USER HANDBOOK
10H52167UM01 - rev. 8
CHLORIDE 80-NET
1. SAFETY................................................................................................................. 5
1.1. Intended use....................................................................................................... 5
1.2. Warning notice ................................................................................................... 5
1.3. Safety Notices .................................................................................................... 5
1.4. Overheating ........................................................................................................ 6
1.5. Emergency measures......................................................................................... 6
1.6. Danger areas ...................................................................................................... 7
1.7. Leakage currents ................................................................................................ 7
1.8. Radio frequency interference ............................................................................. 7
1.9. Batteries - (EXTERNAL ONLY)............................................................................ 7
1.10. Re-packaging .................................................................................................... 8
2. INTRODUCTION................................................................................................... 9
2.1. Notes to the EC Declaration of Conformity ........................................................ 9
2.2. Symbols and pictograms .................................................................................... 9
2.3. Terms used ........................................................................................................ 10
2.4. Documentation structure.................................................................................... 10
3. PREPARATION FOR USE..................................................................................... 11
3.1. Transport ............................................................................................................ 11
3.2. Delivery and storage........................................................................................... 11
3.3. Unpacking........................................................................................................... 11
3.4. Environmental conditions ................................................................................... 12
3.5. Access to area .................................................................................................... 12
3.6. Installation site.................................................................................................... 13
3.7. Floor ................................................................................................................... 14
4. INSTALLATION .................................................................................................... 15
4.1. Electrical preparations ........................................................................................ 15
4.2. Currents and suggested cable sizes................................................................... 15
4.3. Physical appearance ........................................................................................... 16
4.4. External protection devices ................................................................................ 19
4.5. Backfeed protection ........................................................................................... 24
4.6. External electrical connections ........................................................................... 25
4.7. Power connections............................................................................................. 25
4.8. Connecting the batteries .................................................................................... 28
4.9. Connections between battery cubicles and UPS ............................................... 30
4.10. Handling the batteries ...................................................................................... 31
5. INTERFACES ........................................................................................................ 33
5.1. RS232 Service port - X3...................................................................................... 34
5.2. RS232 Life.net port - X6 ..................................................................................... 34
5.3. Computer relay interface - (Output - X7)............................................................. 34
5.4. Emergency Power Off (E.P.O.) - (Input - X8) ...................................................... 35
5.5. External Battery Temperature sensor - (input - XT1) .......................................... 35
5.6. External Battery Switch status - (input - XT2) ..................................................... 35
5.7. E.P.O. Active - (output - XT3).............................................................................. 36
5.8. Backfeed Protection Active - (output - XT4)........................................................ 36
5.9. Service Interface - (AP10-X4).............................................................................. 36
1. SAFETY
1.1. INTENDED USE
This device serves as an uninterruptible power supply (UPS) for connected loads. The de-
vice is in compliance with all relevant safety regulations concerning information technol-
ogy equipment, including electronic appliances for use in an office environment.
Warning
The UPS contains capacitors which continue to store energy for a period
of time after the device has been disconnected from the mains sup-
ply(ies) and battery. This voltage (> 400 V DC) is present at the battery
terminals. For this reason, check that the UPS and the external mains sep-
aration device are switched off and the battery fuses removed. Before
continuing work, measure the voltage at the battery terminals and at the
mains input filter and wait until this has dropped to 0 V or wait at least
5 min. after disconnecting. Failure to do this can lead to severe electrical
shock and even death.
• During the turn on and turn off procedures QS9 is operated only when the inverter is
OFF.
• The batteries installed in the battery extension kits contain electrolytic substances.
Under normal conditions the containers are dry, but a damaged battery may leak
electrolyte which can be dangerous in contact with the skin and cause irritation to
the eyes. Should this happen wash the affected part with copious amounts of water
and seek immediate medical advice.
• Voltage is present on the battery contacts at all times.
• Even when discharged a battery has the capacity to supply a high short circuit cur-
rent, which, in addition to causing damage to the battery itself and associated
cables, may expose the operator to the risk of burns.
