PROJECT G+5 BUILDING HEAT LOAD FLOOR 1st f

LOCATION Laxmi nagar , New delhi. SPACE REFERENCE


CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Area or Sun Gain or Volume (CuFt)
Estimate for
Item Factor Btu/Hour W
Temp. Design Conditions DB (F)
Quantity
ROOM HEAT Diff. Ambient 110.00
ROOM SENSIBLE HEAT Room 75.00
Solar Gain - Glass Difference 35.00
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Ventilati
Glass - SW SqFt x F x 0.00 CFM Per Person 30.00 No
Glass - W 164.00 SqFt x 40.00 F x 0.65 4,264.00 CFM Per SqFt 0.33 Sqft
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft 1,609.65 x
Solar & Transmission Gain - Walls & Roof CFM Infiltratio
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window x
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x
Wall - E SqFt x F x 0.00 Open Doors x
Wall - SE SqFt x F x 0.00 Crack (feet) x
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from M
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew Poi
Transmission Gain - Except Walls & Roof Indicated ADP (°F)
All Glass 40.00 SqFt x 35.00 F x 0.65 910.00 Selected ADP (°F)
Partition 300.80 SqFt x 30.00 F x 0.32 2,887.68 Dehumidified R
Ceiling 160.96 SqFt x 30.00 F x 0.16 772.61 (Room DB - ADP) x CF
Floor 160.96 SqFt x 30.00 F x 0.16 772.61 DEHUMIDIFIED Cfm (AIR QUANTITY)
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 76.00 CFM x 35.00 T.Diff x 1.08 2,872.80 Dehumidified Rise x 1.08
Outside Air 180.00 CFM x 35.00 T.Diff x 0.3x 1.08 2,041.20
Internal Heat
People 6.00 Nos. x 245.00 Btu/Hour Per Person 1,470.00 TOTAL HEAT CAPACITY
Lighting 160.97 SqFt x 0.75 W/SqFt x 3.41 409.14 3.01 TR =
Equipments 160.97 SqFt x 2.48 W/SqFt x 3.41 1,363.94 CFM =1
Power 0.00 kW/H x 0.00 0.00
Sub Total 17,763.98
Factor 5-10% 1,776.40
Effective Room Sensible Heat 19,540.38 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 76.00 CFM x 9.00 Gr/Lb x 0.68 465.12 12,000.00
Outside Air 180.00 CFM x 9.00 Gr/Lb x BFx0.68 330.48
People 6.00 Nos. x 205.00 Btu/Hour Per Person 1,230.00
Sub Total 2,025.60
Factor 2.5 - 5% 101.28
Effective Room Latent Heat 2,126.88 2.00
EFFECTIVE ROOM TOTAL HEAT 21,667.26
OUTSIDE AIR HEAT
Sensible 180.00 CFM x 35.00 F(TD) x CF x 1.08 4,762.80 3.00
Latent 180.00 CFM x 9.00 Gr/Lb x CF x 0.68 771.12 4.00
OUTSIDE AIR TOTAL HEAT 5,533.92 Notes:
GRAND SUB-TOTAL HEAT 27,201.18
Factor 1 - 3% 816.04
GRAND TOTAL HEAT 28,017.21
TONS=GRAND TOTAL HEAT/12000 2.33
1st floor Right side
HALL
160.97
10.00
1,609.65
Summer
WB (F) RH (%) SH Gr/Lb
75.00 20.00 75.00
63.00 50.00 66.00
- - 9.00

= 0.30
= 0.70
CFM Ventilation
= 6.00 = 180.00
x 160.97 = 53.12
= 1.00
1.00 x1/60 = 26.83
CFM Infiltration
cfm/window = 0.00
cfm/door = 0.00
cfm/door = 0.00
cfm/ft = 0.00
0.00
Supply CFM from Machine
Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 53.50
Dehumidified Rise
= 15.05
DEHUMIDIFIED Cfm (AIR QUANTITY)

