You are on page 1of 25

SIEMENS

CONTENTS

Page No.

1 INTRODUCTION 3

2 DESIGN CRITERIA FOR BATTERY SIZING 3

3 CALCULATION FOR NUMBER OF CELLS 4

4 DESIGN CRITERIA FOR BATTERY CHARGER SIZING 5

5 REFERENCES 5

6 ASSUMPTIONS 5

7 CALCULATION 5-13

i 220V DC LOAD DETAILS 6-8


ii LOAD SUMMARY 9
iii LOAD CYCLE TABLE & GRAPH 10
iv AH SIZING CALCULATION OF BATTERY & BATTERY CHARGER 11-12

8 RESULT 12

9 ANNEXURES:-

i 66 kV & 220 kV C&R PANEL LOAD 13

ii SAS PANEL LOAD 14

iii PER BAY LCC LOAD 15

iv CATALOGUE - VALVE REGULATED LEAD ACID BATTERY 16-37


SIEMENS
1 INTRODUCTION:
DC Power Supply is the most reliable source of power supply for control, prote
-ction interlock & annunciation requirements both during the AC power failure
and in normal operating conditions. In other words, it is "back bone" of the sub-station.

This document is intended to size the 220V valve regulated lead acid type battery &
battery charger requirement for the 220 kV Main & 66 kV substation at BIPL.
The battery is sized in accordance with the IEEE 485-1997.

220V DC Power supply will consist of two number 100% rated battery along with two
number of 100% rated float cum boost charger to charge above battery.

2 DESIGN CRITERIA FOR BATTERY SIZING:


The discharge capacity of the battery shall be sufficient to supply loads during a
discharge time of 3 hour.
The battery shall be capable of following conditions:
i Simultaneous tripping of all 220kV or 66 kV breakers during the busbar fault at the
begininning of the cycle. Tripping load is considered for one minute.

ii Supplying of normal standing load (DC Continuous load) for the full discharge period

iii Supplying emergency lighting load for a period of 1 hour.

iv Supplying load for sequential closing of breakers (one breaker at a time) at the end of
load cycle. This load is considered for complete one minute duration.

v Accordingly, the load cycle is divided in four section:


The section, corresponding time & considered load are as per following

Section Number Time Period Load Considered

Section - 1 0 - 1 min. Momentary Tripping load + Continuous load

Section - 2 1 - 60 min. Continuous load + Emergency loads


Section - 3 60 - 179 min. Continuous load

Section - 4 179 - 180 min Momentary Closing Load + Continuous load

vi The end cell voltage (ECV) has been considered as 1.85 Volts / cell.

vii Design Margin Considered 20% as per TQ

viii Standard electrolyte temperature considered for battery = 27 deg. C

ix The calculation is performed based on published data for HBL Valve Regulated Lead
Acid Battery.

x Aging Factor considered 1.25 as per IEE-485, Cl. No. 6.2.3.

On the final calculated Ampere Hour Capacity & the next higher battery size available
from the selected vendor list is selected.
SIEMENS
3 CALCULATION FOR NUMBER OF CELLS

Nominal Voltage of the system = 220 V

Maximum Allowable system voltage percentage = +10 %

Maximum allowable system voltage = 242 V

Minimum allowable system voltage = -10 %

Minimum allowable system voltage = 198 V

End cell voltage = 1.85 V

Float charging voltage = 2.25 V

Maximum allowable system voltage


No. of cells (Cell) required =
cell voltage required for float charging

= 242 / 2.25
= 107.56

Minimum No. of cells required = 108

No. of cells selected = 108

Minimum battery voltage at the end of load cycle = No. of cells x End cell Voltage

= 108 x 1.85
= 199.8 V
Which is higher than minimum allowable system voltage

Hence, the number of cells selected as 108 is justified.


SIEMENS
4 DESIGN CRITERIA FOR BATTERY CHARGER SIZING

The battery charger is sized based on one number of applications envisaged.

i Under normal float charge conditions (with AC supply available), the battery
charger will cater to the continuous load of the DC system plus trickle charging
of the battery.

ii The batteries may require boost charging from time to time, dependending
upon service conditions & other external forces. Under boost charge condition
the charger shall be capable of supplying full boost charge requirement, taking
care not to exceed the maximum permissible battery voltage & simultaneously
cater to the continuous load requirement of the DC system.