• Battery voltages can be hazardous. The voltage of a single cell is not dangerous,
however a number of such blocks, connected in series, can produce dangerous volt-
ages. During maintenance, disconnect the battery blocks so that not more than five
batteries are connected in series.
• Periods of storage or disuse may not exceed 6 months, at 20°C, without the batter-
ies being recharged. If this period is exceeded it is essential that the battery be
recharged, which requires that the UPS be switched on. Guarantee is void if these
instructions are not followed. However, it is advised that recharging be carried out at
least once every 4 months.
• Since new batteries often do not provide full capacity after an initial charge it may be
necessary to carry out a number of discharge/recharge cycles before optimum per-
formance is achieved.
• In order to protect the environment batteries must be disposed of in accordance
with the regulations governing disposal of toxic and harmful waste.
1.10. RE-PACKAGING
To re-package, proceed as follows:
Do not pack the equipment until at least six hours have elapsed since the
last recharge.
Place the equipment in bags made of a material sufficiently porous to
allow it to breathe (e.g. 100μm polyethylene).
2. INTRODUCTION
This User’s Manual contains information regarding the installation, operation and use of
the Uninterruptible Power System (UPS) 80-NET.
It is advised that this document be consulted before installation of the equipment, whose
operation shall only be carried out by qualified personnel.
Thereafter, it shall be kept and referred to whenever it is necessary to carry out work on
the UPS.
Warning
Indicates instructions which, if not observed, may result in danger to life,
safety, the reliability of your device or data security.
Notice
Indicates additional information and tips.
Figure 1 - Unpacking
If it is not intended that the UPS be used within seven days of delivery, attention shall be
paid to the storage conditions.
• If the batteries or the equipment are to be stored they must be kept in a clean, dry
environment and away from extremes of temperatures.
Installation altitude in m
USABLE
AREA 769 - 100/120 kVA
1044 - 160 kVA
1169 - 200 kVA
494
118.5
109
53
53
50 50
138 25 147
25
25
550
25
825 - 100/120 kVA
1100 - 160 kVA
1225 - 200 kVA
Figure 3 - Glandplates
3.7. FLOOR
The floor where the UPS is installed must be even and level, its load-carrying capacity
must also be sufficient to support the floor loading of the UPS - the UPS footprints are
illustrated in Fig. 4 and Fig. 5, the weight may be found in the Data Tables in “Technical
data” on page 81.
50
Ø 11
750 800
53 50
447 25
25 25
550
Figure 4 - Footprint 60/80 kVA
50
Ø 11
750 800
53 25
50
25 25
825 - 100/120 kVA
1100 - 160 kVA
1225 - 200 kVA
4. INSTALLATION
4.1. ELECTRICAL PREPARATIONS
In order to guarantee safe working conditions, ensure all voltage sources are isolated be-
fore carrying out the power connections. ENSURE CORRECT POLARITY!
Ensure that the live input source cannot accidentally be connected to the UPS dur-
ing installation.
Notice
Installation may only be carried out by qualified technicians and in con-
formity with the applicable safety standards.
For electrical installation, the nominal current rating of the source must be
observed.
Notice
Should there be any variation in the conditions it will be necessary to
verify whether the cable dimensions satisfy the requirements of IEC-
287 and DIN VDE 0298. In cases where the cables are so long that they
cause a drop in voltage of >3%, a larger dimension shall be selected.
If mainly non-linear loads are present in your system, the neutral con-
ductor (N) carries 1.7 times the current of the other conductors and
should be dimensioned accordingly.
Routing of cables (e.g. mains cables, communication or data lines) to
other equipment should be kept separate from that of the UPS (I/P, O/P,
and external battery cables).
Display Display
60/80kVA 100/120kVA
Display
Connectivity panel
QS3
QS9
160 kVA
Display
Connectivity panel
QS3
QS9 QS14
200 kVA
Warning
The following label must be displayed on all switching devices installed in
the same electrical system as the UPS, even when these are located at a
distance from the area in which it is located (according to European stand-
ard EN 62040-1):
A differential device installed on the input bypass supply senses the sum of all earth leak-
age currents in both the UPS and the load it supplies.
