Project name: Dương (H5)


Battery Calculation Customer:
UPS Model: R2K

UPS specification
Battery Diagram
UPS model R2K Delta
Output Capacity 2 kVA
Output Power Factor 0.9
Output Power 1.8 kW
UPS1
Real load 1.8 kW
Back-up time requitement 240 min
Battery system voltage 48 V
Battery Series Number 4 NOS
Battery mode efficiency Load
25% 90 %
50% 90 % 4 NOS
75% 90 %
100% 90 %
Minimum cell Voltage 1.75 V
Minimum Battery LVD 42 V

Batttery Output Power Load


25% 0.5 kW
50% 1.0 kW
75% 1.5 kW 2 String
100% 2.0 kW

1. Determine Battery Watt per Block and Watt per Cell


Battery Watt per Block > 500 w/block at at 1.75 V
Battery Watt per Cell > 84 w/cell at at 1.75 V

2. Select battery LONG 2 strings where w/cell shall be> 42 w/cell

Choose Watt per cell = 37.3 at 300 mins

3. Design Re-check
Back-up time support at 1.8 kW = 266.4 min Design Margin = 11%
Maximum Discharge current 24 A or 12 A per string 0.06 C max discharge

4. Design summary
Battery Brand LONG
Total Battery Quantity 8 blocks ắc quy 100AH 31.3 KG
Back-up time at full load 266.4 min
Total Weight 250.4 kg
Recommended Fuses A x pcs
Recommended ISO SW 63 A x 1 pcs