= 1,202.19 CFM

= 565.03 L/s

TR = 3.01
CFM =1202.19

= 2.33 TR
933.91 cfm
PROJECT G+5 BUILDING HEAT LOAD FLOOR
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE
CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Area or Sun Gain or Volume (CuFt)
Estimate for
Item Factor Btu/Hour W
Temp. Design Conditions
Quantity
ROOM HEAT Diff. Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N 0.00 SqFt x 0.00 F x 0.00 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Venti
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W SqFt x F x 0.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof CFM Infilt
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E SqFt x F x 0.00 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00 Supply CFM fro
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Ro
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew
Transmission Gain - Except Walls & Roof Indicated ADP (°F)
All Glass 0.00 SqFt x 35.00 F x 0.65 0.00 Selected ADP (°F)
Partition 147.40 SqFt x 30.00 F x 0.32 1,415.04 Dehumidifie
Ceiling 54.31 SqFt x 30.00 F x 0.16 260.69 (Room DB - ADP) x CF
Floor 54.31 SqFt x 30.00 F x 0.16 260.69 DEHUMIDIFIED Cfm (AIR QUANTIT
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 20.00 CFM x 35.00 T.Diff x 1.08 756.00 Dehumidified Rise x 1.08
Outside Air 180.00 CFM x 35.00 T.Diff x 0.3x 1.08 2,041.20
Internal Heat
People 6.00 Nos. x 245.00 Btu/Hour Per Person 1,470.00 TOTAL HEAT CAPACITY
Lighting 54.32 SqFt x 2.20 W/SqFt x 3.41 407.47 1.37
Equipments 54.32 SqFt x 11.04 W/SqFt x 3.41 2,044.78
Power 0.00 kW/H x 0.00 0.00
Sub Total 8,655.86
Factor 5-10% 865.59
Effective Room Sensible Heat 9,521.45 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 20.00 CFM x 9.00 Gr/Lb x 0.68 122.40 12,000.00
Outside Air 180.00 CFM x 9.00 Gr/Lb x BFx0.68 330.48
People 6.00 Nos. x 205.00 Btu/Hour Per Person 1,230.00
Sub Total 1,682.88
Factor 2.5 - 5% 84.14
Effective Room Latent Heat 1,767.02 2.00
EFFECTIVE ROOM TOTAL HEAT 11,288.48
OUTSIDE AIR HEAT
Sensible 180.00 CFM x 35.00 F(TD) x CF x 1.08 4,762.80 3.00
Latent 180.00 CFM x 9.00 Gr/Lb x CF x 0.68 771.12 4.00
OUTSIDE AIR TOTAL HEAT 5,533.92 Notes:
GRAND SUB-TOTAL HEAT 16,822.40
Factor 1 - 3% 504.67
GRAND TOTAL HEAT 17,327.07
TONS=GRAND TOTAL HEAT/12000 1.44
1st floor Right side DIMENSION
DINING 7.41 7.33
54.32 Area 54.3153
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONL
543.15
Summer
DB (F) WB (F) RH (%) SH Gr/Lb
110.00 75.00 20.00 75.00
75.00 63.00 50.00 66.00
35.00 - - 9.00

= 0.30
ctor (CF = 1 - BF) = 0.70
CFM Ventilation
30.00 No = 6.00 = 180.00
0.33 Sqft x 54.32 = 17.92
Per Hour (CFM) = 1.00
543.15 x 1.00 x1/60 = 9.05
CFM Infiltration
x cfm/window = 0.00
Doors (People) x cfm/door = 0.00
x cfm/door = 0.00
x cfm/ft = 0.00
0.00
Supply CFM from Machine
oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 52.00
Dehumidified Rise
- ADP) x CF = 16.10
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08 = 547.59 CFM

