Professional Documents
Culture Documents
P.O Box: 53620 Italy
Al Qusais Industrial Area 3 Chloride Silectron
Damascus Street Via France 30
Dubai, UAE. 40023 Castel Guelfo (BO)
Tel: + 971 4 26 766 26 Italy
Fax: + 971 4 26 766 16 Telephone : + 39 0542 632 111
www.site-technology.com Fascimile : + 39 0542 632 120
Italy_sales@chloridepower.com
CHLORIDE UPS 80‐NET SUPERVISORY
OPERATION TRAINING MANUAL
CHLORIDE UPS 80‐NET SUPERVISORY
OPERATION TRAINING MANUAL
P.O Box: 53620
Italy
Al Qusais Industrial Area 3
Chloride Silectron
Damascus Street
Via France 30
Dubai, UAE.
40023 Castel Guelfo (BO)
Tel: + 971 4 26 766 26
Italy
Fax: + 971 4 26 766 16
Telephone : + 39 0542 632 111
www.site-technology.com
Fascimile : + 39 0542 632 120
Italy_sales@chloridepower.com
TABLE OF CONTENTS
TRAINING MODULES
1. TRAINING COURSE SUMMARY
2. THE DESIGN BLOCK DIAGRAM
3. DESCRIPTION OF SYSTEM
4. TRAINING PRESENTATION
5. OPERATION PROCEDURE
6. EMERGENCY & SAFETY
7. OPERATING MODE
8. NORMAL AND SAFE OPERATIONS
9. REFERENCES
1
TRAINING COURSE SUMMARY
COURSE SUMMARY
BASIC LEVEL TRAINING
WHY A UPS DISTURBANCE EMERGENCY&SAFETY
TYPE?
THE DESIGN BLOCK DIAGRAM OPERATING MODE
DESCRIPTION OF SYSTEM NORMAL AND SAFE
OPERATIONS
REFERENCES
TRAINING PRESENTATION
END OF TRAINING QUIZ
OPERATION PROCEDURE
2
THE DESIGN BLOCK DIAGRAM
3
DESCRIPTION OF SYSTEM
CHLORIDE 80-NET
UPS Systems from 60 to 200 kVA
1 Scope
This specification describes a continuous and without interruption, upon failure mission critical converters within the
duty three-phase, solid state, full IGBT or degradation of the commercial AC UPS, are driven by vector control algo-
(Insulated Gate Bipolar Transistor), dou- source. rithms (covered by patents 95 P3875,
ble conversion uninterruptible power The continuity of conditioned electric 95 P3879 and 96 P3198) running on
supply (UPS) system. The UPS shall power shall be delivered for the time dedicated digital signal processor
automatically provide continuity of period defined by the battery system. (DSP) systems.
electrical power, within defined limits The rectifier, the inverter, and other
2 System Description
The single line diagram of the UPS is upon failure or degradation of the com-
shown in Figure 1. The systems shall • Increased power quality mercial AC source. The duration of
operate on two DSP-driven IGBT con- autonomy (i.e. back up power time) in
verters. The vector control technology • Full input Power Factor Correction the event of network failure shall be
will enhance the performance of these (PFC) and very low THDi determined by the battery capacity.
converters. In order to increase sys-
tem redundancy, an independent elec- • Full compatibility with any installa- 2.2 Models available
tronic static bypass shall be integrated tion and/or any standby power gen-
into the UPS. By adding system com- erator The 80-NET range shall include the fol-
ponents, such as parallel kits, CROSS lowing three-phase input/output mod-
switches, safety and disconnecting • Full compatibility with all types of els:
devices, system bypass switches, in loads
addition to software and communica- MODEL Rating (kVA)
tions solutions, it shall be possible to • Power blackout protection 80-NET/60 60
set up elaborate systems to ensure 80-NET/80 80
the complete protection of the loads. • Full battery care
80-NET/100 100
2.1 The system • Energy saving features. 80-NET/120 120
The UPS shall provide high quality AC The UPS shall automatically provide 80-NET/160 160
power for electronic equipment loads continuity of electrical power, within 80-NET/200 200
and shall offer the following features: defined limits and without interruption,
Maintenance Bypass
Bypass
Input
Bypass static
switch
Primary Output
Input Load
Fuse
IGBT IGBT
Rectifier Inverter
Booster/Battery charger
Battery Fuse
Battery System
MKA4CAT0UK80NET/Rev. 4-12/2007/UK 02
CHLORIDE 80-NET
UPS Systems from 60 to 200 kVA
3 Device Description
80-NET is the result of an innovative 3.3.1 Double Conversion Mode 3.3.2 Digital Interactive Mode (DIM)
research and development programme (DCM)
designed to offer users the most reli- If priority has been set to digital inter-
able power supply at a minimum cost 3.3.1.1 Normal (DCM) active mode, intelligent double conver-
and the highest possible energy con- sion technology shall allow 80-NET to
version efficiency. The UPS inverter continuously sup- continuously monitor the condition of
plies the critical AC load. The rectifier the input supply including its failure
3.1 Components derives power from the commercial rate to ensure maximum reliability for
AC source and converts it into DC critical users. On the basis of the
The UPS shall consist of the following power for the inverter and the battery analysis performed, it shall decide
major components: charger. The Battery Charger keeps the whether to supply the load through the
Battery in a fully charged and optimum direct line or the conditioned line.
