JANUARY 19, 2015 REF. NO: 001-2015

MR. BERNARD M. ALEGRADO


PRESIDENT& CHIEF OPERATING OFFICER
AMBIENTE DESIGNS INTERNATIONAL
TINGUB, MANDAUE CITY

SUBJECT : FINAL LOAD COMPUTATION


(For Tenants DHL)

Dear Sir:

Sending herewith at your end is the final load computation and design of tenant “DHL” including the additional
load at zone-4 and DHL office located at Admin Office.

I. REVISED SCHEDULE OF LOADS FOR DHL, PANEL “LPA ”


CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION HP KW Volts AB BC CA I 3P AT POLE
1 43-36w Fluorescent Lamp 1.548 220 8.79 20 2P
2 43-36w Fluorescent Lamp 1.548 220 8.79 20 2P
3 43-36w Fluorescent Lamp 1.548 220 8.79 20 2P
4 43-36w Fluorescent Lamp 1.548 220 8.79 20 2P
5 8-250w Metal Halide Lamp 2.000 220 11.36 20 2P
6 2-500w Computer, 1-600w Water 2.165 220 12.30 20 2P
Dispenser, 1- 65w Stand Fan, 1-
500w Brometral
7 46-36w Fluorescent Lamp 1.656 220 7.53 15 2P
8 46-36w Fluorescent Lamp 1.656 220 7.53 15 2P
9 5-250w Metal Halide Lamp 1.250 220 7.10 15 2P
10 5-250w Metal Halide Lamp 1.250 220 7.10 15 2P
11 5-250w Metal Halide Lamp 1.250 220 7.102 15 2P
12 5-250w Metal Halide Lamp 1.250 220 7.102 15 2P
13 5-36w Fluorescent lamp, 1-9w P.L. 0.180 220 1.07 15 2P
14 5- Duplex Convenience outlet 1.800 220 8.18 20 2P
15 1-3 Tons ACU 3.680 220 17.00 30 2P

TOTAL 24.32 41.8 37.8 48.7


9 9 6 8

Page 1 of 2
COMPUTATION:
IT = 1.732 [48.78 + (0.25 x 17.00)] x 0.70 D.F.
= 91.85 AMPS.
SIZE OF WIRE : 3-30 MM2 THW CU. WIRE
PROTECTION : USE 150AT225AF. 2P, 240V CIRCUIT BREAKER

II. REMARKS:

1. In the previous set-up, the total connected load of DHL is 10.357 kilowatts
2. The type of service for the previous set-up is single phase system, 220 volts, 60 Hz with
2-22 mm2 THW copper wire power supply coming from the source.
3. In the current set-up, the total connected load increases to 24.329 kilowatts, meaning the total
Connected, double compared to the previous set-up
4. Due to the increase of connected load, the existing 2-22 mm2 single phase feeder line of DHL is no
longer sufficient to carry the entire load of the present set-up

III. RECOMMENDATIONS:
1. Convert the single phase system feeder line of DHL to three-phase system, 220 volts, 60 Hz..
2. Provide 3-30 mm2 THW copper wire from the Electrical Room to the Main Circuit breaker of DHL
3. Provide three-phase kilowatt-hour meter to DHL as the prescribe kwhr meter

SUBMITTED BY:

ROMEO P. DELA PEÑA


Registered Electrical Engineer
PRC Reg. No. : 7860
Date : 04-12-97
Cell. No. : (0917)936-5601; (0922)232-4355
Email Add : romy_lou@yahoo.com

Page 2 of 2