Department of Physics, College of Saber, University of Aden, 867 Street 10B, Sheikh Othman, Aden, Yemen
shehababdulwadood@gmail.com
Abstract. This paper presents an overview of how the or distribution lines struck. In the case of overhead dis-
lightning strikes and their effects on power distribu- tribution lines, it is not necessary that a stroke contact
tion systems can be modeled, where the results give a the line to produce overvoltages dangerous to equip-
clear picture of how to eliminate the devastating im- ment. This is so because ”induced voltages” caused
pact, caused by lightning, by using lightning arresters. by the collapse of the electrostatic field with a nearby
The program ATP-Draw (Alternative Transient Pro- stroke may reach values as high as 300 kV [1].
gram) was used to simulate the problem and was applied
Lightning is classified as a transient event. In or-
on a part of a power network.The simulation was done
der to understand the effect of lightning, it is best to
once when the lightning strikes a transmission line and
acquire some knowledge as to what lightning is, how
a substation with no lightning arresters in use and once
it is caused, and where it is most likely to occur [2].
more with their use. The source of the lightning was
The amount of energy contained in a lightning stroke
represented by the ATP models (Type-15 surge function
is very high and it can be extremely destructive, even
and Type-13 ramp function) and the surge arrester was
a single stroke to a distribution line can be sufficient
represented by the MOV-Type 92 component. The volt-
to cause a blackout throughout a feeder.
age was recorded at the substation 110/22 kV and at
all loads in the electric network, and was drawn by the Lightning is the main reason for outages in transmis-
PlotXWin program. The results obtained indicate that sion and distribution lines [3]. When lightning strikes
the voltages induced by the lightning can reach values a power line, it is like closing a ”big switch” between
of the order of millions over insulation flashover levels a large current source and the power line circuit. The
for 22 kV equipment, where is clearly seen in Fig. 9 to sudden closing of this ”big switch” causes an abrupt
Fig. 13 and Tab. 10, which requires the installation of change in the circuit conditions, creating a transient.
lightning arresters. There is also the case when the lightning strikes the
vicinity of the power line and the large magnetic field
generated from the lightning current cause mutual cou-
pling between the power line and the lightning. The
Keywords event alters the conditions of the power line circuit, as
a result, produce an electrical transient [4].
Lightning, lightning arresters, MOV, overvolt-
The study of lightning strokes in power lines is very
age, residual voltage.
important because it is known that lightning does
strike the same structure over and again. This can
be a very serious problem for power lines, typically,
1. Introduction the highest structures located in high incidence light-
ning regions. Any structure, no matter its size, may
be struck by lightning, but the probability of a struc-
Lightning is the most frequent cause of overvoltages on
ture been struck increases with its height [5]. Very
distribution systems. Basically, lightning is a gigan-
close dart leaders can make as significant a contribu-
tic spark resulting from the development of millions of
tion as return strokes in inducing voltages and currents
volts between clouds or between a cloud and the earth.
on power systems [6].
It is similar to the dielectric breakdown of a huge ca-
pacitor. The voltage of a lightning stroke may start
at hundreds of millions of volts between the cloud and
earth. Although these values do not reach the earth,
millions of volts can be delivered to the buildings, trees
c 2013 ADVANCES IN ELECTRICAL AND ELECTRONIC ENGINEERING 433
POWER ENGINEERING AND ELECTRICAL ENGINEERING VOLUME: 11 | NUMBER: 6 | 2013 | DECEMBER
c 2013 ADVANCES IN ELECTRICAL AND ELECTRONIC ENGINEERING 434
POWER ENGINEERING AND ELECTRICAL ENGINEERING VOLUME: 11 | NUMBER: 6 | 2013 | DECEMBER
voltage-current or V-I characteristic, ignorable power are connected in parallel and separated by inductance
losses, high level reliability in the operation time, high L1 . Capacitance C is the value of terminal to termi-
speed response to the over-voltages, simplicity of de- nal of capacitor and the resistor represents of arrester
sign, easier for maintenance and long life time. Accu- which has the value of the whole resistance of 1 MΩ.
rate modeling and simulation of their dynamic char-
Other models are developed and simplified such as
acteristics are very important for arrester allocation,
a Popov model for switching studies, and its param-
systems reliability and insulation coordination stud-
eters can be estimated by an iterative trial and error
ies [9], [10], [11]. For switching over voltages studies,
procedure, proposed in [13], and a CIGRE model [14].
the surge arresters can be represented by their nonlin-
ear V-I characteristics (or U-I characteristics). How-
ever, such a presentation would not be suitable for fast
front transient and lightning surge studies. Because 6. Parameters of A0 and A1
the MO surge arrester exhibits dynamic characteristics
such that the voltage across the surge arrester increases To define non-linear parameter resistors, A0 and A1 the
as the time-to-crest of the arrester current decreases reference from the committee of IEEE W.G. 3.4.11 is
and the voltage of arrester reaches a peak before the used. The experiments obtain the characteristic curves
arrester current peaks [9]. Typically, the residual volt- of current and voltage of both non-linear resistors as
age for an impulse current having a front time equal shown in the curves in Fig. 2 [10] or in Tab. 3 below
to 1 µs is 8–12 % higher than that of predicted for an [9].
