You are on page 1of 41

OISD-RP-149

FOR RESTRICTED
CIRCULATION ONLY
No.

DESIGN ASPECTS FOR SAFETY


IN
ELECTRICAL SYSTEM

OISD - RECOMMENDED PRACTICES - 149


First Edition, February, 1996
Amended Edition, September 2001

Oil Industry Safety Directorate


Government of India
Ministry of Petroleum & Natural Gas
OISD - RP - 149
First Edition
February, 1996
Amended Edition,
September 2001

FOR RESTRICTED
CIRCULATION ONLY

DESIGN ASPECTS FOR SAFETY


IN
ELECTRICAL SYSTEM

Prepared by:
COMMITTEE ON “DESIGN ASPECTS FOR ELECTRICAL SAFETY”

OIL INDUSTRY SAFETY DIRECTORATE


2ND FLOOR, “KAILASH”
26, KASTURBA GANDHI MARG
NEW DELHI - 110 001
NOTE
OISD publications are prepared for use in the oil and gas
industry under Ministry of Petroleum and Natural Gas. These are the
property of Ministry of Petroleum and Natural Gas and shall not be
reproduced or copied and loaned or exhibited to others without written
consent from OISD.

Though every effort has been made to assure the accuracy and
reliability of the data contained in these documents, OISD hereby
expressly disclaims any liability or responsibility for loss or damage
resulting from their use.

These documents are intended to supplement rather than


replace the prevailing statutory requirements.

Note 3 in superscript indicates the


modification/changes/addition based on the
amendments approved in the 19 th Safety Council
meeting held in September, 2001July, 1999
FOREWORD

Oil Industry in India is nearly 100 years old. Due to various collaboration
agreements a variety of international codes, standards and practices are in vogue,
Standardisation in design philosophies, operating and maintenance practices at a
national level was hardly in existence. This lack of uniformity coupled with feedback from
some serious accidents that occurred in the recent past in India and abroad, emphasised
the need for the industry to review the existing state of art in designing, operating and
maintaining oil and gas installations.

With this in view, the Ministry of Petroleum and Natural Gas in 1986 constituted
a Safety Council assisted by the Oil Industry Safety Directorate (OISD) staffed from
within the industry in formulating and implementing a series of self-regulatory measures
aimed at removing obsolescence, standardising and upgrading the existing standards to
ensure safer operations. Accordingly OISD constituted a number of functional
committees comprising of experts nominated from the industry to draw up standards and
guidelines on various subjects.

The present document on “Design Aspects for Safety in Electrical System” was
prepared by the Functional committee on “Design Aspects for Electrical Safety”. This
document is based on the accumulated knowledge and experience of industry members
and the various national and international codes and practices.

It is hoped that provisions of this document if implemented objectively, may go a


long way to improve the safety to reduce accidents in Oil and Gas Industry. Users are
cautioned that no document can be a substitute for the judgement of responsible and
experienced engineer.

Suggestions are invited from the users after it is put into practice to improve the
document further. Suggestions for amendments, if any, to this standard should be
addressed to :

The Co-ordinator
Committee on “Design Aspects for Electrical Safety”
Oil Industry Safety Directorate
2nd Floor, “Kailash”
26, Kasturba Gandhi Marg
New Delhi - 110 001

This document in no way supersedes the statutory regulations of Chief Controller


of Explosives (CCE), Factory Inspectorate or any other statutory body which must be
followed as applicable.
COMMITTEE
ON
DESIGN ASPECTS FOR ELECTRICAL SAFETY
---------------------------------------------------------------------------------------------------------------------------------
NAME ORGANISATION
---------------------------------------------------------------------------------------------------------------------------------
LEADER

Shri V. P. Sharma Engineers India Limited

MEMBERS

Shri R. Sankaran Madras Refineries Limited

Shri U. P. Singh Indian Oil Corporation Limited

Shri Narendra Kumar Gas Authority of India Limited

Shri R. Raghupathy Engineers India Limited

MEMBER CO-ORDINATORS

Shri N. V. Mani Oil Industry Safety Directorate

Shri J. K. Jha Oil Industry Safety Directorate


---------------------------------------------------------------------------------------------------------------------------------
In addition to the above, several other experts from Industry contributed in the preparation,
review and finalisation of this document.
DESIGN ASPECTS FOR SAFETY IN ELECTRICAL SYSTEM

CONTENTS
-------------------------------------------------------------------------------------------------------
SECTION DESCRIPTION PAGE NO.
---------------------------------------------------------------------------------------------------------------------------------
1.0 INTRODUCTION

2.0 SCOPE

3.0 DEFINITIONS

4.0 POWER SYSTEM DESIGN

4.1 Capacity of Electrical Plant

4.2 Neutral Earthing

4.3 Short Circuit Capacities

4.4 Insulation Coordination

4.5 Protection and Metering

4.6 Emergency Power Supply

4.7 Critical Power Supply Systems

5.0 ELECTRICAL EQUIPMENT FOR CLASSIFIED


AREA

6.0 SUB-STATION LOCATION/LAYOUT

7.0 ELECTRICAL EQUIPMENT

7.1 Characteristics

7.2 Equipment Features

7.2.1 Transformers

7.2.2 H.V/M.V Switchboards

7.2.3 Motors (H.V & M.V)

7.2.4 Battery Charger and Distribution Board

7.2.5 Batteries and Battery Accessories

7.2.6 Equipment for Uninterrupted Power Supply


System

7.2.7 Capacitor Banks

7.2.8 Emergency Generator

---------------------------------------------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------------------
SECTION DESCRIPTION PAGE NO.
---------------------------------------------------------------------------------------------------------------------------------

7.2.9 Cables

7.2.10 Control Station

7.2.11 Convenience Receptacles

7.2.12 Actuators for Motor Operated Valves

8.0 PLANT CABLING

9.0 Plant Lighting

10.0 Plant Earthing

11.0 PLANT SAFETY AND SECURITY SYSTEMS

11.1 Plant Fire Detection and Alarm System

11.2 Communication System

11.2.1 Telephone System

11.2.2 Public Address System

11.2.3 Emergency Communication System


(Hot Line System)

11.2.4 Radio Communication System

a) Portable Walkie-Talkie System


b) VHF System

11.2.5 Telex System

12.0 MOBILE EQUIPMENT FOR HAZARDOUS


AREAS

12.1 Portable Hand Lamps

12.2 Diesel Engines

12.3 Storage Batteries

12.4 Testing Equipment

12.5 Miscellaneous Requirements

12.6 Vehicles

13.0 REFERENCES

=====================================================================
DESIGN ASPECTS FOR SAFETY IN ELECTRICAL SYSTEM

1.0 INTRODUCTION A connection to the general mass of


earth by means of an earth electrode. An
Safety in electrical system draws object is said to be ‘earthed’ when it is
maximum attention especially in the electrically connected to an earth
hydrocarbon industry, where classified electrode; and a conductor is said to be
hazardous atmosphere may be ‘solidly earthed’ when it is electrically
encountered and electricity may connected to earth electrode without a
constitute one of the sources of ignition fuse, switch, circuit-breaker, resistance or
for fire accidents and explosions. Besides impedance in the earth connection.
equipment damage and property loss,
electrical hazards may lead to injuries ii) Earth Continuity Conductor -
and fatalities to personnel due to electric
shock and burns. The electrical system The conductor, including any clamp,
designer, hence, faces a challenge to connecting to the earthing lead or to each
provide a safe and reliable electrical other of those parts of an installation
system. which are required to be earthed.

It is therefore imperative that safety iii) Earth Electrode -


aspects are built into the electrical
system right from the design and A metal plate, pipe or other conductor
engineering stage with the main objective embedded in the soil that makes a direct
of minimising equipment/system failure contact to the general mass of the earth.
to prevent injury to personnel and
damage to system components. iv) Earthing Lead -

Following the guidelines and adhering to The final conductor by which the
the safe practices given in this standard, connection to the earth electrode is made.
would ensure adequate levels of safety in
the electrical facilities of Oil Industry. v) Voltage, Low - (LV)

2.0 SCOPE The voltage which does not normally


exceed 250 volts.
This document recommends minimum
requirements in the design and vi) Voltage, Medium - (MV)
engineering of electrical installations in
the petroleum oil and gas sector. The voltage which normally exceeds 250
However, this standard does not cover volts but does not exceed 650 volts.
offshore installations. It also excludes
drilling rigs and well head installations. vii) Voltage High - (HV)
This standard is not intended for use as a
comprehensive design manual for The voltage which normally exceeds 650
electrical power system design. The volts but does not exceed 33 KV
standard in no way supersedes the
statutory regulations of the Chief viii) Voltage, Extra-High-(EHV)
Electrical Inspectorate, Factory
inspectorate, Chief Controller of The voltage which exceeds 33 KV under
Explosives, Director General Mines normal conditions.
Safety, Central Electricity Authority or ix) Impulse -
other Government bodies, which shall be
followed as applicable. Usually a periodic transient voltage or
current which rises rapidly to a peak value
and then falls, generally more slowly, to
3.0 DEFINITIONS zero.

I) Earth Connection - x) Earth Fault -]


Accidental connection of a conductor to A general term covering switching
earth. When the impedance is negligible, devices and their combinations with
the connection is called a dead earth-fault. associated control, measuring,
protective and regulating equipment;
xi) Earth Leakage Current - also assemblies of such devices and
equipment with associated inter-
The current following to earth on account connections, accessories, enclosures
of imperfect insulation. and supporting structures intended in
principle for use in connection with
xii) Insulation Fault - generation, transmission, distribution
and conversion of electrical energy.
An abnormal decrease in insulation Controlgear are switching devices
resistance. intended in principle for the control of
electrical energy consuming equipment.
xiii) Overload -
xx) Flame Arrestor -
Operating conditions in an electrically
undamaged circuit which cause an A device for releasing gas from an
overcurrent. enclosure in such a way that in case of
an internal explosion there is no
xiv) Short-Circuit - appreciable increase in internal pressure
and the released gas will not ignite the
The intentional or accidental connection of surrounding flammable atmosphere.
two points of a circuit. The term is often
applied to the group of phenomena which xxi) Nominal Voltage (of an Installation)
accompany a short circuit between points
at different potentials. Voltage for which an installation or part
of an installation is designated.
xv) Symmetrical breaking current
xxii) Highest System Voltage
The symmetrical breaking current, during
opening of a circuit breaker in the event of The highest R.M.S. phase to phase
a short circuit, is the r.m.s. value of the voltage, which occurs under normal
symmetrical short circuit current flowing operating conditions at any time and at
through the first phase to open at the any point in the system. It excludes
instant of contact separation. voltage transients (such as those due to
system switching) and temporary
xvi) Peak short circuit current voltage variation due to abnormal
system conditions (such as those due to
This is the highest instantaneous value of fault conditions on sudden disconnection
current after the occurrence of short of large loads).
circuit. It is given as a peak value. Its
magnitude depends on the instant of the xxiii) Lightning Protective System -
cycle at which the short circuit occurs.
The whole system of interconnected
xvii) Redundancy conductors used to protect a structure
from the effects of lightning.
Duplication of elements in a system or
installation, for the purpose of xxiv) Portable Equipment -
enhancing the reliability or continuity of
operation of the system or installation. Equipment which can be moved even
while in operation or which can easily
xviii) Electrical Equipment - be moved from one place to another
while connected to the electric supply.
The electrical machines, apparatus and
circuits forming part of an electrical xxv) Hand-Held Equipment -
installation or a power system.
Portable equipment intended to be
xix) Switchgear and Controlgear- held in the hand during normal use in
which the motor, if any, forms an
integral part of the equipment.
capable of ignition is likely to be
xxvi) Stationary Equipment - present;

Either fixed equipment or equipment b) Petroleum or any flammable liquid


not provided with a carrying handle having flash point above 65°C is
and having such a mass that it cannot likely to be refined, blended,
easily be moved. handled or stored at or above its
flash point.
xxvii) Fixed Equipment -
Zone 0 An area in which a flammable
Equipment fastened to a support or atmosphere is present
otherwise secured in a specific continuously, or is present for long
location. periods.