• IGBT Rectifier operational condition. The inverter con- This operational mode, which allows
verts the DC power into clean and reg- significant energy savings by increas-
• IGBT Battery Charger / Booster ulated AC power which is supplied to ing the overall AC/AC efficiency of the
the critical load (conditioned line). The UPS, is primarily intended for general
• IGBT inverter static switch monitors and ensures purpose ICT applications. However, it
that the inverter tracks the bypass sup- does not provide the same output
• Dedicated digital signal processor ply frequency. This ensures that any power quality as when the UPS oper-
(DSP) control systems for each automatic transfer to the bypass sup- ates in double conversion mode.
IGBT converter ply (due to an overload etc.) is fre- Therefore it will be necessary to verify
quency synchronised and does not whether this mode is appropriate for
• Electronic static switch and bypass cause interruption to the critical load. special applications. Digital interactive
supply mode is not available for parallel sys-
3.3.1.2 Overload (DCM) tems.
• Manual maintenance bypass
switch In the event of an inverter overload, 3.3.2.1 Normal (DIM)
manual stop or failure, the static
• Matching battery cubicles switch shall automatically transfer the The operating mode will depend on
critical load to the bypass line without the quality of the mains supply in the
3.2 Microprocessor control and interruption. short-term past. If the line quality has
diagnostics remained within permitted tolerance
3.3.1.3 Emergency (DCM) parameters in this timeframe, the
Operation and control of the UPS shall direct line will provide continuous sup-
be provided through the use of micro- Upon failure or reduction of the com- ply to the critical AC load through the
processor-controlled logic. Indications, mercial AC source (see the Technical bypass static switch. The IGBT inverter
measurements and alarms, together Data table for tolerances) the inverter control will remain in constant opera-
with battery autonomy, shall be shown shall supply the critical load, drawing tion and synchronisation with the
on an illuminated, forty character liquid power from the associated battery direct line without driving the IGBT.
crystal display (LCD). The procedures through the battery Booster. There This ensures that the load can be
for start up, shutdown and manual shall be no interruption to the critical transferred to the conditioned line
transfer of the load to and from bypass load upon failure, reduction or restora- without any break in supply where
shall be explained in clear step-by-step tion of the commercial AC source. there is a deviation from the selected
sequences on the LCD display. While the UPS is powered by the bat- input power tolerance levels. If the
teries, indications shall be provided of direct line failure rate has been outside
3.3 Intelligent double conversion actual autonomy time remaining as permitted parameters, 80-NET shall
operating modes well the duration of the mains failure. supply the load from the conditioned
line. The battery charger supplies the
80-NET shall adopt intelligent double 3.3.1.4 Recharge (DCM) energy necessary for maintaining max-
conversion technology which allows imum charge to the battery.
the UPS to operate in double conver- Upon restoration of the commercial
sion or digital interactive mode accord- AC source, even where batteries are
ing to the selected priority. completely discharged, the rectifier
The UPS will operate as follows: shall restart automatically, 'walk in'
and gradually take over both the invert-
er and battery charger. This function
shall be fully automatic and shall cause
no interruption to the critical load.
03 MKA4CAT0UK80NET/Rev. 4-12/2007/UK
CHLORIDE 80-NET
UPS Systems from 60 to 200 kVA
3 Device Description
3.3.2.2 Inverter stop (DIM) ditioned line for a period of time This will thus render possible the real-
dependant on the direct line failure time control of the inverter electronics,
If the inverter is stopped for any rea- rate (the conditioned line draws power resulting in obvious advantages con-
son there is no transfer to the condi- from the mains not the battery). cerning the performance of the power
tioned line and the load continues to When the direct line has stabilised, components. These advantages will
be supplied by the direct line. The 80-NET returns to normal operation. be:
mains voltage and frequency values The battery charger automatically
must be within the tolerance limits begins to recharge the battery, so that • Improvement of short circuit
specified. maximum autonomy is guaranteed in behaviour, as individual phases can
the shortest possible time. be more quickly controlled
3.3.2.3 Overload (DIM)
3.3.3 Maintenance bypass • Synchronism or phase angle preci-
In the event of an overload with a dura- sion between UPS output and
tion in excess of the maximum capaci- If for any reason it is necessary to take bypass supply even in the case of a
ty specified for the bypass static the UPS out of service for mainte- distorted mains voltage
switch, the load is maintained on the nance or repair, the UPS shall be fitted
direct line and a warning message on with an internal maintenance bypass • High flexibility in parallel operation:
the LCD display will appear (F52) to switch which enables a load transfer to parallel blocks may be housed in
warn the user about the potential risk a bypass supply with no interruption to separate rooms.