The higher of the two ratings (float charging condition & boost charging cond
-ition calculated as above) will be considered for rating the charger

5 REFERENCES
1. Specification (HC16079000-CV03-00-ACA-140001 Subsection: D8)
2. IEEE 485-1997
3. Protection SLD for 220 kV Main Station (G71770-90949-S152) & 66 kV Station
(G71770-90949-S153)
4. Load list of CRP, SAS & LCC Panels.
5. Battery Catalogue

6 ASSUMPTIONS

i The calculation is performed based on published data of HBL Nife/Eq. battery


(as per approved make) "Valve Regulated Lead Acid type".

ii Total Emergency lighting load considered 1500 W as per TQ point no. 9.3. 25 nos. of
60 W DC GLS lamps (NXC101 / BJDB100BC or equivalent) considered for
DC emergency lights and located at staircase, passgae and exit locations. 1

iii DC Load details are considered based on our standard 220kV GIS product (8DN9) &
66 kV GIS product (8DN8), CRP & SAS

iv DC Load details of Trafo. RTCC & marshalling Box are considered as per
V manufacturer.

7 SIZING CALCULATIONS

i 220V DC Load details

ii Load summary

iii Load cycle table & Graph

iv AH Sizing calculation of Battery & Battery Charger

8 RESULTS
SIEMENS
220V DC LOAD DETAILS_220 kV Main Station

CONSIDERED LOAD OF 220kV SYSTEM

Momentary Tripping Emergency Continuous Momentary


Unit Load Total Load
No. of Load (A) Loads (A) Loads (A) Closing Load (A)
Sl. No. Description Duty Cycle Remarks
Feeders
(VA) (VA) 0 - 1 min. 1 - 60 min. 60 - 179 min 179 - 180 min.

(VA1) (VA=VA1*Q) (A=VA/220) (A=VA/220) (A=VA/220) (A=VA/220)

Protective relay for Incoming


1 cont. 2 95 190 0.86 0.86 0.86 0.86
feeder bay

Protective relay for Outgoing


2 cont. 3 102 306 1.39 1.39 1.39 1.39
feeder bay including future bays

3 Protective relay for Bus PT cont. 0 0 0 0.00 0.00 0.00 0.00 Annexure -I

Protective relay for Bus Coupler


4 cont. 1 72 72 0.33 0.33 0.33 0.33
bay
Protective relay for Busbar (Main
5 cont. 1 112 112 0.51 0.51 0.51 0.51
& Backup)
Considered one of the maximum Intermittent
load for 220kV & 66kV System.
Intermittent relay loads for all
6 0 - 1 min. 225 0.00 0.00 0.00 0.00 Hence, for 66kV is the maximum intermittent
bays
load so that we have to considered the same
in the load cycle.

Load for Tripping coil-1


7 0 - 1 min. 6 675 4050 0.00 0.00 0.00 0.00
(Normal release) Considered one of the maximum tripping load
for 220kV & 66kV System. Hence, for 66kV is
the maximum momentary tripping load, so
that we have to considered the same in the
Load for Tripping coil-2 load cycle.
8 0 - 1 min. 6 675 4050 0.00 0.00 0.00 0.00
(Normal release)

9 Closing coil load 179 - 180 min. 1 675 675 0.00 0.00 0.00 0.00
Considered one of the maximum closing load
& spring charging load for 220kV & 66kV
System. Hence, for 66kV is the maximum
momentary closing load, so that we have to
considered the same in the load cycle.
10 Spring charging 179 - 180 min. 1 1980 1980 0.00 0.00 0.00 0.00

Sub-Total = 3.09 3.09 3.09 3.09


SIEMENS
220V DC LOAD DETAILS_220 kV Main Station

CONSIDERED LOAD OF 66 kV SYSTEM

Momentary Tripping Emergency Continuous Momentary


Unit Load Total Load
No. of Load (A) Loads (A) Loads (A) Closing Load (A)
Sl. No. Description Duty Cycle Remarks
Feeders
(VA) (VA) 0 - 1 min. 1 - 60 min. 60 - 179 min 179 - 180 min.

(VA1) (VA=VA1*Q) (A=VA/220) (A=VA/220) (A=VA/220) (A=VA/220)

Protective relay for incomer


1 cont. 3 49 147 0.67 0.67 0.67 0.67
feeder including future bays

Protective relay for outgoing


2 cont. 9 64 576 2.62 2.62 2.62 2.62
feeder including future bays

Protective relay for Bus Coupler Annexure -I


3 cont. 2 44 88 0.40 0.40 0.40 0.40
bay

Protective relay for Busbar (Main


4 cont. 2 104 208 0.95 0.95 0.95 0.95
& Backup)

5 Protective relay for future Bus PT cont. 2 9 18 0.08 0.08 0.08 0.08

Intermittent relay loads for all Considered maximum intermittent relays load
6 0 - 1 min. 225 1.02 0.00 0.00 0.00
bays for operation of the busbar protection.