xxviii) Self Powered Vehicle - Zone 1 An area in which a flammable


atmosphere is likely to be present
A vehicle used for the conveyance of periodically or occasionally during
stationary equipment (e.g. normal operation.
compressors), personnel or goods in
which petroleum or storage battery is Zone 2 An area in which a flammable
used to generate the motive power. atmosphere is not likely to occur in
normal operation and if it does
xxix) Flammable Material - occur, it will exist for a short time
only.
A flammable material is a gas, vapour,
liquid, and/or mist which can react xxxiv) Non-hazardous (Safe) Area -
continuously with atmospheric oxygen
and which may therefore, sustain a An area, no part of which is within a
fire or explosion when such reaction is hazardous area.
initiated by a suitable spark, flame or
hot surface. xxxv) Electrical Apparatus for Hazardous
Areas
xxx) Flammable Mixture -
Electrical apparatus which will not
A mixture of flammable gas, vapour, ignite the surrounding flammable
or mist with air under atmospheric atmosphere in which it is used.
conditions, in which after ignition,
combustion spreads throughout the xxxvi) Intrinsic Safety (Ex-i) (Ref : IS : 5780)
unconsumed mixture.
A circuit or part of a circuit is
xxxi) Hazard - intrinsically safe when any spark or
thermal effect produced normally (that
The presence, or the risk of presence, is, by breaking or closing the circuit)
of a flammable mixture. or accidentally (for example by short-
circuit or earth fault) is incapable,
xxxii) Hazardous (Flammable) Atmosphere - under prescribed test conditions, of
causing ignition of a prescribed gas or
In accordance with the Petroleum vapour.
Rules, an atmosphere containing any
flammable gas or vapour in a An intrinsically safe apparatus is one
concentration capable of ignition. in which all electrical circuits are
intrinsically safe. It is placed in one of
xxxiii) Hazardous Area - the following categories:

In accordance with the petroleum


rules, an area shall be deemed to be a
hazardous area, where:
a) Category (Ex-ia)
a) Petroleum having flash point
below 65°C or any flammable gas Apparatus in this category is
or vapour in a concentration incapable of causing ignition in
normal operation, or with a single service are immersed in oil to a
fault, or with any combination of sufficient depth to prevent ignition of
two faults applied with a specified an explosive gas mixture that may be
safety factor for current and/or present above the surface of the oil,
voltage. and all live parts on which areas do
not occur in normal service are either
b) Category (Ex-ib) immersed in oil or protected by some
other recognised techniques.
Apparatus in this category is
incapable of causing ignition in xxxxi) Non-sparking Apparatus (Ex-n) (Ref :
normal operation, or with any IS 8289) -
single fault applied, with a
specified safety factor for current Apparatus which in normal operation
and/or voltage. is not capable of igniting a
surrounding explosive atmosphere,
xxxvii) Flameproof Enclosure (Ex-d)-(Ref : IS and in which a fault capable of
: 2148) causing ignition is not likely to occur.

An enclosure for electrical apparatus xxxxii) Increased Safety (Ex-e) (Ref : IS :


that will withstand, when the covers or 6381)
other access doors are properly
secured, an internal explosion of the A method of protection in which
flammable gas or vapour which may measures additional to those adopted
enter it or which may originate inside in ordinary industrial practice are
the enclosure, without suffering applied, so as to give increased
damage and without communicating security against the possibility of
the internal flammation to the external excessive temperatures and the
flammable gas or vapour for which it occurrence of arcs or sparks in
is designed, through any joints or electrical apparatus which does not
structural openings in the enclosure. produce arcs or sparks in normal
service.
xxxviii) Pressurised Enclosure (Ex-p) (see IS :
7389 (part 1) - xxxxiii) Special Protection ‘S’ -

An enclosure for electrical apparatus A kind of protection which does not fall
in which the entry of flammable gas or into any of the recognised techniques,
vapour is prevented by maintaining but which may be demonstrated to
the air (or other non-flammable gas) afford equivalent levels of protection
within the enclosure at a pressure to equipment intended for use in
above that of the external classified hazardous areas. This is to
atmosphere. develop new ideas before standard
specifications are available.
xxxix) Sand-filled apparatus (Ex-q) (Ref : IS :
7724)- The certificate will normally describe
the techniques and conditions of use.
Electrical apparatus which has all its
live parts entirely embedded in a
mass of powdery material, in such a 4.0 Power System Design
way that under the conditions of use
for which the apparatus has been i) The design of electrical installation
designed, no arc occurs within the shall ensure provision of a safe and
outer explosive atmosphere either by reliable supply of electricity at all
the transmission of flame or by the times. Safe conditions shall be
overheating of the walls of the ensured under all operating conditions
enclosure. including those associated with start-
up and shut down of plant, as well as
xxxx) Oil Immersed Apparatus - (Ex-o) those arising out of failure of electrical
(Ref : IS : 7693) - equipment. The isolation of a part of
system of electrical equipment due to
Electrical apparatus in which all parts either maintenance or shutdown shall
on which are may occur in normal not compromise safety. Power
distribution system shall constitute - Critical loads (e.g. computer, fire
sub-stations located near load centres water pumps, communication,
as far as practical. instrumentation controls etc.)

ii) The design shall be broadly based iii) Required redundancy (based on specific
upon the following factors: process/operating needs) shall be built in
the substation which feeds power supply
- Safety to personnel and equipment to the process units/important facilities so
during operation and maintenance, that in case of tripping of one feeder, the
unit/facility may not be adversely affected.
- Reliability of service,
iv) The power system design shall ensure
- Ease of maintenance, system reliability. This assumes particular
significance where inplant generation
- Convenience of operation, supplements the external power supply.
For this, quick isolation of inplant system
- Maximum interchangeability of from faulty grid, inplant load shedding etc.
equipment, may need detailed consideration.

- Elimination of fire risk, v) Before carrying out system design, it is


recommended that the following minimum
- Facility for ready addition of future information/data be obtained, from the
loads. power supply authorities:

- Suitability for applicable a) Incoming grid voltage and frequency,


environmental factors. actual variation limits, guaranteed
power availability.
iii) Special attention is drawn to Chapter X
of IE rules which includes requirements b) Existing fault level of feeding bus and
for design of electrical system as system expansion factor for fault
applicable to oil mines. level.

4.1 Capacity of Electrical Plant c) Location of feeding substation and


routing of supply lines/feeder and the
reliability of power supply.
i) All the components of the electrical
system shall be sized to suit the d) Size of conductor and current carrying
maximum load, under the most severe capacity.
operating conditions. The amount of
electrical power consumed by each e) Supply system neutral earthing.
process unit shall be calculated for its
operation at the design capacity. f) Details of protection relays and their
Accordingly, the maximum settings at sending end breaker side.
simultaneous consumption of power,
required by continuously operating g) Required metering arrangements at
loads shall be considered and receiving end.
additional margin shall be taken into
account for intermittent service loads, if vi) When capacitors are added to the system
any. for power factor improvement, necessary
system study may be carried out to
ii) While carrying out load analysis, loads decide measures for avoiding problems
shall be characterised under different due to hormonics, system resonance,
heads as under: oscillatory torques in rotating equipment,
in rush current, increase in voltage
- Normal loads across capacitors due to use of series
(continuous/intermittent loads) reactor, harmonic loading of capacitor,
etc. The above assumes particular
- Essential loads (Emergency loads) significance where there is captive
generation.

4.2 Neutral Earthing


unearthed system) unearthed system shall
4.2.1 Earthed System have provision for detecting earth fault and
for isolation of faulty section through the
i) Power system neutral shall be earthed: use of core balance current transformers.
The current transformers (CTS) shall be
a) To limit the difference of electric potential sized in relation to the system capacitive
between all uninsulated conducting currents arising due to distributed
objects in a local area. capacitance of the entire network. The
system shall also include alarm/tripping
b) To provide for isolation of faulty equipment provision using unbalance voltage sensing
and circuits when a fault occurs. through open delta potential transformers
(PTs) under earth fault conditions. Besides
c) To limit overvoltages appearing on the it is recommended that provision of ‘on line
system under various conditions. insulation monitoring facilities’ may be
considered.
ii) The neutral earthing system employs one
of the following methods: 4.3 Short Circuit Capacities

a) Solid earthing for low, medium voltage i) Each short-circuit interrupting device shall
system (upto 650V) and for high have fault duty higher than the maximum
voltage above 11 K.V. value of short circuit current calculated at
its location. The related switchgear and bus
b) Resistance earthing for 3.3 KV to 11KV ducts shall withstand the above maximum
system. fault current (mechanical and thermal
stresses) for a minimum duration of one
iii) The values of neutral earthing resistors second.)
normally applied in industrial power
system are selected to meet the governing ii) The sizing of high voltage cables shall be
criteria for limiting transient over-voltages, based on the short circuit withstand
i.e. earth fault current should not be less capacity for a minimum time period as
than the system charging current. dictated by the protection system in
Besides, the value of neutral earthing addition to the maximum anticipated load
resistor selected shall limit the earth fault current carrying capacity.
current to a value, which shall be sufficient
for selective and reliable operation of iii) It is to be noted that in the case of
earth fault protection system. generators, whose excitation power is
terminal dependent, short circuit in the
However, where an earthing transformer is system will result in drop of the terminal
used for obtaining the system neutral, the voltage and consequently the over-current
zero sequence reactance limit (i.e. RO > 2 protective devices may not get adequate
X0) should also be considered. (R0 - zero current for operation. To avoid such a
sequence resistance of the circuit situation, necessary excitation support shall
including neutral resistor and X0 zero be provided unless & otherwise required.
sequence inductive reactance of the
circuit). iv) While sizing, the system necessary
consideration shall be given to restrict the
iv) The neutral earthing resistor shall be able system voltage drop within permissible
to carry at least 10% of its rated current limits during starting of large rated motor
continuously, unless otherwise required, or group of motors. At the same time, the
and full rated current (100%) for a short circuit current shall be kept within
minimum duration of 10 seconds. limits keeping in view of the market
availability of switchgears. Reduced
4.2.2 Unearthed System voltage starting (soft start feature) for
motors may be considered as per system
i) It is recommended that use of unearthed requirements.
system may be avoided since arcing
ground faults can result in severe over 4.4 Insulation coordination
voltages.
i) The insulation of electrical facilities shall
ii) Where unavoidable (such as expansion be designed considering the system
projects where existing systems have voltage, the system neutral earthing, and
the over-voltages resulting due to system general, and plant feeders connected to a
fault, switching or lightning surges. The captive power plant bus in particular.
insulation co-ordination between the Wherever the system is resistance
electrical equipment and the protective earthed, restricted earth fault protection
devices shall be done in line with IS: 3716 may be provided for transformer
and IS: 2165. secondary.

ii) Insulation coordination is a correlation of iv) Particular care should be taken in the
insulation of equipment and circuit with selection of protective devices for
the characteristic of protective devices machines and equipment operating in
such that the insulation is protected from hazardous areas, so as to isolate the
over voltages. faulty section in the shortest time possible.
For high voltage system, protective relays
iii) The rated insulation level of Switchgears shall be used. For medium voltage
shall refer to the power frequency systems, direct acting releases and/or
withstand voltage and impulse voltage protective relays may be employed.
withstand values which characterise the
insulation. In respect of systems with In general, quick acting relays (with time
nominal voltage of 132 KV and above, full delays if necessary) shall be used and all
insulation values shall be considered for fault tripping shall be done through high
non-effectively earthed system, and speed tripping relays.
reduced insulation values may be used for
effectively earthed system. v) The supply of Energy to every electrical
installation other than low voltage
4.5 Protection and Metering installations below 5 KW and those low
voltage installations which do not attract
i) The protective system shall be selected provisions of Section 30 of the Indian
and coordinated to ensure the following: Electricity Act, 1910, shall be controlled by
an earth leakage protective device so as
a. Protection of equipment against to disconnect the supply instantly on the
damage which can occur due to internal occurrence of earth fault or leakage of
or external short circuits, overloading, current (IE Rule 61A).
abnormal operating conditions,
switching, lightning surges, etc. Provided that the above shall not apply to
overhead supply lines having protective
b. The continuity of operation of those devices which are effectively bonded to
parts of the system not affected by the the neutral of supply transformers and
fault, is maintained. conforming to Rule 91 of I.E. Rules, 1956.

