SCHEDULE OF LOADS, PANEL “LPA” (FINAL FINISHING AREA)

CKT AMPERES PROTECTION


NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 36W TLD FLOURESCENT LIGHT 28 1.07 230 12.04 20 2P 5.5 MM THW 15 MM DIA.PVC
2 36W TLD FLOURESCENT LIGHT 28 1.07 230 12.04 20 2P 5.5 MM2 THW 15 MM DIA.PVC
3 36W TLD FLOURESCENT LIGHT 28 1.07 230 12.04 20 2P 5.5 MM2 THW 15 MM DIA.PVC
4 36W TLD FLOURESCENT LIGHT 28 1.07 230 12.04 20 2P 5.5MM2 THW 15 MM DIA.PVC
5 36W TLD FLOURESCENT LIGHT 28 1.07 230 12.04 20 2P 5.5 MM2 THW 15 MM DIA.PVC
6 36W TLD FLOURESCENT LIGHT 28 1.07 230 12.04 20 2P 5.5 MM2 THW 15 MM DIA.PVC
7 36W TLD FLOURESCENT LIGHT 28 1.07 230 12.04 20 2P 5.5 MM2 THW 15 MM DIA.PVC
8 36W TLD FLOURESCENT LIGHT 28 1.07 230 12.04 20 2P 5.5 MM2 THW 15 MM DIA.PVC
9 DUPLEX CONVENIENCE OUTLET 8 1.6 230 8.69 15 2P 3.5 MM2 THW 15 MM DIA.PVC
10 36W TLD FLOURESCENT LIGHT 8 0.26 230 3.44 15 2P 3.5 MM2 THW 15 MM DIA.PVC
TOTAL 10.42 36.12 36.12 36.21

COMPUTATION:

IT = {1.732 [36.21 + (0.25 x 12.04)]} x 0.80 D.F.


= 54.34 AMPS.
SIZE OF WIRE : 3-22 MM2 THW CU. WIRE
SIZE OF CONDUIT : 25 MM DIA. PVC PIPE
PROTECTION : USE 100AT/225AF. 3P, 240V CIRCUIT BREAKER
SCHEDULE OF LOADS, PANEL “LPB” (PRODUCTION AREA)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 METAL HALIDE, 400W 4 1.6 230 10.0 20 2P 5.5 MM THW 15 MM DIA.PVC
2 METAL HALIDE, 400W 4 1.6 230 10.0 20 2P 5.5 MM2 THW 15 MM DIA.PVC
3 METAL HALIDE, 400W 4 1.6 230 10.0 20 2P 5.5 MM2 THW 15 MM DIA.PVC
4 METAL HALIDE, 400W 4 1.6 230 10.0 20 2P 5.5MM2 THW 15 MM DIA.PVC
5 METAL HALIDE, 400W 4 1.6 230 10.0 20 2P 5.5 MM2 THW 15 MM DIA.PVC
6 METAL HALIDE, 400W 4 1.6 230 10.0 15 2P 3.5 MM2 THW 15 MM DIA.PVC
7 METAL HALIDE, 400W 2 0.8 230 5.0 15 2P 3.5 MM2 THW 15 MM DIA.PVC
8 PERIMETER LIGHT 14 0.7 230 6.9 15 2P 3.5 MM2 THW 15 MM DIA.PVC
9 SECURITY LIGHT 14 0.7 230 6.1 15 2P 3.5 MM2 THW 15 MM DIA.PVC
10 SPARE 1.0 230 5.43 15 2P 3.5 MM2 THW 15 MM DIA.PVC
TOTAL 12.8 30.43 26.9 26.1

COMPUTATION:

IT = {1.732 [30.43 + (0.25 x 10.0)]} x 0.80 D.F.