Considered the maximum no. of breaker that


Load for Tripping coil-1 will operate for busbar protection.
7 0 - 1 min. 14 675 9450 42.95 0.00 0.00 0.00
(Normal release) (Per trip coil consumption is 225W, i.e. per
bay 3no. (therefore, 3x225 = 675 W).

Considered the maximum no. of breaker that


Load for Tripping coil-2 will operate for busbar protection.
8 0 - 1 min. 14 675 9450 42.95 0.00 0.00 0.00
(Normal release) (Per trip coil consumption is 225W, i.e. per
bay 3no. (therefore, 3x225 = 675 W).

Considered 1 no. of breaker that will operate


for restoration.
9 Closing coil load 179 - 180 min. 1 675 675 0.00 0.00 0.00 3.07
(Per Closing coil consumption is 225W, i.e. per
bay 3no. (therefore, 3x225 = 675 W).
Considered the 1 no. of breaker will operate at
one time.
10 Spring charging 179 - 180 min. 1 1980 1980 0.00 0.00 0.00 9.00
(Per Spring coil consumption is 660W, i.e. per
bay 3no. (therefore, 3x660 = 1980 W).
Sub-Total = 91.65 4.71 4.71 16.78
SIEMENS
220V DC LOAD DETAILS_220 kV Main Station

CONSIDERED MISCELLANEOUS LOAD

Momentary Tripping Emergency Continuous Momentary


Unit Load Total Load
No. of Load (A) Loads (A) Loads (A) Closing Load (A)
Sl. No. Description Duty Cycle Remarks
Feeders
(VA) (VA) 0 - 1 min. 1 - 60 min. 60 - 179 min 179 - 180 min.

(VA1) (VA=VA1*Q) (A=VA/220) (A=VA/220) (A=VA/220) (A=VA/220)

1 Load of 220kV & 66 kV LCC Panel cont. 1388.5 1389 6.31 6.31 6.31 6.31 Annexure - II & III

2 Misc. Load of aux. system cont. 75 75 0.34 0.34 0.34 0.34 DC lamps, aux contectors, relays etc.

3 RTCC Panel load including future cont. 3 75 225 1.02 1.02 1.02 1.02 Assumed

Emergency lighting for control Considered emergency lighting load for 1 Hour
4 cont. 1500 6.82 6.82 0.00 0.00
room building for 1500 W DC lights.

Load for 415V AC LT Switchgear


5 & DC Indication Lamp of Battery cont. 200 0.91 0.91 0.91 0.91 Assumed
Charger

SAS System Loads


(i.e. Ethernet switches, GPS, DC
6 cont. 1 500 500 2.27 2.27 2.27 2.27 Annexure - I
panel load, data concentrator
etc.)

7 NIFPS System for Transformer cont. 3 200 600 2.73 2.73 2.73 2.73
1

Sub-Total = 20.40 20.40 13.58 13.58


SIEMENS
LOAD SUMMARY

Load Duration
Sl. No. Description
0 - 1 min. 1 - 60 min. 60 - 179 min 179 - 180 min.

1 CONSIDERED LOAD OF 220kV SYSTEM 3.09 3.09 3.09 3.09

2 CONSIDERED LOAD OF 66 kV SYSTEM 91.65 4.71 4.71 16.78

3 CONSIDERED MISCELLANEOUS LOAD 20.40 20.40 13.58 13.58

TOTAL LOAD 115.14 A 28.21 A 21.39 A 33.46 A

CONSIDERING 90% OF THE NOMINAL CELL VOLTAGE 115.14/0.9 28.21/0.9 21.39/0.9 33.46/0.9

127.93 A 31.34 A 23.77 A 37.17 A


SIEMENS
LOAD CYCLE TABLE & GRAPH

Load Cycle Table

Duration Load Description Load (A)


1 min Momentary Tripping load + Continuous load + Emergency load 127.93 A
59 min Continuous load + Emergency load 31.34 A
179 min Continuous load 23.77 A
1 min Momentary Closing Load + Continuous load 37.17 A