= 257.37 L/s
AT CAPACITY
TR = 1.37
CFM =547.59
HEAT CAPACITY
= 1.44 TR ACCEPT THIS TR
577.57 cfm ACCEPT THIS CFM
E COLOR BOXES ONLY
PROJECT G+5 BUILDING HEAT LOAD FLOOR
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE
CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Area or Sun Gain or Volume (CuFt)
Estimate for
Item Factor Btu/Hour W
Temp. Design Conditions
Quantity
ROOM HEAT Diff. Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Venti
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W 164.00 SqFt x 40.00 F x 0.65 4,264.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof CFM Infilt
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E SqFt x F x 0.00 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S 59.10 SqFt x 43.00 F x 0.48 1,219.82
Wall - SW SqFt x F x 0.00 Supply CFM fro
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Ro
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew
Transmission Gain - Except Walls & Roof Indicated ADP (°F)
All Glass 40.00 SqFt x 35.00 F x 0.65 910.00 Selected ADP (°F)
Partition 101.60 SqFt x 30.00 F x 0.32 975.36 Dehumidifie
Ceiling 148.68 SqFt x 30.00 F x 0.16 713.66 (Room DB - ADP) x CF
Floor 148.68 SqFt x 30.00 F x 0.16 713.66 DEHUMIDIFIED Cfm (AIR QUANTIT
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 76.00 CFM x 35.00 T.Diff x 1.08 2,872.80 Dehumidified Rise x 1.08
Outside Air 60.00 CFM x 35.00 T.Diff x 0.3x 1.08 680.40
Internal Heat
People 2.00 Nos. x 245.00 Btu/Hour Per Person 490.00 TOTAL HEAT CAPACITY
Lighting 148.68 SqFt x 0.40 W/SqFt x 3.41 204.57 2.48
Equipments 148.68 SqFt x 2.35 W/SqFt x 3.41 1,193.48
Power 0.00 kW/H x 0.00 0.00
Sub Total 14,237.76
Factor 5-10% 1,423.78
Effective Room Sensible Heat 15,661.54 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 76.00 CFM x 9.00 Gr/Lb x 0.68 465.12 12,000.00
Outside Air 60.00 CFM x 9.00 Gr/Lb x BFx0.68 110.16
People 2.00 Nos. x 205.00 Btu/Hour Per Person 410.00
Sub Total 985.28
Factor 2.5 - 5% 49.26
Effective Room Latent Heat 1,034.54 2.00
EFFECTIVE ROOM TOTAL HEAT 16,696.08
OUTSIDE AIR HEAT
Sensible 60.00 CFM x 35.00 F(TD) x CF x 1.08 1,587.60 3.00
Latent 60.00 CFM x 9.00 Gr/Lb x CF x 0.68 257.04 4.00
OUTSIDE AIR TOTAL HEAT 1,844.64 Notes:
GRAND SUB-TOTAL HEAT 18,540.72
Factor 1 - 3% 556.22
GRAND TOTAL HEAT 19,096.94
TONS=GRAND TOTAL HEAT/12000 1.59
1st floor Right side DIMENSION
BEDROOM 10.5 14.16
148.68 Area 148.68
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOX
1,486.80
Summer
DB (F) WB (F) RH (%) SH Gr/Lb
110.00 75.00 20.00 75.00
75.00 63.00 50.00 66.00
35.00 - - 9.00

= 0.30
ctor (CF = 1 - BF) = 0.70
CFM Ventilation
30.00 No = 2.00 = 60.00
0.33 Sqft x 148.68 = 49.06
Per Hour (CFM) = 1.00
1,486.80 x 1.00 x1/60 = 24.78
CFM Infiltration
x cfm/window = 0.00
Doors (People) x cfm/door = 0.00
x cfm/door = 0.00
x cfm/ft = 0.00
0.00
Supply CFM from Machine
oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 54.15
Dehumidified Rise
- ADP) x CF = 14.60
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08 = 993.59 CFM