= 26.34 AMPS.
SIZE OF WIRE : 3-22 MM2 THW CU. WIRE
SIZE OF CONDUIT : 25 MM DIA. PVC PIPE
PROTECTION : USE 100AT/225AF. 3P, 240V CIRCUIT BREAKER
SCHEDULE OF LOADS, PANEL “LPC” (MEZZANINE BLDG.)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 PIN LIGHT, 8W, SOCKET TYPE 17 0.14 230 3.2 15 2P 3.5 MM THW 15 MM DIA.PVC
2 2x36W FLOURESCENT LIGHT 10 0.72 230 3.7 15 2P 3.5 MM2 THW 15 MM DIA.PVC
3 2x36W FLOURESCENT LIGHT 10 0.72 230 3.7 15 2P 3.5 MM2 THW 15 MM DIA.PVC
4 2x36W FLOURESCENT LIGHT 10 0.72 230 3.7 15 2P 3.5MM2 THW 15 MM DIA.PVC
5 2x36W FLOURESCENT LIGHT 10 0.72 230 3.7 15 2P 3.5 MM2 THW 15 MM DIA.PVC
6 PIN LIGHT, 8W, SOCKET TYPE 15 0.12 230 2.8 15 2P 3.5 MM2 THW 15 MM DIA.PVC
7 PIN LIGHT, 8W, SOCKET TYPE 14 0.12 230 2.7 20 2P 3.5 MM2 THW 15 MM DIA.PVC
8 DUPLEX CONVENIENCE OUTLET 14 2.8 230 12.2 20 2P 5.5 MM2 THW 20 MM DIA.PVC
9 DUPLEX CONVENIENCE OUTLET 14 2.8 230 12.2 20 2P 5.5 MM2 THW 20 MM DIA.PVC
10 2x36W FLOURESCENT LIGHT 18 1.3 230 6.7 15 2P 3.5 MM2 THW 15 MM DIA.PVC
11 LIGHTINGS 12 0.74 230 4.1 15 2P 3.5 MM2 THW 15 MM DIA.PVC
12 LIGHTINGS 13 0.68 230 4.1 15 2P 3.5 MM2 THW 15 MM DIA.PVC
13 2x36W FLOURESCENT LIGHT 12 0.86 230 4.4 15 2P 3.5 MM2 THW 15 MM DIA.PVC
14 2x36W FLOURESCENT LIGHT 12 0.86 230 4.4 15 2P 3.5MM2 THW 15 MM DIA.PVC
15 2x36W FLOURESCENT LIGHT 12 0.86 230 4.4 15 2P 3.5 MM2 THW 15 MM DIA.PVC
16 15-DUPLEX C.O. & 5-EX FAN 20 3.3 230 13.9 20 2P 5.5 MM2 THW 15 MM DIA.PVC
17 5 TONS A.C. 5 32.05 230 125.7 170 3P 60 MM2 THW 40 MM DIA.PVC
18 3 TONS A.C. 1 4.68 230 25.4 40 2P 8.0 MM2 THW 20 MM DIA.PVC
19 AIRCON, CASSETTE TYPE 1 5.6 230 30.4 50 2P 8.0 MM2 THW 20 MM DIA.PVC
20 WINDOW TYPE, A.C. 1 0.75 230 5.1 15 2P 3.5 MM2 THW 15 MM DIA.PVC
21 WINDOW TYPE, A.C. 2 1.5 230 10.2 20 2P 5.5 MM2 THW 15 MM DIA.PVC
TOTAL 62.04 50.3 56.2 58.5 125.7

COMPUTATION:

IT = {1.732 [58.5 + (0.25 x 30.4)] + 125.7} x 0.80 D.F.