Load Cycle

130

120

110

100

90

80
LOAD
(A) 70

60

50

40

30

20

10

0
0 60 120 180

TIME (M)
SIEMENS
AH SIZING CALCULATION OF 220V BATTERY & BATTERY CHARGER

CELL SIZING CALCULATION

1. NOMINAL SYSTEM VOLTAGE (VN) = 220 Volts

2. HIGHEST SYSTEM VOLTAGE (VH) = 242 Volts

3. LOWEST SYSTEM VOLTAGE AT END OF DUTY CYCLE (VL) = 198 Volts

4. END CELL VOLTAGE = 1.85 Volts

5. NO. OF CELLS = 108 Nos

CAPACITY REQUIRED SECTION


DURATION RATING SIZE (AH)
PERIOD LOAD (A) CHANGE IN TIME TO END OF
OF PERIOD FACTOR AT T
(1) (A1) LOAD (A) SECTION POSITIVE NEGATIVE
(Mins) Min Rate (Kt)
VALUE VALUE
SECTION-1- FIRST PERIOD ONLY
1 A1=127.93 A1-0 =127.93 M1= 1 T=M1=1 0.5 63.97 -
TOTAL 63.97
SECTION-2- FIRST TWO PERIOD ONLY
1 A1=127.93 A1-0 =127.93 M1= 1 T=M1+M2=60 1.880 240.51 -
A2-A1=
2 A2=31.34 M2= 59 T=M2=59 1.849 -178.56
-96.59
TOTAL 61.95
SECTION-3- FIRST THREE PERIOD ONLY
1 A1=127.93 A1-0 =127.93 M1= 1 T=M1+M2+M3=179 4.077 521.61
A2-A1=
2 A2=31.34 M2= 59 T=M2+M3=178 4.054 -391.62
-96.59
A3-A2=
3 A3=23.77 M3= 119 T=M3=119 3.044 -23.06
-7.58
TOTAL 106.92
SECTION-4- FIRST FOUR PERIOD ONLY
1 A1=127.93 A1-0 =127.93 M1= 1 T=M1+M2+M3+M4=180 4.100 524.52
A2-A1=
2 A2=31.34 M2= 59 T=M2+M3+M4=179 4.077 -393.82
-96.59
A3-A2=
3 A3=23.77 M3= 119 T=M3+M4=120 3.070 -23.26
-7.58
A4-A3=
4 A4=37.17 M4= 1 T=M4=1 0.500 6.70
13.41
TOTAL 114.14

Maximum section size = 114.14 AH

Required Size = Maximum section Size x Design margin x Temperature correction


factor x Aging factor
= 114.14 x 1.2 x 1.14 x 1.25

Battery Size Calculated = 195.18 Ah

Nearest standard rating = 200 Ah

Battery Size Chosen & Model = T-200 HP (200 AH)


SIEMENS

FLOAT CUM BOOST CHARGER SIZING CALCULATION

A) ON LINE FLOAT CHARGER RATING


Float Charger Rating = 1.2 x Average DC Load
Average DC Load = Area of Load Cycle / Time of Load Cycle
= 34.823 Amps
Float Charger rating calculated = 42 Amps (Considered design margin 20%)
Float Charger rating chosen = 45 Amps

B) OFF LINE BOOST CHARGER RATING


Boost Charger Rating (As per HBL Power System) = (14% of Ah Rating of Bat. + Cont. Current)
= (0.14 x 200) + 23.77
Boost Charger rating calculated = 62.12 Amps (Considered design margin 20%)

Boost Charger rating chosen = 65 Amps

Charger Rating Chosen = 45 / 65 Amp. at 220V DC

RESULT

Voltage level = 220V DC (± 10%)

No. of Battery Cells = 108 Nos.

AH Capacity = T-200 HP (200 AH)

Float cum Boost Charger rating = 45 / 65 Amp

Charger Rating Selected = 65 Amp


Value of "Kt"
For 60th Minute = 1.88
For 1 Minute = 1.88/60 = 0.03

For 59th Min = 1.88 - 0.03


For 59th Min = 1.849

For 120th Minute = 3.07


For 1 Minute = 3.07/120 = 0.03

For 119th Min = 3.07 - 0.03


For 119th Min = 3.044

For 180th Minute = 4.1


For 1 Minute = 4.1/180 = 0.02

For 179th Min = 4.1 - 0.02


For 179th Min = 4.077

For 178th Min = 4.1 - 0.02 - 0.02


For 178th Min = 4.054
ANNEXURE -1

CRP DC LOAD

66 kV Bussection-1 Panel - 1 No.