= 466.99 L/s
AT CAPACITY
TR = 2.48 ACCEPT THIS TR
CFM =993.59
HEAT CAPACITY
= 1.59 TR
636.56 cfm ACCEPT THIS CFM
EN IN BLUE COLOR BOXES ONLY
PROJECT G+5 BUILDING HEAT LOAD FLOOR
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE
CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Area or Sun Gain or Volume (CuFt)
Estimate for
Item Factor Btu/Hour W
Temp. Design Conditions
Quantity
ROOM HEAT Diff. Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E 40.00 SqFt x 12.00 F x 0.65 312.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Venti
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W SqFt x F x 0.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof CFM Infilt
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E 101.60 SqFt x 29.00 F x 0.48 1,414.27 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00 Supply CFM fro
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Ro
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew
Transmission Gain - Except Walls & Roof Indicated ADP (°F)
All Glass 40.00 SqFt x 35.00 F x 0.65 910.00 Selected ADP (°F)
Partition 161.60 SqFt x 30.00 F x 0.32 1,551.36 Dehumidifie
Ceiling 172.19 SqFt x 30.00 F x 0.16 826.49 (Room DB - ADP) x CF
Floor 172.19 SqFt x 30.00 F x 0.16 826.49 DEHUMIDIFIED Cfm (AIR QUANTIT
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 56.00 CFM x 35.00 T.Diff x 1.08 2,116.80 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 35.00 T.Diff x 0.3x 1.08 1,360.80
Internal Heat
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 172.19 SqFt x 0.58 W/SqFt x 3.41 340.99 2.06
Equipments 172.19 SqFt x 2.61 W/SqFt x 3.41 1,534.41
Power 0.00 kW/H x 0.00 0.00
Sub Total 12,173.61
Factor 5-10% 1,217.36
Effective Room Sensible Heat 13,390.97 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 56.00 CFM x 9.00 Gr/Lb x 0.68 342.72 12,000.00
Outside Air 120.00 CFM x 9.00 Gr/Lb x BFx0.68 220.32
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 1,383.04
Factor 2.5 - 5% 69.15
Effective Room Latent Heat 1,452.19 2.00
EFFECTIVE ROOM TOTAL HEAT 14,843.16
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 35.00 F(TD) x CF x 1.08 3,175.20 3.00
Latent 120.00 CFM x 9.00 Gr/Lb x CF x 0.68 514.08 4.00
OUTSIDE AIR TOTAL HEAT 3,689.28 Notes:
GRAND SUB-TOTAL HEAT 18,532.44
Factor 1 - 3% 555.97
GRAND TOTAL HEAT 19,088.42
TONS=GRAND TOTAL HEAT/12000 1.59
1st floor Right side DIMENSION
MASTER BEDROOM 12.16 14.16
172.19 Area 172.1856
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOX
1,721.86
Summer
DB (F) WB (F) RH (%) SH Gr/Lb
110.00 75.00 20.00 75.00
75.00 63.00 50.00 66.00
35.00 - - 9.00

= 0.30
ctor (CF = 1 - BF) = 0.70
CFM Ventilation
30.00 No = 4.00 = 120.00
0.33 Sqft x 172.19 = 56.82
Per Hour (CFM) = 1.00
1,721.86 x 1.00 x1/60 = 28.70
CFM Infiltration
x cfm/window = 0.00
Doors (People) x cfm/door = 0.00
x cfm/door = 0.00
x cfm/ft = 0.00
0.00
Supply CFM from Machine
oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 53.50
Dehumidified Rise
- ADP) x CF = 15.05
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08 = 823.86 CFM

