Professional Documents
Culture Documents
net/publication/266102662
CITATIONS READS
0 5,124
5 authors, including:
Some of the authors of this publication are also working on these related projects:
Experimental Investigation of Creep Characteristic of Spacer Insulation Component between Winding Turns in Power Transformers under Different Operating
Conditions View project
Determination of Optimum Tilt Angle for Different PV Technologies Considering Ambient Conditions: A Case Study for Burdur, Turkey View project
All content following this page was uploaded by Ramazan Ayaz on 26 September 2014.
Abstract: There are many equipment such as transformers, high voltage cables,
insulators, breakers, etc., work in power systems under high voltages. The insulation oils
are used in such systems to provide the insulation and cooling respectively for high
voltages and temperature rises in conductors. These kinds of oils should be qualified in
terms of insulation and should have some certain features for power system stability.
Therefore, suitability of the physical, chemical and electrical properties of the insulation
oils is specified with standard tests. These tests are performed according to the IEC
60156, ASTM D1816 and ASTM D877 .In this study, breakdown voltage variation of
insulation oil which is used for high voltage equipment is investigated for particular
working conditions. In experimental study, there are two types of insulation oils which are
non-aged and aged insulating oils. Breakdown voltages of these insulation oils are
measured for different voltage rising speed mentioned in three related standards. In
addition, two types of electrodes, which are specified in standards, are used in all
breakdown voltage measurements. The results of this study showed that different types
of electrodes, rising speed of applied voltage and the quality of insulation oil have a
significant effect on the insulation breakdown voltage.
In this study, cylindrically and spherically shaped In the study, two types of oil samples are used as
electrode systems used horizontally. Voltage rate follows.
of rise, voltage form and ambient conditions are
specified according to IEC 60156, ASTM D1816 Sample 1: Non-aged oil sample
and ASTM D877 standards. Measurement results
obtained are analyzed and discussed. The results Sample 2: Aged oil sample
obtained from the experimental measurements are
analyzed to evaluate the breakdown quality of The results obtained are given in section 3.
insulation oil.
3 EXPERIMENTAL RESULTS AND
2 EXPERIMENTAL SETUP ANALYSIS
Voltage rising rate and electrode types has to be Spherical and cylindrical electrode types are used
considered in the tests which are done to specify in all measurements. The gap between the
the dielectric parameters of oils. For this reason, electrodes is set to 2.5 mm for all tests. Voltage
tests have to be done within the scope of increasing rate was changed in each test.
standards. In IEC 60156 standard, sphere - sphere Depending on the voltage increasing rate for a
and cylindrical electrodes are used in the tests fixed electrode gap, breakdown voltages are
done to specify starting point of partial discharge compared for non-aged and aged oil sample. In
and disruptive voltage. Also, distance between addition, breakdown strengths of insulating oils are
electrodes is 2.5 mm and rising rate of voltage is 2 examined for the same electrode arrangements.
kV/s [12]. For the same purpose, rising rate of the The measurements are realized under 0.5 kV/s, 2
voltage is 0.5 kV/s in ASTM D1816 standard and 3 kV/s and 3 kV/s voltage increasing rate.
kV/s in ASTM D877 standard [13-14].
The measurements are carried out 4.5 minutes
Tests are performed by “HiPotronics” insulation oil after filling the test cell with oil sample. Six
test device which is shown in Figure 1. This device breakdown strength values are measured for each
could supply three voltage rising rate according to voltage-raising rate and the average values are
the IEC 60156, ASTM D1816 and ASTM D877 calculated. Between the measurements, 1.5
standards. Additionally, the device makes it minutes is waited.
possible to perform test in different geometries as
cylindrical electrode (left) and spherically shaped 3.1 Non-aged oil sample with sphere to sphere
electrode (right) shown in Figure 2. electrode arrangement
In this study, a non-aged oil sample for testing
purposes is discussed. Sphere-sphere electrode
system was used to determine the breakdown
strength and voltage. Gap between the electrodes
during the measurements was fixed at 2.5 mm. Six
measurements are obtained for the 0.5 kV/s, 2
kV/s and 3 kV/s voltage-raising rate. These values
are given in Figure 3 and average values of results
Figure 1: Insulation are given in Table 1.
Table 2: Average test results of non-aged oil for
cylindrical electrode system