= 192.15 AMPS.
SIZE OF WIRE : 3-100 MM2 THW CU. WIRE
SIZE OF CONDUIT : 50 MM DIA. PVC PIPE
PROTECTION : USE 250AT/600AF. 3P, 240V CIRCUIT BREAKER
SCHEDULE OF LOADS, PANEL “LPD” (BASE PREPARATION)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 2x40 W FLOURESCENT LIGHT 12 0.96 230 10.3 20 2P 5.5 MM THW 15 MM DIA.PVC
2 2x40 W FLOURESCENT LIGHT 12 0.96 230 10.3 20 2P 5.5 MM2 THW 15 MM DIA.PVC
3 2x40 W FLOURESCENT LIGHT 12 0.96 230 10.3 20 2P 5.5 MM2 THW 15 MM DIA.PVC
4 DUPLEX CONVENIENCE OUTLET 7 1.4 230 7.6 20 2P 3.5MM2 THW 15 MM DIA.PVC
5 DUPLEX CONVENIENCE OUTLET 7 1.4 230 7.6 20 2P 3.5 MM2 THW 15 MM DIA.PVC
6 DEHUMIDIFIER-1 1 2.6 230 14.13 30 2P 5.5 MM2 THW 15 MM DIA.PVC
7 DEHUMIDIFIER-2 1 2.6 230 14.13 30 2P 5.5 MM2 THW 15 MM DIA.PVC
8 DEHUMIDIFIER-3 1 2.6 230 14.13 30 2P 5.5 MM2 THW 15 MM DIA.PVC
9 DEHUMIDIFIER-4 1 2.6 230 14.13 30 2P 5.5 MM2 THW 15 MM DIA.PVC
10 DEHUMIDIFIER-5 1 2.6 230 14.13 30 2P 5.5 MM2 THW 15 MM DIA.PVC
11 DEHUMIDIFIER-6 1 2.6 230 14.13 30 2P 5.5 MM2 THW 15 MM DIA.PVC
12 SPARE 1.0 230 5.43 15 2P 3.5 MM2 THW 15 MM DIA.PVC
TOTAL 22.28 46.16 46.16 43.99

COMPUTATION:

IT = {1.732 [46.16 + (0.25 x 14.3)]} x 0.80 D.F.


= 73.15 AMPS.
SIZE OF WIRE : 3-30 MM2 THW CU. WIRE
SIZE OF CONDUIT : 32 MM DIA. PVC PIPE
PROTECTION : USE 100AT/225AF. 3P, 240V CIRCUIT BREAKER
SCHEDULE OF LOADS, PANEL “LPE” (UTILITY BUILDING)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 15 HP MOTOR 1 11.2 230 35.1 60 3P 14 MM THW 32MM DIA.PVC
2 5.5 HP MOTOR 1 4.1 230 12.9 30 3P 5.5 MM2 THW 20 MM DIA.PVC
3 3 HP MOTOR 1 2.2 230 6.9 20 3P 3.5MM2 THW 15MM DIA.PVC
4 1-2 X40W F.L. & 10-1x40W F.L. 11 0.48 230 4.17 15 2P 3.5MM2 THW 15MM DIA.PVC
5 1x40W F.L. 12 0.48 230 4.17 15 2P 3.5 MM2 THW 15MM DIA.PVC
6 100W P.L. 7 0.7 230 6..0 15 2P 3.5 MM2 THW 15 MM DIA.PVC
7 DUPLEX CONVENIENCE OUTLET 11 1.9 230 10.3 20 2P 5.5 MM2 THW 20 MM DIA.PVC
8 DUPLEX CONVENIENCE OUTLET 10 1.8 230 9.8 20 2P 3.5 MM2 THW 15 MM DIA.PVC
9 10-1x40W F.L. & 2-50W P.L. 12 0.5 230 5.3 15 2P 3.5 MM2 THW 15 MM DIA.PVC
10 SPARE 1.5 230 8.15 20 2P 3.5 MM2 THW 15 MM DIA.PVC
TOTAL 24.86 18.32 14.47 15.1 54.9

COMPUTATION:

IT = {1.732[18.32+(0.25 x 8.15)] + 54.9+(0.25 x 35.1)} 0.80 D.F.