To avoid spurious operation, the following must be taken into consideration when select-
ing differential protection devices for installation on input lines:
1 The nominal value of ID must take into account the earth leakage current of the UPS
and the load, in normal operating conditions: ID = IDUPS + load leakage current.
N.B. The maximum limit for UPS earth leakage current is 5% of the nominal input
current (see EN62040-1-1, Art. 4.5.13.)
2 Be of a delayed operation type (greater than 300mS);
3 The type of differential switch used must conform to product regulation EN62040-1-
1, Art. 4.5.12.
In the case of parallel distributed systems a single, common differential protection device
shall be fitted upstream of the point at which the line divides to supply the bypass inputs
of the UPS. Installation of separate devices in divers configurations can result in spurious
operation.
In order to guarantee correct current distribution in the neutral cables, installation person-
nel shall ensure that their lengths be as equal as possible.
If, however, the bypass lines are drawn from sources that are galvanically isolated from
each other, a differential protection device may be installed on each line.
N.B. In this case, and in cases when the load is supplied from the Bypass via the Bypass
Static Switch, the isolated sources are connected in parallel. It should be evaluated, on
an individual basis, whether any resultant imbalance between the currents on the Bypass
lines is compatible with the respective protection devices.
4.4.2. Primary mains input
These should be capable of protecting the primary AC mains supply up-line of the UPS,
and should take into account the maximum current drain of each UPS as shown in
Table 1 on page 21.
4.4.3. Bypass mains supply
Bypass mains input protection devices must have the following characteristics:
1 A max. current rating in accordance with the values in Table 1 on page 21;
2 A I2t rating lower than that of the thyristor (see “Static bypass” on page 85 for pre-
arc I2t ratings) in order to protect it in the event of an output short circuit - in order to
allow for component tolerances, the external protection device pre-arc I2t rating
should not exceed 80% of the SCR I2t rating;
3 A pre-arc I2t rating higher than that of the Inverter fuse (already fitted inside the UPS
- see “Static bypass” on page 85 for pre-arc I2t ratings) so that the Inverter fuse
blows in the event of an overcurrent caused by an internal failure. In this case the
load is supplied by the Bypass - in order to allow for component tolerances, the
external protection device pre-arc I2t rating should be at least 20% higher than that
of the Inverter fuse
4.4.4. Battery input
These should be capable of protecting the battery against short-circuits, and should take
into account the maximum current drain (in discharge at 1.8V per cell), see Table 1 on
page 21. These devices should be fitted as close as possible to the battery.
4.4.5. UPS Output line
As load(s) can be supplied through the Uninterruptible Power System from two sources,
the protection system on the output line should take into account the ratings of the fol-
lowing supplies:
Supply from inverter:
see Table 1 on page 21 and Table 11.1.4 on page 83
Supply from bypass static switch and maintenance bypass static switch:
see Table 1 on page 21 and Table 11.1.5 on page 85
N.B. If a single differential breaker is installed upstream of the UPS, any fault in the in-
stallation earthing system will result in the interruption of power to both the mains input
and the direct line.
Table 1 indicates cable dimensions and the protection devices (fuses) which must be
installed by the user to protect both these and the equipment.
1) For a nominal voltage of 380V multiply the current value by 1.05; for 415V, multpily by 0.95
The purpose of this note is to provide information and warning regarding a potential risk
to the operational integrity of an installed UPS system, posed by the presence of foreign
material inside or in the vicinity of the UPS module and the associated auxiliary equip-
ment/components.
This risk is especially high if conductive materials find their way inside the UPS module
or the associated auxiliary equipment/components.
The risk potentially involves damage to the installed UPS equipment, and subsequently
degradation or loss of power to the connected critical site-load.
CHLORIDE employs the highest safety standards in equipment design, to ensure that no
live parts are exposed to external contact, and also to ensure that the equipment is pro-
tected against the introduction of foreign bodies when operational (built to IP20 with op-
tional filters available for specific conditions).
