Professional Documents
Culture Documents
ISSN 0941-0643
1 23
Your article is protected by copyright and all
rights are held exclusively by Springer-Verlag
London Ltd., part of Springer Nature. This e-
offprint is for personal use only and shall not
be self-archived in electronic repositories. If
you wish to self-archive your article, please
use the accepted manuscript version for
posting on your own website. You may
further deposit the accepted manuscript
version in any repository, provided it is only
made publicly available 12 months after
official publication or later and provided
acknowledgement is given to the original
source of publication and a link is inserted
to the published article on Springer's
website. The link must be accompanied by
the following text: "The final publication is
available at link.springer.com”.
1 23
Author's personal copy
Neural Computing and Applications
https://doi.org/10.1007/s00521-019-04185-x (0123456789().,-volV)(0123456789().,-volV)
ORIGINAL ARTICLE
Abstract
The protection of mutually coupled series capacitor-compensated (SCC) parallel transmission lines is a more complicated
task than uncompensated lines due to the effect of mutual coupling, inter-circuit faults, and non-linearity of effective
impedance of SCC line. A method that can overcome these issues and still work efficiently is a supervised learning-based
method which is an adaptive technique. Hence, in this work, various supervised learning-based intelligent schemes like
artificial neural network (ANN), support vector machines (SVM), and decision tree (DT) are employed to find a suit-
able method for the protection of series capacitor-compensated lines. Discrete wavelet transform has been used to process
the three-phase current signals of the parallel lines measured at one terminal only. A moving window of 20 samples is
selected, and approximate wavelet coefficient is calculated up to level 1 using DB-4 mother wavelet. The resultant is then
given as input to the intelligent schemes (ANN, SVM, and DT). The proposed intelligent schemes have been tested with
variety of fault conditions such as inter-circuit faults, cross-country faults, transforming faults, single-circuit operation, and
high resistance faults. A large number of fault simulation studies corroborate that DT-based fault classification method is
better than ANN and SVM. The accuracy of faulty phase and ground identification scheme is 100% for all the tested fault
cases. Hence, the proposed supervised learning-based intelligent method can be implemented in real power system network
effectively.
Keywords Artificial neural network Series compensation Mutual coupling Fault phase identification
Fault classification Decision tree Support vector machine
123
Author's personal copy
Neural Computing and Applications
123
Author's personal copy
Neural Computing and Applications
BUS1 BUS2
C1
200km
C2
Source 1 Source 2
400kV 400kV
Load
Load 250MW
100MW
100MVAr
RELAY
Fault
Pre-process the current signal using Obtain the zero sequence current
discrete wavelet transform with DB-4 of both circuits.
Fig. 1 Flow diagram of faulty phase and ground identification and classification scheme
Fig. 1. Different steps involved in design of proposed is not a faulty phase in both cases. Furthermore, if the two
scheme are described hereunder. cases are compared, it can be seen that in case 2 the
magnitude of current of healthy phase A2 is appreciably
2.1 Power system network under study large or almost equal to faulty phase A1 current magnitude.
So in case of parallel series-compensated line, most of the
The power system network under study is shown in Fig. 1 protection schemes based on thresholding fail due to non-
comprising of 400-kV, 50-Hz series-compensated line of linearity of the series-compensated transmission system.
length 200 km. Two capacitors C1 and C2 are placed in the Consequently, feature selection process should be carried
two circuits 1 and 2, respectively, near to relaying point. out carefully to extract all the needed information. Dif-
The degree of compensation is set to 40%. Consider two ferent fault cases are simulated for training and testing of
fault cases: A1G fault in circuit 1 at 1 km with classification scheme.
R = 0.001 X and another A1G fault in circuit 1 at 190 km
with R = 100 X. Figure 2 shows the three-phase currents 2.2 Input feature selection
of the two circuits and three-phase voltages. As it is A1G
fault, the current magnitude of faulty phase A1 after the During fault in any one circuit of the double-circuit SCC
inception of fault should be higher than other phases. But line, the current signals of both the circuits undergo large
due to the effect of mutual coupling, current magnitude of changes. So the current signals of both the circuits are
corresponding A2 phase of circuit 2 is also high although it chosen as input feature to the supervised learning method.