= 79.15 AMPS.
SIZE OF WIRE : 3-38 MM2 THW CU. WIRE
SIZE OF CONDUIT : 32 MM DIA. PVC PIPE
PROTECTION : USE 150AT/225AF. 3P, 240V CIRCUIT BREAKER
SCHEDULE OF LOADS, PANEL “PPA” (PRODUCTION AREA)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 PANEL SAW 7.6 230 23.9 40 3P 8.0 MM THW 20 MM DIA.PVC
2 COPY TURNING 12.0 230 37.7 60 3P 14 MM2 THW 25 MM DIA.PVC
3 JOINTER 5.5 230 17.3 30 3P 5.5 MM2 THW 20 MM DIA.PVC
4 EDGE SANDER 2.2 230 6.9 20 3P 3.5MM2 THW 15 MM DIA.PVC
5 OVERHEAD ROUTER 2.9 230 9.1 20 3P 3.5 MM2 THW 15 MM DIA.PVC
6 SHAPER 5.5 230 17.3 40 3P 5.5 MM2 THW 20 MM DIA.PVC
7 COPY SHAPER 12.0 230 37.7 60 3P 14 MM2 THW 25 MM DIA.PVC
8 BAND SAW 3.9 230 12.2 30 3P 5.5 MM2 THW 20 MM DIA.PVC
9 OVERHEAD ROUTER 2.9 230 9.1 20 3P 3.5 MM2 THW 15 MM DIA.PVC
10 SHAPER 4.0 230 12.6 30 3P 5.5 MM2 THW 20 MM DIA.PVC
11 EDGE SANDER 2.4 230 7.5 20 3P 3.5 MM2 THW 15 MM DIA.PVC
12 RADIAL ARM SAW 2.2 230 6.9 20 3P 3.5 MM2 THW 15 MM DIA.PVC
13 THICKBNESS PLANER 4.5 230 14.1 30 3P 5.5 MM2 THW 20 MM DIA.PVC
14 PANEL SAW 4.8 230 15.1 30 3P 5.5 MM2 THW 20 MM DIA.PVC
TOTAL 72.4 227.4

COMPUTATION:

IT = [227.4 + (0.25 x 37.7)] x 0.80 D.F.


= 189.46 AMPS.
SIZE OF WIRE : 3-150 MM2 THW CU. WIRE
SIZE OF CONDUIT : 50 MM DIA. PVC PIPE
PROTECTION : USE 300AT/600AF. 3P, 240V CIRCUIT BREAKER
SCHEDULE OF LOADS, PANEL “PPB” (PRODUCTION AREA)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 3N-1 12 230 37.7 60 3P 14 MM THW 25 MM DIA.PVC
2 OVERHEAD ROUTER 3.6 230 11.3 30 3P 5.5 MM2 THW 20 MM DIA.PVC
3 THICKNESS PLANNER 3.7 230 11.6 30 3P 5.5 MM2 THW 20 MM DIA.PVC
4 JOINTER 5.5 230 17.3 30 3P 5.5MM2 THW 20 MM DIA.PVC
5 TENONER 5 230 15.7 30 3P 5.5 MM2 THW 20 MM DIA.PVC
6 BORING MACHINE 2.2 230 6.9 20 3P 3.5 MM2 THW 15 MM DIA.PVC
7 CARVING MACHINE 7 230 21.9 30 3P 5.5 MM2 THW 20 MM DIA.PVC
8 OVERHEAD ROUTER 2.2 230 6.9 20 3P 3.5 MM2 THW 15 MM DIA.PVC
9 DOUBLE END MITRE 4.4 230 13.8 30 3P 5.5 MM2 THW 20 MM DIA.PVC
10 RADIAL ARM SAW 2.2 230 6.9 20 3P 3.5 MM2 THW 15 MM DIA.PVC
TOTAL 47.8 150

COMPUTATION:

IT = [150 + (0.25 x 37.7)] x 0.80 D.F.


= 127.54 AMPS.
SIZE OF WIRE : 3-80 MM2 THW CU. WIRE
SIZE OF CONDUIT : 50 MM DIA. PVC PIPE
PROTECTION : USE 300AT/600AF. 3P, 240V CIRCUIT BREAKER
SCHEDULE OF LOADS, PANEL “PPC” (PRODUCTION AREA)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 SPRAY BOOTH-1 3.7 230 11.6 30 3P 5.5 MM THW 20 MM DIA.PVC
2 SPRAY BOOTH-2 3.7 230 11.6 30 3P 5.5 MM2 THW 20 MM DIA.PVC
3 SPRAY BOOTH-3 3.7 230 11.6 30 3P 5.5 MM2 THW 20 MM DIA.PVC
4 SPRAY BOOTH-4 3.7 230 11.6 30 3P 5.5MM2 THW 20 MM DIA.PVC
5 SPRAY BOOTH-5 3.7 230 11.6 30 3P 5.5 MM2 THW 20 MM DIA.PVC
6 SPRAY BOOTH-6 3.7 230 11.6 30 3P 3.5 MM2 THW 15 MM DIA.PVC
7 SILO-1 18.5 230 58.0 80 3P 22 MM2 THW 32 MM DIA.PVC
8 SILO-2 11 230 34.5 50 3P 14 MM2 THW 25 MM DIA.PVC
9 SILO-3 15 230 47.0 75 3P 22 MM2 THW 22 MM DIA.PVC
10 SILO-4 22 230 69.0 100 3P 30 MM2 THW 32 MM DIA.PVC
TOTAL 88.7 278.1

COMPUTATION:

IT = [278.1 + (0.25 x 69.0)] x 0.80 D.F.