c. Personnel and plant safety. vi) Metering instruments shall be provided on


plant Main Switch Board to monitor the
ii) Accordingly, relays and protective devices power consumption and supervision of all
shall be suitably selected and coordinated. concerned parameters like current,
As a minimum, differential protection shall voltage, power, frequency, power factor
be provided for the following: etc. Ammeters in the field for monitoring
motor current may be provided as per
a. Transformers rated 5 MVA and above, process requirements. Metering and
protection current transformers shall be
b. Induction and synchronous motors preferably kept separate. In the case of
rated 1500 KW and above, contactor controlled feeders having long
length of control cables (more than 800
c. Generators rated 2 MVA and above. Mts. or so) due consideration shall be
given to the effect of capacitance on
d. Bus differential shall be provided for all ON/OFF operations of contactor.
H.T. switchgear having direct
connection with the inplant generators vii) Recommended relay protections for
and other vital H.T. switchgear. Transformers, motors and feeders which
are generally encountered in distributing
iii) Longitudinal differential protection shall be network are given below :
provided for important plant feeders in
---------------------------------------------------------------------------------------------------------------------------------
RELAY TRANSFORMER MOTOR OUTGOING INCOMER
REF :ANSI/IEEE POWER DIST HV HV MVPCCC HV MVPCC
(IEEC 37.2)
--------------------------------------------------------------------------------------------------------------------------------
A. 51 IDMTL O.C. YES YES - YES YES YES YES
(4) (4)

B. 51(N) IDMTL E.F. YES NO - YES YES YES YES


(7) 4) (4)

C. 5IN BACK UP E.F. YES YES - NO NO NO NO


(SECONDARY SIDE
NEUTRAL)

D. MOTOR PROTECTION NO NO YES NO NO NO NO


RELAY WITH LOCKED
ROTOR FEATURE
(50, 51, 50N, 46, 49, 50L/R)

E. 50N INST REST EF YES NO - NO NO NO NO


(SECONDARY SIDE)

F. 50 INST.O.C YES YES - NO NO NO NO

G. 50N INST.EF (R) YES YES - NO NO NO NO


(6)

H. 87 DIFF.PROT. YES NO YES YES NO NO NO


(1) (2) (3)

I. 86 TRIPPING RELAY YES YES YES YES YES YES YES

J. 95 TRIP CKT SUP. YES YES YES YES NO YES NO

K. 63TX AUX RLYTRAFO YES YES - NO NO NO NO

L. 27,2 UNDERVOLTAGE - - YES - - YES YES


WITH TIMER (5) (5)
--------------------------------------------------------------------------------------------------------------------------------

(1) For transformers rated 5 MVA and above


(2) For motors rated 1500 KW and above
(3) For critical/long feeders.
(4) These relay functions can be substituted by inherent releases.
(5) Wherever Autotransfer feature is provided.
(6) Provide INST E/F 50N for transformers with primary delta.
(7) Provide IDMTL E/F 51N for transformer with primary star
viii) Medium Voltage Motor Protection: ii) Overall generator unit transformer
differential protection.
The minimum protection requirement shall
include fuses and thermal overload relay - In installations where generator is
suitably co-ordinated with contactor operating in parallel with the grid,
characteristics as per applicable Indian special protection such as out of
Standards (BIS). However M.V. Motors step relay may be required.
controlled by circuit breakers may have
either releases or relay for Motor - It is recommended that
Protection. synchorising check relay for bus
coupler may be provided on those
- Large MV Motors which are contactor switchboards having grid as well as
fed (90 KW and above) may have core in plant supply with manual transfer
balance earth fault protection in addition & momentary paralleling feature.
to bimetal and fuse combination or
composite motor protection relay. In addition to electrical protection
relays, rotating machines may also
- Bimetal relays shall be preferably with require tripping/alarm for excessive
inherent protection against single vibration, high winding temperature
phasing. and high bearing temperature.

ix) Generator Protection : x) Capacitor Protection

The Protecting generally used for The protective requirements of capacitors


generators are as under. However the provided for power factor correction will
actual protective requirements will vary vary depending upon the rating and the
from case to case, depending upon the system configuration.
rating, excitation system, operation, type
of prime mover etc. The recommended protections include:

- Differential protection (87 G) i) IDMTL over-current with high set


element for protection against short
- Stator earth fault (51 N) circuits.

- Rotor earth fault (61) ii) Instantaneous earth fault

- Voltage controlled overcurrent (51V) iii) Neutral phase displacement

- Reverse power (32) iv) Under voltage

- Field failure (40) v) Over voltage

- Unbalanced loading protection (46) vi) Each element of basic capacitor unit
may have its own built in fuse, which
(Negative sequence current protection) shall isolate the faulty capacitor.

- Stator winding temperature protection The capacitor bank feeders shall generally
(49 T) be tripped on bus under/over voltage
conditions and necessary interlock shall
- Under frequency protection (81) be provided for re-switching to take care
of capacitor residual voltage.
When generator with unit transformers
is employed besides individual M.V capacitors of smaller ratings may be
equipment protection, the following controlled with switch fuse units.
additional protections are
recommended: The continuous current rating of fuses and
switching devices for capacitors should be
i) Transformer over fluxing protection 30% higher than the normal full load
current.
4.6 Emergency Power Supply continuity of supply to critical loads (e.g.
process control, communication, fire
i) This is an independent back-up source of alarm systems etc.) in the event of
electric energy that upon failure or outage normal/emergency supply failure.
of normal source, automatically provides
reliable electric power within specified 4.7.1 Un-interrupted Power Supply (UPS)
time to critical devices and equipment
whose failure to operate satisfactorily may i) An un-interrupted power supply shall be
jeopardise the health and safety of provided, as required for meeting critical
personnel or result in damage to property. loads that cannot withstand a momentary
interruption/other A.C. mains disturbance
ii) The emergency power supply system shall in supply voltage. A separate battery shall
feed the following loads to enable be provided for UPS system.
continuity of supply in the event of failure
of MAIN SUPPLY. ii) Following loads shall be connected to the
UPS system:
- Electrical loads essential for the
safe shutdown of the plant. - Critical instrumentation and process
control,
- Emergency lighting, security
lighting, obstruction lights. - Critical communication equipment,

- Process plant instruments as - Microprocessor based distributed


required digital control system.

- Communication equipment, Fire UPS system shall be fed from the


Alarm control panels. emergency system, wherever provided.

- D.C. Supply system, UPS system iii) In case of total power failure, un-
interrupted power supply shall be
- Auxiliaries of emergency set as available for at least 30 minutes or as
applicable determined by the process considerations.

- Fire fighting equipment excluding iv) Each branch circuit of the UPS distribution
main fire water pumps system shall have a fused disconnect
switch. The fuse shall be fast clearing type
- Essential ventilation loads, and and the fuse rating shall be coordinated
with the rating of the UPS system.
- Loads critical for process, plant and
personnel safety. 4.7.2 DC Power Supply

iii) Emergency power supply shall be i) Unless otherwise specified, independent


available as per process/equipment DC power supply systems shall be
requirements, but within a period not provided for the following:
exceeding 30 seconds from the instant of
failure of normal supply. - Plant shut-down system and DC
instrumentation.
iv) Unless otherwise required, the emergency
generator in general may not run - Electrical switchgear controls and
continuously in parallel with the normal critical (escape) lighting, critical
power supply system. However, to D.C. drives viz. LUBE OIL PUMPS
facilitate periodic testing and maintenance etc.
it is preferable to include synchronising
facilities for short time parallel operation ii) Each DC power supply system shall
of D.G. set unless objected to by electrical include charger-cum-rectifier, battery and
supply authorities. DC distribution board. DC link in the UPS
system shall generally not be tapped for
4.7 Critical Power Supply Systems DC instrumentation power supply except
in rare circumstances.
i) These systems shall have inherent
independent battery backup to maintain
iii) Fire alarm system shall have a dedicated and equipment for areas where
24 V DC battery backup system. flammable gas or vapour risks may arise:

iv) It is recommended that D.C. supply for a) Area classification, i.e. Zone 0, 1 or 2
electrical controls, instrumentation, UPS
etc. shall have separate independent b) Gas group classification, i.e. the gas
battery banks. group.

4.7.3 Battery Sizing c) Temperature classification

i) Electrical Switchgear and Controls d) Environmental conditions in which


apparatus is to be installed.
Battery shall normally be sized for a load
cycle having a minimum duration of one Where practicable, electrical
hour. While deciding the load cycle, apparatus in general and switch and
consideration shall be given on specific control apparatus in particular shall
operating/safety requirements of plant & be installed in safe area. Substation
equipment e.g. lube oil pump of STG for and control room shall be located in
bearing oil flushing. The duration for safe area. While deciding the route
battery sizing hence shall vary accordingly of overhead power lines, necessary
as per specific operational requirements. considerations shall be given to
avoid overhead lines passing through
ii) DC Instrumentation Shutdown System hazardous areas.

This shall in general be sized for 30 Electrical equipment intended for


minutes, unless otherwise required. service in hazardous area shall be
selected in accordance with IS : 5571
iii) Fire Alarm System and these shall be approved by
recognised testing and certifying
The battery shall be sized for the authorities i.e. CCE or DGMS or
duration and load in line with the DGFASLI as applicable.
guidelines given in IS 2189.
For details on hazardous area
iv) EPABX (Telephone System) classification, enclosure protection
etc. OISD standard 113, NEC 1985,
This will have an independent battery IS 5571, 5572, IS 13408 Petroleum
back up system. Rules and Oil Mines Regulations
shall be referred.
4.7.4 Annunciation
iii) General guidelines for type of protection
Sensitive earth fault detectors shall be for electrical equipment in hazardous
provided in D.C. system to annunciate areas are enumerated in Table-I.
earth faults.
TABLE-I
5.0 Electrical Equipment for Classified TYPES OF PROTECTION
Areas -----------------------------------------------------------
Area Description Symbol
i) All the areas within the Battery limits Classif-
shall be classified for degree and extent ication
of hazard from flammable materials. The -----------------------------------------------------------
basis for hazardous area classification Zone 0
recognises the differing degrees of - Intrinsic safety category ‘ia’ ‘ia’
probability with which flammable
atmosphere may arise in the installation, Other electrical apparatus, ‘s’
in terms of the frequency of occurrence specifically designed for
and the probable duration of existence on Zone 0. (See Note 1)
each occasion.
Zone 1
ii) Following factors shall be considered for - Any type of protection
proper selection of electrical apparatus adequate for Zone 0.
- Flame proof enclosure ‘d’ Note 5 Name plate details of equipment
intended for use in hazardous area
- Instrinsic safety category ‘ib ‘ib’ shall include relevant marking of
hazardous protection as per
- Pressurisation (See Table II) ‘p’ applicable IS codes.