123
Author's personal copy
Neural Computing and Applications
(a) (c)
(b) (d)
Fig. 2 Case 1 During A1G fault at 1 km with R = 0.001 X: a three-phase currents of two circuits and b three-phase voltage signals. Case 2
During A1G fault at 190 km with R = 100 X: c three-phase currents of two circuits and d three-phase voltage signals
Different fault cases have been simulated in series-com- 2.3 Feature extraction using WT
pensated power system network with variation in different
parameters. The three-phase current signals of both the Wavelet transform (WT) has the ability to extract the
circuits are recorded at one end of the line with sampling required information from non-stationary fault signals. WT
frequency of 1 kHz. Different parameters varied in this has been used by many researchers for different protection
work for simulating the training and testing fault data sets tasks in power transmission network [11, 17–19, 21]. The
are shown in Table 1. From these fault cases, features are choice of mother wavelet is based on the studies of dif-
extracted using discrete wavelet transform which is ferent researchers, and mostly, DB wavelet has been opted
described in the next subsection. by them. In this paper, a moving window of 20 samples is
selected and approximate wavelet coefficient up to level 1
using DB-4 is obtained. Standard deviation is then
Fault location (km) 10, 55, 100, 145 and 190 km 50 different locations
Fault inception angle () 0 In between 0 and 360
Fault resistance (X) 0 and 100 0, 20, 40, 60, 80 and 100 X
Fault type LG, LLG, LL, LLLG, inter-circuit faults, LG, LLG, LL, LLLG, inter-circuit faults, multi-location
single-circuit operation faults, transforming faults, single-circuit operation
Circuit 1 and 2 1 and 2
Total cases 1040 27,500
123
Author's personal copy
Neural Computing and Applications
calculated, and then, the window is moved forward to Figure 3a shows the current signal of phase A1 during
create a new window of 20 samples. Standard deviation of A1B1 fault in circuit 1 at 100 km in 40 ms time. Then,
the approximate coefficients of level 1 is calculated which approximate coefficient at level 1 is taken and standard
shows the deviation of signal from its mean value. Standard deviation is calculated for first 20 samples. Window is then
deviation of current signals is calculated in time domain by moved by one sample so the new window is from sample 2
moving the window sample by sample generated and to sample 21, and the same procedure is repeated with the
repeating the above procedure. The signals are processed in generation of each new sample. Figure 3b shows that
time domain because it will be easy to discriminate extracted feature has zero value up to 20 ms time because
between the faulty and healthy phases. With respect to it requires 20 samples to give first standard deviated sam-
time, the standard deviation of each phase current signal of ple. So at 21 ms time there is a processed signal/sample
both the circuits is calculated, and when a fault occurs, the which is obtained from window of 1–20 ms. Figure 3c
input signals will deviate from normal situation. Figure 3 shows that at 22 ms there is another new sample which is
shows the feature extraction process for current signal. obtained from moving window of 2–21 ms. Figure 3d
(a) (f)
(b) (g)
(c) (h)
(d) (i)
(e) (j)
Fig. 3 a–j Feature extraction using discrete wavelet transforms from instantaneous current signal Ia1 at 100 km during A1B1 fault at 40 ms time
123
Author's personal copy
Neural Computing and Applications
(a)
(b)
Fig. 4 a Phase current signals and b wavelet-processed current signals at 10 km during A1B1G fault at 60 ms time
shows that at 23 ms there is a third sample which is phase identification and zero sequence components for
obtained from moving window of 3–22 samples. Similarly, ground identification. But, the design process of all the
wavelet-processed signals are generated and stored up to methods is different from each other. Different steps
40 ms time. Figure 3e shows that at 41 ms there is a new involved in designing or the application of these methods for
sample which is obtained from moving window of faulty phase and ground identification are described below.