related to this condition. This default power to the critical load. Bypass iso-
behavior can be changed (via a Service lation shall be complete, all service- Several algorithms included in the
accessible firmware setting) to force a able components such as fuses, Vector Control firmware are covered
load transfer to the conditioned line power modules etc. shall be isolated. by patents owned by Chloride (95
(similar to that described below) even Transfer/retransfer of the critical load P3875, 95 P3879 and 96 P3198).
if the bypass source is available. In the may be accomplished by automatic
event of an overload in conjunction synchronisation of the UPS to the 3.4.2 Redundancy, preventive
with an unsuitable bypass mains sup- bypass supply and paralleling the monitoring
ply, 80-NET shall transfer the load from inverter with the bypass source,
the direct line to the conditioned line before opening or closing the bypass In order to maximise the reliability of
(assuming 80-NET was operating from switch as appropriate. the system, the control unit shall mon-
the direct line) and the inverter shall itor a wide number of operating para-
continue to supply the critical load for 3.3.4 Operation without battery meters for the rectifier, inverter and
a period dependant on the degree of battery. All vital operating parameters,
the overload and the UPS features. If the battery is taken out of service for such as temperatures, frequency and
Visual and audio alarms alert the user maintenance, it has to be disconnect- voltage stability at the system input
to the problem. ed from the UPS by means of an exter- and output, load parameters and inter-
nal switch (e.g. situated in the battery nal system values shall be constantly
3.3.2.4 Emergency (due to mains cabinet). monitored and controlled for irregulari-
supply failure or variance beyond The UPS will continue to operate and ties at all times. The system shall react
tolerance limits, DIM) meet the performance criteria speci- automatically before a critical situation
fied with the exception of the battery arises either for the UPS or the load, in
If 80-NET is supplying the load via the backup time. order to ensure the supply of the load
direct line and the bypass mains sup- even in these difficult conditions.
ply varies beyond tolerance levels 3.4 Control and diagnostics
(adjustable using the software), the 3.4.3 Telediagnosis and
load will be transferred from the direct Control of the power electronics mod- telemonitoring
line to the conditioned line. The load is ules shall be optimised in order to pro-
powered from the mains via the recti- vide: In all the above modes of operation,
fier and inverter, (provided the input the UPS may be monitored and con-
mains remains within the tolerances • optimum three-phase supply of the trolled from a remote location such as
stated in tables 11 and 12). Should the load a service centre, in order to maintain
input mains falls below the lower limit the reliability of the system at nominal
the batteries shall be used to power • controlled battery charging levels. Even during complete shut-
the load via the inverter. The user is down of the UPS, information relating
alerted to the battery discharge by • minimum phase effects upon the to the operating parameters shall not
visual and audio alarms and the supply network. be lost thanks to non volatile RAMs,
remaining autonomy is displayed on which will store the information for up
the LCD. During this process, it is pos- By using digital signal processors to 10 years.
sible to extend the remaining autono- (DSP) 80-NET shall implement the
my by switching off non-essential most advanced digital control.
loads.
3.4.1 Vector control
3.3.2.5 Return to normal conditions
(DIM) To ensure the quick and flexible pro-
cessing of measuring data, special
When the mains supply returns to arithmetic algorithms shall be imple-
within tolerance limits, 80-NET will mented in DSP, rapidly generating con-
continue to supply the load via the con- trolled variables as a result.
MKA4CAT0UK80NET/Rev. 4-12/2007/UK 04
CHLORIDE 80-NET
UPS Systems from 60 to 200 kVA
4 General Requirements
4.1 Applied standards 4.4 Neutral connection and
• IEC/EN62040-3 operating require- grounding
Chloride operates a Quality Manage- ments.
ment System which complies with BS The 80-NET output neutral shall be
EN ISO 9001-2000 for the design, • Classification according to IEC/EN electrically isolated from the UPS chas-
manufacture, sales, installation, main- 62040-3: VFI-SS-111 sis. The input and output neutral con-
tenance and service of uninterruptible nections are the same, i.e. they are
power supply systems. The Chloride 4.2 Safety solidly tied together.
