromagnetic fields of the occurs. This event is called a backflash. By referring to
lightning channel. The computation of the phase- figure 1, equations for the crest voltage, the voltage at the
conductor voltage followed previous analysis [4], with the tower top prior to any reflections from the footing
difference that, in the present case, the stroke hits the resistance, and the final voltage can be derived as follows
tower top instead of the ground. This difference is
manifested in the inducing voltage Vi, which is the
voltage in space (in the absence of the phase conductor)
caused by the residual charge in the upper part and the
return-stroke current in the lower part of the lightning
channel. Vi is:
hp
A
Vi   ( 
0
t
)dz (3)

Where Φ is the scalar potential due to the residual charge


in the upper part of the lightning channel, and A is the
vector potential due to the return-stroke current in the
lower part of the channel. For stroke to ground, Φ and A
are

Figure 1. Surge voltages at the tower and across the insulation [5]
r  r
q0 ( r , t  )
VTT   K sp K TT  I
hc
1 c
4 0 z 
 (r , t )  dr 
r  r VTA   K sp K TA  I (4.1)
(4)
VF  Re I
r  r
z I (r , t  ) And the current through the footing resistance is
 c (5)
A( r , t )  0
4 
0
r  r
dr 
IR 
Re
I (4.2)
Ri
4

Where insulation. Replacing V1 of Eq. (7) with CFO, the current


T obtained is the critical current IC at and above which
K TT  Re   T Z T T flashover occur, i.e.,
tf
CFO
IC  (4.9)
K TA
T
 Re   T Z T A  KTA  CKTT  K SP
tf Since KTT is in many cases approximately equal to KTA,
 then approximately, 
T     
K SP  1   R 1   T  1  2 S    R T 1  4 TS     R T  2 1  6 T S 
CFO  .....
    I C   (4.10)
 tf   tf   1  C  K
t f  TT K SP
(4.3) The probability of a flashover is the probability that the
For these equations: stroke current I equals or exceeds the critical current IC, or

Z g Ri Z  Ri Z g  2 Ri Pr ob I  I C   P I C    f  I dI (4.11)


Re  T  T  IC
Z g  2 Ri ZT  Ri Z g  2 Ri The backflash rate BFR is this probability times the
Zg number of strokes, NL, that terminate on the ground wires,
R  (4.4) or
Z g  2 Ri
BFR= N L P  I C  (4.12)
Also, the tail of the voltages can be conservatively
approximated by a time constant τ: Where
Zg
NL  Ng
 28h 0.6
 Sg 
  TS (4.5) (4.13)
Ri 10
That is, the equation for the tail of the surge is Where h is the tower height (meters), Sg is the horizontal
 (t t f ) /  distance between the ground wires (meters), and N g is the
eTT  VF e (4.6) ground flash density (flashes/km2-year), thus the BFR is
To be complete the definition of the variables are: in terms of flashovers per 100 km-years.
tf = time to crest of the stroke current, μs The equations for KTT and KI show that the voltage across
C = coupling factor the insulation increases as the time to crest of the stroke
ZT = surge impedance of the tower, ohms current decreases. This is caused by the tower component
Zg = surge impedance of the ground wires, ohms of voltage. Thus the critical current increases as the time
TT = tower travel time, μs to crest increases. Therefore, theoretically, all fronts
TA = tower travel time to any location on the tower A, should be considered. To do this, the equation for BFR
μs should be changed to the following:
TS = travel time of a span, μs
I = stroke current, KA BFR=0.6 NL P(IC) (4.14)
IR = current through footing of struck tower, KA
Ro = measured or low-current footing resistance, ohms
Ri = impulse or high-current footing resistance, ohms
 = time constant of tail, μs
Now, to provide first estmate of the backflash rate, the 5. Simulation & Results
BFR, examine figure 6. The surge voltage on the ground
wires produces a surge voltage on the phase conductor The 230 kV HV line of figure 2 whose characteristics are
equal to the coupling factor C times the voltage on the given in table I, are used to calculate the backflash rate
ground wires, or CVTT. Also note that the voltage VTA is using different methods. Also, this case study will include
located on the tower opposite the phase conductor. the following
Therefore, the crest voltage across the insulation V1 is
1. The effect of decrease of resistance from Ro versus Ri
V1  I  KTA  CKTT  K SP (4.7) 2. One versus two shield wires
3. The effect of underbuilt shield or ground wire
Also, note that the crest voltage VIF across the insulation
caused by the footing resistance is
As shown in the figure 3 & 4 the backflash rate for the
VIF  1  C  Re I (4.8) above mentioned high voltage lines with span length of
For a flashover to occur, the voltage across the insulator 300 meters and CFO of 1200kV has been calculated by
V1, must be equal to or greater than the CFO of the
5