21–40 ms. Figure 3f–i shows that at 42 ms, 43 ms, 44 ms,
45 ms there are new samples which are obtained from 2.4.1 Construction of decision tree
22–41-ms, 23–42-ms, 24–43-ms, 25–44-ms moving win-
dows, respectively. Figure 3j shows the extracted features A decision tree is a flowchart-like tree structure which learns
of current signals of phase A1 up to 100 ms time. from class-labeled training samples where each internal node
Further, Fig. 4a shows the instantaneous three-phase denotes a test on an attribute, each branch represents an
current signals of both circuits during A1B1G fault at 10 km outcome of the test, and each leaf node holds a class label
in 60 ms time. During A1B1G fault, the current magnitudes [22]. For a given sample in which the associated class label is
of A1 and B1 phases of circuit 1 are much higher than other unknown, the attribute values of the sample are tested against
phases. Current magnitudes of A2 and B2 phases of circuit 2 the decision tree. Class of the test sample is decided by
are also greater than normal situation due to the effect of tracing a path from the root to a leaf node. For construction of
mutual coupling between phases. Moreover, phase C1 and decision tree, attribute selection measures have been used to
C2 currents do not change because they are not involved in select the attribute that best partitions the samples into dis-
fault loop. Figure 4b shows the discrete wavelet transform- tinct classes. In this work, Gini index is used for splitting
processed current signals of both circuits. criteria. Let D be the data partition of training set of class-
labeled samples. Suppose the class label attribute has m
2.4 Design of different training modules distinct values defining m distinct classes, Ci (for
for faulty phase and ground identification i = 1,…,m). Let Ci,D be the set of samples of class Ci in D.
Gini index measures the impurity of D given in (1)
In this paper, fault phase and ground identification has been X m
presented using ANN, SVM, and DT as depicted in Fig. 1. Gini(DÞ ¼ 1 p2i ð1Þ
All the three methods are supervised learning methods, i.e., i¼1
they go through training phase in the presence of known where pi is the probability of a sample in D belonged to
targets. During training phase, all the three methods employ C
class Ci and is estimated by Di;D . The sum is computed over
the wavelet-processed current signals as input for faulty
123
Author's personal copy
Neural Computing and Applications
m classes. The Gini index considers a binary split for each of tree contain variables x1 and x2 which represent zero
attribute. The reduction in impurity that would be incurred sequence currents of circuit 1 and circuit 2, respectively.
by a binary split on a discrete or continuous-valued attri- DT module compares these values with certain thresholds
bute A is given in (2). The attribute that maximizes the considering all attributes and decides the class labels
reduction in impurity is selected as the splitting attribute. accordingly.
DGini(AÞ ¼ Gini(DÞ GiniAðDÞ ð2Þ
2.4.2 Construction of SVM
In decision tree algorithm, tree pruning is used to identify
and remove noise or outliers in the training data for Support vector machine is a supervised learning method
improving the classification accuracy of test data. These that is used to analyze data and recognize patterns [23].
methods use statistical measures to remove the least reli- SVM constructs a hyperplane that has the largest distance
able branches. The decision tree network takes wavelet- to the nearest training data point of any class. The hyper-
processed current samples of different fault cases as input planes in the higher-dimensional space are defined as the
and the corresponding target label. Target labels used for set of points whose dot product with a vector in that space
different faulty phases and ground identifications are is constant. The vectors defining the hyper planes can be
shown in Table 2. After training the DT module, the per- chosen to be linear combinations with parameters ai of
formance is investigated for unseen fault patterns and is feature vectors. The points X in the feature space that are
illustrated in Table 3. Training accuracy is checked by mapped into the hyper plane are defined by Eq. (3)
determining the re-substitution errors. Optimal tree for X
ai kðXi ; X Þ ¼ Constant ð3Þ
phase and ground identification after tree pruning is
i
obtained based on testing accuracy. Optimal decision tree
obtained after training for ground identification module is SVM hyperplane is shown in Fig. 6 which can be
shown in Fig. 5. described by Eqs. (4) and (5). The distance between these
Figure 5 shows that leaf nodes contain classes: NG (in two hyperplanes is found to be kW2 k; therefore, kW k should
numerical ‘1’), G1 (in numerical ‘2’), G2 (in numerical be minimized to obtain better results.