SL NO. DEVICE Operation Voltage W W Qty Total VA / W Total VA / W
Relays, Aux. Relays, Indication Lamps,
Continuous Intermittent Continuous Intermittent
Transducers, Annunciator, Hooter etc
1 7SJ80 DC 220V 12 1 12 0
2 7SJ85 DC 220V 12 1 12 0
3 RXMS1/RXME1 DC 220V 3.5 1 0 3.5
4 RXMM1/RXSF1 DC 220V 1.1 0 0 0
5 RXMVB4/RXMVB2 DC 220V 3 1 0 3
6 TSR DC 220V 3 5 15 0
7 RXTMA DC 220V 5 1 5 0
8 7PJ11 DC 220V 15 0 0 0
9 RXTCS DC 220V 2.7 0 0 0
10 RXPSU14N/RXPSU6N DC 220V 6 0 0 0
11 7SS525 DC 220V 10 0 0 0
12 ANNUNCIATOR DC 220V 10 0 0 0
Total 44 6.5

66 kV Bussection-2 Panel - 1 No.


SL NO. DEVICE Operation Voltage W W Qty Total VA / W Total VA / W
Relays, Aux. Relays, Indication Lamps,
Transducers, Annunciator, Hooter etc Continuous Intermittent Continuous Intermittent
1 7SJ80 DC 220V 12 1 12 0
2 7SJ85 DC 220V 12 1 12 0
3 RXMS1/RXME1 DC 220V 3.5 1 0 3.5
4 RXMM1/RXSF1 DC 220V 1.1 0 0 0
5 RXMVB4/RXMVB2 DC 220V 3 1 0 3
6 TSR DC 220V 3 5 15 0
7 RXTMA DC 220V 5 1 5 0
8 7PJ11 DC 220V 15 0 0 0
9 RXTCS DC 220V 2.7 0 0 0
10 RXPSU14N/RXPSU6N DC 220V 6 0 0 0
11 7SS525 DC 220V 10 0 0 0
12 ANNUNCIATOR DC 220V 10 0 0 0
Total 44 6.5
66 kV Outgoing Panel - 9 Nos. (6 + 3 Future)
SL NO. DEVICE Operation Voltage W W Qty Total VA / W Total VA / W
Relays, Aux. Relays, Indication Lamps,
Continuous Intermittent Continuous Intermittent
Transducers, Annunciator, Hooter etc
1 7SJ80 DC 220V 12 1 12 0
2 7SD80 DC 220V 12 1 12 0
3 7SJ85 DC 220V 12 1 12 0
4 RXMS1/RXME1 DC 220V 3.5 1 0 3.5
5 RXMM1/RXSF1 DC 220V 1.1 0 0 0
6 RXMVB4/RXMVB2 DC 220V 3 2 0 6
7 TSR DC 220V 3 6 18 0
8 RXTMA DC 220V 5 2 10 0
9 7PJ11 DC 220V 15 0 0 0
10 RXTCS DC 220V 2.7 0 0 0
11 RXPSU14N/RXPSU6N DC 220V 6 0 0 0
12 7SS525 DC 220V 10 0 0 0
13 ANNUNCIATOR DC 220V 10 0 0 0
Total 64 9.5

66 kV Incomer Panel - 3 Nos. (2 + 1 Future)


SL NO. DEVICE Operation Voltage W W Qty Total VA / W Total VA / W
Relays, Aux. Relays, Indication Lamps,
Continuous Intermittent Continuous Intermittent
Transducers, Annunciator, Hooter etc
1 7SJ80 DC 220V 12 1 12 0
2 7SJ85 DC 220V 12 1 12 0
3 RXMS1/RXME1 DC 220V 3.5 1 0 3.5
4 RXMM1/RXSF1 DC 220V 1.1 0 0 0
5 RXMVB4/RXMVB2 DC 220V 3 2 0 6
6 TSR DC 220V 3 5 15 0
7 RXTMA DC 220V 5 2 10 0
8 7PJ11 DC 220V 15 0 0 0
9 RXTCS DC 220V 2.7 0 0 0
10 RXPSU14N/RXPSU6N DC 220V 6 0 0 0
11 7SS525 DC 220V 10 0 0 0
12 ANNUNCIATOR DC 220V 10 0 0 0
Total 49 9.5
66 kV Busbar Panel - 2 Nos.
SL NO. DEVICE Operation Voltage W W Qty Total VA / W Total VA / W
Relays, Aux. Relays, Indication Lamps,
Continuous Intermittent Continuous Intermittent
Transducers, Annunciator, Hooter etc
1 7SS85 DC 220V 48 1 48 0
2 RXMS1/RXME1 DC 220V 3.5 2 0 7
3 RXMM1/RXSF1 DC 220V 1.1 0 0 0
4 RXMVB4/RXMVB2 DC 220V 3 10 0 30
5 TSR DC 220V 3 2 6 0
6 RXTMA DC 220V 5 10 50 0
7 7PJ11 DC 220V 15 0 0 0
8 RXTCS DC 220V 2.7 0 0 0
9 RXPSU14N/RXPSU6N DC 220V 6 0 0 0
10 7SS525 DC 220V 10 0 0 0
11 ANNUNCIATOR DC 220V 10 0 0 0
Total 104 37
220 kV Bus Coupler Panel - 1 No.
SL NO. DEVICE Operation Voltage W W Qty Total VA / W Total VA / W
Relays, Aux. Relays, Indication Lamps,
Continuous Intermittent Continuous Intermittent
Transducers, Annunciator, Hooter etc
1 7SJ80 DC 220V 12 1 12 0
2 6MD85 DC 220V 28 1 28 0
3 RXMS1/RXME1 DC 220V 3.5 1 0 3.5
4 RXMM1/RXSF1 DC 220V 1.1 0 0 0
5 RXMVB4/RXMVB2 DC 220V 3 1 0 3
6 TSR DC 220V 3 9 27 0
7 RXTMA DC 220V 5 1 5 0
8 7PJ11 DC 220V 15 0 0 0
9 RXTCS DC 220V 2.7 0 0 0
10 RXPSU14N/RXPSU6N DC 220V 6 0 0 0
11 7SS525 DC 220V 10 0 0 0
12 ANNUNCIATOR DC 220V 10 0 0 0
Total 72 6.5