= 236.28 AMPS.
SIZE OF WIRE : 3-200 MM2 THW CU. WIRE
SIZE OF CONDUIT : 80 MM DIA. PVC PIPE
PROTECTION : USE 400AT/600AF. 3P, 240V CIRCUIT BREAKER
SCHEDULE OF LOADS, PANEL “PPD” (PRODUCTION AREA)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 SPRAY BOOTH-7 3.7 230 11.6 30 3P 5.5 MM THW 20 MM DIA.PVC
2 SPRAY BOOTH-8 3.7 230 11.6 30 3P 5.5 MM2 THW 20 MM DIA.PVC
3 SPRAY BOOTH-9 3.7 230 11.6 30 3P 5.5 MM2 THW 20 MM DIA.PVC
4 SPRAY BOOTH-10 3.7 230 11.6 30 3P 5.5MM2 THW 20 MM DIA.PVC
5 FINGER DUCTING 2.2 230 6.9 20 3P 3.5 MM2 THW 15 MM DIA.PVC
6 SYSTEMS 32 5.0 230 15.7 30 3P 5.5 MM2 THW 20 MM DIA.PVC
7 MORTIZER 3.2 230 10.0 20 3P 3.5 MM2 THW 15 MM DIA.PVC
8 CIRCULAR SAW 3.0 230 9.4 20 3P 3.5 MM2 THW 15 MM DIA.PVC
9 DOUBLE END MITRE 4.4 230 13.8 30 3P 5.5 MM2 THW 20 MM DIA.PVC
10 RADIAL ARM SAW 2.5 230 7.8 20 3P 3.5 MM2 THW 15 MM DIA.PVC
11 COPY TURNING 3.75 230 11.8 30 3P 5.5 MM2 THW 20 MM DIA.PVC
12 EDGE SANDER 2.4 230 7.5 20 3P 3.5 MM2 THW 15 MM DIA.PVC
13 EDGE SANDER 2.4 230 7.5 20 3P 3.5 MM2 THW 15 MM DIA.PVC
14 OVERHEAD ROUTER 3.6 230 11.3 30 3P 5.5MM2 THW 20 MM DIA.PVC
15 SHAPER 5.5 230 17.3 30 3P 5.5 MM2 THW 20 MM DIA.PVC
16 SHAPER 5.5 230 17.3 30 3P 5.5 MM2 THW 20 MM DIA.PVC
17 SHAPER 5.5 230 17.3 30 3P 3.5 MM2 THW 15 MM DIA.PVC
18 OVERHEAD ROUTER 3.6 230 11.3 30 3P 5.5 MM2 THW 20 MM DIA.PVC
TOTAL 67.35 211.3

COMPUTATION:

IT = [211.3 + (0.25 x 17.3)] x 0.80 D.F.