Environmental Policy and Manage- Therefore the UPS shall not modify the
ment Systems comply with EN ISO 14 In terms of general and safety require- state of the upstream neutral, in any
001 and Chloride is committed to ments, the UPS conforms to standard operating mode, and the neutral state
implementing a policy of continuous IEC/EN 62040-1-1 governing use in of the distribution downstream from
improvement to production processes unrestricted access locations. the UPS is imposed by the mains one.
and pollution reduction. 80-NET shall 80-NET shall be used in installations
carry the CE mark in accordance with 4.3 EMC and surge suppression with grounded neutral; for further
the Safety and EMC Directives details please contact Chloride
2006/95 (superseding the 73/23 and Electromagnetic effects shall be min- Technical Support.
successive amendments), 89/336, imised in order to ensure that comput-
92/31 and 93/68. 80-NET is designed er systems and other similar electron- 4.5 Materials
and manufactured in accordance with ic loads shall neither be adversely
the following international standards: affected by nor affect the UPS. The All materials and components com-
UPS shall be designed to meet the prising the UPS shall be new and of
• IEC/EN62040-1-1 general and safe- requirements of EN 50091-2, class RS. current manufacture.
ty requirements The manufacturer and customer in
partnership agree to ensure the essen-
• EN50091-2 EMC requirements tial EMC protection requirements for
the specific resulting installation.
05 MKA4CAT0UK80NET/Rev. 4-12/2007/UK
CHLORIDE 80-NET
UPS Systems from 60 to 200 kVA
80%
• To recharge the batteries taking the
power from the DC bus, when the
primary input mains is within the Time
given tolerances
Battery
• To provide the suitable full DC status
power, taken from the batteries, to
the IGBT output inverter if the pri- Charging/
mary mains is unavailable. floating
idle
6.2 Battery charger mode (no discharge)
The selection of the optimum charging 6.5.1 Sealed, maintenance-free lead • Minimum battery test voltage
method shall be completely managed acid accumulators: (V) 1.9
by the microprocessor. Several differ-
ent charging methods are available. Charging is at constant current up to • Nominal voltage (V) 2.0
the maximum floating voltage level.
6.3 Voltage regulation, temperature Thereafter the voltage shall be kept at • Battery discharging alarm (V) 2.20
compensation a constant level within narrow limits @ 20°C
(single-step charging method).
In order to ensure optimum battery • Float voltage (V) 2.27 @ 20°C
charging, float voltage shall be auto- 6.5.2 Sealed, low-maintenance lead
matically adjusted to the ambient tem- acid accumulators or NiCd accumu- • High voltage alarm (V) 2.4
perature. The IGBT rectifier shall be lators:
capable of supplying the battery charg- 6.7.2 Automatic battery test
er with DC voltage at rated power, Charging is at increased charging volt-
even if the UPS input AC voltage is age and constant charging current The operating condition of the
below the nominal voltage specified. A (boost charge phase). When the charg- batteries shall be automatically tested
further reduction of the input AC volt- ing current falls short of a lower thresh- by the control unit at selectable
age (within specified limits) will inhibit old value the battery charger shall auto- intervals, e.g. weekly, fortnightly or
the battery charger but will not require matically return to floating voltage level monthly. A short-time discharge of the
the discharging of the batteries. See (two-step charging method). battery will be made to confirm that all
Figure 3 for details. the battery blocks and connecting
6.6 Overvoltage protection elements are in good working order.
6.4 Residual ripple filtering In order to preclude a faulty diagnosis
The battery charger shall automatically the test will be launched 24 hours after
The battery charger output shall have a switch off if the DC battery voltage the latest battery discharge at the
residual voltage ripple of <1% RMS. exceeds the maximum value associat- earliest. The battery test shall be
ed with its operational status. performed without any risk to the load,
6.5 Capacity and charging charac- even if the battery is completely
teristics 6.7 Battery management defective. Users shall be alerted to a
detected battery fault. The battery test
When the primary mains is not suit- Using advanced battery care (ABC) the shall not cause any degradation in terms
able to supply the rectifier, the DC/DC 80-NET series shall increase battery of the battery system life expectancy.
converter (booster mode) will provide life by up to 50%. The main battery
the required power to the inverter care features are described as follows. 6.7.3 Ambient temperature
using the energy stored in the battery. compensated battery charger
After the discharge of the battery and 6.7.1 Operating parameters
when the input AC power is restored, The float voltage shall be automatically
the rectifier will power the inverter and When operating with a maintenance adjusted as a function of the tempera-
recharge the batteries through the free, valve regulated lead acid battery ture in the battery compartment
DC/DC converter in battery charger (VRLA), the parameters per cell shall (-0.11% per °C) in order to maximise
mode. The following charging methods be as follows: battery operating life.
MKA4CAT0UK80NET/Rev. 4-12/2007/UK 06
CHLORIDE 80-NET
UPS Systems from 60 to 200 kVA
From the DC voltage of the intermedi- The inverter transient voltage shall not The inverter shall provide harmonic neu-
ate circuit the inverter shall generate exceed Class 1 limits when subjected tralisation and filtering to limit the THD
sinusoidal AC voltage for the user load to application or removal of 100% load on the voltage to less than 3% with a
on the basis of pulse-width modulation as defined by IEC/EN62040-3. linear load. For reference non-linear load
(PWM). By means of the digital signal (as defined by IEC/EN62040-3) the THD
processor (DSP) of the control unit the 7.3 Frequency regulation shall be limited to less than 5%.
