The document discusses power, reactive power, apparent power, power factor, and how to improve power factor by adding a capacitor in parallel with an inductive load. It provides equations for real power, reactive power, apparent power, power factor, impedance, current, and capacitor value. It explains that adding a capacitor can reduce the reactive power consumed by the inductive load, bringing the overall power factor closer to 1.

Uploaded by

নিঝুম
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
141 views13 pages

Power Factor Correction Guide

The document discusses power, reactive power, apparent power, power factor, and how to improve power factor by adding a capacitor in parallel with an inductive load. It provides equations for real power, reactive power, apparent power, power factor, impedance, current, and capacitor value. It explains that adding a capacitor can reduce the reactive power consumed by the inductive load, bringing the overall power factor closer to 1.

Uploaded by

নিঝুম
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

1

Real Power, P = Vm I m cos( v − i ) = Vrms I rms cos( v − i ) = S cos( v − i ) (Unit: Watt)


2
1
Reactive Power, Q = Vm I m sin( v − i ) = Vrms I rms sin( v − i ) = S sin( v − i ) (Unit: VAR)
2
S=Apparent Power
Complex Power, (Unit: VA)
1 1
S = Vm I m cos( v − i ) + j Vm I m sin( v − i )
2 2 (rectangular form)
1
= Vm I m  v − i (polar form)
2
(Unit: VA)
1
= Vm  v I m  − i
2
1
= V I*
2
= Vrms I rms
V
Z=
I 1
S = V I*
V =Z I 2
V 1
I = = Z I I*
Z 2
1 2
= Z I
2
1
= Z Im2
2
1
= ( R + jX ) I m 2 [ Z = R + jX ]
2
1 1
= Im2 R + j Im2 X
2 2

= P + jQ
or
1 Vm 2
S=
2 Z*
Power Factor Improvement Try to make the overall pf close to 1
Why???
To reduce loss in the line (system loss) by minimizing current drawn from the source

Let
Real power consumption by the resistive part of the
load=P

Reactive Power consumption by the inductance


part of the load= Q1= QL

The load has apparent power = S1


Power factor angle=θ1

Using power triangle


Power Factor Improvement How??? Use a capacitor parallel to the over all load

Real power consumption by the resistive part of the


load=P (didn’t change)
Total Reactive Power consumption by the
inductance as well capacitive part of the load=
Q2=QL-QC
The load has apparent power = S2
Power factor angle=θ2
Using power triangle
V
Ic = [in rms]
Zc
1
Z c = Rc − jX c where, Rc = 0 and X c =
C
complex power by the capacitor,
Sc = Pc − jQc here, Pc = 0
= V I c*
* 2 2
V V V
=V * = =−j
Zc jX c Xc Where,
V
2 Qc = P(tan 1 − tan  2 )
− jQc = − j
Xc 1 : pf angle before using the capacitor
2

Qc =
V  2 : pf angle after using the capacitor
1/ C
Q
C = 2c
V  Value of the capacitor required to improve power factor
Q) Two devices are connected in parallel with a 120 V rms 60 Hz source. Device 1 draws 360 W with unity
pf. Device 2 absorbs 1440 W with a pf of 0.7 lagging. Find the value of the capacitor so that the magnitude
of the source current equals 10 A rms. What is the power factor combination of the two-device-capacitor
combination?