- Sand filling ‘q’ Note 6 Flameproof enclosures are covered


under compulsory certification.
- Other electrical apparatus ‘s’
specifically designed for Zone 1 TABLE-II
MINIMUM ACTIONS ON FAILURE OF
Zone 2
PROTECTIVE GAS FOR TYPE OF
- Any type of protection ade- PROTECTION ‘P’
quate for Zone 0 or Zone 1 -----------------------------------------------
Area Classification Enclosure s Enclosure
does not contain
- Increased safety (See Note 2) ‘e’ contain ignition-
ignition- capable
- Non-sparking apparatus capable apparatus
(See Note 2) ‘n’ apparatus
-----------------------------------------------------------
- Pressurisation (See table II) ‘p’ Zone 1 Alarm Alarm
and
- Oil Immersion (see note 4) ‘o’ switch off

Note 1 It may be noted that as per petroleum Zone 2 No action Alarm


rules the use of intrinsically safe required
electricity apparatus in zone ‘0’ area is -----------------------------------------------------------
permitted only when the use of such 6.0 SUBSTATION LOCATION / LAYOUT
apparatus cannot be completely
excluded, whereas the Oil Mines The sub-station shall be located in a safe
regulations prohibit use of any area. Consideration shall be given to
electrical equipment in zone ‘0’ areas. cooling tower sprays, vapours
contributing to insulation break down,
Note 2 The apparatus with type of protection vehicular traffic accessibility for
‘e’ and type of protection ‘n’ when installation of equipment or any other
installed outdoors shall have factor that might affect the safe
enclosures providing at least the IS operation of the sub-station. (Refer
4691/2147. also OISD Standard 118 ‘Layout for
Oil and Gas Installations’)
a. IP 55 where there are uninsulated
conducting parts internally, and i) In large plants, the main sub-station floor
shall be raised above grade level and the
b. IP 44 for insulated parts. space below the sub-station floor shall be
utilised for installation of cable trays. The
Note 3 Presently there are apprehensions on substation cellar shall have preferably a
the suitability of use of high voltage clear height of 2 meters. The switchgear
Type ‘e’ and Type ‘n’ motors in Zone-2 rooms shall preferably be pressurised to
areas. Since the research work is still prevent ingress of dust. Large substation
inconclusive, the existing standards shall have three entries, one for
for Ex ‘e’ and Ex ‘n’ motors have not equipment entry, second for normal entry
been revised. Advice of the concerned and the third emergency exit. Where as
statutory authority should be sought required normal and equipment entries
while selecting Ex ‘e’ or Ex ‘n’ high can be combined.
voltage motors in Zone-2 areas.
Pressurised sub station shall have
Note 4 Oil-immersed apparatus may be used necessary Airlock lobby for the normal
only in case its security will not be entry.
impaired by tilting or vibration of the
apparatus. Small and medium size substations shall
have one equipment cum normal entry
and the second for emergency exit.
Emergency exit door in substation shall Exhaust of Diesel Engine shall be kept
open outwards. The main entry for away from Process/Hydrocarbon area.
operating personnel shall be preferably
provided with double door system. vii) Transformer yard/bay shall be provided
Operator cabin may be separately located with fencing and gate and shall have fire
to avoid repeated opening of doors and isolation walls for individual transformers.
dust entry to substation. Pressurised Oil immersed equipment involving use of
substation building shall have fixed large quantity of oil shall have oil soak pit
glazing with minimum number of openable and drain arrangement as per Indian
windows. All openings shall be kept Electricity Rules and regulations. *Fire
properly closed to maintain sufficient fighting equipment, first-aid boxes, etc.
pressure inside to prevent dust entry. shall also be provided as required.
(Further guidelines on this can be had
ii) Non pressurised remote switch from OISD standard 116 - ‘Fire Protection
room/offsite substation shall have fixed facilities for Petroleum Refineries and
glazing with suitable exhaust fans with Oil/Gas Processing Plants’ and OISD
louvers to meet the ventilation standard 117 ‘Fire Protection Facilities for
requirements. Proper maintenance and Petroleum Depots and Terminals.)
care shall be taken to keep the room free
from dust. viii) The substation equipment layout and the
clearances between different equipment
iii) The building shall sized to take care of shall be planned to ensure ease of
present/future needs and to maintain operation and maintenance and meet all
adequate clearances between equipment, requirements from the point of view of
and equipment and wall for ease of safety of the operating personnel.
operation and maintenance. Small sub-
stations shall suitably elevated by ix) Clearance between various equipment
compacting the soil so that the bottom of shall also satisfy respective equipment
the cable trench within substation is above manufacturer’s requirements and Indian
the surrounding grade level. Electricity Rules. Where these are not
specified the following minimum
iv) Normally transformers, reactors, neutral clearances are recommended as general
earthing resistors etc. shall be installed guidelines.
outdoor. Equipment like UPS system and
frequency stablisers shall be installed in a a) At the rear of H.V.
separate air-conditioned room. The battery Swbd : 1500mm
banks shall be located in a separate,
freely ventilated room in the sub-station b) At the front HV
building alongwith the necessary exhaust Swbd : 2000mm
system and water connection. Floor of the
battery room and the walls upto height of c) At the side of
one metre shall have acid resisting various boards
material/coating/be painted with acid/alkali from wall 1000mm
resistive paint or otherwise protected.
d) At the front
v) Necessary space to keep equipment of various boards 1500mm
under repair such as breakers, switch between front to -2000 mm
control gear items, spares/consumables front of two boards
like fuses etc. shall also be identified in (say DRAWOUT
building layout. MCCS) facing
each other.
vi) It may be preferable to locate DG sets in a
separate house/shed away from Sub e) At the rear of MV 1000mm
station in a safe area to reduce noise level Switchboards
in substation. If required DG set of smaller requiring rear access
rating may be located in substation
building provided the substation is located f) Rear clearance in
in a safe area. However in such cases, the other cases More than
foundation of such D.G. sets shall be 750mm
structurally delinked from the slab or floor otherwise
of the rest of the substation building.
less than Electrical equipment shall be suitable
200mm. with respect to the maximum steady
voltage (rms value for AC) likely to be
g) Transformers with applied, as well as overvoltages likely to
wall on one side As per IS occur.
Tansformers with 100028
wall on three sides. Note: For certain equipment, it may be
necessary to take account of the lowest
h) Clear height of voltage likely to occur.
busduct 2000mm
from finished Considerations shall also be given to the
floor level protective measures inherent in the
systems and the method of neutral
I) Clear space betw- earthing viz. earthed or unearthed
een Switch Board 1000mm system.
top and beam soffit
ii) Current
(Note : The maximum length of switchgear
lineup may preferably be limited All electrical equipment shall be selected
to 15-20 metres considering with respect to the maximum steady state
operation and maintenance current (rms value for AC) which it has to
requirements. carry in normal service, and with respect
to the currents (prospective, short circuit
x) It is recommended that battery room, currents) likely to be carried under
UPS room, charger room, operator’s abnormal conditions and the period (for
room of large sub stations, located close example, operating time of protective
to process units should have blast proof devices, if any) during which it may be
walls. This is to protect vital control expected to flow.
power sources from any external
damage, thus ensuring availability of iii) Frequency
control power for safe shutdown in
disastrous conditions suitable for indoor Electrical equipment shall be suitable for
use. continuous operation with respect to the
system rated frequency with variation
7.0 ELECTRICAL EQUIPMENT limits likely to occur.

Electrical equipment shall be selected, iv) Power


sized and installed so as to ensure
adequacy of performance, safety and All electrical equipment to be selected on
reliability. The equipment in general the basis of their power characteristics
shall conform to relevant Indian shall be suitable for the duty demanded
Standards and shall be suitable for from the equipment, taking into account
installation and satisfactory operation in the load factor and the service conditions.
the service conditions envisaged. Each equipment shall be able to deliver its
Specific attention is drawn to IS:9676 rated power for specified supply and site
for deciding the design ambient conditions with temperature rise remaining
temperature of electrical equipment. well within the design limits as per
applicable IS codes.
7.1 CHARACTERISTICS
v) System earthing
Every item of electrical equipment
selected shall have suitable All electrical equipment shall be selected
characteristics appropriate to the values considering the system neutral earthing
and conditions on which the design of the particularly in high voltage systems where
electrical installation is based and shall in resistance earthing is commonly
particular, fulfil the requirements given in employed.
Clause i) to vii) below.
vi) Conditions of Installation
I) Voltage
a) All the electrical equipment selected
shall have proper protection against
corrosive and solvent agents, water
ingress, thermal and mechanical a) All electrical equipment shall be
stresses as determined by the selected so that it will not cause
environmental factors. If, however, an harmful effects on other equipment or
item of equipment does not have by impair the supply during normal
design, the properties corresponding service including switchgear
to its location, it may be used on operations. In this context, the factors
condition that adequate additional which may have an influence include:
protection is provided as part of the
completed electrical installation. In * Power factor
addition to the above, noise level and
cooling/ventilation shall also be * Inrush current
considered.
* Asymmentrical load
PAINTING
* Harmonics
a) Rotating Machinery
* transient voltage
Internal and external parts of the dips/overshoots.
casing and all metal parts likely to
come in contact with the surrounding b) Energised parts shall be sufficiently
air shall be protected with anti- enclosed or isolated so as not to
acid/anti alkali epoxy paint that will expose personnel to explosion, fire,
resist corrosion under the particular arcing, or shock hazards. Adequate
atmospheric conditions. safety features shall be incorporated
in equipment design for the safety of
b) Switchgear panels and operating personnel.
service boards
7.2 EQUIPMENTS FEATURES
All metal surfaces shall be thoroughly
cleaned and degreased to move mill Certain essential safety features in
scale, rust, grease and dirt. Fabricated design to be considered in specifying
structures shall be pickled and then and sizing of commonly encountered
rinsed to remove any trace of acid. equipment such as Transformer,
The under surface shall be prepared Switchgear, Motors, Cables, Battery
by applying a coat of phosphate paint, charger Battery, and U.P.S. etc. are
and a coat of yellow zinc chromate enumerated below.
promer. The under surface shall be
made free from all imperfections 7.2.1 Transformers
before undertaking the finishing coat.
i) The KVA rating shall depend upon the
After preparation of the under surface, maximum simultaneous continuous load
the switchboard shall be spray painted and probable system expansion loads. In
with two coats of final paint. Colour general, the rating and the percentage
shade of final paint shall generally be impedance of each transformer shall be
light admiralty grey shade No. 631 as selected to limit the continuous current
per IS:5, unless otherwise required. rating and short circuit current to values
The finished panels shall be dried in within the ratings of available switchgear.
stovings ovens in dust-free The transformer impedances shall
atmosphere. Panel finish shall be free generally be as per Indian standards
from imperfections like pinholes, unless otherwise required. The rating and
orange peels, runoff paint, etc. the percentage impedance of transformer
shall be compatible to permit start of
All unpainted steel parts shall be highest rated motor while the transformer
cadmium plated or suitably treated to is preloaded with maximum operating
prevent rust corrosion. base load.