IGBT of the inverter shall be controlled
so that DC voltage is divided up into The inverter output frequency shall be 7.5 Neutral sizing
pulsed voltage packets. Thanks to a controlled to achieve the following per-
low-pass filter the pulse-width modu- formances: The sizing of the inverter neutral shall
lated signal shall be converted into be oversized on all ratings in order to
sinusoidal AC voltage. No isolation 7.3.1 Steady state cope with the combination of harmon-
transformer is needed for the IGBT ics on the neutral wire when driving
inverter, with the great benefits of: The inverter steady-state output fre- single-phase reference non-linear
energy conversion efficiency, physical quency, when synchronised to bypass loads. The inverter neutral is sized x 1.7
size and weight of the modules. supply, shall not deviate by more than in relation to the phase.
±1% adjustable to ±2%, ±3%, ±4%.
7.2 Voltage regulation 7.6 Overload
7.3.2 Frequency slew rate
The inverter output voltage on the The inverter shall be capable of sup-
three phases shall be individually con- The frequency slew rate shall be <1 Hz plying an overload of 125% for 10 min-
trolled to achieve the following perfor- per second. utes and 150% for one minute of the
mances: nominal power.
7.3.3 Frequency slew rate
7.2.1 Steady state 7.7 Inverter shutdown
The output frequency of the inverter
The inverter steady state output volt- shall be controlled by a quartz oscilla- In the event of an internal failure the
age shall not deviate by more than tor which can be operated as a free inverter shall be immediately shut down
±1% in a steady state condition for running unit or as a slave for synchro- by the control unit. The UPS device or
input voltage and load variations within nised operation with a separate AC the parallel-operated UPS systems shall
the quoted limits. source. The accuracy of the frequency continue to supply the load from the
control shall be ±0.1% when free-run- bypass supply without interruption, if it
ning. is within permissible limits.
07 MKA4CAT0UK80NET/Rev. 4-12/2007/UK
CHLORIDE 80-NET
UPS Systems from 60 to 200 kVA
The inverter shall guarantee the sym- The inverter short circuit capacity of
metry of the output voltages at ±1% 80-NET for the first 10ms shall be
for balanced loads and ±3% for 100% >200% for any short circuit configura- Output Power
unbalanced loads. tion. After the first 10ms, it shall limit
the current to >150% for not more 115
7.9 Phase displacement than 5s, then it shall shut down.
112
MKA4CAT0UK80NET/Rev. 4-12/2007/UK 08
CHLORIDE 80-NET
UPS Systems from 60 to 200 kVA
Graphical LCD
screen
Navigation buttons:
left soft-key,
up and down button,
right soft-key
“System Normal”
LED
“Reset” push button
(e.g. audible signal
silence for warning
ON OFF and alarm conditions)
“Warning” LED
KEYBOARD
9.3 Start and Stop inverter push The control shall incorporate a safety
buttons feature to prevent inadvertent opera-
Start inverter operation
tion yet still allow for rapid shutdown in
The Start and Stop push buttons are the event of an emergency. To stop the
integrated into the mimic panel board, inverter the user must press and hold
and have the following predefined the Stop button for two seconds. An
functions: audio alarm shall be activated during
Stop inverter operation this delay time.
09 MKA4CAT0UK80NET/Rev. 4-12/2007/UK
CHLORIDE 80-NET
UPS Systems from 60 to 200 kVA
9.6 LCD display menus description IGBT Rectifier and Booster/Battery Load/Bypass Static Switch
Charger converter This menu shall display alarms, current
By using the appropriate push buttons This menu shall display rectifier status, per phase, frequency measurements,
it shall be possible to browse the fol- booster/charger status, alarms, volt- load percentage capacity per phase
lowing menus: age, total DC current, battery current and the peak factor Ipk/Irms for each
with polarity and battery temperature. phase of the load current. It shall be
When the output inverter is supplied possible to display the total time the
by the battery, the module shall display load has been supplied by the inverter,
remaining autonomy time. A change in and by bypass, the number of mains
load shall cause the autonomy indica- failures and the total duration of these
tor to display the new autonomy time. failures.
Bypass Supply
This menu shall display alarms, phase
to neutral voltages and frequency
measurements.
MKA4CAT0UK80NET/Rev. 4-12/2007/UK 10
CHLORIDE 80-NET
UPS Systems from 60 to 200 kVA
11 MKA4CAT0UK80NET/Rev. 4-12/2007/UK
CHLORIDE 80-NET
UPS Systems from 60 to 200 kVA
The UPS handles 6 Input/Output digital Fan (On-Off) In Battery Compartment Battery Fuse Monitor
control signals (4 inputs, 2 outputs)
that can be programmed via the Battery Compartment Overheated Generator On
display and/or PPVIS (service software Hydrogen Present Remote Inverter Stop
tool) for a wide set of functions. The
inputs are opto-isolated and can be SBS Bypass Switch Closed Air conditioning failure
driven by external dry-contacts (e.g. SBS Output Switch Open
relay contacts); the outputs are relay
contacts rated 1A, 230V AC/DC.