220 kV Incomer Panel - 2 Nos.


SL NO. DEVICE Operation Voltage W W Qty Total VA / W Total VA / W
Relays, Aux. Relays, Indication Lamps, Continuous Intermittent Continuous Intermittent
Transducers, Annunciator, Hooter etc
1 7SD61 DC 220V 10 1 10 0
2 7SJ80 DC 220V 12 1 12 0
3 6MD85 DC 220V 33 1 33 0
4 RXMS1/RXME1 DC 220V 3.5 4 0 14
5 RXMM1/RXSF1 DC 220V 1.1 1 0 1.1
6 RXMVB4/RXMVB2 DC 220V 3 2 0 6
7 TSR DC 220V 3 10 30 0
8 RXTMA DC 220V 5 2 10 0
9 7PJ11 DC 220V 15 0 0 0
10 RXTCS DC 220V 2.7 0 0 0
11 RXPSU14N/RXPSU6N DC 220V 6 2 0 12
12 7SS525 DC 220V 10 0 0 0
13 ANNUNCIATOR DC 220V 10 0 0 0
Total 95 33.1
220 kV Transformer Outgoing Panel - 3 Nos. (2 + 1 Future)
SL NO. DEVICE Operation Voltage W W Qty Total VA / W Total VA / W
Relays, Aux. Relays, Indication Lamps,
Transducers, Annunciator, Hooter etc Continuous Intermittent Continuous Intermittent
1 7UT DC 220V 7 1 7 0
2 7SJ80 DC 220V 12 1 12 0
3 6MD85 DC 220V 33 1 33 0
4 7SR24 DC 220V 10 1 10 0
5 RXMS1/RXME1 DC 220V 3.5 1 0 3.5
6 RXMM1/RXSF1 DC 220V 1.1 4 0 4.4
7 RXMVB4/RXMVB2 DC 220V 3 2 0 6
8 TSR DC 220V 3 10 30 0
9 RXTMA DC 220V 5 2 10 0
10 7PJ11 DC 220V 15 0 0 0
11 RXTCS DC 220V 2.7 0 0 0
12 RXPSU14N/RXPSU6N DC 220V 6 2 0 12
13 7SS525 DC 220V 10 0 0 0
14 ANNUNCIATOR DC 220V 10 0 0 0
Total 102 25.9

220 kV Busbar Protection Panel - 1 No. (Main)


SL NO. DEVICE Operation Voltage W W Qty Total VA / W Total VA / W
Relays, Aux. Relays, Indication Lamps,
Transducers, Annunciator, Hooter etc Continuous Intermittent Continuous Intermittent
1 TSR DC 220V 3 2 6 0
4 RXMS1/RXME1 DC 220V 3.5 2 0 7
6 RXMVB4/RXMVB2 DC 220V 3 5 0 15
8 RXTMA DC 220V 5 5 25 0
2 7SS85 DC 220V 28 1 28 0
Total 59 22

220 kV Busbar Protection Panel - 1 No. Backup)


