BATTERY RUN TIME CALCULATION EATON 93PR 100kW

UPS: 100kVA/100kWatt Power Factor (PF): 1.0


Load: 70A (50kVA@50%) Cut off voltage: 1.7V/cell
No. of Battery: 40 units external No. of Cell: 6 Cells (1 Cell per 2V)
Efficiency UPS: 96% No. of String/Bank: 1 Bank

𝑊𝑎𝑡𝑡 𝑈𝑃𝑆 (𝑉𝐴) 𝑥 𝐿𝑜𝑎𝑑 (%) 𝑥 𝑃𝐹


=
𝐶𝑒𝑙𝑙 𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 𝑥 𝑁𝑜. 𝑂𝑓 𝐵𝑎𝑡𝑡𝑒𝑟𝑦 𝑥 𝑁𝑜. 𝑂𝑓 𝐶𝑒𝑙𝑙 𝑥 𝑆𝑡𝑟𝑖𝑛𝑔

𝑊𝑎𝑡𝑡 100,000 𝑉𝐴 𝑥 50% 𝑥 1.0


=
𝐶𝑒𝑙𝑙 96% 𝑥 40 𝑥 6 𝑥 1

𝑊𝑎𝑡𝑡
= 217
𝐶𝑒𝑙𝑙

Refer to discharge table of 12V 120AH battery:

At cut off voltage of 1.7 V per cell, UPS EATON 93PR 100kVA using 40 units External Battery of 12V
120AH with 50kVA loads could get backup time approximately at: 30 MINUTES

*Values are in theory calculation only. Real values might change based on temperature, UPS efficiency, load percentage,
and mains power factor.