Emergency Power Off (EPO) is
programmed as standard: this
command electronically shuts down
the rectifier, the inverter and the
bypass switch. The backfeed
protection control (see paragraph 8.2)
command is associated with a
dedicated contact output terminal
(refer to the User Manual for further
details).
9.9 LIFE.net The communication of UPS data to the The service centre shall analyse histor-
Chloride LIFE Command Centre shall ical data and issue a regular detailed
In order to increase the overall reliabil- take be transmitted via the integrated report to the customer informing him
ity of the system, 80-NET will be deliv- modem at the following intervals: of the UPS operational condition and
ered with the LIFE.net communication any critical states.
kit, providing connection to Chloride’s • ROUTINE: settable at intervals of The LIFE.net centre allows the possi-
LIFE.net diagnostic service. between five minutes and two bility of activating the LIFE-SMS deliv-
LIFE.net shall allow the remote diagnosis days (typically once a day) ery system option, where the cus-
of the UPS through telephone lines or tomer may receive SMS notification
GSM link in order to ensure maximum • EMERGENCY: when a problem which will be activated in the event of
reliability of the UPS throughout its occurs or parameters are beyond one of the following:
operational life. The monitoring shall be tolerance limits
a real 24-hour, 365 day service thanks • Mains power failure
to a unique feature that allows trained • MANUAL: following a request
Service Engineers to remain in con- from the command centre • Mains power recovery
stant electronic contact with the ser-
vice centre, and therefore the UPS. During the call the command centre • Bypass line failure
The UPS shall automatically dial up the shall:
service centre at defined intervals to • Load supplied by reserve.
provide detailed information that shall • Identify the UPS connected
be analysed in order to predict near
term problems. In addition, it shall be • Request the data stored in the UPS
possible to control the UPS remotely. memory since the last connection
MKA4CAT0UK80NET/Rev. 4-12/2007/UK 12
CHLORIDE 80-NET
UPS Systems from 60 to 200 kVA
10 Mechanical Data
10.1 Enclosure If these conditions are not met (with 10.4 Enclosure design
one fan failed), the UPS shall supply
The UPS shall be housed in a space- the load through the static bypass if an All surfaces of the enclosure shall be
saving modular enclosure with front overheating of the converters occurs. finished with an electrostatically
doors and removable panels (protec- The failed fan condition will be applied epoxy coat. The coating shall
tion as standard to IP 20). The enclo- immediately notified by the UPS have a thickness of at least 60
sure shall be made of zintec coated through all the user interfaces and microns. Standard colour of the
sheet steel. The doors shall be lock- through the LIFE.net service. The enclosure shall be RAL 7035 (light
able. cooling air entry shall be in the base grey).
and the air exit at the top of the device.
10.2 Ventilation The enclosure shall be installed with at 10.5 Access to integrated
least 500 mm of free space between subassemblies
Forced redundant air cooling will the device and roof of the enclosure in
ensure that all the components are order to allow cooling air to exit All internal subassemblies shall be
operated within their specification. unhindered. accessible for typical and most
Airflow shall be controlled according to frequent maintenance from the front
load demand. The UPS shall also be 10.3 Cable entry of the unit via hinged doors. Rear
capable of preserving normal opera- access shall not be required for
tions even with one cooling fan Cable entry shall be from the bottom installation or servicing. The UPS shall
stopped (due to a failure) with 70% of or bottom-side of the cabinet. Top be forkliftable from the side after the
the output nominal load @ 25°C ambi- cable entry shall be available as an removal of the bottom trim panels.
ent temperature. option.
11 Environmental Conditions
The UPS shall be capable of with- 11.1 Ambient temperature 11.3 Altitude
standing any combination of the envi-
ronmental conditions listed below. It 0° to 40°C The maximum altitude without derat-
shall operate without mechanical or Maximum average daily temperature ing shall be 1000 metres above sea
electrical damage or degradation of (24 hr) 35°C level (for higher altitudes 80-NET com-
operating characteristics. Maximum temperature plies with IEC/EN 62040-3).
(8 hr) 40°C
13 MKA4CAT0UK80NET/Rev. 4-12/2007/UK
4
TRAINING PRESENTATION
80-Net TRAINING COURSE
80-Net TRAINING COURSE
PRODUCT DESCRIPTION
BLOCK DIAGRAM
OPERATIONAL PROCEDURES
POWER DIAGRAMS
CONTROL LOGIC
PICTURES
80-Net TRAINING COURSE
PRODUCT DESCRIPTION
New topology UPS which uses an IGBT inverter in place of the usual
SCR rectifier.