‘3’), and G12 (in numerical ‘4’) which represent ground is
W Xþb¼1 ð4Þ
not involved, circuit 1 is grounded, circuit 2 is grounded,
and both circuits are grounded, respectively. Internal nodes W X þ b ¼ 1 ð5Þ
Table 2 Fault type and the target outputs/labels for DT and SVM networks
Fault type Phase identification target Ground identification target Fault type Phase identification target Ground identification target
output output output output
No fault 1 1 A2B2 12 1
A1G 2 2 B2C2 13 1
B1G 3 2 C2A2 14 1
C1G 4 2 A2B2C2G 15 2
A1B1G 5 2 A1B2G 16 4
B1C1G 6 2 A1C2G 17 4
C1A1G 7 2 B1A2G 18 4
A1B1 5 1 B1C2G 19 4
B1C1 6 1 C1A2G 20 4
C1A1 7 1 C1B2G 21 4
A1B1C1G 8 2 A1B2 16 1
A2G 9 3 A1C2 17 1
B2G 10 3 B1A2 18 1
C2G 11 3 B1C2 19 1
A2B2G 12 3 C1A2 20 1
B2C2G 13 3 C1B2 21 1
C2A2G 14 3 – – –
123
Author's personal copy
Neural Computing and Applications
G12 G2 G1 G12
123
Author's personal copy
Neural Computing and Applications
123
Author's personal copy
Neural Computing and Applications
Fig. 7 During A1G fault at 125 km in 40 ms, with R = 0.001 X. identification output of DT module. e Faulty phase identification
a Three-phase currents of circuit 1. b Three-phase currents of circuit output of SVM module. f Ground identification output of SVM
2. c Faulty phase identification output of DT module. d Ground module
Fig. 8 a–h Faulty phase and ground identification outputs of ANN module during A1G fault at 125 km in 40 ms, R = 0.001 X
123
Author's personal copy
Neural Computing and Applications
A1G 1 2 2 2 2 1 0 0 0 0 0 1 0
B2G 21 10 3 10 3 1 0 0 0 0 0 0 1
C1G 41 4 2 4 2 0 0 1 0 0 0 1 0
A2B2 61 12 1 12 1 0 0 0 1 1 0 0 0
B1C1 81 6 1 6 1 0 1 1 0 0 0 0 0
C2A2 101 14 1 14 1 0 0 0 1 0 1 0 0
A1B1G 121 5 2 5 2 1 1 0 0 0 0 1 0
B2C2G 141 13 3 13 3 0 0 0 0 1 1 0 1
C1A1G 161 7 2 7 2 1 0 1 0 0 0 1 0
A2B2C 181 15 1 15 1 0 0 0 1 1 1 0 0
A1B1C 199 8 1 8 1 1 1 1 0 0 0 0 0
phase identification time is within 10 ms time for all the time, phases A1 and B2 and grounds G1 and G2 start
tested fault cases. increasing to ‘1,’ proving that there is fault in A1 and B2
phases involving ground. Both G1 and G2 become ‘1’
3.2 Effect of inter-circuit faults which indicates both circuit 1 and circuit 2 are grounded.
All other phase outputs remain ‘0.’ Similarly different fault
Inter-circuit faults are those faults which involve phases of cases are tested using DT and SVM module. Some of test
both circuits. Inter-circuit faults are two types: earthed and results of faulty phase and ground identification using all
unearthed inter-circuit faults [3]. ANN-based faulty phase the three methods during inter-circuit faults are shown in
and ground identification outputs are shown in Fig. 9a–h Table 5. From test results, it can be observed that all the
during A1B2G inter-circuit fault at 55 km in 40 ms time. three schemes are able to correctly identify the inter-circuit
From Fig. 9a, d, f, h it can be observed that after 40 ms faults.