However, it is not practically possible for CHLORIDE to ensure that foreign bodies will
not be introduced during the site installation works, when the UPS doors & covers are
"open" and the electrical-terminals are exposed for power-line connections to be made
by the electrical contractor/installer.
It is also not uncommon to have other trades working in the same (UPS equipment) room
during the site-installation period, sometimes involving working above the UPS equip-
ment and associated auxiliary equipment/components.
To avoid the possibility of a major disruption to site operations, and risks to prop-
erty and personnel, including the possibility of a fatality, it must be the responsi-
bility of each site's facility manager or construction manager, to ensure that the
introduction of foreign bodies to the UPS module and associated auxiliary equip-
ment/components is prevented.
UPS modules and their associated auxiliary equipment/components are all thoroughly in-
spected by CHLORIDE engineers prior to any commissioning and testing works being
performed on site. Our engineers are instructed to abort all live work upon identification
of conductive foreign bodies until the equipment and area has been thoroughly cleaned
of any contaminants.
However, the person responsible for the site must ensure that the UPS module and as-
sociated auxiliary equipment/components, and the immediate surroundings is kept clean
and free of any possible conductive material such as metallic foil, food wraps, cable
shields, washers and other hardware, scrap metal, swarf and dust.
If the UPS system is shutdown after the commissioning & testing works are completed,
the UPS room must be kept clean to avoid the possibility (during restart) of the consider-
able volume of air-flow produced by UPS operation to dislodge &/or drag any foreign bod-
ies into the equipment resulting in system failure and possible supply interruption to the
critical site-load, and several hours of downtime occasioned by the damage typically as-
sociated with such events.
If the UPS is left running/operational at the completion of the commissioning and testing
works, the room similarly needs to be kept clean to avoid ingress of any foreign bodies
into the UPS module via the UPS forced air-flow.
CHLORIDE will not accept any liability or expenditure associated with incidents caused
by the presence of introduced conductive foreign bodies in the UPS module or associat-
ed auxiliary equipment/components originated during pre-commissioning or post-com-
missioning activities within the UPS environment.
External External
protection protection
Backfeed
Protection
disconnector
U V W N U1 V1 W1
Battery
C+ XT4
D-
External
protection
U2 V2 W2 N
External
protection
To loads
Notice
In case of a TN-C distribution system, connect an insulated jumper be-
tween UPS ground and the UPS Neutral connector.
Refer to local Standards and regulations for the correct jumper cross
section.
Connect the mains supply PEN cable to the UPS Neutral connector (N).
Notice
Ensure that the mains and load conductors are connected to the UPS as a
clockwise (right hand) 3 phase system.
U V W N U1 V1 W1 U2 V2 W2 N
C+ D-
328 338
60/80kVA
U V W N U1 V1 W1 U2 V2 W2 N D-
C+
338
328
100/120kVA
C+ D-
U V W N U1 V1 W1 U2 V2 W2 N
361
328
160 kVA
C+ D-
U V W N U1 V1 W1 U2 V2 W2 N
394.5
358
200 kVA
Before connecting the batteries, please read the notice and warning
label on the UPS or battery cubicle.
Notice
Full safety instructions concerning the use and maintenance of UPS bat-
teries are provided in the appropriate battery manufacturers' manuals.
The battery safety information contained in this section relates to key con-
siderations which must be taken into account during the installation
design process, and may affect the design outcome, depending on local-
ised conditions.
Warning
Special care should be taken when working with the batteries associated
with the 80-NET. When all batteries are connected together the overall
voltage exceeds 500V.
It is most important to ensure that the batteries are installed separately, in
a purpose-designed, lockable, dedicated battery cabinet or battery room.
Battery cabinet specifications can be found in “Empty battery cubicle” on
page 77 of this manual.
Warning
In the event of malfunction, the battery shelves and/or cabinet chassis or
battery frames may become live!