MAIN CHARACTERISTICS:
Low input THDi
Hi h efficiency
High ffi i
SIZES AVAILABLE:
April 2005 = 80kva & 120kva ->
> (60) – 80 – (100) - 120
End of 2005 = 160kva & 200kva
80-Net TRAINING COURSE
BLOCK DIAGRAM
RSS
RECT INV
CHARGER/
BOOST
80-Net TRAINING COURSE
INSTALLATION & CONNECTIONS
NEUTRAL CONNECTION
The unit require the presence of an input neutral connected to reserve and primary lines.
The two neutrals are linked inside the UPS.
SERVICE ACCESSIBILITY
The unit can be completely maintained from the front. Side panels are remouvable.
Fans can be replaced from top side.
BYPASS
1 - stop inverter
2 – close bypass switch QS3
3 – open output switch QS4
4 – open battery switch QS9
5 – open reserve switch QS2
6 – open input switch QS1
80-Net TRAINING COURSE
OPERATIONAL PROCEDURES
SAFETY
Due to the absence of an Inverter Static switch (see ‘Power diagrams’ section for more details),
the inverter is always directly connected with AC output, as well as the DC section, through
the reverse diodes of inverter IGBTs.
IGBTs
RSS ON
RECT OFF
QS4 CLOSED
QS9 OPEN
80-Net TRAINING COURSE
PICTURES
OUTPUT SWITCH
QS4
BATTERY SWITCH
QS9
5
OPERATION PROCEDURE
OPERATION PROCEDURES –REDUNDANT WITH EXTERNAL BYPASS
START-UP
SHUTDOWN
1. Switch OFF Inverter by pressing push button for at least 3 seconds of both the UPS (A&B) continuously in the
front panel display.
2. Switch OFF QS4 of both UPS (A& B).
3. Switch OFF QS6/F1-QS7/F2 / QS9 of both UPS (A&B)
4. Switch OFF QS2 of both UPS (A&B).
5. Switch OFF QS1 of both UPS (A&B).
1. Switch OFF the Inverter by pressing push button in the front panel of both the UPS (A&B) at least 3 seconds
continuously.
2. Turn the External Bypass Switch Handle to position I+II and then to position II
3. Switch OFF QS4 of both UPS (A&B).
4. Switch OFF QS6/F1-QS7/F2/ QS9 of both UPS (A&B).
5. Switch OFF QS2 of both UPS (A&B)
6. Switch OFF QS1 of both UPS (A&B).
1. Switch ON QS1 of UPS (A&B) and wait for DC voltage build up.
2. Switch ON QS2 of UPS (A&B) ensure the static bypass is turned ON.
3. Switch ON QS6/F1-QS7/F2/ QS9 of UPS (A&B).
4. Switch ON QS4 of UPS (A&B).
5. Turn the External Bypass Switch Handle to position I+II and then to position I
6. Press Inverter ON push button of both the UPS (A&B) for 3 seconds continuously in the front panel display.
1. Press Inverter OFF & Reset pushbutton together of the particular UNIT for 3 seconds continuously in the front
panel display.
2. Make sure the Inverter is OFF for that UNIT and then Switch OFF QS4.
3. Disconnect the POB cables and join them together to reset the faults on the other UPS.
4. Switch OFF QS6/F1-QS7/F2 / QS9 for that UNIT.
5. Switch OFF QS2 for that UNIT.
6. Switch OFF QS1 for that UNIT.
1. Switch ON QS1 of the UPS and wait for DC voltage build up.
2. Reconnect the POB Cables in the UNIT and reset the faults on both the UPS (A&B).
3. Switch ON QS2 of the UPS.
4. Switch ON QS6/F1-QS7/F2/ QS9 of the UPS.
5. Switch ON QS4 of the UPS.
6. Press Inverter ON push button of the UPS for 3 seconds continuously in the front panel display.
QS1-MAINS INPUT BREAKER
QS2-RESERVE INPUT ISOLATOR
QS6F1-QS7F2/QS9- BATTERY ISOLATOR
QS4-OUTPUT ISOLATOR
QS5/QS14-NEUTRAL BREAKER.
SHUTDOWN
1. Switch OFF Inverter by pressing push button for at least 3 seconds of the UPS continuously
in the front panel.
2. Switch OFF QS4 of the UPS.
3. Switch OFF QS6F1-QS7F2/QS9 of the UPS.
4. Switch OFF QS2 of the UPS.
5. Switch OFF QS1 of the UPS.
1. Switch OFF the Inverter by pressing push button in the front panel of the UPS at least 3
seconds continuously.