impulse current having a front time equal to 8 µs. The
residual voltage for longer time-to-crests between 45
and 60 µs, is 2–4 % lower than that of a 8 µs current
impulse [11]. In order to reproduce the MO surge ar-
rester dynamic characteristics mentioned previously, a
lot of researches have been done on modeling and sim-
ulation of MO surge arresters [11]. A dynamic model
has been presented based on the data base of [9] for fast
impulse currents (time-to-crest of 0,5–4,5 µs). To esti-
mate the model parameters, an iterative trial and error
procedure has been proposed, which matches the peak
of discharge voltage obtained with 8 × 20 µs impulse
current.
Fig. 2: V-I characteristics of nonlinear A0 and A1 .
c 2013 ADVANCES IN ELECTRICAL AND ELECTRONIC ENGINEERING 435
POWER ENGINEERING AND ELECTRICAL ENGINEERING VOLUME: 11 | NUMBER: 6 | 2013 | DECEMBER
9. ATP-Draw Modeling
The other values: number of phases: 3, shell core,
The supply network is represented by the source of test frequency 50
√ Hz and the connection is Ynyn (volt-
voltage with amplitude equals to Eq. (3) [14] and it’s age divided by 3).
internal impedance (R = 0, 803 Ω, L = 25, 56 mH) cal-
culated from the short-circuit power SK”. The model • The transmission lines 22 kV are made of AlFe6
of the supply network by ATP-Draw was AC3ph-Type and all are modeled by LCC Lines/Cables proce-
14 (Steady-state (cosinus) function 3 phase). dure as an overhead line, 3phase with PI-Model.
c 2013 ADVANCES IN ELECTRICAL AND ELECTRONIC ENGINEERING 436
POWER ENGINEERING AND ELECTRICAL ENGINEERING VOLUME: 11 | NUMBER: 6 | 2013 | DECEMBER
Ground resistivity ρ = 20 Ωm, Freq. init = 50 Hz. • The lightning flash is implemented in ATP-Draw
The parameters are in Tab. 5 and the placement of using three shunt connected ideal current sources.
the conductors as shown in Fig. 4. The simulation The first stroke, represented in Fig. 5, was sim-
was done with the assumption that the placement ulated using a Type-15 surge function [17]. This
of the conductors on the tower for all lines is (1,75, function is suitable and given by:
0,4, -1,75 and for ground -0,09), Vtower = 10, 25 m
f (t) = amplitude eAt − eBt .
(4)
and Vmid = 10 m.
The constants amplitude, A and B were selected
Tab. 5: The parameters of the transmission lines.
to provide a surge value of 10 kA for the duration of
Section Rout Resis React 0,6 ms. Constants values are presented in Tab. 7.
Line
area [mm2 ] [cm] [Ω·km−1 ] [Ω·km−1 ]
Tab. 7: The surge function values.
1 185 0,95 0,1773 0,3272
2 120 0,8 0,234 0,421
Amplitude A B T-start T-stop
3 95 0,675 0,319 0,430
[A] [l·s−1 ] [l·s−1 ] [s] [s]
Ground 35 0,42 0,778 0,428
16000 -8500 -60000 0 0,0006
Stroke 1 2
Amplitude [A] 5000 3000
T0 [s] 0 0
A1 [A] 0 0
T1 [s] 0,0003 0,0003
T-start [s] 0,06 0,03
T-stop [s] 0,0603 0,1203
Fig. 4: Dimensions of the tower.
c 2013 ADVANCES IN ELECTRICAL AND ELECTRONIC ENGINEERING 437
POWER ENGINEERING AND ELECTRICAL ENGINEERING VOLUME: 11 | NUMBER: 6 | 2013 | DECEMBER
Max. continous
operating voltage 22
Uc (kVcrest)
Rated Voltage Ur
27, 5
kV (rms)
Residual voltage
(Ures ) in kV 1 kA 2,5 kA 5 kA 10 kA 20 kA
(crest) at speci-
fied discharge
current (crest) 64 67,8 71,7 77 87,4
wave 8/20 µs
Temporary t = 1 s, UT OV = 1, 325 × Uc
overvoltage t = 3 s, UT OV = 1, 300 × Uc
(TOV) UT OV t = 10 s, UT OV = 1, 275 × Uc
c 2013 ADVANCES IN ELECTRICAL AND ELECTRONIC ENGINEERING 438
POWER ENGINEERING AND ELECTRICAL ENGINEERING VOLUME: 11 | NUMBER: 6 | 2013 | DECEMBER
Fig. 9: Voltages at substation 110/22 kV for the three scenarios. Fig. 12: Voltages at load 3 (sec. side) for the three scenarios.