= 215.63 AMPS.
SIZE OF WIRE : 3-150 MM2 THW CU. WIRE
SIZE OF CONDUIT : 65 MM DIA. PVC PIPE
PROTECTION : USE 300AT/600AF. 3P, 240V CIRCUIT BREAKER
SCHEDULE OF LOADS, PANEL “PPE” (PRODUCTION AREA)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 OVERHEAD ROUTER 3.6 230 11.3 30 3P 5.5 MM THW 20 MM DIA.PVC
2 COPY SHAPER 12 230 37.7 60 3P 14 MM2 THW 25 MM DIA.PVC
3 MOULDER 5 230 15.7 30 3P 5.5 MM2 THW 20 MM DIA.PVC
4 COPY SHAPER 15 230 47.1 75 3P 22 MM2 THW 32 MM DIA.PVC
5 CARVING MACHINE 9.6 230 30.1 50 3P 8.0 MM2 THW 25 MM DIA.PVC
6 BAND SAW 3.8 230 11.9 30 3P 5.5 MM2 THW 20 MM DIA.PVC
7 COPY MILLING 8.75 230 27.5 40 3P 8.0 MM2 THW 25 MM DIA.PVC
8 BAND SAW 3.6 230 11.3 30 3P 5.5 MM2 THW 20 MM DIA.PVC
9 BAND SAW 6.14 230 19.3 40 3P 5.5 MM2 THW 20 MM DIA.PVC
10 TAYLOR CLAMP CARRIER 5.5 230 17.3 30 3P 5.5 MM2 THW 20 MM DIA.PVC
11 MOULDER 2.5 230 7.8 20 3P 3.5 MM2 THW 15 MM DIA.PVC
12 CUT-OFF SAW 7.5 230 23.5 40 3P 8.0 MM2 THW 25 MM DIA.PVC
13 THICKNESS PLANNER 4.5 230 14.1 30 3P 5.5 MM2 THW 20 MM DIA.PVC
14 JOINTER 4.8 230 15.1 30 3P 5.5MM2 THW 20 MM DIA.PVC
15 THICKNESS PLANNER 3.7 230 11.6 30 3P 5.5 MM2 THW 20 MM DIA.PVC
16 PANEL SAW 7.64 230 23.9 40 3P 5.5 MM2 THW 20 MM DIA.PVC
17 SINGLE RIP SAW 10 230 31.4 50 3P 8.0 MM2 THW 25 MM DIA.PVC
18 VENNER TRIMMER 2.2 230 6.9 20 3P 5.5 MM2 THW 20 MM DIA.PVC
TOTAL 115.83 363.5

COMPUTATION:

IT = [363.5 + (0.25 x 47.1)] x 0.80 D.F.


= 375.28 AMPS.
SIZE OF WIRE : 2 SETS OF 3-125 MM2 THW CU. WIRE
SIZE OF CONDUIT : 2 SETS OF 65 MM DIA. PVC PIPE
PROTECTION : USE 500AT/600AF. 3P, 240V CIRCUIT BREAKER
SCHEDULE OF LOADS, PANEL “PPF” (PRODUCTION AREA)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 CNC MACHINE 36 230 65 150 3P 50 MM THW 40 MM DIA.PVC
2 CNC MACHINE 36 230 65 150 3P 50 MM2 THW 40 MM DIA.PVC
3 CNC MACHINE 36 230 65 150 3P 50 MM2 THW 40 MM DIA.PVC
4 CNC VACUUM 5.5 230 17.3 30 3P 5.5 MM2 THW 20 MM DIA.PVC
5 CNC VACUUM 5.5 230 17.3 30 3P 5.5 MM2 THW 20 MM DIA.PVC
6 CNC VACUUM 5.5 230 17.3 30 3P 5.5 MM2 THW 20 MM DIA.PVC
7 EDGE SANDER 10 230 31.4 50 3P 8.0MM2 THW 25 MM DIA.PVC
8 HOT PRESS 22 230 60.9 100 3P 30 MM2 THW 32 MM DIA.PVC
9 HOT PRESS 23 230 72.2 100 3P 30 MM2 THW 32 MM DIA.PVC
10 EDGE SANDER 8.05 230 25.3 40 3P 8.0 MM2 THW 20 MM DIA.PVC
11 EDGE SANDER 1.1 230 3.5 15 3P 3.5 MM2 THW 15 MM DIA.PVC
TOTAL 188.65 440.2

COMPUTATION:

IT = [440.2 + (0.25 x 65)] x 0.80 D.F.


