You are on page 1of 2

Water Balancing Details

Formation A
1 Primary Pump (1104 GPM) +1 Secondary Pump (1740 GPM)
Left Wing No Reading* Suction Pressure
Right Wing 1190/1581 GPM SP(1740 GPM) 64 PSI
Chiller 1 (460 TR) 360 GPM* PP(1104 GPM) 63 PSI
Chiller 3 (345 TR) No Reading

"No Reading" is because dedicated pump of the wing was off.


360 GPM at Chiller 1 (460 Tr) was due to fact that water is circulating between the pumps through D-Coupler

Formation B
1 Primary Pump (1104 GPM)+1 Primary Pump (828 GPM) +1 Secondary Pump (1740 GPM) +1 Seconda

Left Wing 811/984 GPM Suction Pressure


Right Wing 1195/1581 GPM SP(1740 GPM) 62 PSI
Chiller 1 (460 TR) 354 GPM SP(1026 GPM) 64 PSI
Chiller 3 (345 TR) 792 GPM PP(1104 GPM) 62 PSI
PP(828 GPM) 62 PSI

Formation C
1 Primary Pump (1104 GPM)+2 Primary Pump (828 GPM) +1 Secondary Pump (1740 GPM) +2 Seconda

Left Wing 852/984 GPM Suction Pressure


Right Wing 1250/1581 GPM SP(1740 GPM) 62 PSI
Chiller 1 (460 TR) 360 GPM SP(1026 GPM) 64 PSI
Chiller 3 (345 TR) 915 GPM SP(1026 GPM) 60 PSI
PP(1104 GPM) 60 PSI
PP(828 GPM) 60 PSI
PP(828 GPM) 60 PSI
ng Details

condary Pump (1740 GPM)


Discharge Pressure
115 PSI
83 PSI

en the pumps through D-Coupler

ndary Pump (1740 GPM) +1 Secondary Pump (1026 GPM)

Discharge Pressure
114 PSI
107 PSI
87 PSI
86 PSI

ndary Pump (1740 GPM) +2 Secondary Pump (1026 GPM)

Discharge Pressure
112 PSI
110 PSI
110 PSI
85 PSI
80 PSI
88 PSI