Notice
The requirements of the EC directives are satisfied when battery cubicles
are used with original accessories. If alternative batteries are used, you
must ensure that the applicable EC directives are met and declare con-
formity. The UPS must still be parameterised with the service software
and fitted with an all-pole disconnecting device and fuses, according to
table 1 “Conductor cross sections and fuses of standard UPS”. When
dimensioning your battery cables, note the connection tolerances at ter-
minals +/-.
Warning
ENSURE CORRECT POLARITY !
Notice
The most common battery type used in UPS installations is the valve
regulated battery.
Valve regulated cells are not sealed.
The amount of gas given off is less than for flooded cells, but when plan-
ning the battery installation, allowance must be made for adequate ven-
tilation and heat dissipation.
Valve-regulated cells are not completely maintenance-free. They must
be kept clean and their connections checked periodically to ensure they
are tight, and that there is no evidence of corrosion.
It is inevitable that the batteries will lose some charge during transpor-
tation and storage; before attempting to carry out an autonomy test, en-
sure that the batteries are fully charged as this may take several hours.
Cell performance typically improves after a few discharge/recharge
cycles.
Notice
The battery charger is configured for 240 cells valve regulated battery
(2.27V/cell). The maximum recharge current setting is specified in tab.
10.1.3 (see: Max. batt. recharge current setting range: 240 cells @ Vi/p =
340 V and nominal load). Several charging methods, based on the type of
battery, are available and can be configured by authorized personal only.
QS9
C+ D-
X1
Warning
Batteries are a potential source of danger due to their electrical charge
and chemical composition. Therefore observe the battery handling
instructions of the manufacturer. These usually can be found in the mate-
rial which accompanies the shipment.
Notice
When recharging, observe the indications on the packaging
Notice
Before exchanging batteries, both the batteries in the cubicle, as well as
those to be installed must be fully charged.
Warning
If a battery has been disconnected and is to be reconnected, the battery
isolator may only be reconnected after you have made certain that voltage
with the correct polarity is present in the intermediate circuit (see Con-
necting the Batteries).
5. INTERFACES
80-NET is equipped with two slot card bays:
• a slot available for use with a connectivity option, typically ManageUPS Net SNMP
Adapter. Refer to CHLORIDE Connectivity Solutions for more details about available
expansion slot cards (XS3);
• a slot for the LIFE.net slot modem (see LIFE.net Software and Installation Instruc-
tions - 10H52127PAMC), this is fitted as standard (user removable) (XS6);
two standard serial interfaces:
• a RS232 COM interface configured for use with PPVIS or external connectivity solu-
tions (X3) - this is available when the XS3 slot is empty, or when the MUN card is
installed;
• a RS232 COM interface for data transfer protocol, modem or external connectivity
solutions (X6) - this is not available when the slot modem is installed;
Also available are:
• external Battery Temperature sensor (input - XT1);
• external Battery Switch status (input - XT2);
• EPO activated (output - XT3);
• Backfeed Protection activated (output - XT4);
• an AS400 compatible contact interface for signal exchange (output - X7);
• an interface to allow emergency shut down of the Bypass, Inverter and Rectifier
(EPO) (input - X8).;
All of which are located on the Connectivity Panel (see Fig. 13).
The optional I/O connectors (behind the cover on the Connectivity Panel) include
• 4 free parameterizable Input contacts (AP10 - XT6);
• 2 free parameterizable Output contacts (AP10 - XT5);
• Service Interface (AP10 - X4);
The interfaces can be used for:
• Direct communication between UPS and computer;
• Integration of the UPS as client into a network via MopUPS or ManageUPS (see
“MopUPS shutdown and monitoring software” on page 78)
• Transfer of operational states to external alarm systems
The required communication software and interface cables are available as options.
The interfaces can also be programmed via PPVIS (service software tool) for a wide range
of functions.
The serial interfaces are isolated and RS232 compatible.
The inputs are opto-isolated and can be driven by external dry-contacts (e.g. relay con-
tacts); the outputs are 24VDC 1A/120VAC 1A rated relay contacts.