Fig. 9 a–h Fault phase identification and ground identification outputs of ANN module during A1B2G inter-circuit fault at 55 km in 40 ms time
123
Author's personal copy
Neural Computing and Applications
A1B2 5 16 1 16 1 1 0 0 0 1 0 0 0
A1C2 15 17 1 17 1 1 0 0 0 0 1 0 0
B1A2 35 18 1 18 1 0 1 0 1 0 0 0 0
B1C2 55 19 1 19 1 0 1 0 0 0 1 0 0
C1A2 75 20 1 20 1 0 0 1 1 0 0 0 0
C1B2 95 21 1 21 1 0 0 1 0 1 0 0 0
A1B2G 115 16 3 16 3 1 0 0 0 1 0 1 1
A1C2G 135 17 3 17 3 1 0 0 0 0 1 1 1
B1A2G 155 18 3 18 3 0 1 0 1 0 0 1 1
B1C2G 175 19 3 19 3 0 1 0 0 0 1 1 1
C1A2G 185 20 3 20 3 0 0 1 1 0 0 1 1
C1B2G 195 21 3 21 3 0 0 1 0 1 0 1 1
3.3 Performance during single-circuit operation DT-based phase identification module which becomes ‘5’
after 49 ms time, exemplifying that there is A1 and B1
Double-circuit transmission lines are sometimes operated phase fault. Figure 10d shows the output of DT-based
as single circuit due to disconnection of one circuit when ground identification module which becomes ‘2’ after
there is fault in that circuit. In this situation, if a fault 49 ms time, confirming that there is ground fault in circuit
occurs in the operated circuit, it should be detected. Dif- 1. Some of the test results of single-circuit operation are
ferent fault cases have been studied during single-circuit also shown in Table 6.
operation using all the three supervised learning tech-
niques. Figure 10 shows the inputs and outputs of DT 3.4 Performance during multi-location fault
module during A1B1G fault at 171 km at 40 ms time with
circuit 2 open. Figure 10a shows the three-phase currents Multi-location faults are those faults which occur at two
of circuit 1 during fault at 40 ms time. Figure 10b shows different locations at the same or different time. Multi-
the three-phase currents of circuit 2 which is nearly zero location faults are also called as cross-country faults by
because circuit 2 is open. Figure 10c shows the output of some researchers. Different multi-location fault cases are
Fig. 10 During A1B1G fault at 55 km in 40 ms time with circuit 2 open. a Three-phase currents of circuit 1. b Three-phase currents of circuit 2.
c Faulty phase identification output of DT module. d Ground identification output of DT module
123
Author's personal copy
Neural Computing and Applications
A1G, 13 km Open 2 2 2 2 1 0 0 0 0 0 1 0
A1B1G, 53 km Open 5 2 5 2 1 1 0 0 0 0 1 0
A1B1, 103 km Open 5 1 5 1 1 1 0 0 0 0 0 0
A1B1C1, 153 km Open 8 1 8 1 1 1 1 0 0 0 0 0
Open A2G, 17 km 9 3 9 3 0 0 0 1 0 0 0 1
Open A2B2G, 57 km 12 3 12 3 0 0 0 1 1 0 0 1
Open A2B2, 107 km 12 1 12 1 0 0 0 1 1 0 0 0
Open A2B2C2, 157 km 15 1 15 1 0 0 0 1 1 1 0 0
A1G, 13 km B1G, 43 km 5 2 5 2 1 1 0 0 0 0 1 0
B2G, 33 km C2G, 63 km 13 3 13 3 0 0 0 0 1 1 0 1
C1G, 53 km A1G, 83 km 7 2 7 2 1 0 1 0 0 0 1 0
A2B2G, 83 km C2G, 113 km 15 3 15 3 0 0 0 1 1 1 0 1
B1C1G, 103 km A1G, 133 km 8 2 8 2 1 1 1 0 0 0 1 0
C2A2G, 123 km B2G, 163 km 15 3 15 3 0 0 0 1 1 1 0 1
A1B1, 143 km C1G, 183 km 8 2 8 2 1 1 1 0 0 0 1 0
B2C2, 163 km A2G, 193 km 15 3 15 3 0 0 0 1 1 1 0 1
C1A1, 183 km B1G, 199 km 8 2 8 2 1 1 1 0 0 0 1 0
tested using all the three methods, and some of the test identification modules. Different cases of transforming
results are given in Table 7. It can be observed that all the faults are tested with all the three methods, and some of the
supervised learning techniques can detect the multi-loca- results are shown in Table 8. The results corroborate that
tion faults correctly. Fault phase identification and ground the different techniques correctly identify the transforming
identification time for all the three methods is within 10 ms faults as well.
for all the tested fault cases.
