You are on page 1of 1

According to Saudi Electricity company standards TES-P-103.

03-rev 0

Rating of Battery charger (Ar) = SF x IL + (BIF x AH) / RT

Ar = Minimum required charger output

SF = Service factor = 1.2

IL = Continuous DC Load in Amp = 66.62

BIF = Battery inefficiency factor = 1.5

AH = AH rating of the battery = 1145

RT = Recharge time in hours = 6

Ar = 1.2 x 66.62 + ((1.5*1145)/6) = 1.2 x 66.62 + 286.25 = 79.944 + 286.25 = 366.194 A