Fig. 10: Voltages at load 1 for the three scenarios. Fig. 13: Voltages at the end point of line 1 for the three sce-
narios.
c 2013 ADVANCES IN ELECTRICAL AND ELECTRONIC ENGINEERING 439
POWER ENGINEERING AND ELECTRICAL ENGINEERING VOLUME: 11 | NUMBER: 6 | 2013 | DECEMBER
c 2013 ADVANCES IN ELECTRICAL AND ELECTRONIC ENGINEERING 440
POWER ENGINEERING AND ELECTRICAL ENGINEERING VOLUME: 11 | NUMBER: 6 | 2013 | DECEMBER
References
[1] BEATY, H. W. Standard Handbook for Electrical
Engineers. New York: McGraw-Hill Professional,
2006. ISBN 978-0071762328.
Fig. 19: Dissipated energy at loads.
[2] BURKE, J. J. Power Distribution Engineering–
Fundamentals and applications. New York: CRC
Press, 1994. ISBN 978-0824792374.
c 2013 ADVANCES IN ELECTRICAL AND ELECTRONIC ENGINEERING 441
POWER ENGINEERING AND ELECTRICAL ENGINEERING VOLUME: 11 | NUMBER: 6 | 2013 | DECEMBER
[3] GREENWOOD, A. Electrical Transients in [12] FERNANDEZ, F. and R. DIAZ. Metal oxide surge
Power Systems. New York: John Wiley & Sons, arrester model for fast transient simulations. In:
1991. ISBN 978-0471620587. International Conference on Power System Tran-
sients IPST01. Rio De Janeiro: Federal University
[4] RODRIGUEZ-SANABRIA, D. and C. RAMOS- of Rio de Janeiro, 2001, pp. 144-1–144-5.
ROBLES. Lightning and Lightning Arrester Sim-
ulation in Electrical Power Distribution Sys- [13] POPOV M., L. SLUIS and G. C. PAAP.
tems. In: Electrical and Computer Engineering: Application of a new surge arrester model
University of Puerto Rico [online]. 2005. Avail- in protection studies concerning switching
able at: http://ece.uprm.edu/~lorama/Proy_ surges. IEEE Power Engineering Review. 2002,
Rayos03.pdf. vol. 22, iss. 9, pp. 52–53. ISSN 0272-1724.
DOI: 10.1109/MPER.2002.4312562.
[5] UMAN, M. A. All About Lightning. Toronto:
Dover Publications, 1986. ISBN 978-0486252377. [14] THANASAKSIRI, T., S. PREMRUDEEP-
REECHACHAN, W. TAYATI and P. JI-
[6] RAKOV, V. A., M. A. UMAN, K. J. RAMBO, RAPONG. Improving the Lightning Performance
M. I. FERNANDEZ, R. J. FISCHER, G. of Overhead Distribution Lines in Thailand
H. SCHNETZER, R. THOTTAPPILLIL, A. Using Lightning Protection Design Workstation
EYBERT-BERARD, J. P. BERLANDIS, P. LA- (LPDW). In: Proceedings of the IASTED Inter-
LANDE, A. BONAMY, P. LAROCHE and national Conference, PowerCon 2003 (Special
A. BONDIOU-CLERGERIE. New Insights into Theme: BLACKOUT). New York: Acta Press,
Lightning Processes from Triggered-Lightning Ex- 2003, pp. 39–48. ISBN 978-0889864009.
periments in Florida and Alabama. Journal of
Geophysical Research. 1998, vol. 103, no. D12, [15] Leuven EMTP Center. Alternative Transients
pp. 14117–14130. ISSN 2156-220. Program: Rule Book. Heverlee: EMTP, 1987.
[7] DIENDORFER G., W. SCHULZ and V. A. [16] MIKULEC M. and V. HAVLICEK. Fundamen-
RAKOV. Lightning Characteristics Based on tals of electromagnetic circuits 1. Prague: CVUT,
Data from the Austrian Lightning Locating Sys- 1997. ISBN 80-01-01620-X.
tem. IEEE Transactions on Electromagnetic Com-
patibility. 1998, vol. 40, iss. 4, pp. 452–464. [17] PRIKLER, L. and H. K. HOIDALEN. ATPDraw
ISSN 0018-9375. DOI: 10.1109/15.736206. version 5.6 for windows 9x/NT/2000/XP/Vista:
Users Manual. 2002. Available at: http://www.
[8] MACKEVICH, J. P. Proper Lightning Arrester elkraft.ntnu.no/atpdraw/ATPDMan56.pdf.
Application Improves Distribution System Relia-
bility. In: 2nd International Conference on Ad- [18] High Voltage Products: Surge Arrester. In:
vances in Power System Control, Operation and ABB Switzerland Ltd. [online]. 2013. Avail-
Management, 1993. APSCOM-93. Hong Kong: able at: http://www.abb.com/product/us/
IEEE, 1993, pp. 153–158. ISBN 0-85296-569-9. 9AAC710009.aspx.