SL NO. DEVICE Operation Voltage W W Qty Total VA / W Total VA / W
Relays, Aux. Relays, Indication Lamps,
Transducers, Annunciator, Hooter etc Continuous Intermittent Continuous Intermittent
1 TSR DC 220V 3 0 0 0
4 RXMS1/RXME1 DC 220V 3.5 0 0 0
6 RXMVB4/RXMVB2 DC 220V 3 5 0 15
8 RXTMA DC 220V 5 5 25 0
2 7SS85 DC 220V 28 1 28 0
Total 53 15
Control & Relay Panel DC Load Details
SL NO. DEVICE Operation Voltage W W Qty Total VA / W Total VA / W
Continuous Intermittent Continuous Intermittent
1 66 kV Bussection-1 Panel - 1 No. DC 220V 44 6.5 1 44 6.5
2 66 kV Bussection-2 Panel - 1 No. DC 220V 44 6.5 1 44 6.5
3 66 kV Outgoing Panel - 9 Nos. (6 + 3 DC 220V 64 9.5 9 576 85.5
Future)
66 kV Incomer Panel - 3 Nos. (2 + 1
4 DC 220V 49 9.5 3 147 28.5
Future)
5 66 kV Busbar Panel - 2 Nos. DC 220V 104 37 2 208 74
Total 1019 201
Considered intermittent load: 225
1 220 kV Bus Coupler Panel - 1 No. DC 220V 72 6.5 1 72 6.5
2 220 kV Incomer Panel - 2 Nos. DC 220V 95 33.1 2 190 66.2
220 kV Transformer Outgoing Panel - 3
3 Nos. (2 + 1 Future) DC 220V 102 25.9 3 306 77.7

220 kV Busbar Protection Panel - 1 No.


4 DC 220V 59 22 1 59 22
(Main)
220 kV Busbar Protection Panel - 1 No.
5 Backup) DC 220V 53 15 1 53 15
Total 680 187.4
Considered intermittent load: 225
SAS System DC Load Details

Power Summated
Consumers Requirement Quantity Base Power Remarks
(W) (W)
Ethernet Switches in SAS Panel 30 2 60
Data Concentrator (AK1703) 40 1 40
GPS 30 1 30
I/O Rack 40 1 40
Ethernet Switches in Other Panels 30 6 180
Others 150
Summation 500
Annexure - 2

220 kV GIS DC LOADs:

Kind of Load
=D01, D02, D04 + 1 No. Future Trafo Bay Quantity Load per Device Sum No. of Bay Total
Circuit breaker Close-Coil (KK1) (Q0) 3 225 675
Circuit breaker Trip-Coil 1 (KK3) (Q0) 3 225 675
Circuit breaker Trip-Coil 2 (KK4) (Q0) 3 225 675
Peak (non Circuit breaker Close-spring charge motor (M1) (Q0) 3 660 1980
permanenet) Disconnector Switch drive motor (M1) (Q1, Q2, Q9)-Gang operated, -1
Load qty per disconnector 3 200 600
Maintenance earth Switch drive motor (M1) (Q51,Q52), -1 qty per
earth switch 2 200 400
High speed earthing switch drive motor (Q8) 1 200 200

=D05 (Line + BBE) Quantity Load per Device Sum No. of Bay Total
Circuit breaker Close-Coil (KK1) (Q0) 3 225 675
Circuit breaker Trip-Coil 1 (KK3) (Q0) 3 225 675
Circuit breaker Trip-Coil 2 (KK4) (Q0) 3 225 675
Peak (non Circuit breaker Close-spring charge motor (M1) (Q0) 3 660 1980
permanenet) Disconnector Switch drive motor (M1) (Q1, Q2, Q9)-Gang operated, -1
Load qty per disconnector 3 200 600
Maintenance earth Switch drive motor (M1) (Q51,Q52,Q15,Q25), -1
qty per earth switch 4 200 800
High speed earthing switch drive motor (Q8) 1 200 200

=D03 (BC + BBM) Quantity Load per Device Sum No. of Bay Total
Circuit breaker Close-Coil (KK1) (Q0) 3 225 675
Circuit breaker Trip-Coil 1 (KK3) (Q0) 3 225 675
Circuit breaker Trip-Coil 2 (KK4) (Q0) 3 225 675
Peak (non Circuit breaker Close-spring charge motor (M1) (Q0) 3 660 1980
permanenet)
Load Disconnector Switch drive motor (M1) (Q1, Q2, Q11, Q12)-Gang
operated, -1 qty per disconnector 4 200 800
Maintenance earth Switch drive motor (M1) (Q51,Q52,Q53,Q54), -1
qty per earth switch 4 200 800
Kind of Load
=D01, D02, D04 + 1 No. Future Trafo Bay Quantity Load per Device Sum No. of Bay Total
Fault Annunciator (H501) 1 12 12
Digital meter (P401) 1 1.5 1.5
Permananat Contactor Relay 3RH (K211, etc.) 10 4 40
Load Position indicator (H0-H52) 7 2.5 17.5
Other devices 1 20 20
Total in Watts 91 4 364