3.6 Effect of fault resistance
3.5 Performance during transforming fault
The effect of fault resistance is more likely during ground
Transforming faults are those faults which start from one faults whose probability is around 90% (LG, LLG, and
type of fault and get transformed to another type of fault LLLG) of all faults. Moreover, the effect of fault resistance
after few cycles. Suppose A1B1 fault occurs in the net- is predominant if the faulty phase is grounded through high
work, and after sometimes, A1 and B1 conductor falls on resistance medium. Fault cases with varying fault resis-
C1 phase and all the three phases are grounded. In this tance are tested with all the three methods. Figure 12
case, an A1B1 phase–phase fault gets transformed into shows the inputs and outputs of DT- and SVM-based
A1B1C1G three phases to ground fault (symmetrical); scheme during B2G fault at 143 km in 40 ms time with
therefore, it is called as transforming fault. Figure 11 R = 100 X. Figure 12a, b shows the faulty phase and
shows the output of SVM module during B1C1G fault at ground identification outputs of DT module, respectively.
60 ms which gets transformed to A1B1C1G fault at 82 ms. Figure 12c, d shows the faulty phase and ground identifi-
Figure 11a, b shows the current signals of both the circuits cation outputs of SVM module, respectively. Some of the
wherein B1 and C1 phase currents increase after occur- test results of varying resistance are shown in Table 9. It
rence of fault at 60 ms. While after 82 ms time, the A1 can be observed that proposed scheme works accurately for
phase current also starts increasing. So B1C1G fault is high resistance faults also.
transformed to A1B1C1G fault at 82 ms time. Figure 11c–j
shows the outputs of ANN-based fault phase and ground
123
Author's personal copy
Neural Computing and Applications
(a) (b)
(c) (d)
(e) (f)
(g) (h)
(i) (j)
Fig. 11 Fault phase identification and ground identification outputs of ANN scheme during B1C1G fault in 60 ms transformed to A1B1C1G
fault in 82 ms time at 110 km
3.7 Faults near boundaries performance. Test results of near and far end faults are
given in Table 10. It can be observed that fault near
Faults that occur near to the relay end or far to the relay end boundaries in the series-compensated parallel transmission
cannot be detected accurately by most of the methods. In lines can be detected using all the three methods. Fault
this work, near and far end fault cases are tested using all phase and ground identification time is within 10 ms time
the three methods. Faults near to the relay are simulated up for all the tested fault cases.
to 3 km with a step of 0.5 km. Faults near to the receiving
ends are also simulated from 190 to 200 km in step of
1 km. Far end and near end fault cases are then tested with
trained ANN, SVM, and DT modules to check the
123
Author's personal copy
Neural Computing and Applications
22 A1G at 40 ms to A1B1G at 65 ms 5 2 5 2 1 1 0 0 0 0 1 0
42 A1B1G at 40 ms to A1B1C1G at 70 ms 8 2 8 2 1 1 1 0 0 0 1 0
62 A1B1 at 40 ms to A1B1C1G at 65 ms 8 2 8 2 1 1 1 0 0 0 1 0
82 B2G at 40 ms to A2B2G at 80 ms 12 3 12 3 0 0 0 1 1 0 0 1
102 B2C2G at 40 ms to A2B2C2G at 60 ms 15 3 15 3 0 0 0 1 1 1 0 1
122 B2C2 at 40 ms to A2B2C2G at 75 ms 15 3 15 3 0 0 0 1 1 1 0 1
142 C1G at 40 ms to B1C1G at 67 ms 6 2 6 2 0 1 1 0 0 0 1 0
162 C1A1G at 40 ms to A1B1C1G at 73 ms 8 2 8 2 1 1 1 0 0 0 1 0
182 C1A1 at 40 ms to A1B1C1G at 79 ms 8 2 8 2 1 1 1 0 0 0 1 0
Fig. 12 During B2G fault at 143 km in 40 ms with R = 100 X. a Faulty phase identification output of DT module. b Ground identification output
of DT module. c Faulty phase identification output of SVM module. d Ground output of SVM module
The proposed method has been tested for different loca- In this section, a comparative analysis of different intelli-
tions of series capacitor; for example, series capacitor is gent methods used for fault phase identification and clas-
placed in the middle or at one end or at both ends of the sification is presented. The performance of DT-, SVM-,
