Professional Documents
Culture Documents
These are not-so-easy, but also not-too-hard questions for you to try to answer and
test your electrician skills. Whether you are a novice in a field of electrical
engineering or a professional electrician, these questions will move your brain cells
for sure! To check your results, take a peek for answers at the bottom of article.
Let’s start.
Question #1
Building “A” is supplied with 120/240 volt single-phase powerfrom building “B” on the
same property. “B” is supplied from a three-wire with two ungrounded conductors and
one neutral without any metallic water pipe or other metal equipment connections to the
building or equipment ground fault protection installed.
Question #2
A feeder runs from one part of a building to another under the floor in two parallel sets
of rigid non-metallic conduits with typeRHW copper conductors size AWG #500 and
is protected by800 ampere fuses. It must have a minimum size copper
equipment grounding conductor in each conduit run of no less than which of the
following:
A. 1/0 AWG
B. 20 AWG
C. 10 amps
D. 5 AWG
Question #3
A surge arrestor for a 480 volt electrical system requires a connecting conductor that
is #14 copper or larger.
A. True
B. False
Question #4
If a single family dwelling unit has 2680 square feet of living space and all of the 120
volt general illumination circuits are rated at 15 amperes, then the minimum number of
circuits required is which of the following:
A. 5
B. 6
C. 7
D. 8
Question #5
A single family dwelling with 2400 square feet of living area has a 120/240 volt three-
wire electrical service and contains the following:
The total minimum load required for the general illumination, small appliances, and
laundry without any demand factors would be which of the following:
A. 1500 VA
B. 7200 VA
C. 11700 VA
D. 15000 VA
A. 240 amps
B. 208 amps
C. 90 VA
D. 25 VA
Question #7
In order to correct the power factor, a three-phase, 480 volt, 92 kVAR capacitor
bank located 6 feet from the main service of a3200 square foot office building has a
minimum required ampere rating for the conductors in the capacitor bank of which of
the following:
A. 240 amps
B. 180 amps
C. 150 amps
D. 110 amps
Question #8
In an 8 unit apartment building, each kitchen contains a 3.5 kW 240 volt electric
range. The demand load for the electric service to the building must include an
allowance for the minimum demand load of all of the ranges, which would be which of
the following:
A. 28 kVA
B. 21 kVA
C. 14 kVA
D. 7.5 kVA
Question #9
A retail store has 3000 square feet and 30 feet of show window. The service is
a 120/240 volt single phase 3-wire service, and there is an actual connected lighting
load of 8500 VA.
There are a total of 80 duplex receptacles. Given these facts, the total calculated load
is which of the following:
A. 9000 VA
B. 12200 VA
C. 16200 VA
D. 28400 VA
Question #10
A project requires the installation of twelve 1.4 ampere, 120 volt, fluorescent lights
fixtures on two 20 amp branch circuits, as well as three 120 volt, 5.6 ampere
electric fans on individual circuits in a building with a 120/240 single phase three-
wire electric service.
The minimum neutral current allowed for these loads is which of the following:
A. 0 amps
B. 5.6 amps
C. 16.8 amps
D. 33.6 amps
Answers
To prove your electrician skills, your results should be the same as provided
answers. NEC articles mentioned in answers you can observe in a free draft
version of NEC 2014 //