= 365.18 AMPS.
SIZE OF WIRE : 2 SETS OF 3-150 MM2 THW CU. WIRE
SIZE OF CONDUIT : 2 SETS OF 65 MM DIA. PVC PIPE
PROTECTION : USE 600AT/800AF. 3P, 240V CIRCUIT BREAKER
SCHEDULE OF LOADS, PANEL “PPG” (PRODUCTION AREA)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 SILO-5 26 230 81.6 125 3P 30 MM THW 32 MM DIA.PVC
2 SILO-6 18.5 230 58.0 125 3P 30 MM2 THW 32 MM DIA.PVC
3 AIR COMPRESSOR-1 22 230 69 100 3P 30 MM2 THW 32 MM DIA.PVC
4 AIR COMPERESSO-2 22 230 69 100 3P 30 MM2 THW 32 MM DIA.PVC
5 AIR COMPERESSO-3 15 230 47.1 75 3P 22 MM2 THW 32 MM DIA.PVC
6 3 TONS ACCU 3.8 230 11.9 30 3P 5.5 MM2 THW 20 MM DIA.PVC
7 3 TONS AHU 1.5 230 4.7 20 3P 3.5 MM2 THW 15 MM DIA.PVC
8 SPLICING MACHINE 1.0 230 3.1 15 3P 3.5 MM2 THW 15 MM DIA.PVC
9 SPLICING MACHINE 1.0 230 3.1 15 3P 3.5 MM2 THW 15 MM DIA.PVC
TOTAL 110.8 347.5

COMPUTATION:

IT = [347.5 + (0.25 x 81.6)] x 0.80 D.F.


= 294.32 AMPS.
SIZE OF WIRE : 2 SETS OF 3-100 MM2 THW CU. WIRE
SIZE OF CONDUIT : 2 SETS OF 50 MM DIA. PVC PIPE
PROTECTION : USE 450AT/600AF. 3P, 240V CIRCUIT BREAKER
SCHEDULE OF LOADS, PANEL “PPH” (PRODUCTION AREA)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 WIDE BELT SANDER 40 230 110.7 175 3P 60 MM THW 40 MM DIA.PVC
2 DMC WBS 64 230 177.2 250 3P 125 MM2 THW 65 MM DIA.PVC
3 ORMA 35 230 89.0 150 3P 50 MM2 THW 40 MM DIA.PVC
TOTAL 139 376.9
COMPUTATION:
IT = [376.9 + (0.25 x 177.2)] x 0.80 D.F.
= 294.84 AMPS.
SIZE OF WIRE : 2 SETS 3-100 MM2 THW CU. WIRE
SIZE OF CONDUIT : 2 SETS OF 50 MM DIA. PVC PIPE
PROTECTION : USE 450AT/600 AF. 3P, 240V CIRCUIT BREAKER

SCHEDULE OF LOADS, PANEL “PPI” (PRODUCTION AREA)


CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 RADION FREQUENCY PRESS 20 230 62.8 100 3P 60 MM THW 40 MM DIA.PVC
2 MULTI-RIP SAW (SCM) 25.14 230 68.0 125 3P 125 MM2 THW 65 MM DIA.PVC
3 SCM WBS 48.4 230 134 200 3P 50 MM2 THW 40 MM DIA.PVC
TOTAL 93.54 264.80
COMPUTATION:
IT = [264.8 + (0.25 x 134)] x 0.80 D.F.
= 238.64 AMPS.
SIZE OF WIRE : 3-200 MM2 THW CU. WIRE
SIZE OF CONDUIT : 80 MM DIA. PVC PIPE
PROTECTION : USE 400AT/600AF. 3P, 240V CIRCUIT BREAKER
DISTRIBUTION PANEL NO.1 (MDP-1)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 PANEL “LPA” 10.42 230 36.12 36.12 36.21 100 3P 22 MM THW 25 MM DIA.PVC
2 PANEL “LPB” 12.8 230 30.43 26.9 26.1 100 3P 22 MM2 THW 25 MM DIA.PVC
3 PANEL “LPC” 62.04 230 50.3 56.2 58.5 125.7 250 3P 100 MM2 THW 50 MM DIA.PVC
4 PANEL “LPD” 22.28 230 46.16 46.16 43.99 100 3P 30 MM2 THW 32 MM DIA.PVC
5 PANEL “LPE” 24.86 230 18.32 14.47 15.1 54.9 150 3P 38 MM2 THW 32 MM DIA.PVC
6 PANEL “PPA” 72.4 230 227.4 300 3P 150 MM2 THW 50 MM DIA.PVC
7 PANEL “PPB” 47.8 230 150 300 3P 80 MM2 THW 50 MM DIA.PVC
8 PANEL “PPC” 88.7 230 278.1 400 3P 200 MM2 THW 80 MM DIA.PVC
TOTAL 341.25 181.33 179.85 179.9 836.1

COMPUTATION:

IT = {1.732[181.33 + (0.25 x 50.3)] +836.1 + (0.25 x 278.1)} x 0.80 D.F.