If these parts are moving elements, ii) Transformers connected to Grid supply
then these shall be greased. may have ON LOAD TAP CHANGERS for
inplant control of secondary voltage. Plant
vii) Prevention of Harmful effects
distribution transformers may have OFF remain inside the cubicle even in the test
CIRCUIT TAP changers. position. There shall be distinct overall
door for the breaker compartment and it
iii) In addition to standard accessories, the should be lockable. All circuit breaker
transformer shall be provided with trucks of the same rating shall be
auxiliary devices/protective devices such interchangeable.
as Buchholz relay, oil level and oil temp.
indicator with alarm trip output contacts vi) Suitable interlocks shall be provided to
and current transformers for the prevent faulty operation such as:
secondary side neutral for Protection.
Transformers of rating above 2000 KVA - ‘Pluging in’ or ‘drawing out’ of a closed
may be preferably have winding breaker.
temperature indicators with Alarm/Trip
provisions. - ‘Pluging in’ a breaker with earthing
isolator closed.
7.2.2 High Voltage (H.V)/Medium Voltage
(M.V) Switchboards - ‘Closing’ of earthing isolator with the
breaker ‘Plugged in’.
i) These shall be designed to ensure
maximum safety during operation, - Pulling out of auxiliary circuit plug with
inspection, connection of cables and breaker in service position.
maintenance with Switchboards
energised. - Pushing in breaker to service position
with auxiliary circuit plug not in
ii) The switchboard shall be totally enclosed, position.
dust and vermin proof.
- Opening of compartment door with
iii) Each unit of the switchgear shall have isolating switch in ON position and
necessary internal sheet metal barrier to vice-versa for Motor Control Centres.
form separate compartments for buses
instruments/relays/cable connections etc. The maximum height of operating
Compartment for cable connection shall handle/switches shall not exceed 1800
allow cable pulling, termination and mm and the minimum height not
connection work with switchgear below 300 mm.
energised. Suitable arc propagation
barriers shall also be provided. - It shall not be possible to operate the
Independent pressure release flaps shall circuit-breaker unless it is fully in
preferably be provided for each different service or Test or isolated position.
compartment of H.V. Switchboards.
Terminal strip for outgoing control cable vii) Suitable eye bolts for lifting of panels
connections should be accessible to shall be provided. On removing the eye
facilitate working and testing with breaker bolts, no holes offering access to panel
in test/service condition and while the shall be permitted.
switchboard is energised.
viii) Different sections, viz. busbar,
iv) Barriers shall be provided to permit switchgear, cable, relays and meters etc.
personnel to work safely within an empty shall be compartmentalised. Busbars and
compartment with the bus bars energised. supports shall withstand specified short
The minimum clearance and creepage circuit level without permanent
distance of bus bars shall conform to IS deformation. Busbars shall be preferably
4237. sleeved and joints shall be
taped/shrouded. Minimum clearances
v) The drawout carriage on the switchboard between live parts, between live parts to
shall have three positions viz., ‘Service’, Earth and Neutral shall conform to
‘Test’ and ‘drawn out’. Automatic safety applicable IS code (IS 4237)
shutters shall be provided to ensure the Switchboards shall have additional safety
inaccessibility of all live parts after the features such as falling tool shrouds for
breaker is drawn out. It shall not be trapping of free fall of maintenance tools
possible to drawout the carriage or rack it on live parts. Busbar supports shall be of
in with circuit breaker closed. The synthetic material with high tracking
breaker/contractor feeder trolley shall index. The switchboard shall have earth
busbar of adequate size. The switchgear iii) High voltage motors shall be suitable for
drawout trolley (in case of drawout starting under specified load conditions with
design) shall have suitable scraping earth 80% of the rated voltage at the terminals
connection. Feeder tag plates shall be and medium voltage motors shall be
provided at both front and rear side of suitable for starting under specified load
panels. Where required, busbar routing conditions with 75% of the rated voltage at
shall be clearly marked on the back side the terminals.
of the H.V. Switch board panels for easy
identification during maintenance. iv) The permissible noise level shall not
exceed the stipulations laid down in IEC
ix) All non-current carry metallic parts of 34-9.
mounted equipment/components shall be
bonded to the earth bus. v) Motor vibrations shall be within the limits of
IS-4729 unless otherwise specified for the
x) Surge absorbers to limit the switching driven equipment. Motors with sleeve
surges shall be provided as dictated by bearings may require proximity probes to
the type of arc quenching media and measure shaft vibration adjacent & relative
switching device. to the bearings.

xi) Starting of motors from substation shall i) Motors shall be required for continuous,
not be allowed and switch boards shall satisfactory operation at rated output under
not have close push button at the following conditions :
switchboard for motor starting.
a) The terminal voltage differing from its
xii) In specific cases, motors requiring rated value by not more than ± 6%.
frequent start/stop, (e.g. product, loading
pumps etc.) shall be controlled by b) The frequency differing from its rated
contractor feeder appropriate to its rating. value by not more than ± 3%

xiii) Switch Boards shall have anti c) Any combination of (a) and (b).
condensation heaters.
vii) Motor ratings and torque characteristics
7.2.3 MOTORS HIGH VOLTAGE (H.V.) shall be adequate to accelerate the load
& MEDIUM VOLTAGE (M.V) from zero to rated speed under starting
requirements as stipulated by process
7.2.3.1 General operating conditions. Normally, the
starting time shall be less than the hot
(1) Motors shall be totally enclosed, withstand time of the motor.
fan cooled type as far as
practicable. As a minimum, all viii) M.V. Motors in general and H.V. Motors
H.V. motors shall have anti where required shall be suitable for
condensation heaters. The restarting under full load after a
minimum degree of enclosure momentary loss of voltage with the
protection for motor shall be possibility of application of 100 percent of
preferably IP 44 for indoor use the rated voltage, when the residual
and IP 55 for outdoor duty motors. voltage has dropped down to 50 percent
and is in phase opposition to the applied
ii) Generally Motors upto and including 160 voltage.
KW shall be rated for medium voltage and
motors of rating above 160 kw shall be ix) Motor bearings shall be selected to give a
rated for high voltage. If required, the rating minimum L-10 life rating of 5 years
of medium voltage motors may be (40,000 hours) at rated operating condition
extended upto and including 200 KW. (the L-10 rating life is the number of hours
Sleeve or anti friction type bearings shall at constant speed that 90% of a group of
be used. Vertical motors shall have thrust identical bearings will complete or exceed
bearings suitable for the load imposed by before the first evidence of failure). The
the driven machinery. Unless otherwise bearings shall be adequate to absorb axial
specified, all motors shall be designed for thrust in either direction produced by the
‘Direct ON line’ starting. motor itself or due to shaft expansion. On
line greasing facility should be provided
on motor for all grease lubricated bearings
(anti friction bearings). Wherever and a decay time to half the peak voltage
spaceheaters are provided for motors, a of between 3 & 10 (microsecond).
separate terminal box should be provided Un = rated line to line voltage.
for termination of spaceheater cables, as
far as practicable. ix) Polarisation index

7.2.3.2 H. V. Motors Polarisation index of H.V. stator winding


shall have a value of at least 2. If the
i) Winding insulation shall be class F and insulation value of the motor exceeds a
temperature rise limited to that specified in value of 120 (Un+1) (where Un is rated line
the applicable IS for class B insulation. - line voltage (KV) mega ohm, a minimum
polarisation index of 1.5 is acceptable.
ii) Motors shall be designed to allow minimum
number of consecutive hot starts as 7.2.3.3 M. V. Motors
dictated by process operating
requirements. Number of uniformly spaced i) Motors shall be designed to allow three
startups in an hour shall be a minimum of consecutive starts from cold condition, two
three. consecutive starts from hot condition and
four uniformly distributed starts in one hour.
iii) The main power Terminal Box shall be
phase segregated and suitable to withstand ii) Motors shall be provided with minimum
the specified fault level for a minimum class ‘B’ insulation or class ‘F’ insulation
duration of 0.2 sec. (Commensurate with may be considered for special applications
instantaneous short circuit protection). and permissible temperature rise above the
Winding ends shall be preferably brought specified ambient temperature shall be
out and star point made in a separate limited to the values applicable for class ‘B’
terminal box. Neutral terminal box shall insulation. The windings shall be
have necessary space provision to mount tropicalised and adequately braced. The
differential CTs for motors of rating 1500 ends of the windings shall be brought out in
KW & above. a terminal box with six terminals with
suitable links to connect them in Delta.
iv) Motors of rating above 1000 kw shall be However, motors rated upto 2.2 KW may
provided with RTDs, BTDs. Separate be connected in star with three terminals.
terminal boxes shall be provided for space
heater and RTDs, BTDs. iii) The terminal box of motor controlled by air
circuit breaker shall be capable of
v) Induced voltage at the shaft of the motor withstanding the full internal short circuit
having uninsulated bearing system shall conditions, with the specified system fault
not exceed 250 mV r.m.s. for roller and ball level for a minimum duration of 0.2 second
bearings and 400 mV r.m.s. for sleeve (Commensurate with instantaneous short
bearings with the motor running at no load. circuit protection). Where motor control is
Alternatively, the non driving end bearing through contactor and MCCB, or back up
shall be insulated from the motor frame to fuse, the terminal box shall be able to
avoid circulating current. withstand the let-through energy of
protective devices corresponding to
vi) The insulated bearing end shield or maximum system fault level.
pedestal shall bear a prominent warning
and manufacturer shall provide detailed iv) The terminal box shall be of sturdy
drawing showing insulation arrangement. construction and large enough to facilitate
easy connection of required number of
vii) Motors shall be designed to withstand cable runs and size. (specifically
impulse voltage of at least (4Un+5) KV with Aluminium Conductor Cables). Additional
a wave front raise time of 1.2 microsecond trifurcating boxes may be considered for
and decay time of 50 microsecond to half motors requiring termination of two or more
the peak voltage. parallel runs of power cables.

viii)The interturn insulation of H.V. motors 7.2.4 Battery Charger and D.C.
shall be able to withstand a peak voltage of Distribution Board
at least 0.5 (4Un+5) KV with a wave front
rise time between 0.5 & 1.5 microsecond Charger and D.B. shall be floor mounted,
free standing, metal enclosed and vermin
proof type having front access hinged door the battery set. In case of mains failure, the
and suitable for indoor use. battery shall supply the necessary power to
the inverter. The inverter in turn feeds the
This shall consist of battery load through the static switch. If the
charger/rectifier, which shall feed the load inverter malfunctions or is overloaded, the
and keep the batteries under fully charged load shall be instantaneously transferred to
condition. Provision shall also be made for the by-pass line through the static switch.
necessary boost charging/initial charging of Normally the inverter shall be operated in
battery. synchronised mode with the by-pass line,
and manual forward transfer or manual
7.2.5 Batteries and Battery Accessories reverse transfer shall be effected without
any break.
i) This shall be indoor stationary type (lead
acid/Ni-Cd etc.) with adequate capacity to Automatic forward transfer, in case of
meet the backup requirements as inverter malfunction, shall be effected with
envisaged in the duty cycle. Accessories a break not exceeding 5 ms.
shall generally be as follows :
7.2.7 Capacitor Banks
- Battery stand made of treated first
class teakwood assembled without the i) The capacitor shall conform to IS 2834
use of any metal fastenings.
- specifications for shunt capacitor for power
- Intercell, inter ro and inter bank system.
connectors and end take offs.
ii) H. V. capacitor shall comprise appropriate
- Porcelain cell insulators, stand nos. of basic single phase units (minimum
insulators. 4 nos. basic units in parallel per phase)
which shall be connected in star formation.
- Hydrometers suitable for specific
gravity readings. iii) Capacitor banks shall be with necessary

- Cell number plates and fixing pins as 7.2.7 Capacitor Banks


required.
i) The capacitor shall conform to IS 2834 -
- Thermometer with specific gravity specifications for shunt capacitor for power
correction scale Nos. system.

- Cell testing voltmeter (3V-0-3V) ii) H. V. capacitor shall comprise appropriate


complete with leads 1 Metre. nos. of basic single phase units (minimum
4 nos. basic units in parallel per phase)
- Rubber gloves which shall be connected in star formation.
- Rubber aprons
- Spanner Set. iii) Capacitor banks shall be with necessary
discharge resistors to reduce the terminal
ii) While sizing the battery following factors voltage of each unit to a value equal to or
shall be taken in to consideration, in less than 50V in 5 minutes.
addition to envisaged duty cycle :
iv) Steel rack assembly suitable for outdoor
- Temperature correction factor. installations (where outdoor location is
- Ageing factor as applicable. required) to accommodate the basic
capacitor units with necessary post
7.2.6 Equipment for Uninterrupted insulators. Panel assembly (where indoor
Power Supply System location is required) to accommodate the
basic capacitor units, interconnecting
i) This shall be of free-standing, floor busbars, insulators etc. The panel shall
mounted, metal enclosed and vermin proof have minimum IP-51 protection and shall
type having hinged door for front access be constructed with sheet steel of minimum
and suitable for indoor use. thickness 2.0 mm.

ii) Under normal conditions, the rectifier-cum-


charger shall feed the inverter and charge
v) Necessary series reactor to limit in rush vii) Diesel Engine installation, do not call
current and suppress harmonics (where for Area Classification, provided the D.G.
required) room is properly ventilated. Normally the
ventilation provided to remove heat from
vi) The impregnant in the capacitors shall be the radiator is adequate to take care of
non-toxic. hazard aspect.