=D05 (Line + BBE) Quantity Load per Device Sum No. of Bay Total
Fault Annunciator (H501) 1 12 12
Digital meter (P401, P405) 2 1.5 3
Permananat Contactor Relay 3RH (K211, etc.) 10 4 40
Load Position indicator (H0-H52) 9 2.5 22.5
Other devices 1 20 20
Total in Watts 97.5 1 97.5

=D03 (BC + BBM) Quantity Load per Device Sum No. of Bay Total
Fault Annunciator (H501) 1 12 12
Digital meter (P401, P415, P425) 3 1.5 4.5
Permananat Contactor Relay 3RH (K211, etc.) 10 4 40
Load Position indicator (H0-H52) 9 2.5 22.5
Other devices 1 20 20
Total in Watts 99 1 99

Total in Watts 560.5


Annexure - 3

66 kV GIS DC LOADs:

Kind of Load
=F01, F02, F03, F04, F06, F07, F08 & F09 (Incomer & Outgoing Feeder) Quantity Load per Device Sum No. of Bay Total
Circuit breaker Close-Coil (KK1) (Q0) 3 225 675
Circuit breaker Trip-Coil 1 (KK3) (Q0) 3 225 675
Peak (non Circuit breaker Trip-Coil 2 (KK4) (Q0) 3 225 675
permanenet) Circuit breaker Close-spring charge motor (M1) (Q0) 3 660 1980
Load High speed earthing switch drive motor (Q8) 1 200 200
3 Position Switch Motor (M1) (QZ1) 1 120 120
3 Position Switch Motor (M1) (QZ9) 1 120 120

=F05 (Bus Sectionliser-1, BBM + BBE) Quantity Load per Device Sum No. of Bay Total
Circuit breaker Close-Coil (KK1) (Q0) 3 225 675
Circuit breaker Trip-Coil 1 (KK3) (Q0) 3 225 675
Peak (non Circuit breaker Trip-Coil 2 (KK4) (Q0) 3 225 675
permanenet) Circuit breaker Close-spring charge motor (M1) (Q0) 3 660 1980
Load WIP Earthing Switch Motor (Q15, Q16) 2 200 400
3 Position Switch Motor (M1) (QZ11, QZ12) 2 120 240
3 Position Switch Motor (M1) (QZ1, QZ2) 2 120 240

=F10 (Bus Sectionliser-2) Quantity Load per Device Sum No. of Bay Total
Circuit breaker Close-Coil (KK1) (Q0) 3 225 675
Peak (non Circuit breaker Trip-Coil 1 (KK3) (Q0) 3 225 675
permanenet) Circuit breaker Trip-Coil 2 (KK4) (Q0) 3 225 675
Load Circuit breaker Close-spring charge motor (M1) (Q0) 3 660 1980
3 Position Switch Motor (M1) (QZ1, QZ2) 2 120 240
Kind of Load
=F01, F02, F03, F04, F06, F07, F08 & F09 (Incomer & Outgoing Feeder) Quantity Load per Device Sum No. of Bay Total
Fault Annunciator (H501) 1 5 5
Digital meter (P401) 1 1.5 1.5
Permananat Contactor Relay 3RH (K211, etc.) 10 4 40
Load Position indicator (H0-H51) 6 2.5 15
Other devices 1 20 20
Total in Watts 81.5 8 652

=F05 (Bus Sectionliser-1, BBM + BBE) Quantity Load per Device Sum No. of Bay Total
Fault Annunciator (H501) 1 5 5
Digital meter (P401, P415, P425) 3 1.5 4.5
Permananat Contactor Relay 3RH (K211, etc.) 10 4 40
Load Position indicator (H0-H51) 11 2.5 27.5
Other devices 1 20 20
Total in Watts 97 1 97

=F10 (Bus Sectionliser-2) Quantity Load per Device Sum No. of Bay Total
Fault Annunciator (H501) 1 5 5
Digital meter (P401) 1 1.5 1.5
Permananat Contactor Relay 3RH (K211, etc.) 10 4 40
Load Position indicator (H0-H51) 5 2.5 12.5
Other devices 1 20 20
Total in Watts 79 1 79

Total in Watts 828