XT3 XT4
XT1 XT2
I/0 XS3 XS6
CONNECTIONS
INSIDE
X8 X7 X3 X6
(N.C. EPO)
Notice
The interface cables must be shielded and located away from the power
cables (min. 20 cm). The shield must be connected at both ends. Control
and power cables must cross at a 90° angle.
For an external battery cabinet temperature measurement sensor, connect the temper-
ature sensor to the XT1 interface.
The interface is a 2-pole screw terminal (Phoenix 1.5/2 STF) that accepts wires up to
0.75mm2.
To monitor the state of an external battery breaker (open or closed), connect an auxiliary
contact to the XT2 interface.
The interface is a 2-pole screw terminal (Phoenix 1.5/2 STF) that accepts wires up to
0.75mm2.
For a remote indication of the EPO status, connect the XT3 interface to the input contacts
of an external alarm system. External contact rating: 1A 110 Vac.
The interface is a 2-pole screw terminal (Phoenix 1.5/2 STF) that accepts wires up to
0.75mm2.
If the energy backfeed via the electronic static switch is detected, the UPS generates a
logic command at the XT4 interface; connect this interface to the auxiliary terminals of a
switch capable of isolating the UPS input supply. External contact rating: 1A 110 Vac.
The interface is a 2-pole screw terminal (Phoenix 1.5/2 STF) that accepts wires up to
0.75mm2.
See Fig. 16 - i)
A
i) B
E
A
ii)
Warning
To avoid overheating inside the UPS, do not operate the unit with the rec-
tifier running, the Inverter switched off and the Bypass switch open for
extended periods.
IGBT
U1, V1,
W1 QS2
Rectifier
U, V, W U2, V2, W2
QS1
IGBT QS4
Inverter
QS14
Booster/Battery charger
Battery fuse
QS9
N C+, D- N
• QS1 = OPEN
• QS2 = OPEN
• QS3 = CLOSED
• QS4 = OPEN
• QS9 = OPEN
(See Fig. 6 on page 16 and Fig. 18 on page GB- 45).
Warning
During parallel operation of UPS units, the load switching function of the
built-in service bypass must be carried out by an external switching
device (see “If the loads no longer need power, you may now open the
6.6. COMMISSIONING
6.6.1. Forming
If the UPS devices have not been used for a period of more than one year, the interme-
diate circuit capacitors must be reformed. If the UPS devices are commissioned within
one year after delivery (check nameplate), this action is not necessary.
Danger
Do not connect any devices that may overload the UPS or draw direct cur-
rent from it.
Notice
If these instructions are not observed correctly, problems may be experi-
enced with the electrical supply.
UPS xxxkVA may be viewed (see “Display” on page 53), and the
STOP IN STANDBY buzzer is silenced, while the Inverter continues to
supply the load
Once the last Inverter Stop button has been pressed for two seconds, all the Inverters in
the system switch off and the Load is transferred to the Bypass supply.
Until all the Inverters have switched off and the Load is transferred to the Bypass, the
"STOP IN STANDBY" command may be reset on any, or all, of the UPS, by pressing the
Inverter Start button on the control panel for a minimum of two seconds.
Refer also to para 7.2. on page 53
6.8.3. Parallel UPS - Start Inverter
To switch ON the Inverters of the UPS in a parallel system, press, and hold, the Inverter
Start button on each UPS control panel, one by one, after two seconds, the message:
Once the last Inverter Start button has been pressed, all the Inverters in the system
switch ON and the Load is supplied from the Inverters.
Until all the Inverters have switched ON the "START IN STANDBY" command may be re-
set on any, or all, of the UPS by pressing and holding the Inverter Stop button on the con-
trol panel for a minimum of two seconds.
Refer also to para 7.2. on page 53
DISPLAY
1 4
5 6
7
10
8
11
• Start Inverter
Press the Inverter ON button for 5 seconds.
• Stop Inverter
Press the Inverter OFF button for 5 seconds, an audible alarm will sound during
this delay period.
The UPS can be manually switched between bypass and on-line operation using the keys
“Inverter ON” (I) and “Inverter OFF” (O).