transmission line. Various fault cases have been simulated and ANN-based schemes for test data set under varying
and tested with placement of capacitor. Some of the test fault parameters is evaluated and compared in terms of
results are given in Table 11. From Table 11, it can be different parameters in Tables 12 and 13. The accuracy of
observed that the placement of series capacitor did not the three methods is 100% for all the tested fault cases. The
affect the performance of the scheme. time required to detect the fault is less than 5 ms for most
cases for all three methods. Time required for detecting the
phase and ground is within 10 ms for all the tested fault
cases. In case of big data, the DT scheme performance
remains unaffected while ANN- and SVM-based
scheme performance may degrade. Moreover, the proposed
123
Author's personal copy
Neural Computing and Applications
0 A1B1 4 5 1 5 1 1 1 0 0 0 0 0 0
5 B1C1 14 6 1 6 1 0 1 1 0 0 0 0 0
10 C1A1 24 7 1 7 1 1 0 1 0 0 0 0 0
20 A2B2C2G 34 15 3 15 3 0 0 0 1 1 1 0 1
30 A2G 44 9 3 9 3 0 0 0 1 0 0 0 1
40 B2G 54 10 3 10 3 0 0 0 0 1 0 0 1
50 C2G 64 11 3 11 3 0 0 0 0 0 1 0 1
60 A1B1G 74 5 2 5 2 1 1 0 0 0 0 1 0
70 B1C1G 84 6 2 6 2 0 1 1 0 0 0 1 0
80 C1A1G 94 7 2 7 2 1 0 1 0 0 0 1 0
90 A1G 104 2 2 2 2 1 0 0 0 0 0 1 0
100 B1G 114 3 2 3 2 0 1 0 0 0 0 1 0
scheme has been compared with few existing schemes for 5 Conclusion
SCC lines and is reported in Table 14. It can be seen that
proposed scheme and ref [14] utilize wavelet decomposi- In this work, a comparative study of intelligent computing
tion up to level one only while other schemes [16, 21] use techniques such as ANN, SVM, and DT has been done for
6th and 8th level of wavelet decomposition, respectively. faulty phase identification and classification in series-
Thus, the computational requirement is more in [16, 21] compensated parallel transmission lines. Current signals of
than in the proposed method. Further, his proposed both the circuits are taken as input and processed with
scheme offers the highest accuracy among other reported wavelet transform to obtain the feature. The input feature
schemes [14, 16, 21]. obtained is given as input to the intelligent computing-
based method to identify the faulty phase and ground. The
merits of the proposed DT-based method can be outlined as
follows:
123
Author's personal copy
Neural Computing and Applications
Table 12 Performance of DT-, SVM-, and ANN-based schemes for test data set under varying fault parameters
Parameters used Number of fault cases tested DT SVM ANN
\ 5 ms \ 10 ms \ 5 ms \ 10 ms \ 5 ms \ 10 ms
Malathi et al. Wavelet transform extreme learning machine 28,800 1st level 99.11
[14]
Eristi [16] Wavelet transform and adaptive neuro-fuzzy inference 23,436 6th level 99.301
system
Raval et al. [21] Wavelet and artificial neural networks 1650 8th level 98.3
Proposed method Wavelet and DT 27,500 1st level 100
123
Author's personal copy
Neural Computing and Applications
• The accuracy of fault phase and ground identification EHV transmission lines. IEE Proc Gener Transm Distrib
scheme is 100% for all the fault cases tested. 143:535–540
11. Song YH, Johns AT, Xuan QY (1997) Protection scheme for
• It is not affected by parameters like mutual coupling, EHV transmission systems with thyristor controlled series com-
inter-circuit faults, single-circuit operation, multi-loca- pensation using radial basis function neural networks. Electr
tion faults, transforming faults, high fault resistance, Mach Power Syst 25:553–565
fault inception angle, fault location, and fault type. 12. Parikh UB, Das B, Maheshwari R (2010) Fault classification
technique for series compensated transmission line using support
• Response time of all the three methods is within half vector machine. Int J Electr Power Energy Syst 32:629–636
cycle time for all the tested fault cases. 13. Dash P, Samantaray S, Panda G (2007) Fault classification and
• Intelligent computing techniques can be effectively section identification of an advanced series compensated trans-