using CIGRE method software and simplified method. factors are increased and are more uniform. Figure 7
The comparison appears acceptable for the line with shows the dramatic decrease in BFR for this case.
tower height of 35 meters, but for tower height of 70
meters the simplified method is inadequate. So, the
CIGRE method is always the proper tool.

Using the CIGRE method, the BFR of the single circuit


230 kV is shown in Fig. 5 as a function of R O with the
ratio ρ/RO as a parameter. To illustrate the effect of the
decrease of resistance with current, a curve labeled R i=RO
for which the footing resistance is not decreased is also
presented.

Figure 3. Comparasion of BFRs for CIGRE method and simplified


method, 230kV double circuit towers with two ground wires and height
of 35 meters

Figure 4. Comparasion of BFRs for CIGRE method and simplified


method, 230kV double circuit towers with two ground wires and height
Figure 2. 230 kV Tower Dimensions of 70 meters

For some applications, where the cost of two shield wires


is not economically and technically justified, or where
there is low ground flash density, a single shield wire can
be used. The single wire increases the value of R e,
decreases the coupling factor, and thus increase the BFR.
To illustrate, the curves of Fig. 6 have been constructed to
compare one and two shield wires for a 230 kV double-
circuit line and two shield wires for a single-circuit 230
kV line. Using one shield wire on the double-circuit line
essentially doubles the BFR as compared to the two- Figure 5. Effect of decrease to high-current footing resistance
shield-wire case.

A ground wire located below the phase conductors cannot


truthfully be called a shield wire, since it has no shielding
function. Rather, its function is to increase the coupling
factor to the lower phases, those phases that are most
likely to flashover. For example, for the 230-kV double-
circuit, two-ground-wire line with a shield wire height of
35 meters and coupling factor to the top, middle, and
bottom phase of 0.350, 0.248, and 0.183, respectively,
installing a ground wire at 12 meters above ground at the Figure 6. Tow shield wires for the 230kV double circuit line with height
center of the tower increases these coupling factors to of 35 m decrease the BFR, p/Ro=20
0.441, 0.347, and 0.307, respectively. Thus all coupling
6

[1] P. Chowdhuri, J. G. Anderson, W. A. Chisholm, T. E.


Field, M. Ishii, J. A. Martinez, M. B. Marz, J.
McDaniel, T. R. McDermott, A. M. Mousa,T. Narita,
D. K. Nichols, & T. A. Short, Parameters of
Lightning Strokes: A Review, IEEE Transactions and
Power delivery, March 28, 2003.

[2] P. Chowdhuri, A.K. Mishra & B.W. McConnell, Volt-


time characteristics of short air gaps under
Figure 7. An underbuilt ground wire decreases the BFR, 230kV double nonstandard lightning voltage waves, ibid., Vol. 12,
circuit line with height of 35 m, p/Ro=20. No. 1, pp. 470-476, 1997.

[3] P. Chowdhuri, A.K., Parameters of Lighting Strokes


6. Conclusion and Their effect on Power Systems, Vol. 12, No. 1,
pp. 1047-1051, 2001
The most significant parameters of the lightning return
stroke to estimate the severity on the power system are: (i) [4] P. Chowdhuri, A.K., S. Li & P. Yan Rigorous analysis
peak current, (ii) current front time, (iii) velocity and (iv) of back-flashover outages caused by direct lightning
total charge of the flash. strokes to overhead power lines, IEEE Proceedings,
2002
The electromagnetic fields of the lightning channel and
the magnetic fields of the traveling current waves along [5] Andrew R. Hileman, Insulation Coordination for
the power-line tower will significantly affect the Power Systems, (Eastern Hemisphere Distribution,
insulator-string voltage, and hence the outage rate due to New York, 1999)
backflash. Analytical methods to estimate the backflash
outage rate have been proposed, which should result in [6] R. Thottappillil & M. A. Uman, Comparison of
better prediction of the lightning performance of overhead lightning return stroke models, J. Geophys. Res., vol.
power lines. 98, pp. 22 903–22 914, 1993.