• Silencing Buzzer
To silence the Buzzer press the Reset button momentarily
• Reset button
In order to restore normal operation of the UPS following a fault condition, after having
corrected the situation causing the fault, press the Reset button for at least one second.
The RESET button also serves as a function control for the control panel LEDs. All LEDs
on the control panel illuminate for approx. 1.5 s after pressing the button in normal oper-
ation (no warning or fault indicators present), followed by the last five warning indicators
appearing one after the other in the two-digit display. If a fault occurs, pressing the button
mutes the audible signal and, once the fault has been corrected, pressing the button
brings the UPS into operation again.
• Keyboard lock
The mimic panel is equipped with a front panel key that disables all the mimic panel com-
mands when the lock is set to “OFF”.
In this state, if the operator attempts to perform any of the following actions, the mes-
sage "COMMANDS DISABLED" appears in the LCD:
7.2. DISPLAY
The Display provides the user with a range of information and functions that can be ac-
cessed using the control panel navigation keys 1 to 4 (see Fig. 23 - on page 51).
UPS modifications and settings may only be carried out by appropriately qualified
technicians. Settings should be tested only if the loads supplied by the UPS are
non-critical.
The Main Page dispays a block diagram of the UPS, using standard technical symbols to
indicate the current operating state (e.g. on-line operation, battery operation, by-pass op-
eration, etc.), load level, and remaining auonomy. To access the Main Menu page from
the Main (default) page, press the Right soft key (key 4 - see Fig. 23 - on page 51). From
here you can scroll through the various sub-menus by using the Up and Down soft keys
(2 and 3). Press the Right soft key to select any menu from the list, and the Left soft key
(1) to return to the Main Menu page.
After 30 seconds of inactivity (i.e. without buttons being pressed) the display reverts to
the default page.
The table on the following page provides a summary of the sub-menus.
When the UPS is not in normal operating mode, you can access the "Warning and Alarm"
summary page directly from the Main (default) page. Warnings and alarms are identified
by text strings and codes (see Table 11 on page 62 and Table 12 on page 65). When bat-
tery operation, the display switches between warning code and estimated backup time
(minutes).
Notice
The acoustic alarm may be activated at various times in this procedure. It
can be switched off by pressing the "Test/Reset" pushbutton.
Warning messages may appear briefly on the display. However, these may
be disregarded.
To access the guided procedures select “Guided Procedures” from the display Main
Menu (see Table 9 on page 54). The procedures available for the current UPS configura-
tion are displayed. The following table lists the various procedures that can be carried out
for each configuration:
Manual Bypass
Stop
Exit Inverter
The various UPS switches are also represented - the Maintenance Bypass switch, QS3,
is shown in the open (OFF) position in the above example - these show the current status
of the switches, and flash to indicate the user must open, or close, the corresponding
switch.
In this case, the message “Stop Inverter” appears in the bottom right of the display, and
the Stop symbol flashes over the Inverter, indicating that the user must stop
the Inverter by pressing the corresponding button on the “Control Panel” on page 51.
(See “Instruction messages” on page 60 for full list of instruction messages).
PROCEDURE:
Manual Bypass
3 The message “Close QS3” is displayed, and the symbol representing QS3 on the
display begins to flash.
4 The message “Open QS4” is displayed, and the symbol representing QS4 on the
display begins to flash.
Manual Bypass
QS4
Manual Bypass
QS2
Manual Bypass
QS9
Exit Open QS9
7 The message “Open QS1” is displayed, and the symbol representing QS1 on the
display begins to flash.
Manual Bypass
QS1
Manual Bypass
Procedure not OK
Waiting Bypass ON
7.7. TROUBLESHOOTING
7.7.1 Rectification of Errors
If, in spite of the high reliability of this device, problems should occur, please check the
following points before contacting the responsible customer service representative:
Is the mains voltage present at the UPS input?
Is the input fuse defective or have circuit breakers tripped?
If you contact the responsible customer service representative, please have the follow-
ing information ready:
• Device information = model, order no., series no. as per nameplate
• An exact description of the problem (what loads are being operated, does the
problem occur regularly or sporadically etc.)