2. Switch ON QS3 of the UPS.
3. Switch OFF QS4 of the UPS.
4. Switch OFF QS6F1-QS7F2/QS9 of the UPS.
5. Switch OFF QS2 of the UPS.
6. Switch OFF QS1 of the UPS.
1. Switch ON QS1 of the UPS and wait for the DC voltage build up.
2. Switch ON QS2 of the UPS ensure the static bypass is turned ON.
3. Switch ON QS9 of the UPS.
4. Switch ON QS4 of the UPS.
5. Switch OFF QS3 of the UPS.
6. Press Inverter ON push button of the UPS for 3 seconds continuously in the front panel
display.
6
EMERGENCY AND SAFETY
80-NET – Technical Manual
1.2 Safety
1.2.1 General
Chloride puts personal safety before all other considerations. For this reason, before
carrying out any work on the UPS units, you must carefully read all the safety
procedures indicated in this manual as well as in the user manual and apply them.
What’s important?
80-Net contains dangerous voltages. As a result, any work which requires opening of the
protective panels must only be carried out by technical personnel authorised by Chloride .
Any maintenance work carried out in the UPS units must always be done with the
machine in bypass state, as indicated in the user manual.
Before starting to service the UPS, be sure to read this manual carefully for a correct
and safe operation.
Warning:
The intermediate circuit contains voltages, even after the mains power supply voltage has
been disconnected. Before operating inside the equipment, always disconnect the
batteries using the disconnecting switch and make sure that the voltages in the
intermediate circuit has dropped to 0V.
The connections between the rectifier and the inverter remain live for a considerable time.
Any work on the UPS including parameter changes should only be performed, if the reaction of
the UPS is absolutely clear and not harming the UPS or its proper function. If you are not sure
what the reaction will be, please contact the Chloride Service Support, before you act.
1.2.2 Emergency
In the event of an emergency, you can immediately cut the power supply to the
machinery by simply opening all of the switches in the unit. Open output switch QS4
first, before opening the other switches. These switches are located behind the door on
the front of the 80-NET.
You can also cut the power by pressing the EPO emergency stop push button, if this
option is installed.
Warning:
In case of using the EPO, be aware that the battery voltage is still present on the UPS!!
What’s important?
Do not touch the casualty with your hands until
he or she has been isolated from all the live parts.
After this seek immediately help.
What’s important?
It must always be remembered that, once the second access panels are removed, live
components are exposed.
7
OPERATING MODE
80-NET – Technical Manual
Online mode
Normal UPS operating mode.
The connected loads are supplied from the
mains via the inverter. The batteries are
charged as necessary. The inverter reliably
filters mains disturbances and provides a
stable, interference-free supply to the load.
On the control panel, when the UPS is in
online operation, the green “OK” LED is
illuminated. Figure 1-4: Operating Mode – Online
In this operating mode, the UPS switches to battery operation if a mains failure occurs.
If an overload or short circuit occurs at the UPS output, or if there is a fault in the
inverter, the UPS switches to bypass operation.
Battery mode
In this operating mode, the connected load
is supplied from the batteries via the
inverter.
In the event of power failure, battery
operation is automatically activated and
supplies the loads without interruption. If the
power failure lasts longer than 30 s, the
UPS signals a Warning condition (Warning
18i1). Figure 1-5: Operating Mode - Battery
In battery operation, the “OK” LED (green) on the control panel and the “WARNING”
LED (yellow) are flashing.
From this operating mode, the UPS automatically returns to online operation within the
backup time once the mains supply returns. If the power failure lasts longer than the
loads can be supplied by the battery, the UPS provides relevant information via its
interfaces. Computers can be automatically powered down with additional software
(optional).
Bypass mode
In this operating mode, the connected loads
are supplied from the mains via the
electronic bypass. The electronic bypass
serves to further ensure power to the loads.
If an overload or short-circuit at the UPS
output occurs, it is automatically activated to
ensure uninterrupted power supply to the
loads.
Figure 1-6: Operating Mode - Bypass
The “WARNING” LED (yellow) on the control panel illuminates and every 30 seconds a
acoustic signal is given.
From this operating mode, the UPS automatically returns to online operation after the
fault is corrected.
8
NORMAL AND SAFE OPERATION
CHLORIDE 80-NET Normal and safe operation
Warning
To avoid overheating inside the UPS, do not operate the unit with the rec-
tifier running, the Inverter switched off and the Bypass switch open for
extended periods.
U1, V1,
W1 QS2
IGBT
Rectifier
U, V, W U2, V2, W2
QS1
IGBT QS4
Inverter
QS14
Booster/Battery charger
Battery fuse
QS9
N C+, D- N
• QS1 = OPEN
• QS2 = OPEN
• QS3 = CLOSED
• QS4 = OPEN
• QS9 = OPEN
(See Fig. 6 on page 16 and Fig. 15 on page 39).
Warning
During parallel operation of UPS units, the load switching function of the
built-in service bypass must be carried out by an external switching
device (see chapter 8 “PARALLEL OPERATION”).
9
REFERENCES
REFERENCES