In this report, equations were developed to estimate the [7] V. Cooray & R. E. Orville, The effect of the variation
BFR that include the tower component of voltage; their of current amplitude, current rise time and return
use is called CIGRE method. This method is suffiently stroke velocity along the return stroke channel on the
complex so that the use of the computer program is electromagnetic fields generated by the return stroke,
suggested. The effect of decrease of the concentrated J. Geophys. Res., vol. 95, pp. 18 617–18 630, 1990.
grounds value on the BFR was addressed. Also, the effect
of the number of shield wires as well as adding underbuilt [8] Dennis W. Lenk, F. Richard Stockum & David E.
shield or ground wire were highlighted. Grimes,A new approach to distribution arrester
design, IEEE Transactions on power delivery, vol. 3,
The 230 kV line design from SEC is considered very No. 2, April 1988.
highly engineered, using two ground shield wires with 7.3
meter span at each side made almost a full cover for both [9] P. Pinceti & M. Giannettoni, A simplified model for
circuits. This tower can be considered as lightning proof. zinc oxide surge arrester, IEEE Transactions on
power delivery, Vol. 14, No. 2, April 1999.

7. Acknowledgment Biographies
The authors express appreciation to Saudi Electric
Bander J. Qahtani; Born in Al-Khobar 1979. He obtained his
Company engineers for thier time and support also their B.Sc. degree in electrical engineering with honors from King
gratitude to KFUPM for educational, studies facilities and Fahd University of Petroleum & Minerals (KFUPM) in 2002. In
support. the year 2000 he was selected as distinguished student for Saudi
Aramco Scholarship program. During his studies at KFUPM he
has conducted several term projects and studies dealing with
References: Industrial power systems. Upon graduation, Bandar was
employed by Aramco as instrument engineer with Southern Area
Producing Engineering Department (SAPED) in Abqaiq. He is
enrolled in the Msc. Program at KFUPM. Bandar has published
7

and presented many technical papers and reports to region, and includes, power system analysis, Power Quality & Harmonics,
international conferences. overvoltages analysis on Power Systems, Transmission and
Distribution Systems. Dr. Shwehdi is active in IEEE activities.
M. H. Shwehdi (S'74, M'85, SM 90) received the B. SC. degree He is listed as a distinguished lecturer with the DLP of the
from University of Tripoli, Libya in 1972. He obtained the M. IEEE/PES DLP upon the Board selection, was named and
Sc. Degree from the University of Southern California and Ph.D. awarded the 2001 IEEE/PES outstanding chapter engineer,. He
degree from Mississippi State University in 1975 and 1985 was named and awarded the 1999 IEEE WG for standard award,
respectively all in electrical engineering. He was a consultant to the GCC-CIGRE 1998 best applied research award, IEEE/IAS
A.B. Chance Company, and Flood Engineering. Dr. Shwehdi Outstanding Supervisor for Student Research 1989, 1990, and
held teaching positions with the University of Missouri- the IEEE outstanding student advisor in 1990.
Columbia, Texas A & I University, University of Florida and
Penn. State University from 1991-1993. At present he is
associate professor with the King Fahd University of Petroleum
& Minerals (KFUPM), Saudi Arabia. His research interest

Table I Characteristics of Lines, Distances in meters


System
h yA yB yC Sg Sa Sb Zg ZT CA CB CC
Voltage
230 35 29 24 18 5 8 11 379 190 35. 25. 18.
a
230 35 29 24 18 0 8 11 600 190 22. 16. 12.
230 70 64 59 53 5 8 11 421 210 42. 34. 28.
b
230 35 29 24 18 5 8 11 239 190 44. 35. 31.
a
Single ground wire. b Underbuilt ground wire at h=12 m at center of tower

You might also like