= 387.21 L/s
AT CAPACITY
TR = 2.06 ACCEPT THIS TR
CFM =823.86
HEAT CAPACITY
= 1.59 TR
636.28 cfm ACCEPT THIS CFM
EN IN BLUE COLOR BOXES ONLY
PROJECT G+5 BUILDING HEAT LOAD FLOOR 1st f
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE
CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Area or Sun Gain or Volume (CuFt)
Estimate for
Item Factor Btu/Hour W
Temp. Design Conditions DB (F)
Quantity
ROOM HEAT Diff. Ambient 110.00
ROOM SENSIBLE HEAT Room 75.00
Solar Gain - Glass Difference 35.00
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Ventilati
Glass - SW SqFt x F x 0.00 CFM Per Person 30.00 No
Glass - W 164.00 SqFt x 40.00 F x 0.65 4,264.00 CFM Per SqFt 0.33 Sqft
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft 1,609.65 x
Solar & Transmission Gain - Walls & Roof CFM Infiltratio
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window x
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x
Wall - E SqFt x F x 0.00 Open Doors x
Wall - SE SqFt x F x 0.00 Crack (feet) x
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from M
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew Poi
Transmission Gain - Except Walls & Roof Indicated ADP (°F)
All Glass 40.00 SqFt x 35.00 F x 0.65 910.00 Selected ADP (°F)
Partition 218.30 SqFt x 30.00 F x 0.32 2,095.68 Dehumidified R
Ceiling 160.97 SqFt x 30.00 F x 0.16 772.63 (Room DB - ADP) x CF
Floor 160.97 SqFt x 30.00 F x 0.16 772.63 DEHUMIDIFIED Cfm (AIR QUANTITY)
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 76.00 CFM x 35.00 T.Diff x 1.08 2,872.80 Dehumidified Rise x 1.08
Outside Air 180.00 CFM x 35.00 T.Diff x 0.3x 1.08 2,041.20
Internal Heat
People 6.00 Nos. x 245.00 Btu/Hour Per Person 1,470.00 TOTAL HEAT CAPACITY
Lighting 160.97 SqFt x 0.75 W/SqFt x 3.41 409.14 2.84 TR =
Equipments 160.97 SqFt x 2.48 W/SqFt x 3.41 1,363.94 CFM =1
Power 0.00 kW/H x 0.00 0.00
Sub Total 16,972.03
Factor 5-10% 1,697.20
Effective Room Sensible Heat 18,669.23 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 76.00 CFM x 9.00 Gr/Lb x 0.68 465.12 12,000.00
Outside Air 180.00 CFM x 9.00 Gr/Lb x BFx0.68 330.48
People 6.00 Nos. x 205.00 Btu/Hour Per Person 1,230.00
Sub Total 2,025.60
Factor 2.5 - 5% 101.28
Effective Room Latent Heat 2,126.88 2.00
EFFECTIVE ROOM TOTAL HEAT 20,796.11
OUTSIDE AIR HEAT
Sensible 180.00 CFM x 35.00 F(TD) x CF x 1.08 4,762.80 3.00
Latent 180.00 CFM x 9.00 Gr/Lb x CF x 0.68 771.12 4.00
OUTSIDE AIR TOTAL HEAT 5,533.92 Notes:
GRAND SUB-TOTAL HEAT 26,330.03
Factor 1 - 3% 789.90
GRAND TOTAL HEAT 27,119.93
TONS=GRAND TOTAL HEAT/12000 2.26
1st floor Right side
HALL
160.97
10.00
1,609.65
Summer
WB (F) RH (%) SH Gr/Lb
75.00 20.00 75.00
63.00 50.00 66.00
- - 9.00

= 0.30
= 0.70
CFM Ventilation
= 6.00 = 180.00
x 160.97 = 53.12
= 1.00
1.00 x1/60 = 26.83
CFM Infiltration
cfm/window = 0.00
cfm/door = 0.00
cfm/door = 0.00
cfm/ft = 0.00
0.00
Supply CFM from Machine
Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 53.25
Dehumidified Rise
= 15.23
DEHUMIDIFIED Cfm (AIR QUANTITY)

= 1,135.39 CFM

= 533.63 L/s

TR = 2.84
CFM =1135.39

= 2.26 TR
904.00 cfm
PROJECT G+5 BUILDING HEAT LOAD FLOOR
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE
CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Area or Sun Gain or Volume (CuFt)
Estimate for
Item Factor Btu/Hour W
Temp. Design Conditions
Quantity
ROOM HEAT Diff. Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N 0.00 SqFt x 0.00 F x 0.00 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Venti
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W SqFt x F x 0.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof CFM Infilt
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E SqFt x F x 0.00 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00 Supply CFM fro
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Ro
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew
Transmission Gain - Except Walls & Roof Indicated ADP (°F)
All Glass 0.00 SqFt x 35.00 F x 0.65 0.00 Selected ADP (°F)
Partition 156.60 SqFt x 30.00 F x 0.32 1,503.36 Dehumidifie
Ceiling 61.20 SqFt x 30.00 F x 0.16 293.76 (Room DB - ADP) x CF
Floor 61.20 SqFt x 30.00 F x 0.16 293.76 DEHUMIDIFIED Cfm (AIR QUANTIT
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 20.00 CFM x 35.00 T.Diff x 1.08 756.00 Dehumidified Rise x 1.08
Outside Air 180.00 CFM x 35.00 T.Diff x 0.3x 1.08 2,041.20
Internal Heat
People 6.00 Nos. x 245.00 Btu/Hour Per Person 1,470.00 TOTAL HEAT CAPACITY
Lighting 61.20 SqFt x 1.96 W/SqFt x 3.41 409.04 1.39
Equipments 61.20 SqFt x 9.80 W/SqFt x 3.41 2,046.00
Power 0.00 kW/H x 0.00 0.00
Sub Total 8,813.12
Factor 5-10% 881.31
Effective Room Sensible Heat 9,694.43 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 20.00 CFM x 9.00 Gr/Lb x 0.68 122.40 12,000.00
Outside Air 180.00 CFM x 9.00 Gr/Lb x BFx0.68 330.48
People 6.00 Nos. x 205.00 Btu/Hour Per Person 1,230.00
Sub Total 1,682.88
Factor 2.5 - 5% 84.14
Effective Room Latent Heat 1,767.02 2.00
EFFECTIVE ROOM TOTAL HEAT 11,461.45
OUTSIDE AIR HEAT
Sensible 180.00 CFM x 35.00 F(TD) x CF x 1.08 4,762.80 3.00
Latent 180.00 CFM x 9.00 Gr/Lb x CF x 0.68 771.12 4.00
OUTSIDE AIR TOTAL HEAT 5,533.92 Notes:
GRAND SUB-TOTAL HEAT 16,995.37
Factor 1 - 3% 509.86
GRAND TOTAL HEAT 17,505.23
TONS=GRAND TOTAL HEAT/12000 1.46
1st floor Right side DIMENSION
DINING 7.5 8.16
61.20 Area 61.2
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONL
612.00
Summer
DB (F) WB (F) RH (%) SH Gr/Lb
110.00 75.00 20.00 75.00
75.00 63.00 50.00 66.00
35.00 - - 9.00