= 993.18 AMPERES
SIZE OF WIRE : 3 SETS OF 3-200 MM2 THW CU. WIRE
SIZE OF CONDUIT : 3 SETS OF 80 MM DIA. PVC PIPE
PROTECTION : USE 1200AT/2000AF. 3P, 240V CIRCUIT BREAKER

SIZE OF TRANSFORMER:
KVA = VOLTS x AMPERE = 240 x 993.18
1000 1000

KVA = 238.36

PROVIDE : 3 UNITS 100 KVA FOR SUBSTATION NO. 1


DISTRIBUTION PANEL NO.2 (DP-2)
CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
2
1 PANEL “PPD” 67.35 230 211.3 300 3P 150 MM THW 65 MM DIA.PVC
2 PANEL “PPE” 115.83 230 363.5 500 3P 2 SETS OF 3-125 MM2 THW 2 SETS OF 65 MM
DIA.PVC
3 PANEL “PPF” 188.7 230 440.2 600 3P 2 SETS OF 3-200 MM2 THW 2 SETS OF 80 MM
DIA.PVC
4 PANEL “PPG” 110.8 230 347.5 500 3P 2 SETS OF 3-125 MM2 THW 2 SETS OF 65 MM
DIA.PVC
5 PANEL “PPH” 139 230 376.9 500 3P 2 SETS OF 3-125 MM2 THW 2 SETS OF 65 MM
DIA.PVC
6 PANEL “PPI” 93.54 230 264.8 400 3P 200 MM2 THW 80 MM DIA.PVC
TOTAL 715.22 2004.2

COMPUTATION:
IT = [2004.2 + (0.25 x 440.2)] x 0.80 D.F.
= 1,691.4 AMPERES
SIZE OF WIRE : 4 SETS OF 3-250 MM2 THW CU. WIRE
SIZE OF CONDUIT : 4 SETS OF 80 MM DIA. PVC PIPE
PROTECTION : USE 1800 AT/2000AF. 3P, 240V CIRCUIT BREAKER

SIZE OF TRANSFORMER:
KVA = VOLTS x AMPERE = 240 x 1691.4
1000 1000

KVA = 405.94

PROVIDE : 3 UNITS 167 KVA SINGLE PHASE, 24KV/240V TRANSFORMER


FOR SUBSTATION NO. 2
OPTION NO.2

SCHEDULE OF LOADS, MAIN DISTRIBUTION PANEL (MDP)


CKT AMPERES PROTECTION
NO. LOAD DESCRIPTION QTY KW VOLTS AB BC CA I 3P AT POLE SIZE OF WIRE SIZE OF CONDUIT
1 DISTRIBUTION PANEL NO.1 341.25 230 181.33 179.85 179.9 836.1 1000 3P 3 SETS OF 3-200 3 SETS OF 80 MM
MM2 THW DIA.PVC
2 DISTRIBUTION PANEL NO.2 715.22 230 2004.2 1800 3P 5 SETS OF 3-250 5 SETS OF 80 MM
MM2 THW DIA.PVC
TOTAL 1056.47 181.33 179.85 179.9 2840.3
COMPUTATION:
IT = {1.732(181.33) +2840.3 + (0.25 x 2004.2)] x 0.80 D.F.
= 2,924.34
SIZE OF WIRE : 5 SETS OF 3-500 MM2 THW CU. WIRE
SIZE OF CONDUIT 5 SETS OF 125 MM DIA. PVC PIPE
PROTECTION : USE 3000AT/4000AF. 3P, 240V AIR CIRCUIT BREAKER

SIZE OF TRANSFORMER:
KVA = VOLTS x AMPERE = 240 x 2924.34
1000 1000

KVA = 701.84

PROVIDE : 750 KVA PAD MOUNTED, 3PHASE, 24KV/240V TRANSFORMER OR


3 UNITS 250 KVA SINGLE PHASE, 24KV/240V TANSFORMER