7.2.8 Emergency Generator 7.2.9 Cables

i) The emergency generating sets shall form i) In order to avoid spread of fire due to
a complete package and shall be designed cables, it is recommended that the outer
to start automatically on power failure and PVC sheath of all cables used in industry
feed the selected loads. It shall be capable shall be flame retardant type conforming to
of taking care of the load variations (e.g. category AF as per IS: 10810. The cable
the starting of largest rated motors on a shall have a low smoke property. The
preloaded system). The unit shall be minimum Oxygen Index shall be 29 Note 3.
complete with necessary starting
equipment, associated control panel and ii) High voltage cables may be
shall be suitable for remote starting. Aluminium/Copper Conductor XLPE
insulated PVC sheathed, armored type.
ii) The regulation of generator voltage shall
be automatic and necessary instruments The conductor screen, XLPE insulation
for metering viz. Ammeter, Voltmeter, screen shall all be extruded in one
Frequency meter, KWH meter, Power operation by ‘Triple Extrusion’ process.
Factor, Hour run counter etc. shall be
included in control panel. iii) 1.1 K.V. grade cables may be
Aluminium/Copper Conductor PVC
iii) Warning of abnormal conditions shall be insulated, PVC sheathed, armored type.
incorporated prior to automatic trip to
prevent unnecessary shutdown. iv) All power and control cables shall
preferably have extruded inner and outer
All the six stator winding ends shall be sheaths.
brought out to an externally mounted
terminal box and shall be connected in star. v) Where single core cables are armored and
Necessary temperature detectors shall be are meant for use on A.C circuits,
provided for the stator winding. The armouring with non-magnetic material (e.g.
terminal box shall have sufficient space to Aluminium) shall be given.
receive the cables of specified size.
The communication cables shall conform to
iv) Emergency D.G. set shall have Auto ITD specification. For fire alarm systems,
starting arrangement but only with manual PVC insulated, armoured and overall PVC
switching off features. The rating (Ampere sheathed cable with 1.5 mm2 copper
Hours) of battery, for cranking the engine conductors may be used.
shall be adequate to make three attempts
with an interval of 5 to 10 seconds, if vi) The power and control cables shall have
required. In case the engine fails to start the following minimum cross sectional
‘FAIL TO START’ annunciation shall be areas :
provided in substation or in control room.
a) Medium voltage 4mm 2
v) The generator set shall be provided with powercable Aluminium or
complete protection against overloads, 2.5 mm 2 Copper
short circuits, ground faults, excitation
failure, prime mover failure and shall b) Control cables 2.5 mm 2(Copper)
include other connected instrumentation (See Note 1 below)
interlocks.
c) Lighting 2.5 mm2 (Copper)/
vi) The load shall be switched on to the 4mm2 (Aluminium)
generator only after the requisite voltage (See Note 2 below).
build-up.
Note 1 In case of difficulty in connecting the
cables to instrument relay Annuciation
terminals, the minimum cross section ii) The control station enclosure shall have
may be reduced to 1.5 mm2 copper. suitable protection for site conditions such
as flameproof, weather-proof, dust-proof,
Note 2 For lighting inside the building copper corrosion resistant, etc.).
conductor cables shall be used.
Where conduit wiring is adopted, iii) The control station shall include the
minimum 1.5 mm2 copper conductor following equipment as per individual
PVC insulated wire may be used. requirements :

Note 3 Conductor size for wiring inside the - Start/stop push button/close,
panel for electronic neutral, Trip Switch
circuits/components shall be as per
manufacturer’s standard. - Ammeter,

vii) Cables shall be properly sized to carry - Local/Remote Selector Switch


without undue temperature rise the load
current under site derated conditions. The - Auto/Manual selector switch and
derating shall take into account ambient air cable glands.
temperature, ground/duct temperature,
grouping and proximity of cables with each iv) Stop push button shall generally have stay
other, thermal resistivity of soil etc. Cables put feature except in the case of critical
protected by fuses shall be able to drives such as lube oil pump etc.
withstand the maximum I2 t let through
energy of fuse. v) Control station shall have suitable locking
facility.
In other cases, cable shall be able to
withstand the fault current for a duration as 7.2.11 Convenience Receptacles
dictated by protective disconnecting
device. i) These shall have the necessary
mechanical interlocks and earthing
viii) The type of cable selected and the facilities. The enclosure shall have
insulation shall be compatible with various suitable protection for site conditions
chemicals encountered in the plant and specified such as flameproof, weather-
other environment conditions such as proof, dust-proof, corrosion resistant, etc.
dampness highly corrosive atmosphere,
high/low temperature, radiation etc., ii) Welding receptacles shall be provided at
bearing in mind that certain chemicals (e.g. suitable locations to ensure accessibility
Benzene, Ethylene chloride) are known to with a 50 meters length of trailing cable to
be detrimental to PVC. any point in the process area. These shall
be rated for 60 A suitable for 415 V, 3-
ix)The selection of voltage rating of H.V. phase system with a scraping earth
cables shall take into account the system connection.
voltage, system earthing arrangements and
type of earth fault protection schemes. iii) Adequate number of sockets for lamps
(Guidelines on this can be had from IEC and portable tools shall be provided at
183). suitable locations to ensure accessibility
with a 15 meters length of cable to any
x) When feeders comprising of parallel runs point in the process area. These shall be
of cables are envisaged, the size and type rated for 15 A single phase supplied at 240
of individual cable shall be identical. V. Hand lamps and portable tools shall be
earthed through flexible cords. The
flexible cable shall have 3 cores of
7.2.10 Control Station multistrand copper conductor of minimum
size equivalent to 1.5 Sq mm, with PVC
i) Each Motor shall be provided with a control insulation and metal braiding. In
station in the field. Motors installed at hazardous areas, handlamps shall be
elevated platforms (such as cooling tower rated for 24 Volts. Accordingly 240/24 V
fan, air fin cooler etc.) shall be provided transformers shall be provided either in
with one stop push button at ground level in the plug or in separate flameproof
addition to one near motor. enclosure.
7.2.12 Actuators for Motor Operated cable manufacturers
Valves recommendations shall be followed.

i) Valves with electrical actuators shall - It should be noted here that the
generally be provided with integral current rating of cables will vary
starters. depending upon laying formation,
method of sheath bonding etc.,
ii) The necessary local/remote selector apart from other derating factors
switch, start/stop control switches or push normally considered. (Ambient
button, torque limit switches etc. shall be temp., depth of laying etc.)
provided on actuator for local/remote
control depending on mode of selection. In iii) All trenches shall be sized depending upon
case of failure of torque limit switches, the the number of cables, and its voltage
mechanical design shall be adequate to grade. High voltage, medium voltage and
stall and trip the motor without damage. other control cables shall be separated
from each other by required spacing or
iii) The control circuits shall AC operated for running through independant pipes,
short distance or DC operated for trenches or cable trays as applicable.
extended distance. The actuator shall be Cable trenches inside substations shall be
provided with an anti condensation heater. filled with sand, pebbles or similar non-
flammable materials or covered with
8.0 Plant Cabling incombustible slabs. If a significant number
of cables are taken on racks/supports
i) Cables below ground may be laid in provided on the side wall of trench.
concrete trench/tunnel or directly buried.
Cables above ground shall be laid in cable iv) RCC covers of trenches shall be effectively
trays/cable racks. sealed to avoid ingress of chemicals and
oils.
However cabling for fire water system
shall as far as possible be taken in v) In unpaved areas, cables may be directly
exclusive route through underground buried in ground. Where underground
trench. cables cross roadways or pipe sleepers at
grade etc., they shall be protected by being
ii) While designing layout with single core drawn through sleeves/ducts to provide a
cable installations following factors shall permanent crossing. Sleeves/ducts ends
be considered : shall be effectively sealed thereafter.

a) Cables are laid as a general practice in vi) Concrete lined trenches shall have suitable
trefoil formation touching each other. drainage arrangement to avoid water
collection. Concrete lined cable trenches
or shall be sealed against ingress of liquid and
gases wherever the trenches leave a
b) flat formation with spacing as per hazardous area or enter control room or
requirement. substation. Pipes laid for mechanical
protection shall be sealed at both ends.
- When cables are laid in a flat
formation, the individual cable fixing vii) Above ground cables shall be well
clamps, and spacers shall be of non supported suitably at every 2 to 2.5 metres
magnetic material. interval and protected against mechanical
damage. Routing shall be decided to avoid
- As a general practice, the sheath of proximity to hot sources, place subject to
single core cables shall earthed to undue fire risk, gas, water, steam oil drains,
keep sheath at earth potential. piping, air conditioning duct etc. Cable
However depending on the current trays, racks and trenches shall sized to
the cable has to carry, the feeder allow for 10 to 20% future cables reserve.
length and permissible sheath Each cable tray tier shall accommodate the
potential, various methods of sheath cables preferably in single layer.
bonding are employed, viz. single
point bonding, bonding at middle, Instrument and communication cables shall
sectionalised bonding etc., for which not be laid in the same trench/tray along
with electrical cables. The overall cable
layouts shall be designed for minimum
interference between signal and power 9.0 Plant Lighting
cables.
This can be broadly classified as under :
viii) Cable cellars and important cable
tunnels shall be provided with fire detection i. Normal lighting
and monitoring devices.
ii. Emergency lighting
ix) Trailing cables for equipment such as
cranes and excavators shall have one iii. Critical lighting
additional core for earthing and the cable
shall be well protected against mechanical i) Normal and emergency lighting system
damage. shall be on 415/240V AC supply, whereas
critical lighting will be either on 220V or
x) Cable straight through joints in power & 110V DC.
control cables shall be avoided as far as
possible. ii) Sufficient lighting shall be provided so as to
enable plant operators to move safely
xi) Only type tested and approved make within the accessible areas of plant and to
termination kits shall be used. While perform routine operations. In the event of
selecting the type of cable kit, necessary normal power failure, emergency lighting
consideration may be given to the may be provided.
additional safety measures needed for
carrying out termination with kits of type iii) Lighting requirements provided during the
such as heat shrinkable type (particularly in failure of power supply for Normal lighting
hazardous areas). are intended broadly,

xii)Cable route markers shall be installed at a. to facilitate carrying out of specified


every 30 metres intervals all along the operations, for safe shutdown of the
cable routes and also at cable joints and plant.
locations where the direction of cable
trench changes. Cable route markers shall b. to gain access and permit ready
extend 600 mm above ground. identification of fire fighting facilities
such as fire water pumps, fire alarm
xiii) Cable installations shall provide for stations etc.
minimum cable bending redii as
recommended by manufacturer. c. Escape route for safe evacuation of
operating personnel.
xiv) Cable trenches in hazardous area
shall be filled with sand and covered with iv) The recommended areas for critical
RCC slabs to prevent accumulation of lighting (D.C.) include :
flammable gas/vapour inside the trench.
- Control rooms (Process & utility)
xv) Cables shall be identified close to
their termination point by cable tag - Main substations
numbers as per cable schedule. Cable tag
numbers shall be punched on aluminium - D. G. Shed
strap 2mm thick flat or circular, securely
fastened to the cable. - Central Fire Station

xvi) Besides each underground cable shall - Fire water pump house (for startup
be provided with identify tags of lead of Diesel driven F.W. pump)
securely fastened at every 30 metres of
underground length with at least one tag at - First Aid Centre
each end before the cable enters the
ground. - Emergency escape route