= 0.30
ctor (CF = 1 - BF) = 0.70
CFM Ventilation
30.00 No = 6.00 = 180.00
0.33 Sqft x 61.20 = 20.20
Per Hour (CFM) = 1.00
612.00 x 1.00 x1/60 = 10.20
CFM Infiltration
x cfm/window = 0.00
Doors (People) x cfm/door = 0.00
x cfm/door = 0.00
x cfm/ft = 0.00
0.00
Supply CFM from Machine
oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 52.00
Dehumidified Rise
- ADP) x CF = 16.10
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08 = 557.54 CFM

= 262.04 L/s
AT CAPACITY
TR = 1.39
CFM =557.54
HEAT CAPACITY
= 1.46 TR ACCEPT THIS TR
583.51 cfm ACCEPT THIS CFM
E COLOR BOXES ONLY
PROJECT G+5 BUILDING HEAT LOAD FLOOR
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE
CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Area or Sun Gain or Volume (CuFt)
Estimate for
Item Factor Btu/Hour W
Temp. Design Conditions
Quantity
ROOM HEAT Diff. Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Venti
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W 164.00 SqFt x 20.00 F x 0.65 2,132.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof CFM Infilt
Wall - N 105.00 SqFt x 27.00 F x 0.48 1,360.80 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E SqFt x F x 0.00 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S 0.00 SqFt x 0.00 F x 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM fro
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Ro
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew
Transmission Gain - Except Walls & Roof Indicated ADP (°F)
All Glass 20.00 SqFt x 35.00 F x 0.65 455.00 Selected ADP (°F)
Partition 181.60 SqFt x 30.00 F x 0.32 1,743.36 Dehumidifie
Ceiling 148.68 SqFt x 30.00 F x 0.16 713.66 (Room DB - ADP) x CF
Floor 148.68 SqFt x 30.00 F x 0.16 713.66 DEHUMIDIFIED Cfm (AIR QUANTIT
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 38.00 CFM x 35.00 T.Diff x 1.08 1,436.40 Dehumidified Rise x 1.08
Outside Air 60.00 CFM x 35.00 T.Diff x 0.3x 1.08 680.40
Internal Heat
People 2.00 Nos. x 245.00 Btu/Hour Per Person 490.00 TOTAL HEAT CAPACITY
Lighting 148.68 SqFt x 0.40 W/SqFt x 3.41 204.57 1.95
Equipments 148.68 SqFt x 2.35 W/SqFt x 3.41 1,193.48
Power 0.00 kW/H x 0.00 0.00
Sub Total 11,123.34
Factor 5-10% 1,112.33
Effective Room Sensible Heat 12,235.67 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 38.00 CFM x 9.00 Gr/Lb x 0.68 232.56 12,000.00
Outside Air 60.00 CFM x 9.00 Gr/Lb x BFx0.68 110.16
People 2.00 Nos. x 205.00 Btu/Hour Per Person 410.00
Sub Total 752.72
Factor 2.5 - 5% 37.64
Effective Room Latent Heat 790.36 2.00
EFFECTIVE ROOM TOTAL HEAT 13,026.03
OUTSIDE AIR HEAT
Sensible 60.00 CFM x 35.00 F(TD) x CF x 1.08 1,587.60 3.00
Latent 60.00 CFM x 9.00 Gr/Lb x CF x 0.68 257.04 4.00
OUTSIDE AIR TOTAL HEAT 1,844.64 Notes:
GRAND SUB-TOTAL HEAT 14,870.67
Factor 1 - 3% 446.12
GRAND TOTAL HEAT 15,316.79
TONS=GRAND TOTAL HEAT/12000 1.28
1st floor Right side DIMENSION
BEDROOM 10.5 14.16
148.68 Area 148.68
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOX
1,486.80
Summer
DB (F) WB (F) RH (%) SH Gr/Lb
110.00 75.00 20.00 75.00
75.00 63.00 50.00 66.00
35.00 - - 9.00

