BATTERY CALCULATION FOR ONE UPS

50KVA ABB UPS SYSTEM WITH 60 MNTS BACKUP @ 50KVA LOAD

Output apparent power (VA) 50,000 A

Output power factor 0.8 B

Inverter efficiency (%) 95.5 C

DC power (W) 41,884.8 D A*B*100/C

Number of batteries 50 E from UPS spec.

Number of cells per battery 6 F from UPS spec.

Total cell number 300 G E*F

Requested autonomy time (min) 15 H

Battery type VRLA I

Float voltage (V/cell) 2.25 J

EOD (V/cell) 1.65 K depend from I and J

Average cell voltage (V/cell) 1.95 L (J+K)/2

Number of battery strings 1 M

Discharge power per battery (W) 837.70 N D/E/M

Discharge power per battery cell (W) 139.62 O D/G/M

Average discharge current (A) 71.60 P D/G/M/L

Given Batteries
50x12V-120AH

Required Watt Given Watt


837.70 880.0