For further details, on installation practices v) The recommended areas for A.C.
and requirements refer OISD Standard 147 emergency lighting includes :
on ‘Inspection and Safe Practices during
Electrical Installations’. - Control rooms (Process & utility)
conditions, necessary incandescent lamps
- Fire water pump house, Fire may be judiciously distributed throughout
stations the plant area. Incandescent lamps may be
considered for emergency lighting to
- Main sub stations achieve this objective, Fluorescent lamps
may be used for indoor lighting in non-
- Foot of stairs and ladder process buildings and control rooms. Safe
area street lighting and yard lighting may
- Platforms with ladders changing employ sodium vapour lamps. Low
direction pressure sodium vapour lamps shall not be
installed in hazardous areas.
- Other changes of floor level, that
may constitute a hazard. x) The illumination levels in different areas
shall be as per good engineering practice.
- Strategic locations in Process, utility Depending on the nature of job activities to
areas where specific safety be carried out the suggested minimum
operations are to be carried out illumination levels for various areas are as
such as : under :
--------------------------------------------------------
* Areas near heat exchangers, Areas Illumination
condensers in Lux
--------------------------------------------------------
* Barring gears of steam turbine - Main roads (along process 7 - 10
units, power houses,
* Some portions of roads workshops, etc.)
interconnecting substations and
process plants. - Secondary roads (along 3 - 5
storage tanks settling
vi) As a good engineering practice the A.C. basins etc.)
emergency load is generally considered as
20-25% of Normal Lighting load. However - Tank farm 10
for small plants, where A.C. emergency
load is not substantial/where there is no - Pump houses, sheds 100
separate standby D.G. set, D.C. critical
lighting system may take care of entire - Main operation platforms 60
emergency lighting. & access stairs

vii) The following operational philosophy - Ordinary platforms 20


is recommended. Under normal operation,
both emergency and normal lighting shall - Process areas, pipe 60
be fed by Normal power source. On failure racks, heat exchanger,
of normal supply, emergency lighting load heater, separators, cooling
will be transferred to emergency source tower, columns, pig
after the start of D.G. set within 15 launching/receiving loading
seconds. Critical lighting (D.C. supply area, flare etc.
based) will be normally kept ‘ON’ and
during Normal/emergency power failure, - Switchgear bldg. 150-200
battery will provide power.
- Transformer bay 100
viii) Besides, adequate number of self
contained portable hand lamps and Battery - Battery room 150
emergency lighting units shall be provided
for immediate use in emergency at remote - Control room bldg./laboratory 400
stations and at other strategic places (safe
areas), wherever required, for personnel - Boiler house 150
safety.
- Charger/UPS rooms 150-200
ix) HPMV/MLL lamps shall generally be used
for outdoor plant lighting. Keeping in view - Cooling tower 60
the restrike time lag and to avoid complete
darkness in case of a voltage dip/brown out - Switchyard (i) operating area 100
xiv)Battery room shall have fixtures mounted
(ii) other areas 50 on wall in order to facilitate easy
replacement of fused lamps. Switches
- Warehouse 100 controlling the lighting fixtures and exhaust
fan shall be installed outside the battery
- Office 300 room.

- Compressor area 200 xv) Switches of lighting panels installed in


hazardous area, shall have a pole to break
- Watchroom 100 the neutral in addition to the poles for
phases.
- Stairs 50
When the means of isolation is located in a
- Corridors/lifts 70 non-hazardous area, the switch shall break
all poles including neutral or alternatively
- Tube well, gate & watchman may break only live poles, the neutral being
booth 100 isolated by a removable link.

- Fire house, garage 100-150 xvi)For details on installation practices refer


----------------------------------------------------------- OISD standard 147.

However, lighting levels in all areas shall 10.0 Plant Earthing


take into consideration the requirements
from point of view of safety, easy operation i) Earthing system in general, shall cover the
and maintenance. following :

xi) The illumination level requirements (during - Equipment earthing for personnel
normal lighting source failure) depends on safety,
the nature of activities to be carried out.
The suggested minimum illumination levels - System neutral earthing, and
are as below :
- Static and lighting protection.
I) Near to areas where Spot
specific safety operations lighting ii) The earthing system envisages an earthing
(visual tasks are to be to be network with designed number of earth
carried out (e.g. control provided electrodes attached to it. The following
room) shall be earthed :

ii) Escape Lighting - System neutral,

a. Escape way (interior) - 5 Lux - Current and potential transformer


secondary neutral
b. Areas at exit door and
at points where it is nec- - Metallic non-current carrying parts of all
essary to emphasise electrical apparatus such as
the position of potential transformers, switchgears, motors,
hazard if any. - 30 Lux lighting/power panels, terminal boxes,
control stations, lighting fixtures,
iii) Other notified general receptacles etc.
outdoor areas - 1 Lux
- Steel structures, Loading platform etc.
xii)The lighting fixtures on various circuits
shall be suitably interlaced so that failure of - Cable trays and racks, lighting mast and
any one circuit do not result in complete poles.
darkness.
- Storage tanks, spheres, vessels, columns
xiii)Taller structures shall have aviation and all other process equipments.
obstruction lighting as per statutory
regulations (D.G.C.A.). - Electrical equipment fencing (e.g.
transformer, yard etc.)
- Cable shields and armour base. An independent earthing network
shall be provided for lighting protection and
- Flexible earth provision for Wagon, this shall be bonded with the main earthing
Truck network below ground, minimum at two
points.
iii) Plant earthing design shall generally be
carried out in accordance with the x) The resistance value of an earthing system
requirements of Indian Electricity Rules to the general mass of earth shall be as
and code of practice for earthing IS 3043. follows :

- As far as possible, all earth - For the electrical system and equipment,
connections shall be visible for inspection. a value that ensures the operation
of the protective device in the
iv) All connections shall be carefully made and electrical circuit but not in excess of
adequately locked against loosening. 5 ohms. However, for generating
Normally earthing system shall comprise of stations and large sub-stations this
GI strip as main earth grid alongwith value shall not be more than 1 ohm.
suitably located GI disconnecting plates to
provide multiple earth connections between - For lightning protection, the value of
earth grid and equipment and for 5 ohms as earth resistance shall be
connections between main earth grid and desirable, but in no case it shall be
electrodes. Alternatively, mild steel strip more than 10 ohms.
can also be used for earth grid after
providing corrosion allowance. xi) The main earthing network shall be used
for earthing of equipment to protect against
v) Connections between GI earth electrode static electricity.
and the disconnecting plates shall be done
by GI strip. For highly corrosive areas, PVC For further details on earthing installation
insulated A1 cond. cable (unarmoured) practices refer OISD standard 147.
may be used. Connections between the
disconnecting plate and various equipment TABLE - III
shall be done by GI strip, GI wire or GI wire -----------------------------------------------------------
rope, size as recommended in Table III. Type of Equipment Bare G.I. Strip/G.I.
Bare Rope or
vi) In corrosive areas, aluminium G.I. Wire
disconnecting plates alongwith suitably -----------------------------------------------------------
sized PVC insulated aluminium conductor Motors upto 3.7 KW No. 8 SWG solid
cables, may be used for earthing wire
grid/connections.
Motors 5.5 KW to 10 mm (3/8") Wire 30
vii) All utility, process pipelines and KW & welding
flanges shall be earthed on entering or receptacles
leaving the hazardous areas, except where
conflicting with the requirements of Motors 37 KW and 16 mm (5/8") above
cathodic protection. In addition, steel pipe including HT Wire Rope
racks in the process units and offsite area Motors
shall be earthed at every 25 meters.
Building Columns 40 X 5 Strip
viii) Equipment located remote from main
earth network may be earthed by means of Storage Tank (Vertical 40 X 5 Strip
individual earth conductors and earth & Horizontal)
electrodes.
Loading Racks 40 X 5 Strip
ix) Lighting protection shall be provided for the
equipment, structures and buildings which Pipe racks, Vessels 10 mm (3/8") &
are higher than 20 metres or as per the risk Heat Exchanvers Wire Rope
index analysis worked out as per IS 2309.
Self-conducting structures do not require Small Equipment & No. 8 SWG Solid
lightning protection with aerial rod and Instruments
down conductors. They shall be connected
to the earthing system at two points of the Lighting, Power & 10 mm (3/8")
Instrument Panels Wire Rope unit control rooms. Operation of each
zone panel may be indicated by audio-
Main Earth Bus/LT & As visual indication in the main control panel
HT SW. Gear Intercon- Calculated in the unit control room as well as in the
nections/Power Trans- other zone panels with distinct colour
former indicating the zone number.

EHV & HV Sub-Stations As Calculated iii) A fire detection and alarm system shall:

Push Button Stations No. 8 SWG Solid a) operate quickly enough to fulfil its
Wire intended functions;

Street Light Poles 10 mm (3/8") b) reliably transmit the detection signal;


Wire Rope
c) Translate this signal into a clear alarm
Lighting Transformer 16 mm (5/8") indication that will attract the attention of
Wire Rope the user in an immediate and
----------------------------------------------------------- unmistakable way and indicate the
Note : Lighting fixtures shall be earthed location of fire and initiate operation of
through the extra core provided in the ancillary service such as fire
lighting cable. extinguishing system, etc;

xii) Earth rods and conductors shall be d) remain insensitive to phenomena other
designed to cope with the conditions than those which its function is to detect;
imposed. The earth conductor shall be and
adequately sized to carry the applicable
maximum earth fault current without e) signal immediately and clearly any
undue temperature rise. All joints shall supervised fault that might jeopardies the
be protected against corrosion. correct performance of the system. The
system shall also include a FIRE SIREN
xiii) All the electrical equipment operating of distinguished tone having a range of
above 250 volts shall have two separate about 8 kms. Audio/visual fire alarm may
and distinct connections to earth grid. be required at the following locations in a
large plant:
11.0 Plant Safety and Security systems
- Control room
This shall include the following systems: - Fire station
- First aid centre
11.1 Plant Fire Detection and Alarm System - Security office
- Fire water pump house
i) The purpose of a fire detection and alarm
system is to detect fire at the earliest and iv) Detailed design, selection and installation
to give an alarm so that appropriate of fire detection and alarm system shall
action can be taken (e.g. evacuation of be as per IS-2189.
personnel summoning the fire fighting
organisation, triggering of extinguishing 11.2 Communication system
process etc.). An alarm system may be
activated by automatic detection devices The plant communication system shall
viz. smoke detectors, heat detectors etc. include some or all of the following
or by manual operation of manual call facilities as per individual plant
points i.e. break glass units. requirements:

ii) Manned locations prone to fire hazard - Telephone


shall have manual call points which on
operation shall give audio-visual - Public address system
indication at the control rooms and
actuate the sirens. If there are many - Emergency communication
manual call point, these may be system
conveniently grouped together to form
various zones and zone panels may be - Radio communication system
installed in convenient places other than
- Telex system. communication between field stations at
the discretion of Master Station.
Certain requirements for each facility are
given below as general recommendation. d) Communication between pre-designated
field stations as per process operating
11.2.1 Telephone System requirements without interference of the
operator manning the master station.
i) A private automatic branch exchange
(PABX) system shall be provided. Trunk e) Operating an alarm call from master
lines connecting with the external control station over all the loud speakers
telephone network shall be provided and during an emergency.
number of trunk lines shall be decided
based on plant size and requirement. ii) Paging speakers provided in areas having
high ambient noise levels shall produce a 6
ii) Selective telephone service control shall be dB paging noise level above anticipated
arranged for all the extensions of the PABX ambient level for effective recognition of
to have one or more of the following speaker’s voice signals.
service functions:
Also the field stations shall be capable of
- All phones shall have direct inter- operating in areas of high noise levels
communication between all the extensions without any interference.
of this exchange and all the extensions
shall be able to accept any external calls 11.2.3 Emergency Communication System
handled by the exchange operators.
i) The ‘Hot line system’ shall be designed to
- Non executive phones shall operate with provide a dependable communication link
operator assistance for connection to between predesignated points of operation.
external lines for both local and long This system shall be completely isolated
distance telephone service. from the telephone system.