= 0.30
ctor (CF = 1 - BF) = 0.70
CFM Ventilation
30.00 No = 2.00 = 60.00
0.33 Sqft x 148.68 = 49.06
Per Hour (CFM) = 1.00
1,486.80 x 1.00 x1/60 = 24.78
CFM Infiltration
x cfm/window = 0.00
Doors (People) x cfm/door = 0.00
x cfm/door = 0.00
x cfm/ft = 0.00
0.00
Supply CFM from Machine
oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 54.30
Dehumidified Rise
- ADP) x CF = 14.49
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08 = 781.87 CFM

= 367.48 L/s
AT CAPACITY
TR = 1.95 ACCEPT THIS TR
CFM =781.87
HEAT CAPACITY
= 1.28 TR
510.56 cfm ACCEPT THIS CFM
EN IN BLUE COLOR BOXES ONLY
PROJECT G+5 BUILDING HEAT LOAD FLOOR
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE
CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Area or Sun Gain or Volume (CuFt)
Estimate for
Item Factor Btu/Hour W
Temp. Design Conditions
Quantity
ROOM HEAT Diff. Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E 20.00 SqFt x 12.00 F x 0.65 156.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Venti
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W SqFt x F x 0.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof CFM Infilt
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E 86.60 SqFt x 29.00 F x 0.48 1,205.47 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00 Supply CFM fro
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Ro
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew
Transmission Gain - Except Walls & Roof Indicated ADP (°F)
All Glass 20.00 SqFt x 35.00 F x 0.65 455.00 Selected ADP (°F)
Partition 201.60 SqFt x 30.00 F x 0.32 1,935.36 Dehumidifie
Ceiling 129.63 SqFt x 30.00 F x 0.16 622.20 (Room DB - ADP) x CF
Floor 129.63 SqFt x 30.00 F x 0.16 622.20 DEHUMIDIFIED Cfm (AIR QUANTIT
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 38.00 CFM x 35.00 T.Diff x 1.08 1,436.40 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 35.00 T.Diff x 0.3x 1.08 1,360.80
Internal Heat
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 129.63 SqFt x 0.77 W/SqFt x 3.41 340.99 1.78
Equipments 129.63 SqFt x 3.47 W/SqFt x 3.41 1,534.44
Power 0.00 kW/H x 0.00 0.00
Sub Total 10,648.86
Factor 5-10% 1,064.89
Effective Room Sensible Heat 11,713.75 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 38.00 CFM x 9.00 Gr/Lb x 0.68 232.56 12,000.00
Outside Air 120.00 CFM x 9.00 Gr/Lb x BFx0.68 220.32
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 1,272.88
Factor 2.5 - 5% 63.64
Effective Room Latent Heat 1,336.52 2.00
EFFECTIVE ROOM TOTAL HEAT 13,050.27
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 35.00 F(TD) x CF x 1.08 3,175.20 3.00
Latent 120.00 CFM x 9.00 Gr/Lb x CF x 0.68 514.08 4.00
OUTSIDE AIR TOTAL HEAT 3,689.28 Notes:
GRAND SUB-TOTAL HEAT 16,739.55
Factor 1 - 3% 502.19
GRAND TOTAL HEAT 17,241.74
TONS=GRAND TOTAL HEAT/12000 1.44
1st floor Right side DIMENSION
MASTER BEDROOM 12.16 10.66
129.63 Area 129.6256
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOX
1,296.26
Summer
DB (F) WB (F) RH (%) SH Gr/Lb
110.00 75.00 20.00 75.00
75.00 63.00 50.00 66.00
35.00 - - 9.00

