Typical small split core Typical small Elkor Typical small Veris split Typical solid core AC
DC current transducer. split core AC current core AC current current transformer.
Notice 3 wires coming transformer. Notice 2 transformer. Notice 2 Notice 2 wires coming
out. wires coming out. wires coming out. out.
Shown above are two typical current sensors – one for DC and one for AC. Current sensors primarily vary in their rating,
the size of the opening in the middle, whether they are AC or DC current sensors, and whether they are split or solid
core. Typically DECK will ship split core current sensors.
Figure 2: Typical Veris Solar Generation Example Setup:
Gen. Gen.
Meter Meter Meter Meter
Source Load Load Source
Dot must face source (Inverter) Dot must face source (Grid)
Figure 5: Building energy with metering at the generation and the building load
Gen. Gen.
Dot must face source (Inverter)
Meter Meter
Source Load
Meter Meter
Load Source
Dot must face source (Grid) Dot must face source (Grid)
Figure 7: Building energy with metering at the generation, net meter, and battery backup
Meter Meter
Load Source
Dot must face source (AC/DC Converter) Dot must face source (grid)
Figure 8: Building energy only with no solar, with metering at the building
Veris Meter configuration: The Veris meter should be configured for ‘2L 1N’.
Veris Meter configuration: The Veris meter should be configured for ‘3L 1N’.
Common: Three-phase 3-wire Delta
Veris Meter configuration: The Veris meter should be configured for ‘3L 1N’. Even though there is no neutral, the Veris
will not calculate phase to neutral values without a neutral, so it is set for 3L1N to force it to run those calculations even
if there is no physical neutral.
Sensors: CTs should be placed on Phase A, B, and C. No voltage tap on Neutral wire.
Veris Meter configuration: The Veris meter should be configured for ‘3L 1N’.
Uncommon: Three-phase 2-wire Corner-Grounded Delta
Veris Meter configuration: Veris meter cannot work with a corner grounded delta system. Veris does offer a meter (not
revenue grade) which will work with this type of configuration. The Elkor meter works.