8. MAINTENANCE
8.1. MAINTENANCE INTERVALS
CHLORIDE recommends that regular maintenance checks be carried out on site by an
authorized customer service. The UPS indicates when the end of a fan’s lifetime has ex-
pired (see Table 12 on page 65). A replacement fan is recommended.
8.4. DECOMMISIONING
8.4.1. Taking out of service
Switch to service bypass
• Switch the UPS to Maintenance Bypass operation (see Table 6 on page 49)
Disconnect batteries
• Open the battery isolator or battery switch if other external batteries are used.
• Before continuing work, measure the voltage at the battery terminals and at the
mains input and wait until this has dropped to 0 V or wait at least 5 min. Failure to do
this can lead to severe electrical shock and possibly death.
The UPS is now in maintenance bypass operating mode. The only voltage present is at
the mains and load terminals. Qualified personnel may now carry out maintenance work
while observing the corresponding safety measures.
Disconnect mains
If the loads no longer need power, you may now open the external mains separation de-
vice for the UPS.
9. PARALLEL OPERATION
Uninterruptible power supplies can be connected in parallel to increase power capacity
or for additional safety (redundancy). If the UPS units are equipped with the additional
POB (Parallel Operation Board) assembly, up to 8 of the same UPS blocks can be oper-
ated in parallel for increased power capacity or redundancy. Your UPS units are equipped
with this option if the order number on the nameplate contains the letter “B” in the ninth
position: CH80 xx-xxBxx-xxxx.
This feature can also be added at a later time and is, therefore, available as an option.
A multiple-block system is automatically regulated and controlled via the controller of the
individual UPS blocks. The available electronic bypasses in the individual blocks work to-
gether just as all the corresponding inverters and divide the load current between them.
All necessary communication for parallel operation is carried out via a shielded 25 con-
ductor cable. Each UPS block is shipped with a 5m long communication cable which is
sufficient for most installation requirements.
When planning the system and during installation, power cables having the same length
are to be used between the input distribution and the input terminals for the bypass and
rectifier (U, V, W, - U1, V1, W1, N), as well as from the UPS outputs (U2, V2, W2, N) to
the parallel connection point on the load side. Differences of 20% are allowed for power
cable lengths of up to 20 m. For larger distances, cable lengths may not vary by more
than 10%. The PE and N terminals must be connected in accordance with the require-
ments of the local mains distribution system (TN-C, TN-S, TN-C-S, TT etc.) For instance,
in TN-C installations the PEN conductor from the supply transformer must be connected
to the UPS PE and N terminals. See note to “External electrical connections” on page 25,
and Fig. 25 on page 75.
9.1. COMMISSIONING
Commissioning of multiple-block systems must be carried out by appropriately trained
technicians.
2)
To
Load
N
BYPASS
3) 1)
U, V, W U2, V2, W2
PE
BLOCK n
N
BYPASS
3) 1)
U, V, W U2, V2, W2
PE
LOAD
L1 DISTRIBUTION
L2
PEN L3 1) See technical data chapter for fuse ratings
2) Values determined by dimension of Service Bypass
3) Circuit breaker or fuse
4) External Service Bypass (Ext.SB) - must be
a switch, a fused switch or a circuit breaker
4)
2)
AP10 - XT6 *
BYPASS
U2
U V2
W2
1) V 3)
W
PE
BLOCK n
AP10 - XT6 *
BYPASS
U2
U V2
W2
1) V 3)
W
PE
BLOCK 1
BLOCK n
BY-
PASS
BLOCK 2
BY-
PASS
BLOCK 1
BY-
PASS
10. OPTIONS
Some of the options listed in this section may modify the data in the standard technical
data tables (see “Technical data” on page 81). It may not be possible to use certain op-
tions simultaneously on the same UPS.
Synch. with
internal ±.1%
clock
Frequency slew rate <1 Hz/s
Output voltage distortion at
100% nominal load <3%
Notice
Pay attention to the information provided on the device labels.