used for the protection of mutually coupled SCC. mission line using support vector machine. IEEE Trans Power
Deliv 22:67–73
14. Malathi V, Marimuthu NS, Baskar S, Ramar K (2011) Applica-
tion of extreme learning machine for series compensated trans-
mission line protection. Eng Appl Art Int 24:880–887
Compliance with ethical standards 15. Pradhan AK, Routray A, Pati S, Pradhan DK (2004) Wavelet
fuzzy combined approach for fault classification of a series-
compensated transmission line. IEEE Trans Power Deliv
Conflict of interest The authors declare that they have no conflict of 19:1612–1618
interest. 16. Eristi H (2013) Fault diagnosis system for series compensated
transmission line based on wavelet transform and adaptive neuro-
fuzzy inference system. Measurement 46:393–401
References 17. Raval PD, Pandya AS (2016) Improved fault classification in
series compensated EHV transmission line using wavelet trans-
1. Hingorani NG, Gyugyi L (2001) Understanding FACTS, First form and artificial neural network. In: 2016 IEEE 1st interna-
Indian edition, IEEE Press tional conference on power electronics, intelligent control and
2. Yadav A, Swetapadma A (2014) Improved first zone reach set- energy systems (ICPEICES), Delhi, pp 1–5
ting of artificial neural network-based directional relay for pro- 18. Samantaray SR (2007) Decision tree based fault zone identifi-
tection of double circuit transmission lines. IET Gener Transm cation and fault classification in flexible AC transmission based
Distrib 8:373–388 transmission line. IET-Gen Trans Distrib 3:425–436
3. Swetapadma Aleena, Yadav Anamika (2016) Directional relaying 19. Jamehbozorg A, Shahrtash SM (2010) A decision tree based
using support vector machine for double circuit transmission lines method for fault classification in a single circuit transmission line.
including cross-country and inter-circuit faults. Int J Electr Power IEEE Trans Power Deliv 25:2190–2196
Energy Syst 81:254–264 20. Abdelaziz AY, Mekhamer SF, Ezzat M (2013) Fault location of
4. Swetapadma Aleena, Yadav Anamika (2017) A novel decision uncompensated/series compensated lines using two-ends syn-
tree regression based fault distance estimation scheme for trans- chronized measurements. Electr Power Compon Syst
mission lines. IEEE Trans Power Deliv 32(1):234–245 41(7):693–715
5. Yadav A, Swetapadma A (2016) A finite-state machine based 21. Raval PD, Pandya AS (2017) A hybrid Wavelet-ANN protection
approach for fault detection and classification in transmission scheme for series compensated EHV transmission line. J Intell
lines. Electr Power Compon Syst 44(1):43–59 Fuzzy Syst 32(4):3051–3058
6. Krishnanand KR, Dash PK, Naeem MH (2015) Detection, clas- 22. Han J, Kamber M (2006) Data mining: concepts and techniques,
sification, and location of faults in power transmission lines. Int J 2nd edn. Morgan Kaufmann Publishers, Burlington
Electr Power Energy Syst 31(67):76–86 23. Shawe-Taylor J, Cristianni N (2000) Support vector machines
7. Megahed AI, Moussa AM, Bayoumy AE (2006) Usage of and other kernel based learning methods. Cambridge University
wavelet transform in the protection of series compensated Press, Cambridge
transmission lines. IEEE Trans Power Deliv 21:1213–1221 24. Hagan MH, Demuth HB, Beale MH (1996) Neural network
8. Dash PK, Samantray SR (2004) Phase selection and fault section design. PWS Publishing Co. Boston, ISBN: 0-534-94332-2
identification in thyristor controlled series compensated line using
discrete wavelet transform. Int J Electr Power Energy Syst Publisher’s Note Springer Nature remains neutral with regard to
26:725–732 jurisdictional claims in published maps and institutional affiliations.
9. Abdelaziz AY, Ibrahim AM, Mansour MM, Talaat HE (2005)
Modern approaches for protection of series compensated trans-
mission lines. Electr Power Syst Res 75(1):85–98
10. Song YH, Johns AT, Xuan QY (1996) Artificial neural-network-
based protection scheme for controllable series-compensated
123