- Executive phone service shall include ii) The emergency communication system
direct unassisted (operator bypass) shall include a ‘Direct phone to phone hot
communication to external lines for both line (H.L.) system’ and a ‘Dedicated hot line
local and long distance telephone service. (D.H.L.) system’.

iii) In areas with high ambient noise levels, iii) H. L. System


intensified bell signals may be provided to
produce an effective recognition noise level By removing phone from cradle switch, the
of 6db above anticipated ambient noise corresponding phone at opposite end will
levels. ring till answered or until the phone is
returned back to cradle disengaging the
11.2.2 Public Address System circuit switch.

i) A public address system shall be provided iv) D.H.L. System


for communication within the plant area
and it shall comprise master stations, A simplified selective dial scheme shall be
central cabinet/exchange equipment (field provided to give selective contact between
station modules, amplifiers etc.), field all the extensions of this system. All the
stations, paging loudspeakers etc. The telephones used for the emergency
public address system shall provide, as a communication system shall be red in
minimum, the following facilities: colour and shall have ringing indication
lights.
a) Paging within the plant area over
loudspeaker from the master station 11.2.4. Radio Communication System
located in process control room.
Portable Walkie - Talkie system.
b) Call back from any of the field stations to
the master control station. i) A walkie-talkie system shall be provided for
radio communication within the plant area.
c) Communication or call from Master Control The system shall operate in the simplex
Station to any of the field stations and mode on U.H.F. and the exact frequency
shall be decided in consultation with P & T illuminated. Automatic protection
authorities. employing earth leakage detection scheme
(e.g. using ELCB with current sensitivity of
ii) The system shall consist of base station, 30 mA) shall be provided to disconnect
monitoring receivers, portable stations, supply on occurrence of an earth fault.
antennas and associated accessories. Hand lamps with self contained batteries
Adequate number of hand stations shall be shall have type of protection appropriate to
provided. the applicable hazardous zone.

iii) The system shall enable communication 12.2 DIESEL ENGINES


between portable station and the base
station or between any of the two portable i) The use of permanently installed diesel
stations. The system shall have a range of engines in Zone-0 and zone-1 areas is
approximately 6 km. unacceptable and the use of permanently
installed diesel engines in Zone-2 area
iv) The system shall provide excellent should be avoided wherever possible.
penetration in all operating areas of the
plant with no marginal locations and extend ii) In the event of use of a permanently
beyond the boundaries of the plant. The installed diesel engine, being necessary in
system shall operate above the man-made Zone-2 it is recommended that it should
noise spectrum to provide clear noise free have the following minimum protection to
communication in all areas of high ensure safety :
electrical noise.
a) The starter shall be either of a flameproof
11.2.4.1 VHF System electrical type (usually operated from
the mains supply or battery) or of the
Radio communication (VHF band) may be following non-electric types :
provided for communication between the
plant and pre-designated points outside the i) Pneumatic
plant. The system shall include necessary ii) Hydraulic
transmitter/receivers and associated iii) Spring recoil
antenna. The frequency of operation shall iv) Inertia, or
be decided in consultation with statutory v) Hand start
authorities (P&T).
b) Any other electrical equipment associated
11.2.5 Telex System with the engine shall be flameproof.
Electrical equipment shall be effectively
One telex machine shall be installed in the earthed and bonded.
administration building of the plant.
c) Cooling fan blades shall be made from
non-metallic materials which do not
accumulate electro-static charge.
12.0 MOBILE EQUIPMENT FOR
HAZARDOUS AREAS d) All belts shall be of anti-static, fire-resistant
type.
12.1 PORTABLE HAND LAMPS
e) In order to contain discharge of sparks or
i) Hand lamps for use in hazardous area shall flames from the exhaust system, a gas
be flameproof with an operating voltage of conditioner box and a flame trap shall be
24 V. The hand lamp shall be connected to installed. Alternatively, the exhaust should
the source of supply by a flexible 3x1.5 sq. be designed to discharge to a location
mm copper conductor PVC insulated metal within a safe area.
braided cable.
f) To prevent flashback through induction
This cable should be protected by system, wherever possible, air intakes for
PVC/tough rubber sheath or similar engines shall be located in safe area.
covering. The metallic body or any other Alternatively a flame trap should be
exposed metal part of the hand lamp shall installed.
be connected to earthing system.
g) The surface temperature of the engine and
ii) The source of supply shall be located as exhaust system shall not exceed 250°C
near as possible to the points to be
when tested under full load conditions. In
some situations cooling of the exhaust iv) No screw, stud or bolt-hole shall pass
manifold and piping may be necessary, through the wall of any component of the
using water jacketing or finned coolers system.
and/or high temperature cut/outs or alarms
should be provided. n) Decompression systems should not
normally be provided. However, if they are
h) However when either the free movement of essential, then the decompression parts
air is restricted by thermal or acoustic should be provided with flame traps and
shielding or the ignition temperature of the ducted away to safe area.
surrounding flammable atmosphere is
below 200°C, no engine exposed surface o) The fuel injection pump and governor
temperature shall exceed the minimum where fitted should be so designed that
ignition temperature of the gases involved. reverse running of the engine is not
possible.
i) To prevent overspeeding of the engine due
to induction of flammable gases or 12.3 STORAGE BATTERIES
vapours, means shall be provided to stop
the engine. It can be either : i) Storage batteries shall not be installed in
Zone 1 locations, except those used in
i) a valve to close the air intake, or portable lamps where the enclosure
ii) a system to inject carbon dioxide into housing bulb, switch and battery shall be
the air intake. flameproof type.

j) Alarms of automatic shutdown devices ii) As far as practicable use of storage


shall be provided, actioned by excessive batteries in Zone 2 areas shall be avoided.
water temperature and low lube oil However where unavoidable, storage
pressure. batteries for use in Zone 2 areas shall be
“Increased Safety” type. These shall meet
k) A system using an alarm or trip device to the following requirements :
protect the engine from excessive vibration
should be considered. a) Celluloid and similar combustibles shall not
be used as constructional materials.
l) An engine having a crank case volume of
over 0.5 m3 shall be provided with relief b) Battery containers as well as fittings and
devices. Relief valves or breathers on insulating parts outside the enclosed cells
engines shall be fitted with flame traps or shall not consist of porous materials e.g.
discharge into the induction system wood or other flammable materials and
downstream of the flame trap, if fitted and shall be resistant to flame and the action of
upstream of the shut-off valve, if fitted. electrolytes.
Dipsticks and/or filler caps should be
screwed or effectively secured by other c) Openings of cells necessary for the escape
means. of the gases given off shall be so
constructed as to prevent splashing of the
m) Intake and exhaust system design shall electrolyte.
meet the following minimum requirements:
d) The exterior of the cells shall be so
i) The length of the flame path through or constructed as to resist impact, and the cell
across any joint shall be not less than 13 cases shall be firmly fixed.
mm.
e) The cells shall be so built into the
ii) Suitable metal-clad or other acceptable containers that connection of the cells
jointing material shall be interposed getting loose in operation is improbable
between all joint faces to ensure that and normally, the discharge voltage
leakage does not occur. exceeding 24 volts should not appear
between adjacent rows of cells.
iii) Where valve spindles pass through the
walls of any component of the induction f) The creepage distance between two poles
system, the diametrical clearance shall not of adjacent cells shall not be less than 35
exceed 0.13 mm, unless end caps are mm. Where the discharge voltage exceeds
fitted. 24 volts, the creepage distance shall be
correspondingly increased by 1mm per 2
volts. b) The mobile apparatus shall be used for
temporary purpose only under competent
g) Where voltage of batteries is not less than supervision.
50 volts, either the battery case shall be
subdivided by partitions or the batteries c) No uninsulated current carrying part shall
shall be grouped into containers such that be exposed.
in no grouping does a voltage exceeding
50 volts occur. In these cases, the d) All components shall be accessible for
partitions or the containers shall have maintenance/repairs.
heights of at least half that of the battery
case. e) All remote control or interlock circuits
associated with restrained plug and socket
h) The battery case shall be so constructed as coupling should be intrinsically safe.
to ensure sufficient ventilation in order to
prevent accumulation of gases given off f) All electrical circuits shall be cut off
from the battery, and the free space within automatically in the event of :
the case shall be as small as possible.
i) The current in any circuit exceeding
i) The metallic cover of the battery case shall more than the rated value in any circuit.
be lined with materials resistant to
electrolyte. ii) A leakage current to earth/earth fault.

j) The cover of the battery case shall have 12.6 VEHICLES


special fastenings.
Commercial vehicles such as jeeps, trucks,
k) Exposed live parts of battery contained in a cars etc. shall not be allowed inside
case shall be protected with rubber or hazardous area unless these are
equivalent insulated materials. However, specifically certified by competent authority
the openings for checking voltage may be for use hazardous areas.
provided.
13.0 REFERENCES
Note : Charging of storage batteries shall be
conducted in non-hazardous locations, The following codes, standards and
while the cover of the battery publications have either been referred to or
enclosure is kept open. used in the preparation of this document
and the same shall be read in conjunction
12.4 TESTING EQUIPMENT with this document :

a) All testing equipment such as meggers, i) National Electrical Code of Bureau of


continuity tester etc. shall be intrinsically Indian Standards. (SP-30 : 1984)
safe.
ii) OISD Standards / Recommended Practices
b) Terminal connections shall be made by such as :
crimp type lugs.
a) OISD - 147 “Inspection, and safe
c) Terminals shall be provided with rubber practices during Electrical
covers. Installation”.

d) Enclosure and other constructional features b) OISD - 116 - Fire Protection facilities
shall be suitable as per the area for petroleum refineries and oil/gas
requirement. processing plants.

12.5 MISCELLANEOUS c) OISD - 117 - Fire Protection facilities


REQUIREMENTS for petroleum depots and terminals.

a) The electrical equipment and the system as d) OISD - 118 Layout for Oil and Gas
a part of mobile equipment shall be of Installations
intrinsically safe/flame proof design, if
required to be taken in classified hazardous e) OISD - 113 ‘Electrical Area
areas. Classification’.
* IS 2189 Code of practice for selection,
f) OISD - 137 “Inspection of Electrical installation and maintenance of Automatic
Equipment” Fire Detection and Alarm System.

iii) Indian Electricity Act & Rules 1956 * IS 3034 Code practice for fire safety of
(Ministry of Irrigation & Power, Govt. of industrial buildings, electrical generating
India) and distributing stations.

iv) The Petroleum Rules 1976 (Ministry of * IS 1646 Code of practice for fire safety
Industry, Government of India) of buildings (General) Electrical
Installations.
v) Oil Mines Regulations
* IS 10028 (Part 1, 2 & 3) code of
vi) C.B.I.P. (Central Board of Irrigation & practice for selection, installation and
Power) Technical Report No. 3 ‘Manual on maintenance of transformers.
Layout of Substations’.
* IS 2165 Part (1 & 2) Insulation
vii) BIS (Bureau of Indian Standards) Coordination.
Publications
* IS 2834 Specifications of shunt
* IS 5572 Classification of hazardous capacitor for power system.
areas (other than mines) for electrical
installations. Areas having flammable * IS 13408 Code of Practice for the
gases and vapour selection, installation and maintenance of
Electrical Apparatus for use in potentially
* IS 5571 Guide for selection of explosive atmospheres (other than mining
electrical equipment for hazardous areas. applications or explosives processing and
manufacture)
* IS 13346 General requirements for
electrical apparatus for explosive gas * IS 2148 Flameproof enclosures for
atmosphere electrical apparatus

* IS 8239 Classification of maximum * IS 7389 Pressurised enclosures of


surface temperature of electrical equipment electrical equipment for use in hazardous
for use in explosive atmospheres. areas

* IS 3043 Code of Practice for Earthing. * IS 7724 Sand filled protection of


electrical equipment for use in explosive
* IS 3716 Insulation coordination atmospheres
application guide.
* IS 7693 Oil immersed electrical
* IS 732 Code of practice for electrical apparatus for use in explosive gas
wiring installations. atmosphere

* IS 6665 Code of practice for industrial * IS 8289 Electrical equipment for type
lighting. of protection ‘n’

* IS 3646 Interior illumination : Part 1, * IS 6381 Specification for construction


Part 2 & Part 3. and testing of Electrical apparatus with type
of protection ‘e’
* IS 1944 Code of practice for lighting of
public thoroughfares. * IS 2147 Degrees of protection
provided by enclosures for low voltage
* IS 7689 Guide for control of switchgear and control gear.
undesirable static electricity.
viii) IEC 34-9 Rotating
* IS 2309 Protection of buildings and
allied structures against lightning. Electrical Machine - Part 9 (Noise Limit)

IEC 183 Guide to the selection of high


voltage cables
ANSI/ Standard Electrical Power
System

IEEE Device Standard Function


Numbers C37.2

You might also like