= 0.30
ctor (CF = 1 - BF) = 0.70
CFM Ventilation
30.00 No = 4.00 = 120.00
0.33 Sqft x 129.63 = 42.78
Per Hour (CFM) = 1.00
1,296.26 x 1.00 x1/60 = 21.60
CFM Infiltration
x cfm/window = 0.00
Doors (People) x cfm/door = 0.00
x cfm/door = 0.00
x cfm/ft = 0.00
0.00
Supply CFM from Machine
oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 53.25
Dehumidified Rise
- ADP) x CF = 15.23
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08 = 712.39 CFM

= 334.82 L/s
AT CAPACITY
TR = 1.78 ACCEPT THIS TR
CFM =712.39
HEAT CAPACITY
= 1.44 TR
574.72 cfm ACCEPT THIS CFM
EN IN BLUE COLOR BOXES ONLY
G+5 BUILDING HEAT LOAD 1ST FLOOR

LEFT TOP FLAT IN 1ST FLOOR (3)

ROOMS CALCULATED DEHUMIDIFIED


TR CFM TR CFM
BEDROOM 1.25 501.85 1.92 771.95
DINING 1.42 571.71 1.408 563.5
HALL 1.81 727.12 2.22 890.07
MASTER BEDROOM 1.33 533.15 1.75 703.57

TOTAL TR 7.31 TR
TOTAL CFM 2333.83 CFM

G+5 BUILDING HEAT LOAD 5th FLOOR

LEFT TOP

ROOMS CALCULATED DEHUMIDIFIED


TR CFM TR CFM
BEDROOM 1.43 572 2.25 900
DINING 1.6 640 1.63 655.44
HALL 2.39 956 3.16 1267.87
MASTER BEDROOM 1.44 576 1.78 712

RIGHT TOP

ROOMS CALCULATED DEHUMIDIFIED


TR CFM TR CFM
BEDROOM 1.18 472 1.78 713.39
DINING 1.6 640 1.64 656
HALL 1.4 560 1.95 782
MASTER BEDROOM 1.43 572 1.81 726

TOTAL TR IN RHS IN 1ST FLOOR 17.0259


TOTAL CFM IN RHS IN 1ST FLOOR 5357.111

TOTAL TR IN 1ST FLOOR 32.2159 TR


TOTAL CFM IN 1ST FLOOR 10056.33 CFM

TOTAL TR UPTO 4TH FLOOR 128.8636 TR


TOTAL CFM UPTO 4TH FLOOR 40225.32 CFM
TOTAL TR 1-5th floor 160.6636 TR
total cfm 1-5th floor 50189.32 CFM
G HEAT LOAD 1ST FLOOR

LEFT BOTTOM FLAT IN 1ST FLOOR (4)

ROOMS CALCULATED DEHUMIDIFIED


TR CFM TR CFM
BEDROOM 1.7 680.8 1024.25 2.56
DINING 1.45 582.7 574.54 1.43
HALL 1.36 547.8 858.87 2.14
MASTER BEDROOM 1.385 554.09 694.63 1.73

TOTAL TR 7.88 TR
TOTAL CFM 2365.39 CFM

NG HEAT LOAD 5th FLOOR

LEFT BOTTOM

ROOMS CALCULATED DEHUMIDIFIED


TR CFM TR CFM
HALL 2.5 1000 3.37 348.02
DINING 1.45 580 1.44 577.92
BEDROOM 1.53 612 2.41 966.29
MASTER BEDROOM 1.37 548 1.67 671.46

RIGHT BOTTOM

ROOMS CALCULATED DEHUMIDIFIED


TR CFM TR CFM
BEDROOM 1.2 480 1.74 696.53
DINING 1.47 588 1.41 565.62
HALL 1.32 528 1.59 639.14
MASTER BEDROOM 1.6 640 2.1 840

TOTAL TR IN 5TH FLOOR 31.8


TOTAL CFM IN 5TH FLOOR 9964